Hawk Gladiator User manual

INSTRUCTION MANUAL
Admittance Smart Switch Series
-
An all-round point level switch
-
A higher level of performance

1Sultan 234 Series
Admittance Smart Switch Series Manual
Rev 1.2, June 2008
PROPRIETARY NOTICE
The information contained in this publication
is derived in part from proprietary and patent
data. This information has been prepared for
the express purpose of assisting operating and
maintenance personnel in the efcient use of
the instrument described herein. Publication of
this information does not convey any rights to
use or reproduce it, or to use for any purpose
other than in connection with the installation,
operation and maintenance of the equipment
described herein.
WARNING
This instrument contains electronic components
that are susceptible to damage by static
electricity. Proper handling procedures must
be observed during the removal, installation, or
handling of internal circuit boards or devices:
Handling Procedure:
1. Power to unit must be removed prior to
commencement of any work.
2. Personnel must be grounded, via wrist strap
or other safe, suitable means, before any
printed circuit board or other internal devices
are installed, removed or adjusted.
3. Printed circuit boards must be transported
in a conductive bag or other conductive
container. Boards must not be removed from
protective container until the immediate time
of installation. Removed boards must be
placed immediately in a protective container
for transport, storage, or return to factory.
Comments:
This instrument is not unique in its content
of ESD (electrostatic discharge) sensitive
components. Most modern electronic designs
contain components that utilize metal oxide
technology (NMOS, CMOS, etc.). Experience
has proven that even small amounts of static
electricity can damage or destroy these
devices. Damaged components, even though
they appear to function properly, exhibit early
failure.
General Description
Features 2
Typical Applications 3
Dimensions 5
Mounting 9
Flexile Cable Probe Adjustment 11
Wiring
- Smart Probe 12
- Remote Probe 13
- Relay Functions 14
- Multidrop Connections 15
- HawkLink GSM 16
- Test Terminal 18
Smart Probe Setup Procedure 19
Remote Setup Procedure 22
Remote Software Menu 24
- Software Tree 25
- QuickSet 26
- Advanced Menu 27
- Diagnostic Displays 30
Multidrop Communication 32
Remote Communication 33
Troubleshooting 34
Part Numbering 35
Specications 37
Dielectric Constant 38
CE Declaration 39
Contact Information (back cover)
INTRODUCTION CONTENTS

2
Admittance Smart Switch Series Manual
Rev 1.2, June 2008
3
GENERAL DESCRIPTION
The Gladiator Smart Admittance Switch
is a third generation, state-of-the-art
level probe, designed to operate in
tough industrial environments. The
probe of the Admittance Switch forms
one plate of a capacitance circuit, with
the vessel wall making the second plate.
The dielectric constant of the product
between the probe and the vessel wall
will cause a capacitive change as the
level approaches the probe, and the
output will switch in response. A special
circuit is used to ignore product build-up
between the sensing probe (active ele-
ment) and guard, and also between the
guard and vessel wall. The output has
adjustable hysteresis and delays for ‘on’
or ‘off’ switching.
A test function is available to remotely
conrm the probe integrity by switching
the relay contacts.
The Gladiator Smart Switch Series
includes communications capability for
remote adjustment, control and monitor-
ing.
Principle of Operation
The dielectric constant of the material
in the vessel will be different to that of
air. When the material comes near or in
contact with the probe an admittance
change will occur. The resonant fre-
quency of the internal oscillator will then
change. The relay will switch when the
frequency reaches the user selected
Switch Point value.
Excellent immunity to product build-up
Excellent temperature stability - no
false trips
Simple ‘1-minute’ set-up
Relay outputs: Smart probe (1)
Remote (2)
Remote test function
Adjustable ON and OFF delays (0-20 sec)
Smart communication options:
GosHawk, Modbus,
HART, Probus
DP, DeviceNet
Remote GSM Connection option
Remote amplier to probe separation
up to 500 m (1640 ft)
Bright visual status indication on
Probe
LCD Diagnostic for Remote version
Independant housing alignment after
mounting thread locked
Non contact switching possible with
many materials
•
•
•
•
•
•
•
•
•
•
•
•
•
FEATURES
Probe
Probe Insulation
Guard
Material build up
> 100mm
Ground the housing to
vessel, if vessel is metallic.
Ground the housing to
plant ground, if vessel is
non-metallic.
flatten roof

2
3Sultan 234 Series
Admittance Smart Switch Series Manual
Rev 1.2, June 2008
TYPICAL APPLICATIONS
High level switch in grain application
Cyclone bin level switch
High level switch in plastic pellet silo

4
Admittance Smart Switch Series Manual
Rev 1.2, June 2008
5
Continuous lling with build-up
on probe
High and low level switch in a hopper
If impact from falling material is
expected, mount a protection plate
above the probe to ensure no
physical damage can occur to the
probe in normal operation. If it is not
possible to do this or to move the
probe to an alternative position, use
a microwave switch.
See www.hawkmeasure.com for
further information on Microwave
switches and other level products.
TYPICAL APPLICATIONS
Probe
Low level
(side mounted)
Low level
(top mounted)
High level
(top mounted)

4
5Sultan 234 Series
Admittance Smart Switch Series Manual
Rev 1.2, June 2008
83mm (3.3”)
76.5 (3”)
61mm (2.4”) 8mm (0.3”)
106mm (4.2”)
106mm (4.2”)
10mm (0.4”)
151mm (5.9”)
145mm (5.7”)
38mm (1.5”)
160mm (6.3”)
192mm (7.6”)
166mm (6.5”)
142mm (5.6”)
10.5mm (0.4”)
3 x 20mm (0.7”), 1x16mm (0.6”)
Knock outs
166mm (6.5”)
192mm (7.6”)
160mm (6.3”)
Front Side Back
DIN Rail Mounting
(clips included)
DIMENSIONS
REMOTE AMPLIFIER ENCLOSURE
Xmm
temperature
extension
SS 316
Xmm:
Max. 80ºC (176ºF) ~ no temperature extension required.
Max.150ºC (302ºF) ~ 150mm (5.9”)
Max. 250ºC (482ºF) ~ 250mm (9.8”)
For the 450ºC (842ºF) Probe, a different extension applies.
165mm (6.5”)
125mm (4.9”)
4x18mm (0.7”) holes
10mm (0.4”)
90mm (3.5”)
HIGH TEMPERATURE
EXTENSIONS (<250°C, <482°F)
Remote Probe or Smart Probe
OPTIONAL FLANGE
Low level
(side mounted)
Flange Dimensions - 50mm (2”)
ANSI (Class 150)
A
120.7 4.75”
B
152.4 6”
C
19.1 0.75”
DIN (PN40) 125 4.9” 165 6.5” 18 0.7”
JIS (10K) 120 4.7” 155 6.1” 19 0.75”
A B
C

6
Admittance Smart Switch Series Manual
Rev 1.2, June 2008
7
Probe Length (mm, inch) Active +Guard + Ground
= 50mm, 2”
= 250mm, 9.8”
P30 (300mm,11.8”)
P50 (500mm, 19.7”)
= 750mm, 29.5”
P100 (1000mm, 39.4”)
250mm, 9.8”
250mm, 9.8”
250mm, 9.8”
+
+
+
Ground 100mm (3.9”)Guard 150mm (5.9”)Active (mm)
85mm (3.3”)
probe length
M20 cable gland
or 3/4” NPT adaptor
Window for
viewing status
LEDs
Mounting
thread
90mm (3.5”)
50mm (2”)
16mm (0.6”)
Ground 100mm (3.9”)
Guard 150mm (5.9”)Active (mm)
85mm (3.3”)
probe length
Window for
viewing status
LEDs
Optional Flange
90mm (3.5”)
50mm (2”)
2 x M20
cable glands
or 3/4” NPT adaptors
16mm (0.6”)
DIMENSIONS
REMOTE PROBE SMART PROBE

6
7Sultan 234 Series
Admittance Smart Switch Series Manual
Rev 1.2, June 2008
DIMENSIONS
FLEXIBLE CABLE PROBE
M20 x 1.5
or 3/4” NPT adaptor
115mm
Cable Length (mm, inch) Active + Guard + Ground (Rope Length)
C100 (1000mm, 39.3”) = 750mm, 29.5” + 250mm, 9.8” 451mm, 17.8”
C200 (2000mm, 78.7”) = 1750mm, 68.9” + 250mm, 9.8” 1451mm, 57.1”
C300 (3000mm, 118.1”) = 2750mm, 108.3” + 250mm, 9.8” 2451mm, 96.5”
SS 316
Removable grub screws
for cable adjustment
Ø 8mm (0.3”)
SS 316
Teflon
SS 316
Teflon
SS 316
100mm (3.9”)
Ground
150mm (5.9”)
Guard
Rope
250mm (9.8”)
Weight
Active
Cable Length
Mounting Thread
(1.5” NPT or BSP only)
Ø 40mm (1.6”)
83mm (3.3”)
83mm (3.3”)
215mm (8.4”)

8
Admittance Smart Switch Series Manual
Rev 1.2, June 2008
9
DIMENSIONS
HIGH TEMPERATURE PROBES
HIGH TEMP PROBE (<250°C, <482°F) HIGH TEMP PROBE (450°C, 842°F)
Probe length
150mm
(5.9”)
Guard
Active
Element
Temperature extension
100mm
(3.9”)
Ground Teflon
Teflon
Max 150ºC (302ºF)
Max 250ºC (482ºF)
SS 316
SS 316
SS 316
16mm (0.6”)
Mounting Thread
Ø90mm (3.5”) L100mm (4”)
Aluminium heat sink
Ceramic
Ceramic
Max 450ºC (842ºF)
SS 316
SS 316
36mm (1.4”)
329mm (13”)
Probe length
150mm
(5.9”)
Guard
Active
Element
100mm
(3.9”)
Ground
Mounting Thread
(1.5” NPT or BSP only)
90mm (3.5”)
90mm (3.5”)
(See page 5 for
temperature extension
options)

8
9Sultan 234 Series
Admittance Smart Switch Series Manual
Rev 1.2, June 2008
MOUNTING
Probes can be mounted from the top,
side and bottom.
Points to consider when mounting:
A. Material Infeed Clearance
Install the probe away from the infeed to
minimize the inuence of build-up and
impact forces, and to avoid false trigger-
ing from product ow.
B. Wall Clearance
Install the probe far enough away from
the wall to prevent the probe or cable
from coming into contact with the vessel
wall. Avoid creating a conned area
where material could build-up over time.
See note
C. Nozzle Clearance
Where possible, ensure the probe guard
has at least 100mm clearance from the
nozzle.
D. Top mounting
When top mounting, ensure adequate
clearance is provided between probe
and wall. Avoid creating a conned area
where material could build-up over time.
In the case of cable probe versions,
ensure enough clearance is provided
between the probe and wall to allow for
build-up of material occurring on the
wall.
See note
E. Side mounting
It is highly recommended to install any
side mounted probe at a downward
angle of 30-45º. Use a protection plate
for side mounting where the probe may
be subject to impact strain or collapsing
material.
F. Bottom mounting
Bottom mounting is not recommended.
Only mount from the bottom if no build-
up of material occurs. If low level mount-
ing is required, suitable options are
shown in the diagram on page 10.
CORRECT MOUNTING NOTES:
(Refer to picture on page 10)
Select correct probe for high tem-
perature applications.
Allow adequate air ow for cooling ex-
tensions dissipate heat.
INCORRECT MOUNTING NOTES:
Incorrect mounting because the
probe is too close to the wall or roof.
Positioning too close to a wall or roof
will limit probe sensitivity. Material may
build-up between the probe and the
vessel.
Incorrect mounting because the
probe’s guard is mounted inside the
nozzle. The correct arrangement is for
the guard to protrude out of the mounting
pipe at least 100mm. Product will build-
up in the nozzle.
Recommended 50mm (2”)
Correct Mounting in a Nozzle
min. 100mm (4”)

10
Admittance Smart Switch Series Manual
Rev 1.2, June 2008
11
MOUNTING
Incorrect
Correct Correct
Correct
Correct
Correct (non-preferred
low level mounting)
Correct
Incorrect
2
3
Correct
Correct
3
If necessary mount a
protection plate to
prevent direct impact
or to prevent pull
from down feed.
Flexible cable
Incorrect
2
Incorrect
1
Housing can be rotated
within 200º after the
mounting thread is
tightened, to allow cable
entries to face downwards
or allow optimal cable
clearance.
30-45º
1
Possible
product
build-up
Possible product
build-up

10
11 Sultan 234 Series
Admittance Smart Switch Series Manual
Rev 1.2, June 2008
FLEXIBLE CABLE PROBE ADJUSTMENT
Notes for adjusting probe rope length
The Gladiator rope type probe can be
altered to any sensing length between
approx. 750mm and 3m by cutting down
from the standard sizes as required.
If a new rope is to be used, the rope
should be cut to:
Cable probe length - 549mm = new wire rope
length
(total sensing length - 549mm)
For example, within a 1000mm (1m) cable:
1000 = [rope + 549]
So rope length = 451mm
Remove or install the probe weight grub
screws with a 4mm allen key.
When fastening the rope, apply thread-
locking adhesive onto grub screws
before re-installation.
Weight
Removable SS grub screws
for cable adjustment
Rope
Concealed
rope
Concealed
rope
250mm (9.8”)
83mm83mm
465mm (18.3”)
Cable Probe Length
Incorrect
Correct Correct
Correct
Correct
Correct (non-preferred
low level mounting)
Correct
Incorrect
2
3
Correct
Correct
3
If necessary mount a
protection plate to
prevent direct impact
or to prevent pull
from down feed.
Flexible cable
Incorrect
2
Incorrect
1
Housing can be rotated
within 200º after the
mounting thread is
tightened, to allow cable
entries to face downwards
or allow optimal cable
clearance.
30-45º
1
Possible
product
build-up
Possible product
build-up

12
Admittance Smart Switch Series Manual
Rev 1.2, June 2008
13
WIRING
SMART PROBE
RELAY
1. NC
2. COM
3. NO
COMMS DC-IN AC-IN
4. Test
12-30VDC
80-265 VAC
7.
8.
N
9.
L1
10.
1 2 3 4 5 6 7 8 9 10
RS 485
5.
B
6.
A
S
E
N
S
I
T
I
V
I
T
Y
D
E
L
A
Y
HI FSH TESTCAL
-
GLADIATOR SMART PROBE TERMINAL LAYOUT
Hole for securing of
optional identification tag
M4 grounding screw
Ground the housing to
vessel, if vessel is metallic.
Ground the housing to
plant ground, if vessel is
non-metallic.
The AC earth/ground
cable must be connected
to the ground screw
inside the housing when
using AC power.
If only one cable is used for both
power and output signal, then the
second entry port must be
plugged or blinded. Every Smart
unit is supplied with two M20
glands (or 3/4”NPT adaptors)
mounted on the unit and one
blind plug loose.
Remove Plug-In
terminal block for
easier wiring.
!

12
13 Sultan 234 Series
Admittance Smart Switch Series Manual
Rev 1.2, June 2008
1 2 3 4 5 6 7 8 9 10
GLADIATOR REMOTE AMPLIFIER TERMINAL LAYOUT
GLADIATOR REMOTE PROBE TERMINAL LAYOUT
M4 grounding screw
7.1. 2. 3. 4. 5. 6. 8. 9. 10.
TRANSDUCER
RED
WHITE
BLUE
BLACK
Cable type between Amplifier and Probe
4 conductor shielded twisted pair instrument cable.
Conductor size dependent on cable length.
BELDEN 3084A, DEKORON or equivalent.
Max: BELDEN 3084A = 500m (1640 ft)
Max: DEKORON IED183AA002 = 350m (1150 ft)
Hole for securing of
optional identification tag
Ground the housing to
vessel, if vessel is metallic.
Ground the housing to
plant ground, if vessel is
non-metallic.
Remove Plug-In
terminal block for
easier wiring.
Terminals 1, 2, 3, 4, 9, 10 not used.
AC-IN
A
L1
+
–
DC-INCOMMSSENSOR
N
B
RELAY 2
(FAIL SAFE)
NC
COM
NO
RED
BLACK
BLUE
WHITE
24 VDC 80-265 VAC
RELAY 1
NC
COM
NO
Test in
NOT USED
CURRENT
+–
Is
NOT USED
WIRING
REMOTE PROBE TO AMPLIFER

14
Admittance Smart Switch Series Manual
Rev 1.2, June 2008
15
1 2 3
123
123
123
1 2 3
1 2 3
1 2 3
1 2 3
RISING LEVEL
(not detected)
CONTACT LEVEL
(detected)
FALLING LEVEL
(not detected)
NC NO
NC NO
NC NO
NC NO
NC NO
NC NO
NC NO
NC NO
COM COM
COM COM
COM COM
COM COM
POWER FAILURE
NC NO NC NOCOM COM
INTERNAL FAILURE
POWER FAILURE
OR
SYSTEM OPERATING
NORMALLY
NC NOCOM NC NOCOM
State 1State 2State 1
Smart Probe
terminal numbers
Remote Amplifier
terminal function
labels
FailSafe Low
FSL
FailSafe High
FSH (default)
Relay Status
LED Status
Relay Action
WIRING
RELAY FUNCTIONS
FailSafe Switch Contact Action
Relay 2 - Remote version only.
For Smart Probes the Test termi-
nal can act as a solid state output
with a similar function.
(see page 18)
Level Switch Contact Action
Relay - for Smart Probe Version
(Set Relay Action selection switch
pages 19 and 20)
Relay 1 - for Remote Version
(Set ‘Relay Action’ parameter
pages 23 and 26)
*It is possible for the Gladiator to
switch state before actual product
contact with the probe. State 2 rep-
resents product being detected by
the probe, even if it occurs without
contact.

14
15 Sultan 234 Series
Admittance Smart Switch Series Manual
Rev 1.2, June 2008
Laptop or PC Communications using
PCMCIA card or wired (PSTN) modem
and remote GSM/CDMA connection
with GosHawk software.
A B Gnd A B Gnd A B Gnd
Laptop or PC Communications using
Hawklink USB or RS485 / 232 converter
with GosHawk software.
Hawklink
USB
1 2 3 4 5 6 7 8 9 10
HI
LO
FSH
FSL
OFF OFF
TEST
CAL
ON ON
1 2 1 2
S
E
N
S
I
T
I
V
I
T
Y
D
E
L
A
Y
A B Gnd A B Gnd A B Gnd
PLC / DCS / SCADA for Remote
Communication with Modbus.
A B Gnd A B Gnd A B Gnd
1 2 3 4 5 6 7 8 9 10
HI
LO
FSH
FSL
OFF OFF
TEST
CAL
ON ON
1 2 1 2
S
E
N
S
I
T
I
V
I
T
Y
D
E
L
A
Y
HawkLink
GSM/CDMA unit
White
Blue
Black
Multidrop Connection Using HawkLink USB*
Multidrop GSM/CDMA Connection*
Multidrop Connection to PLC/DCS/SCADA*
* Wiring installation should follow
RS-485 standards for layout and
termination.
1 2 3 4 5 6 7 8 9 10
HI
LO
FSH
FSL
OFF OFF
TEST
CAL
ON ON
1 2 1 2
S
E
N
S
I
T
I
V
I
T
Y
D
E
L
A
Y
1 2 3 4 5 6 7 8 9 10
HI
LO
FSH
FSL
OFF OFF
TEST
CAL
ON ON
1 2 1 2
S
E
N
S
I
T
I
V
I
T
Y
D
E
L
A
Y
1 2 3 4 5 6 7 8 9 10
HI
LO
FSH
FSL
OFF OFF
TEST
CAL
ON ON
1 2 1 2
S
E
N
S
I
T
I
V
I
T
Y
D
E
L
A
Y
1 2 3 4 5 6 7 8 9 10
HI
LO
FSH
FSL
OFF OFF
TEST
CAL
ON ON
1 2 1 2
S
E
N
S
I
T
I
V
I
T
Y
D
E
L
A
Y
WIRING
MULTIDROP CONNECTIONS
123
1 2 3
123
1 2 3
123
123
123
123
RISING LEVEL
(not detected)
CONTACT LEVEL
(detected)
FALLING LEVEL
(not detected)
NC NO
NC NO
NC NO
NC NO
NC NO
NC NO
NC NO
NC NO
COM COM
COM COM
COM COM
COM COM
POWER FAILURE
NC NO NC NOCOM COM
INTERNAL FAILURE
POWER FAILURE
OR
SYSTEM OPERATING
NORMALLY
NC NOCOM NC NOCOM
State 1State 2State 1
Smart Probe
terminal numbers
Remote Amplifier
terminal function
labels
FailSafe Low
FSL
FailSafe High
FSH (default)
Relay Status
LED Status
Relay Action

16
Admittance Smart Switch Series Manual
Rev 1.2, June 2008
17
Connect shield to
DC“-” only at this end.
1 2 3 4 1 2 3 4
1 2 3 4
-
Existing DC power supply
Existing AC power
supply (GSM will be
powered by DC
generated by the Gladiator)
COMMS DC-IN
A
B
12-30VDC
GSM
RS 485
AC-IN
N
L1
80-265VAC
COMMS DC-IN
A
B
12-30VDC
GSM
RS 485
AC-IN
N
L1
80-265VAC
COMMS DC-IN
A
B
12-30VDC
REMOTE AMP
RS 485
AC-IN
N
L1
80-265VAC
COMMS DC-IN
A
B
12-30VDC
RS 485
-
Connect shield to
DC“-” only at this end.
1 2 3 4 2 1 4 3
SMART PROBE
COMMS DC-IN
A
B
12-30VDC
GSM
RS 485
AC-IN
N
L1
80-265VAC
Connect shield to
DC“-” only at this end.
1 2 3 4
COMMS DC-IN
A
B
12-30VDC
REMOTE AMP
RS 485
AC-IN
N
L1
80-265VAC
-
Existing DC power supply
USING DC POWER FROM GLADIATOR SMART PROBE
USING DC POWER DERIVED FROM AC POWERED REMOTE GLADIATOR
USING DC POWER FROM REMOTE GLADIATOR
WIRING
HAWKLINK GSM - CONNECTING POWER AND COMMS
!
NOT POSSIBLE WITH
GLADIATOR SMART
PROBES. INTERNAL
POWER SUPPLY HAS IN-
SUFFICIENT CAPACITY.
!
TERMINAL ORDER VARIES BETWEEN GLADIATOR SMART PROBE
AND REMOTE AMPLIFIER. ENSURE CORRECT LAYOUT IS USED.

16
17 Sultan 234 Series
Admittance Smart Switch Series Manual
Rev 1.2, June 2008
COMMS DC-IN
A
B
12-30VDC
GSM
RS 485
Connect shield to
DC“-” only at this end.
1 2 2 1
AC-IN
N
L1
Separate AC power supply
for the GSM module
or
DC power
supply
COMMS DC-IN
A
B
12-30VDC
RS 485
-
AC-IN
N
L1
80-265VAC
Existing AC
or
DC power
supply
SMART PROBE
80-265VAC
COMMS DC-IN
A
B
12-30VDC
GSM
RS 485
Connect shield to
DC“-” only at this end.
1 2 1 2
AC-IN
N
L1
Separate AC power supply
for the GSM module
or
DC power
supply
COMMS DC-IN
B
A
12-30VDC
RS 485
-
AC-IN
N
L1
80-265VAC
Existing AC
or
DC power
supply
REMOTE AMP
80-265VAC
*
*
*Ensure separate DC supplies have the same ground potential
!
TERMINAL ORDER VARIES BETWEEN GLADIATOR SMART PROBE
AND REMOTE AMPLIFIER. ENSURE CORRECT LAYOUT IS USED.
WIRING
HAWKLINK GSM - CONNECTING POWER AND COMMS
USING SEPARATE AC OR DC POWER WITH SMART PROBE
USING SEPARATE AC OR DC POWER WITH REMOTE GLADIATOR
USING DC POWER FROM GLADIATOR SMART PROBE
USING DC POWER FROM REMOTE GLADIATOR

18
Admittance Smart Switch Series Manual
Rev 1.2, June 2008
19
Terminal Block
PLC / SCADA / DCS Output
Test
Terminal Block
Test
Test
Coil rating
500mW max
or 50mA max
Test
To switch an external relay
+12-24Vdc
PLC
SCADA
DCS Input
Pull up
12-24Vdc
max 50mA
To a PLC input
Externally provided
test button
!
!
PLC/SCADA/DCS GROUND MUST
CONNECT BACK TO GLADIATOR
GROUND OR DC ‘-’ TERMINALS
EXTERNAL PUSH BUTTON GROUND
MUST CONNECT BACK TO GLADIATOR
GROUND OR DC ‘-’ TERMINALS
Test terminal will provide an output which is able to switch an external failsafe relay or PLC/SCADA/DCS input.
During normal system operation this terminal will internally switch a solid state output to ground (or DC ‘-’).
If power fails or an internal system failure occurs, the terminal will act as an open circuit.
Relay will turn on during
normal system operation
or off in failed or unpowered
conditions.
Input will detect ‘0’ state during normal system
operation, or ‘1’ in failed or unpowered conditions.
WIRING
TEST TERMINAL FUNCTION SELECTION
TEST INPUT MODE
Test switch must be in ‘TEST’ (ON) position on Smart Probe - function always enabled on Remote Ampli-
er.
Test terminal acts as an input for remote testing of the instrument’s switching function.
Used to check for malfunction of unit from a remote position, PLC, SCADA etc. For more
information see page 21.
TEST INPUT FROM PLC/SCADA/DCS DIGITAL OUTPUT
OPERATOR CONTROLLED PRESS TO TEST
FAILSAFE OUTPUT MODE (Test switch must be in the ‘OFF’ position - default setting)

18
19 Sultan 234 Series
Admittance Smart Switch Series Manual
Rev 1.2, June 2008
1 2 3 4 5 6 7 8 9 10
HI
LO
FSH
FSL
OFF OFF
TEST
CAL
ON ON
1 2 1 2
S
E
N
S
I
T
I
V
I
T
Y
D
E
L
A
Y
1
5
2
7
10
11
8
3
6
4
9
1
2
3
4
5
6
7
8
9
10
11
Mounting Calibration switch CAL/OFF
Relay action selection
switch
FSH - FailSafe High
FSL - FailSafe Low
Sensitivity Potentiometer
Default 50% = 12 o’clock
HI / LO sensitivity switch
BLUE LED:
Blinking indicates calibration function is on.
Continuously ON indicates failed calibration.
AC Ground - must be used for
AC powered installations
GREEN LED: Power / Status
Blinks to indicate the functioning
is correct and no media is detected.
Continuously ON when media is detected.
Removable terminal block - plug in type
Delay Potentiometer (0-20 sec)
(Default 0 sec. at minimum
position)
Test input function select TEST/OFF
RED LED: Relay status
ON when relay coil is energised
RELAY
1. NC
2. COM
3. NO
COMMS DC-IN AC-IN
4. Test
12-30VDC
80-265 VAC
SMART PROBE REMOVABLE
TERMINAL BLOCK
7.
8.
N
9.
L1
10.
RS 485
5.
B
6.
A
Functionality Description (bold is default)
+-
12
signal
12 Signal indicator
SETUP PROCEDURE
SMART PROBE FUNCTIONALITY LAYOUT
(see page 14)
- Not used in Gladiator Admittance products
Other manuals for Gladiator
5
This manual suits for next models
5
Table of contents
Other Hawk Switch manuals
Popular Switch manuals by other brands

Endress+Hauser
Endress+Hauser Nivotester FTC625 operating instructions

Lantronix
Lantronix SISPM1040 L3 Series Web user guide

Oehlbach
Oehlbach UltraHD Switch 3:1 user manual

Extron electronics
Extron electronics SW MTP T 15HD A Setup guide

epico
epico 6in1 Aluminium Hub 8K manual

Cisco
Cisco WS-C2948G-GE-TX Configuration guide

Cisco
Cisco Catalyst WS-X6704-10GE datasheet

Eaton
Eaton TR7735 manual

Crestron
Crestron DigitalMedia DM-MD64X64 Supplemental guide

Alcatel-Lucent
Alcatel-Lucent OmniAccess 4504 installation guide

Clever Little Box
Clever Little Box Wi-View 300V user guide

D-Link
D-Link DES-3528 - xStack Switch - Stackable Cli reference guide