Hauber HE100 Series User manual

Betriebsanleitung
englisch
Doc ID: M001-HE100 Stand: 2021-06-14
Vibration monitoring unit
HE100 series
Proc. Cont. Eq.
for Ord. Loc.
Proc. Cont. Eq.
for Haz. Loc.
•Vibration velocity (mm/s, rms)
•ATEX / IECEx / EACEx Zone 1 / 2 / 21 / 22
•Analogue current output: 4–20 mA
•Frequency ranges: 10 Hz–1,000 Hz
1 Hz–1,000 Hz
Manufacturing date:
Type designation:
Serial number:

HAUBER-Elektronik GmbH
Operating instructions
Vibration Monitoring Unit
Type HE100
Standard and ATEX / IECEx / EACEx
HE100
Version: 2021-06-14
Attention!
Prior to commissioning the product, the instruction manual must be read and un-
derstood.
All rights reserved, including rights to translation.
Subject to modifications.
Please contact the company with any questions:
HAUBER-Elektronik GmbH
Fabrikstraße 6
D-72622 Nürtingen
Germany
Tel.: +49 (0) 7022 / 21750-0
Fax: +49 (0) 7022 / 21750-50
info@hauber-elektronik.de
www.hauber-elektronik.de

HAUBER-Elektronik GmbH
3
1 Contents
1Contents...................................................................................................................................................3
2Safety information....................................................................................................................................4
3Scope of this instruction manual..............................................................................................................4
4Vibration monitoring unit type HE100......................................................................................................5
5Intended use ............................................................................................................................................5
6Scope of supply .......................................................................................................................................5
7Documents and Certificates.....................................................................................................................5
8Transfer of liability when operating in potentially explosive atmospheres...............................................5
9Application areas and type plate examples.............................................................................................6
10 General Conditions for Safe Operation....................................................................................................7
10.1 HE100.01 (protection ‘pressure resistant housing’)..............................................................................7
10.2 HE100.02 (ignition protection class "intrinsically safe")........................................................................7
11 Technical data..........................................................................................................................................9
11.1 General data.........................................................................................................................................9
11.2 Electrical data .......................................................................................................................................9
11.3 Permitted operating temperature ranges............................................................................................10
11.4 Operating range of the vibration monitoring unit ................................................................................11
11.5Typical frequency response................................................................................................................12
11.6 Mechanical data..................................................................................................................................13
11.7 Housing dimensions............................................................................................................................13
12 Connections...........................................................................................................................................15
13 Assembly and disassembly....................................................................................................................16
13.1 General notes .....................................................................................................................................16
13.2 Fixing the vibration monitoring unit to the mounting surface..............................................................16
14 Installation and commissioning..............................................................................................................17
14.1 General notes .....................................................................................................................................17
14.2 Wiring diagram....................................................................................................................................17
15 Maintenance and repair.........................................................................................................................19
15.1 General notes .....................................................................................................................................19
15.2 Fault resolution table ..........................................................................................................................19
16 Transport, storage and disposal ............................................................................................................20
17 Accessories............................................................................................................................................20
18 HE100 type code ...................................................................................................................................21
19 EU-Declaration of conformity.................................................................................................................22

HAUBER-Elektronik GmbH
4
2 Safety information
2.1 General
The safety instructions are intended to protect people and property from damage and hazards
that could arise as the result of improper use, incorrect operation or other misuse or devices,
especially in explosive areas. Therefore, please read the operating instructions carefully before
working on the product or operating it. The operating instructions must be accessible to operat-
ing personnel at all times.
Please make sure that all documents are present and complete before commissioning or per-
forming other work on the product. If the documents have not all been delivered in full or if fur-
ther copies are necessary, they can also be obtained in other languages.
The product is built according to the latest state of the art. However, hazards to people, machin-
ery and systems can still arise as the result of improper handling, unintended use or operation
and maintenance by persons inadequately trained on the product.
All those who are involved in the installation, operation and maintenance of the product in the
operator’s plant must read and understand the operating instructions.
The product may only be assembled, disassembled, installed and repaired by instructed, suffi-
ciently trained and authorised personnel.
2.2 Symbols used
This symbol indicates an explosion hazard.
This symbol indicates a hazard from electrical current.
This symbol indicates information unrelated to safety.
3 Scope of this instruction manual
This instruction manual for the HE100-type vibration monitoring unit applies to the following vari-
ants:
Standard / ATEX / IECEx / EACEx
The functionality of the versions is identical. The ATEX / IECEx / EACEx versions also possess
certifications and labels which permit use in potentially explosive atmospheres. For further infor-
mation, see chapter "Application areas” on page 6.

HAUBER-Elektronik GmbH
5
4 Vibration monitoring unit type HE100
The HE100-type vibration monitoring unit is used to measure and monitor absolute bearing vi-
brations in machines in line with DIN ISO 10816.
It has the following features:
•Operating principle: The two-wire system.
•Measurement value: The effective value (rms) of the vibration velocity in mm/s, in accord-
ance with DIN ISO 2954.
•Analogue current output: Interference-free DC signal from 4–20 mA, proportional to the
measuring range of the monitoring unit.
•Cable breaks on the monitoring cable can be detected by a downstream evaluation com-
ponent: DC signal value < 3.5 mA.
5 Intended use
The HE100-type is used exclusively for measuring mechanical vibrations in machines and me-
chanical systems. Its use is only permissible within the specifications stated in the data sheet.
Main fields of application: Fans, ventilators, blowers, electric motors, pumps, centrifuges, sep-
arators, generators, turbines and similar oscillating mechanical systems.
6 Scope of supply
All versions include:
•Vibration monitoring unit
•Instruction Manual
7 Documents and Certificates
You can find the following documents and certificates for HE100 type at www.hauber-el-
ektronik.de where they can be viewed and downloaded:
•EU type examination certificate ATEX, no.: PTZ 16 ATEX 0029 X Rev 3
•IECEx certificate of conformity, no.: PTZ 18.0009 X Rev 2
•UL certificate of conformity, no.: E507077-20191126
•EACEx certificate RU C-DE.HA65.B.00053/19
•EAC Declaration
8 Transfer of liability when operating in potentially explosive atmospheres
The owner of the system is exclusively liable for the appropriate configuration of the electrical
connections with respect to explosion protection regulations and correct commissioning.
If the system is installed by a sub-contractor on behalf of the owner, the system may only be
commissioned after the sub-contractor has issued written confirmation in the form of a certificate
of installation that the system has been installed correctly and professionally in accordance with
the applicable legal regulations.
The operator is obliged to notify the responsible authorities of the initial commissioning of explo-
sion-protected systems or system components and their re-commissioning following extensive
changes or maintenance.

HAUBER-Elektronik GmbH
6
9 Application areas and type plate examples
HE100.00
HE100.01
HE100.02
HE100.03
Version
Standard CE / IEC / EAC
UL Proc. Cont. Eq. Ord.
Loc.
ATEX / IECEx / EACEx
Pressure-resistant casing,
Ex db
Protection through housing,
Ex tb
ATEX / IECEx / EACEx
Intrinsic safety Ex ib
UL Proc. Cont. Eq. Haz. Loc.
Division 2
Application area
Atmospheres not at risk of ex-
plosion
Potentially explosive atmos-
pheres of zones
1 and 21
2 and 22
Potentially explosive atmos-
pheres of zones
1 and 21
2 and 22
Potentially explosive atmos-
pheres of division 2
Marking
E507077
Process Control Equipment
for Ordinary Location
II 2G Ex db IIC T4 Gb
II 2D Ex tb IIIC T120 °C Db
-40 °C ≤ TAmb ≤+60°C
PTZ 16 ATEX 0029 X Rev 3
IECEx
Ex db IIC T4 Gb
Ex tb IIIC T120 °C Db
-40 °C ≤ TAmb ≤+60°C
IECEx PTZ 18.0009 X Rev 2
1Ex db IIC T4 X
Ex tb IIIC T120 °C X
-40 °C ≤ TAmb ≤+60°C
№ TP ТС 012/2011
II 2G Ex ib IIC T4 Gb
II 2D Ex ib IIIC T125 °C Db
-40 °C ≤ TAmb ≤+60°C
PTZ 16 ATEX 0029 X Rev 3
IECEx
Ex ib IIC T4 Gb
Ex ib IIIC T125 °C Db
-40 °C ≤ TAmb ≤+60°C
IECEx PTZ 18.0009 X Rev 2
1Ex ib IIC T4 X
Ex ib IIIC T125 °C X
-40 °C ≤ TAmb ≤+60°C
№ TP ТС 012/2011
Class I, Division 2,
Groups A, B, C and D, T4
Class II, Division 2,
Groups F and G, T4
E516625
Process Control Equipment
for Hazardous Location
Type plate
Type: HE100.00.16.00.00.00.000
Item-no.: 12345
Serial-no.: 123456
Measuring range V : 0...16mm/s
Eff
Frequency range V : 10...1000Hz
Eff
-40 °C ≤ TAmb ≤ +60°C
Manufacturer: HAUBER-Elektronik GmbH
Fabrikstraße6· 72622NürtingenGERMANY
www.hauber-elektronik.de
тип: HE100.00.16.00.00.00.000
123456Серийный №.: V: 0...16 мм/сДиапазоны измерений Eff
V: 10...1000 гцДиапазон частот Eff
-40 °C ≤ TAmb ≤ +60°C
производитель: HAUBER-Elektronik GmbH
Fabrikstraße 6 · 72622 Nürtingen Германия
www.hauber-elektronik.de
MADEIN
GERMANY
IEC
E507077
Proc. Cont. Eq.
Ord. Loc.
Type: HE100.01.16.00.00.00.050
Item-no.: 12345
Serial-no.: 123456
Measuring range V : 0...16 mm/s
Eff
Frequency range V : 10...1000 Hz
Eff
-40 °C ≤ TAmb ≤ +60°C
Manufacturer: HAUBER-Elektronik GmbH
Fabrikstraße 6 ·72622 Nürtingen GERMANY
www.hauber-elektronik.de
MADE IN
GERM ANY
IECEx
IECEx PTZ
18.0009 X Rev 2
тип: HE100.01.16.00.00.00.050
123456Серийный №: V: 0...16 мм/сДиапазоны измерений Eff
V: 10...1000 гцДиапазон частот Eff
-40 °C ≤ TAmb ≤ +60°C
1Ex db IIC T4 X
Ex tb IIIC T120 °C Xb
производитель: HAUBER-Elektronik GmbH
Fabrikstraße 6 · 72622 Nürtingen Германия
www.hauber-elektronik.de
0539
No TP TC
012/2011
PTZ 16 ATEX
0029 X Rev 3
II 2G Ex db IIC T4 Gb
II 2D Ex tb IIIC T120 °C Db
Type: HE100.02.16.00.00.00.000
Item-no.: 12345
Serial-no.: 123456
Measuring range V : 0...16 mm/s
Eff
Frequency range V : 10...1000 Hz
Eff
-40 °C ≤ TAmb ≤ +60°C
Manufacturer: HAUBER-Elektronik GmbH
Fabrikstraße 6 ·72622 Nürtingen GERMANY
www.hauber-elektronik.de
MADE IN
GERM ANY
тип: HE100.02.16.00.00.00.000
123456Серийный № V: 0...16 мм/сДиапазоны измерений Eff
V: 10...1000 гцДиапазон частот Eff
-40 °C ≤ T Amb ≤ +60°C
1Ex ib IIC T4 X
Ex ib IIIC T125 °C X
производитель: HAUBER-Elektronik GmbH
Fabrikstraße 6 · 72622 Nürtingen Германия
www.hauber-elektronik.de
No TP TC
012/2011
IECEx
IECEx PTZ
18.0009 X Rev 2
0539
PTZ 16 ATEX
0029 X Rev 3
II 2G Ex ib IIC T4 Gb
II 2D Ex ib IIIC T125 °C Db
Type: HE100.03.16.00.00.00.050
Item-no.: 12345
Serial-no.: 123456
Measuring range V : 0...16 mm/s
Eff
Frequency range V : 10...1000 Hz
Eff
-40 °C ≤ T Amb ≤ +60°C
Manufacturer: HAUBER-Elektronik GmbH
Fabrikstraße 6 ·72622 Nürtingen GERMANY
www.hauber-elektronik.de
MADE IN
GERM ANY
E516625
Proc. Cont. Eq.
Haz. Loc.
тип: HE100.03.16.00.00.00.050
: 123456Серийный № V: 0...16 мм/сДиапазоны измерений Eff
V: 10...1000 гцДиапазон частот Eff
-40 °C ≤ T Amb ≤ +60°C
производитель: HAUBER-Elektronik GmbH
Fabrikstraße 6 · 72622 Nürtingen Германия
www.hauber-elektronik.de
Standards applied
You can find a list of standards, including the related issue dates, in the EU type examination
certificate for the vibration monitoring unit.

HAUBER-Elektronik GmbH
7
10 General Conditions for Safe Operation
The following conditions must be met for safe operation in potentially explosive atmospheres.
10.1 HE100.01 (protection ‘pressure resistant housing’)
Electrical data
min
typ.
max.
Supply voltage
Un
10 V DC
24 V DC
30 V DC
Current
In
4 mA
4...20 mA
25 mA
Tabular 1: Electrical data HE100.01
10.2 HE100.02 (ignition protection class "intrinsically safe")
With the ignition protection class intrinsically safe Ex ib IIC or IIC, the sensor
must only be operated in a certified intrinsically safe electrical circuit. The ma-
ximum values must not be exceeded.
The following values relate to the vibration monitoring unit and the supply and
signal circuit.
Electrical data
Max. input voltage of the vibration monitoring unit
Ui
30 V DC
Max. input current of the vibration monitoring unit
Ii
100 mA
Max. input power of the vibration monitoring unit
Pi
600 mW
Capacity of the vibration monitoring unit
Ci
44 nF
Inductance of the vibration monitoring unit
Li
0 µH
Tab. 2: HE100.02 electrical data

HAUBER-Elektronik GmbH
8
Other conditions
1. Extended ambient temperature range of -40°C to +60°C
2. Equipotential bonding takes place during installation.
3. The instruction manual is to be heeded.
4. The following feed/inlet isolating amplifiers are tested and approved by Hauber-Elektronik
GmbH for intrinsically safe operation:
•Endress und Hauser
Active barrier RN221N with HART® diagnosis
•PHOENIX CONTACT Deutschland GmbH
feed and isolating amplifier MACX MCR-EX-SL-RPSSII 2865340
•Pepperl+Fuchs
SMART transmitter supply unit KFD2-STC3-Ex1
•R. STAHL Schaltgeräte GmbH
transducer supply unit 9260/13-11-10s art. no. 261384
5. The Ex i version must only be operated with the Ex i cable approved by Hauber-El-
ektronik. On this cable, pin 5 of the M12 connector is assigned to the cable shield. (HE
article number: 11141 (2m), 11142 (5m), 11143 (10m), additional lengths available in
stock)
HAUBER-Elektronik is not responsible for changes to the specification of the
feed/inlet isolating amplifier mentioned.

HAUBER-Elektronik GmbH
9
11 Technical data
11.1 General data
Each sensor has one of the measuring and frequency ranges listed. Additional
ranges upon request.
Please specify the measuring and frequency range in your query.
Measuring range:
0–8 mm/s (only for frequency range > 10 Hz)
0–16 mm/s
0–32 mm/s
0–64 mm/s
0–64mm /s
Measurement accuracy:
±10% (as per DIN ISO 2954)
Cross-sensitivity:
< 5%
Frequency range:
10 Hz–1,000 Hz (standard)
1 Hz–1,000 Hz
Calibration point
159.2 Hz and 90% amplitude of the measuring range
Maximum acceleration
±16.5 g
Service life
10 years
MTTF
399 years
Tab. 3: General data
11.2 Electrical data
Output signal:
4–20 mA (proportional to the measuring range)
Voltage supply:
10–30 V DC
Current draw (max.):
25 mA
Apparent ohmic re-
sistance/load (max.):
500 Ω
Fuse*:
30VDC, 3A, medium blow
* Ensure that the supply line is protected by a UL-approved fuse for UL-compliant sensor operation.
Tab. 4: Electrical data

HAUBER-Elektronik GmbH
10
11.3 Permitted operating temperature ranges
Version
Ambient temperature
(TA)
Measuring head temperature
(in the fixing area)
Standard
-40°C to +60°C
-40 °C to +125°C
ATEX / IECEx / EACEx
Pressure-resistant casing, Ex d
Protection through housing, Ex tb
-40 °C to +60 °C
-40 °C to +125°C
ATEX / IECEx / EACEx
Intrinsic safety Ex ib
-40 °C to +60 °C
-40 °C to +125°C
Tab. 5: Permitted operating temperature ranges

HAUBER-Elektronik GmbH
11
11.4 Operating range of the vibration monitoring unit
The operating range is independent of the measuring range. It is deduced from the maximum
acceleration, which is 16.5 g across all frequencies. The maximum measurable vibration ve-
locity is determined by the formula
The following applies to sinusoidal vibration
Fig. 1: shows the operating range of the vibration monitoring unit, which is limited by the maxi-
mum measurable vibration velocity in mm/s depending on the frequency in Hz.
Fig. 1: Operating range diagram
1 Frequency in Hz
2 Vibration velocity in mm/s
3 Operating range of the vibration monitoring unit
Reading examples:
Frequency
(Hz)
Maximum measurable
Vibration velocity
(mm/s)
250
103
400
64
1,000
25
Tab. 6: Operating range reading examples
0
20
40
60
80
100
120
140
160
180
200
0100 200 300 400 500 600 700 800 900 1000
2 →
1→
3

HAUBER-Elektronik GmbH
12
11.5 Typical frequency response
10 Hz–1,000 Hz (standard)
The frequency response is recorded using a reference sensor.
• 4 Hz. . . 1200 Hz acceleration sensor
Fig. 2: Typical frequency response 10 Hz–1000 Hz
1 Frequency in Hz
2 Amplification in dB
1 Hz–1000 Hz
The frequency response is recorded using two reference sensors.
• 1 Hz. . . 10 Hz laser sensor
• 10 Hz. . . 1200 Hz acceleration sensor
Fig. 3: Typical frequency response 1 Hz–1000 Hz
1 Frequency in Hz
2 Amplification in dB

HAUBER-Elektronik GmbH
13
11.6 Mechanical data
Additional materials and fixings can be found in section "HE100 type code" on
page 21.
Housing material:
Stainless steel V2A, material no.: 1.4305 (standard)
Fixing:
Width A/F 24 (hex)
M8 x 8 mm
Incline: 1.25 mm (standard)
Assembly type:
Standing/vertical or lying/horizontal
Measurement direction
Along the fixing axis
Max. torque oft the Sensor
8 Nm
Max. torque of the M12 un-
ion nut on the connector
0.4 Nm
Weight:
ca. 200 g
Protection class:
IP 66/67 (in mated condition)
Tab. 7: Mechanical data
11.7 Housing dimensions
Version: Stan dard and ATEX / IECEx / EACEx
11.7.1 Version: Standard and ATEX / IECEx / EACEx
Intrinsic safety, Ex i
Fig. 4: Housing with M12 connector
All dimensions in mm
1 M12 connector
2 Width A/F 24
3 Fixing
4 Measuring direction along the fixing axis

HAUBER-Elektronik GmbH
14
11.7.2 Version: ATEX / IECEx / EACEx Ex d
Fig. 5: Housing with integrated cable
All dimensions in mm
1 Cable gland for integrated cable
2 Width A/F 24
3 Fixing
4 Measuring direction along the fixing axis

HAUBER-Elektronik GmbH
15
12 Connections
Version:
Standard
Plug, M12, 4-pole
Pin 1:
10…30 V DC
Pin 2:
NC
Pin 3:
4…20 mA
Pin 4:
NC
NC:
Not Connected
Version:
ATEX / IECEx / EACEx pressure-resistant casing Ex d
ATEX / IECEx / EACEx protection through housing, Ex tb
integrated cable
brown
Pin 1:
10…30 V DC
white
Pin 2:
NC
blue
Pin 3:
4…20 mA
black
Pin 4:
NC
PUR sheathed cable; Ø: approx. 6.5 mm,
4-pole, 0.34 mm²
NC:
Not connected
Version:
ATEX / IECEx / EACEx intrinsic safety Ex i
Plug, M12, 5-pole
Pin 1:
10…30 V DC
Pin 2:
NC
Pin 3:
4…20 mA
Pin 4:
NC
Pin 5:
Sensor housing
NC:
Not Connected
The system operates according to the two-wire principle.
I.e. the entire function (voltage supply and current signal) is achieved using 2
wires (Pin 1 and Pin 3).
To avoid capacitive interference, pins 2 and 4 must remain open/unoccupied.

HAUBER-Elektronik GmbH
16
13 Assembly and disassembly
13.1 General notes
Assembly and disassembly work on and with the vibration monitoring unit may only be perfor-
med by an authorised specialist familiar with the safety regulations governing handling electrical
components.
The housing of the vibration monitoring unit must be earthed via the fixing –
through the machine earth of the mounting surface or through a separate pro-
tective conductor (PE).
13.2 Fixing the vibration monitoring unit to the mounting surface
13.2.1 Prerequisites
• Mounting surface is clean and flat; i.e. free of paint, rust, etc.
• Measuring head area of the vibration monitoring unit must lie flat on the mounting surface.
13.2.2 Tool
• Hex key, width A/F 24
13.2.3 Work steps and instructions
• Screw vibration monitoring unit into the threaded hole of the mounting surface in a friction-lo-
cked manner using a hex key. The tightening torque should be 8 Nm.
• The tightening torque of the M12 union nut of the plug connection must not exceed 0.4 Nm
To obtain precise measurement values, the vibration monitoring unit must be
fixed to the mounting surface in a friction-locked manner.
Auxiliary structures for fixing are to be avoided. If unavoidable, make them as
firm as possible!
Earth/ground loops are amongst the most common problems in measurement
set-ups with sensitive sensor technology. These issues arise due to unintentio-
nal differences in potential in the electrical circuit between the sensor and eva-
luation unit. As a countermeasure, we recommend our standard earthing con-
cept or, depending on the application our Alternative earthing concept
Ensure that the earth connection is electrically secure.

HAUBER-Elektronik GmbH
17
14 Installation and commissioning
14.1 General notes
Installation and commissioning the vibration monitoring unit must be performed by an
authorised specialist who is familiar with the safety regulations when handling
electrical components.
Protect the connection cable and any extension cables from electrical interfe-
rence or mechanical damage. Comply with the local regulations and directives.
14.2 Wiring diagram
Earth/ground loops are amongst the most common problems in measurement set-ups with
sensitive sensor technology. These issues arise due to unintentional differences in potential in
the electrical circuit
between the sensor and evaluation unit.
Ensure that the earth connection is electrically secure.
14.2.1 Standard earthing concept
With the standard earthing concept, the sensor cable shield has no connection to the sensor
housing. The sensor housing has the same potential as the machine earth.
1 Machine earth
2 Evaluation unit (measuring device, PLC, etc.)
3 Blue –4–20 mA current signal
4 Brown –10–30 V DC
5 Cable shield
6 Evaluation unit earth potential

HAUBER-Elektronik GmbH
18
14.2.2 Alternative earthing concept
With the alternative earthing concept, the sensor cable shield is connected to the sensor hous-
ing. The sensor housing is uncoupled from the machine earth by means of an EMC adapter
(red). With the alternative earthing concept, an electrically secure earth connection can only be
ensured for versions with an M12 plug connection. For versions with an integrated cable, the al-
ternative earthing concept cannot be used.
1 Machine earth
2 Evaluation unit (measuring device, PLC, etc.)
3 Blue –4–20 mA current signal
4 Brown –10–30 V DC
5 Cable shield
6 Evaluation unit earth potential
7 EMC adapter (Hauber art. no. 10473)
Please advise us if you are opting for the alternative earthing concept when
enquiring. We will offer you the relevant sensor cable and the EMC adapter.
14.2.3 Potentially explosive atmosphere, Ex i earthing concept
For the Ex i sensor, the shield is routed via Pin 5 of the plug connection to the potential of the
sensor housing, which is typically on the machine earth.

HAUBER-Elektronik GmbH
19
1 Machine earth
2 The shield of the Ex i cable is on the po-
tential of the housing via Pin 5 of M12
connector
3 Do not earth the shield
4 Evaluation unit (measuring device, PLC, etc.)
5 Power supply
6 Hauber Ex i sensor
7 Isolating amplifier
8 Potentially explosive atmospheres of
zones 1 and 21 / 2 and 22
9 Area not at risk
15 Maintenance and repair
15.1 General notes
Repair and cleaning work on vibration monitoring units may only be performed
by an authorised specialist familiar with the safety regulations governing hand-
ling electrical components.
Replace defective cables immediately!
A defective vibration monitoring unit must be completely replaced.
The vibration monitoring unit HE100 is maintenance-free.
15.2 Fault resolution table
Fault
Cause
Action
No measured
value
(4-20 mA)
No voltage supply
Check voltage source and/or supply
cable
Connection cable interrupted
Replace connection cable
Fuse defective
Replace fuse
Connection has incorrect polarity
Establish correct connection polarity
Vibration monitoring unit defective
Replace vibration control unit
Incorrect
measurement
value
Vibration monitoring unit not fric-
tion-locked.
Mount vibration monitoring unit in a fric-
tion-locked manner.
Vibration monitoring unit mounted
in wrong position.
Mount vibration monitoring unit in correct
position.
EMC prob-
lems
For further information, see chapter "Al-
ternative earthing concept” on page 18.
Tab. 8: Fault resolution table

HAUBER-Elektronik GmbH
20
16 Transport, storage and disposal
The sensor must be protected from damaging environmental factors and mechanical damage
during transport with the use of adequate packing.
The sensor may not be stored in ambient temperatures outside the permitted operating tempe-
rature.
The product contains electronic components and must be disposed of properly in accordance
with local laws and regulations.
17 Accessories
Accessories
Standard
ATEX / IECEx / EACEx Ex d, tb
ATEX / IECEx / EACEx Ex i
Factory calibration certificate –Art-No.:10419
x
x
x
Evaluation device types 652 and 656
x
x
x
HE400-type portable measuring instrument
x
ATEX / IECEx / EACEx supply isolation amplifier for intrinsic safety Ex I –Art-
No.:10993
x
Magnetic base –Art-No.:10054
x
Various mounting adapters; e.g. M8 -> M10
x
x
x
Configurable mating plug
x
x
Connection cable, socket M12, 4-pin, 0.34 mm²,
L= 2 m, 5 m, 10 m, or customised
x
ATEX / IECEx / EACEx connection cable for intrinsic safety Ex i, M12, 4-pin,
0.34 mm²,
L= 2 m, 5 m, 10 m, or customised
x
Rubber nozzle–Art-No.:10986
x
x
x
Metallic protective hose
x
x
x
EMC adapter –Art-No.:10473
x
For use OUTDOORS or using SPRAY WATER, the vi-
bration monitoring unit should have the rubber nozzle
pulled over it for additional protection.
Rubber nozzle
This manual suits for next models
9
Table of contents
Popular Control Unit manuals by other brands

piezosystemjena
piezosystemjena d-Drive pro instruction manual

Grundfos
Grundfos CU 401 Installation and operating instructions

Eaton
Eaton Vickers DG3V-8 Series Overhaul manual

Parker
Parker IQAN-XC21 Instruction book

Genebre
Genebre 2528V Installation, operation and maintenance manual

Bender
Bender RCMB300 Series manual