FailSafe Switch Contact Action
Relay 2
Setup Procedure
Contact Action
Relay Functions
Select the Switch point
The output relay will switch at the entered % value. The default value of 76% will be
suitable for detecting most media. For detection of lighter / fine products select a lower
% value and vice versa. For heavy materials a higher % setting may be required. When
the level or target falls below the sensors the relay will switch back on.
If product constantly falls in the sensor path choose a higher %.
Select the Switch Time Delay
Set the delay time for the relay switching on and off. If product constantly falls in
front of the sensor path allow a few seconds for ON delay.
Mounting
Do not proceed with this step unless the material or target position is well beneth
the line between the sender and receiver.
Select ‘Yes’ to start the mounting calibration. ‘Wait’ will be displayed during the
calibration for up to 30 seconds. Unit is now able to cancel the influence of the
mounting. The % reading on the back lit display has been zeroed with the existing
process conditions and the measurement history log has been cleared.
Always CAL MOUNT after changing application type or moving the transducers.
Select the required relay action
The Relay action can be defaulted to either ‘ON’ or ‘OFF’ and switch ‘ON’ or ‘OFF’
in response to an instrument failure.
Failsafe High - Relay is energised during normal operation and de-energised
during blocked conditions or unit failure.
Failsafe Low - Relay is de-energised during normal operation and energised
during blocked conditions or unit failure.
Choose Application Type
Alignment - Not used
Blocked Chutes - Configures the unit for blocked chute applications.
Boom Protection - Not used
Other - If you have a light/low dielectric
material which is failing to switch select this
mode and enter a low or lower sens. % value.
Note: If prompted to ‘re-calc app params’ this means you have already selected
Blocked Chute mode and the unit is asking if you wish to re-configure the settings..