Hawk 2000-RANGE-VALVE Series User manual

Overview
Gladiator Acoustic Switch Series
A Higher Level of Performance
Instruction Manual
www.hawkmeasurement.com
For more information, please visit >
SERIES 2000-RANGE-VALVE
Pressure and Level Transmitters

Overview
Gladiator Acoustic Switch Series
2
Introduction
Description Series 2000-RANGE-VALVE
The Series 2000-RANGE-VALVE is a unique combination of the series 2000 and ball Valve. The Series 2000-RANGE-VALVE
is specially designed for the pulp- and paper industry or similar, where clogging is a problem. The very compact construction of
the series 2000-RANGE-VALVE permits flush installation with the tank- or pipe wall. The transmitter part can be removed without
shutting down the process (for example: during cleaning or maintaining activities). The diaphragm (21) is flush with the tank/pipe
when the transmitter is pushed trough the valve and locked in its measuring position. All wetted parts are made of SS 316 (AISI).
Barometric Reference
The SERIES 2000-RAN-VALVE are in basic so-called “relative transmitter” which means that barometric changes will not affect
the zero (4 mA). The venting (4) is placed at the side of the electronic housing and is the barometric reference to atmospheric. The
venting must be kept clean.
SERIES 2000-RANGE-VALVE
Dimensional Drawing
Parts Description (1”)
1. Cover AISI 304
2. Push buttons + display (behind cover)
3. Cover with venting AISI 304
4. Venting PA
5. PG9 cable gland
6. Electronics housing AISI 304
7. Hexagon nut, SW 41 AISI 304
8. Stop AISI 316
9. O-ring (2x) VITON
10. Nipple, SW 41 (1” BSP M 2x) AISI 316
11. Safety Lock AISI 304
12. M4 Bolt AISI 304
13. O-ring VITON
14. Safety Lock AISI 316
15. M4 Bolt (2x) AISI 304
16. Threaded valve joint (1” BSP F) AISI 316
17. Valve body AISI 316
18. M8 Valve Bolt (4x) AISI 316
19. Weld on Nipple diam. 33,4 mm AISI 316
20. Foot with diaphragm AISI 316L
21. Diaphragm Protection AISI 316
Parts Description (1 1/2”) Material
7. Hexagon nut, SW 60 SS 304
10. Nipple, SW 57 (1½’’ BSP M 2x) SS 316
16. Threaded valve joint (1½” BSP F) SS 316
18. M 10 Valve bolt (4x) SS 316
19. Welded spud (outside 48,5 mm) SS 316
For welding and installing the 2000-RANGE-VALVE
read the next page (5) very carefully and follow exactly
the instructions.
Before Welding
1. Unlock the safety lock (14).
2. Unscrew nut (7)
3. Retract transmitter until it does not want any further
4. Unlock the safety lock(11).
5. Unscrew nut (10) from threaded valve joint (16).
6. Retract transmitter from valve
7. Protect diaphragm (21) very carefully
WARNING: Before opening the Valve, make sure that the
transmitter is locked.
WARNING: Read this manual before working with the product. For personal and system safety and for optimum product
performance. Make sure you thoroughly understand the contents before installing, using or maintaining the SERIES
2000-RANGE-VALVE.

Overview
Gladiator Acoustic Switch Series
3
Overview
Welding and Installing Transmitter
For welding and installing the Series 2000-RANGE-VALVE the instructions on the next page must be followed exactly. This is
extremely important to ensure a good working of the system.
Warning:
Improper installation may result in weld spud distortion
A. Installation weld on nipple (gure 1)
1. Remove the weld spud (19) from the valve by unscrewing the
four bolts( 18).
2. Cut a hole in the process vessel/pipe to accept the weld spud.
The hole should produce a tight fit when coupled with the weld
spud.
3. Prepare the vessel hole bevelling the edge to accept filler
material.
4. Position the weld spud in the vessel hole and tack six places.
The weld sequence is shown in figure 1.
WARNING
Excessive heat will distort the weld spud (19). Weld in sections as
shown in Figure 1. allow adequate cooling between passes. To
reduce the chances of distortion to the weld spud, use a heat sink
(22).
B. Installation Valve
1. Mount valve on the weld spud by using the auxiliary tool to
ensure the parts are in-line. Use silicone grease.
2. Tighten the valve bolts (18) (4x)
3. 3.Remove the auxiliary tool and make sure the valve and be
closed and opened easily.
4. Make sure valve is CLOSED.
Warning:
DO NOT DAMAGE THE DIAPHRAGM.
C. Installation transmitter (gure 2)
1. Remove the nipple (10) to the bottom of the transmitter part
as shown in figure 2. Use silicone oil or grease.
2. Make sure the O-ring (13) is properly located.
D. Figure 3
1. Make sure to correctly locate the O-ring (13) into the nipple
2. Position the transmitter into the threaded valve joint and
begin engaging the threads. The transmitter can be rotated
prior to seating enabling the user to optimize access to
calibration adjustments, cable entry and local indicator.
3. Tighten the nipple (10).t.
4. Lock the nipple (10) to the threaded valve joint (16) by means
of the safety lock (11) and two M4 bolts(12).
5. Valve must be opened (90°) VERY slowly.
E. Figure 4
1. Transmitter must be pushed trough valve until hexagon nut
(7) reaches the nipple (10).
2. Begin engaging the threads until stop (8) reaches nipple (10).
3. Tighten hexagon nut (7).
4. Lock the nut (7) to the nipple (10) by means of the safety lock
(14) and two M4 bolts (15)
SERIES 2000-RANGE-VALVE

4
Overview
WARNING:
BEFORE OPENING THE VALVE, MAKE SURE THE TRANSMITTER IS LOCKED.
BE SURE THE VALVE IS CLOSED WHEN HE TRANSMITTER IS RETRACTED FROM VALVE.
THIS IS EXTREMELY IMPORTANT OTHERWISE THE TRANSMITTER WILL PUSH OUT OF THE PROCESS.
Installing Transmitter 2000-RANGE-VALVE
The position of the valve depends on the welding position of the weld-on nipple. Before welding, locate weld-on nipple so that the
valve is in the right position.
* DO NOT DAMAGE THE THREAD.*
Mounting Position
When the transmitter is mounted horizontally, the cable gland MUST be pointed downwards.
Mounting Position Eect
All transmitters are calibrated in vertical position.
If the transmitter is mounted in a different position, there will be a little zero shift.
If the transmitter is mounted up, there is a zero shift (e.g. 4,03 mA instead of 4mA). If the transmitter is mounted down, there is a zero
shift (e.g. 3.97 mA instead of 4mA).
After installation of the transmitter the zero must be set to 4.00 mA with “P103” in the programming mode. This will not
affect the span.
Calibration
All transmitters are fully calibrated at the factory, to the conditions stipulated in users order. When the buyer has not requested
calibration, the transmitter will be calibrated at the highest span. It is advised to re-calibrate the transmitter after shipment.
Under the cover (3) you will find the terminal board.
The push buttons “Zero”, “Span” and “Prog” are under the other
cover (1).
External loads must be placed in the negative leg of the 2-wire
loop.
The figure left shows the wiring connection of the transmitter. The
2-wires must be connected to 3(-) and 4 (+) of the terminal board.
The signal wiring must be shielded and twisted pairs yield best
results. Do NOT run signal wiring in open trays with power wiring,
or near “heavy” electrical equipment (E.g.: Frequency controller or
heavy pumps).
Shielding must always be connected at the side of the power
supply. In case the mounting position is already connected
to earth (e.g. via the tank or pipe line) DO NOT connect the
instrument to earth. Please ensure that the instrument is not
connected to earth twice to prevent the occurrence of an
‘earth loop’. In applications with synthetic mounting positions the
case ground terminal (internal or external) must be connected to
earth.
SERIES 2000-RANGE-VALVE

5
Overview
Remaining
Digital Local Indicator
All transmitters from the Series 2000-RANGE-VALVE are standard equipped with a digital display.
In the standard execution the covers are “closed”. The three push buttons and the display are behind the cover (3).
As an option an “open” cover can be delivered to achieve the display can be used as a local display in the process. The full-scale
point may be set to any value between 0000 and 9999 (4 digit). (Option: “I” extra price).
CE-rulers
All our transmitters are manufactured according to the CE-rules. All transmitters are standard equipped with RFI filters. The influence
on Radio Frequency Interference between 10 MHz to 10 GHz is neglect able.
SERIES 2000-RANGE-VALVE
External Load
The minimum power supply is based on the total circuit resistance.
The maximum permissible load (Ri max.) in case of 24 Vdc is 600
Ω (Ohm).
By increasing the power supply, the external load can be increased
to 1200 Ohm / 36 Vdc. (see figure right).
RI max. = Power Supply - 12 Vdc
20 mA
Traceability of Manufacturing
The year of manufacturing of the transmitter can be traced as follows: take the first two numbers from the serial number that is
engraved in the transmitter and add 1970 to it.
For example: if the serial number is 3902123. The year of manufacturing is 1970 + 39 = 2009.
Software Revisions
Due to the improvements on the Series 2000-RANGE-VALVE, there are several software versions (revisions). For this reason it is
possible the transmitter you are working with does not support some options, which are discussed in this manual. This instruction is
applicable from software revision 8.01. After powering up, the transmitter will show the revision number on the display.

6
Overview
Functions of Push Buttons
The Series 2000-RANGE-VALVE can be programmed easily by
use of the 3 front panel pushbuttons (See picture right).
The display can show engineering units of:
mH2O, inH2O, bar and PSI.
The functions of the three pushbuttons will be explained below.
ZERO SPAN
PROG
PROG
ZERO
SPAN
mH20
inH20
bar
psi
This button has 2 functions:
1. It can be directly used for adjusting the zero (zero / 4mA), with or without a test pressure.
When the zero (4 mA) must be adjusted at 0 (atmospheric pressure), the button must be held
until the word “ZERO” appears on the display. The transmitter is now set to 4 mA.
2. Also, this button must be used for stepping down in the programming menu or to
decrease a value (-).
Note: For canceling the mounting position effect you have to use P103.
This button has 2 functions:
1. It can be directly used for adjusting the span (20 mA), when using a test pressure (air). When
a test pressure (e.g. 2 bar) is supplied to the transmitter, the button must be held until the
word “SPAN” appears on the display. The transmitter is adjusted at 20 mA now. The span can
also be adjusted without test pressure (see P102).
2. Also, this button must be used for stepping up in the programming or to increase a value (+).
This button has 2 functions:
1. It is used to adjust the 14 Programming Points (P101 to P114). Push it once and P100 is
displayed, use the [h] (SPAN) to step to P101 etc.
2. This button must also be used for confirming the adjustments (enter).
For example if you want to change the adjustment in bars (P104), the following steps must be
taken:
1. Push on [PROG] till “100” appears on the display.
2. Push on [SPAN] 4 times to go to point “P104” (adjustment pressure unit).
3. Push [PROG] to confirm this.
4. Push several times on [h] (SPAN) to reach 3 (= bar). See also the conversion table (page 11).
1 = mWC, 3 = bar, 5 = PSI, 11 = inch WC
5. Confirm this by pushing once at [PROG].
The transmitter is now adjusted to read in “bar.
ZERO SPAN
PROG
PROG
ZERO
SPAN
mH20
inH20
bar
psi
ZERO
SPAN
ZERO SPAN
PROG
PROG
ZERO
SPAN
mH20
inH20
bar
psi
ZERO SPAN
PROG
PROG
ZERO
SPAN
mH20
inH20
bar
psi
SERIES 2000-RANGE-VALVE

7
Overview
Programming Points (P101 - P116)
Reading On The Display
On the standard built-in display several values can be shown.
During the programming of the transmitter the display shows all
the information that is needed.
When the transmitter is in the process the display gives all the
information of the process pressure or temperature.
On the display the following units can be showed: mH2O, inH2O,
bar and PSI (see also P104 and P109).
N.B.: The standard transmitter is supplied with two “closed”
covers shielding the buttons and the display. As an option an
“open” cover (IP 65) can be fitted. The display can then be used
as a local process display. (Option: “I” extra price). The full scale
can be set between -9999 and 9999 (4 digit).
Programming points:
P101 Zero adjustment (4 mA)
P102 Span adjustment (20 mA)
P103 Cancel mounting position effect
P104 Adjustment pressure unit (See Conversiontable)
P105 4-20 mA *)
20-4 mA (Reverse output)
P106 Adjustment damping (0 to 25 sec)
P107 Indication of process temp. (Read out on display)
P108 0 = °C (*)
1 = °F
P109 Read out on display:
Curr (0) = current (4 - 20 mA) (*)
Unit (1) = pressure unit (conversiontable)
PerC (2) = percentages
TenP (3) = temperature
Hect (4) = hectoliters
CB n (5) = Cubic meters
Ltr (6) = Liters
P110 Simulation of current
P111 Linearisation
0 = no linearisation (*)
1 = cylindrical tank
2 = vertical tank with cone
3 = vertical tank with spherical cone
P112 Specific density
P113 Write Protection
P114 Response time from push buttons
P115 Service-menu
P116 Service-menu
The following points can be adjusted by means of the three push
buttons.
For an explanation of these points see page 10 to 16 of this
manual.
To change one of these points you have to push on [PROG] until
“100” appears on the display.
To go to from a lower program (P101) to a higher one (P102),
push on button [h] (SPAN).
To confirm the adjustments you always have to press on [PROG].
*) Standard adjustments ex works.
SERIES 2000-RANGE-VALVE
ZERO SPAN
PROG
PROG
ZERO
SPAN
mH20
inH20
bar
psi

8
Overview
SERIES 2000-RANGE-VALVE
Explanation Programming Points P101 to P116
Zero Adjustment (4 mA)
The transmitter as standard is adjusted to 4.00 mA at atmospheric pressure. It is also possible to adjust a zero-
suppression or elevation.
For example: zero elevation of 1 mWK.
1. Push at [PROG] until “100” is shown on the display.
2. Push once at [h] / SPAN till “101”.
3. Confirm this by pushing [PROG].
4. Now the display will show 0.00 mH2O. Push at [h] till 1.00 mH2O is on the display.
5. Confirm with [PROG].
6. The output of the transmitter will be lower than 4 mA. The output at atmospheric pressure will be for example 3.68 mA.
When a pressure of 1 mWC is applied on the diaphragm the output will be 4.00 mA.
The elevation can be canceled by pushing at [ZERO] till zero disappears out of the display. The transmitter is now adjusted
at 4 mA at atmospheric pressure.
P101
Span Adjustment (20 mA) Without Test Pressure
Before adjusting the span take care the right pressure unit is selected. (See also P104 and P109).
Example: Adjustment of the span at 0 - 2 bar.
First off all, the pressure unit must be adjusted at “bar”. (See P104 and P109).
1. Push [PROG] till “100” is shown on the display.
2. Push twice at [h] / SPAN until “102” is on the display.
3. Confirm this by pushing [PROG].
4. Push [SPAN] (+) or [ZERO] (-) to select the measuring range that is required.
5. Confirm by pushing [PROG]. The transmitter is adjusted now.
N.B.: P102 is the adjustment of the total span. When a “compound” range must be adjusted (for example -1 till +3 bar), a
span of 4 bar must be programmed. At P101 (ZERO,4 mA), -1 bar must be adjusted. Now the transmitter is adjusted at: - 1
bar = 4 mA and +3 bar = 20 mA.
N.B.:
It is not possible to show values larger than ‘9999’ or smaller than ‘–9999’ on the display. In this case the display will show:
- - - - For values larger than ‘9999’.
- - - - For values smaller than ‘–9999’.
As long as the display shows “- - - - “, the value will not be saved by pressing “PROG”.
P102

9
Overview
SERIES 2000-RANGE-VALVE
Cancel Mounting Position Eect
All transmitters are calibrated vertically. When a transmitter of the Series 2000-RANGE-VALVE is installed horizontally,
there will be a small “mounting effect” on the zero
(4 mA). For example the transmitter shows 4.03 mA instead of 4.00 mA. This can be easily canceled with P103. In P103
there are three options:
1. ESC:
Nothing can be changed.
Leave without doing anything. (confirm with PROG).
2. RESE T:
Use this option when you are not sure if P103/SET has been done in a proper way. (confirm with PROG).
when using this option the original factory setting will be valid.
3. SET:
Canceling mounting position effect. (confirm with PROG).
When “SET” is selected the transmitter is automatically adjusted at 4.00 mA. The span will not be affected.
CAUTION: Do not apply pressure while executing “cancel mounting position effect”
N.B.:
From revision 2 the description above is valid. Transmitters working with software revision 1 will direct process cancel
mounting position.
P103
Adjustment Pressure Unit On Display (See Conversion Table)
P104
104 Conversion Factor Display
11.000 mH2O (mWC)*
21000 m H2O (mm WC)
30.09806 bar*
498.0665 mbar
51.4223 PSI*
60.0967 Atm
79.80665 KPa
80.009807 MPa
90.1 Kgf/cm2
10 73.556 mm HG
11 39.37 inH20 (“WC)*
12 2.895906 “HG
Several engineering units can be shown on the display
by using a conversion factor. (See conversion table).
Four engineering units will light up on the display
(mH2O, inH2O, bar and PSI).
N.B.: To show one of the engineering units, P109 must
be adjusted at 1 (= pressure unit).
This will be explained with an example (e.g. bar):
1. Push at [PROG] till “100” is shown on the display.
2. Push 4 times at [h], go to [P104].
3. Push at [PROG] to confirm this.
4. Push at [h] / [SPAN] and adjust at 3 (= bar).
1 = mH2O (=mWC), 3 = bar, 5 = PSI, 11 = inch WC.
5. Confirm with [PROG].
The transmitter will now read out in bars.
Conversion Table:
*) Pressure units that can be shown on the display. When
the value of the highest range is larger than 9999, “NA” will
appear in the display (Not Applicable). Another unit must be
chosen.

10
Overview
SERIES 2000-RANGE-VALVE
Reverse Output (20 - 4mA)
The transmitter as standard is adjusted to 4-20 mA.
Push on [PROG] and go to P105.
Push once at [h] to change the output to 20-4 mA (Reverse output).
Push at [PROG] to confirm this.
Now the transmitter will give 20 mA at atmospheric pressure
P105
Adjustment Samping (0 till 25 sec)
In P106 an electronic damping can be adjusted between 0 and 25 seconds.
This can be done with the push buttons [h] (up) and [i] (down).
Always confirm by pushing once at [PROG].
P106
Indication of Process Temperature (Read Out On Display)
1. Push [PROG] until “100” is shown on the display.
2. Push 7 times at [h], go to [P107].
3. Push [PROG] to confirm this. Now the process temperature appears on the display (Indication: +/-2oC).
This will remain on the display. To get the actual pressure back on the display you have to push again on P107 until the
actual pressure appears on the display again.
P107
Temperature In oC OR oF
The temperature of the transmitter is standard adjusted at oC (“DEGR”). When pushing at [h] in P108, this will change into
oF (“FAHR”).
Always confirm by pushing once at [PROG].
P108
Read Out On Display
Curr (0) = current (4 - 20 mA)
Unit (1) = pressure unit (See conversion table)
PErC (2) = percentages (0 - 100%)
TEnP (3) = temperature (oC of oF)
HECt (4) = hectoliter (only in combination with P111)
Cb n (5) = Cubic meter (only in combination with P111)
Ltr (6) = Liters (only in combination with P111)
As standard the transmitter is delivered with read out in mA (0). To change this, follow the next steps:
1. Push [PROG] until “100” is shown on the display.
2. Push 9 times at [h] / SPAN till “109” appears on the display.
3. Confirm with [PROG].
4. Push once at [h].
5. Push [PROG] to confirm this.
The transmitter will now read mH2O (mWC).
The pressure unit can be changed with the conversion table in “P104”.
1 = mH2O (=mWK), 3 = bar, 5 = PSI, 11 = inch WK.
Also the read out can be 0 - 100%. In this case select “P109”, option 2.
P109

11
Overview
Simulation of Current (4 - 20 mA)
The transmitter can be used as a simulator of a current between 4 - 20 mA.
This can be done in P110 with the push buttons [h] and [h].
The user can perform a current simulation (Curr) or a pressure simulation (Unit).
Current-simulation (Curr)
To perform a current-simulation follow the next steps:
1. Push [PROG] until “100” is shown on the display.
2. Push 10 times at [h] / SPAN till “110” appears on the display.
3. Confirm with [PROG].
4. The display will readout ‘Curr’
5. Confirm with [PROG].
6. The display shows ‘4.00’. Push [PROG] and the output changes to 4.00 mA.
7. By pushing [h] / SPAN or [i] / ZERO, you can change the value on the display. The output value will change as soon as
the [h] / SPAN OR [i] / ZERO button is released.
8. Pressing the [PROG]-button again will exit the simulation.
Pressure-simulation (Unit)
To perform a pressure-simulation follow the next steps:
1. Push [PROG] until “100” is shown on the display.
2. Push 10 times at [h] / SPAN till “110” appears on the display.
3. Confirm with [PROG].
4. The display will readout ‘Curr’
5. Press [h] / SPAN once
6. The display will readout ‘Unit’.
7. Confirm with [PROG].
8. The display shows a pressure value. Push [PROG] and the output changes to a mA-output corresponding with the
range entered in menu P101 and P102.
9. By pushing [h] / SPAN or [i] / ZERO, you can change the value on the display. The output value will change as soon as
the [h] / SPAN OR [i] / ZERO button is released.
10. Pressing the [PROG]-button again will exit the simulation.
Note:
• The values that can be entered using the pressure-simulation are related to the adjustments in menu P101 and P102.
These values are also the minimum and maximum values.
• For HART-transmitters: this menu will not work when the device is operating in multi-drop mode.
P110
SERIES 2000-RANGE-VALVE

12
Overview
Linearisation
0 = no linearisation
1 = cylindrical tank (horizontal)
2 = tank with bottom cone
3 = tank with spherical bottom
As standard the transmitter is delivered without linearisation (= 0). However, for a horizontal tank or a tank with a bottom
cone, a linearisation can be applied to achieve the current signal (mA) is equal to the level in the tank. All values must be
programmed in meters.
P111
Cylindrical horizontal tank Cylindrical tank with cone-shaped ends
Linearisation horizontal tank (Cilindric)
Push [PROG] until “100” is shown on the display.
2. Push 11 x at [h] / SPAN till “111” appears. (Confirm with [PROG])
3. Push [h] once. (Confirm with [PROG])
4. Enter the height (H1) of the tank in meters. (Confirm with [PROG])
5. Enter the same height (H2) of the tank in meters. (Confirm with [PROG])
6. Enter the length (L) of the tank. For a “ball” or cone shaped tank, take the cylindrical length plus the length of 1 “ball”
cone. (Confirm with [PROG])
7. Enter H3 in meters if the transmitter is installed like in the left picture. Enter 0m when the transmitter is installed like in
the right picture.
8. Enter the percentage of the actual “full” level (for example 80%).
(Confirm with [PROG]).
SERIES 2000-RANGE-VALVE

13
Overview
Cylindrical horizontal tank Cylindrical tank with cone-shaped ends
Linearization horizontal tank (Elliptic)
1. Push [PROG] until “100” is shown on the display.
2. Push 11 x at [h] / SPAN till “111” appears. (Confirm with [PROG])
3. Push [h] once. (Confirm with [PROG])
4. Enter the height (H1) of the tank in meters. (Confirm with [PROG])
5. Enter the height (H2) of the tank in meters. (Confirm with [PROG])
6. Enter the length (L) of the tank. For a “ball” or cone shaped tank, take the cylindrical length plus the length of 1 “ball”
cone. (Confirm with [PROG])
7. Enter H3 in meters if the transmitter is installed like in the left picture. Enter 0m when the transmitter is installed like in
the right picture.
8. Enter the percentage of the actual “full” level (for example 80%). (Confirm with [PROG]).
Note
If the height (H) of the tank is 1 meter and the maximum level in the tank is 0.8 meter the percentage (point 5) must be set
at 80%. The calibration at P102 must be adjusted at: 1 meter (if s.g. equals 1).
SERIES 2000-RANGE-VALVE

14
Overview
Linearisation Vertical Tank With Cone
1. Push [PROG] till “100” appears on the display.
2. Push 11 times at [h] till “111” appears. (Confirm with [PROG])
3. Push twice at [h]. (Confirm with [PROG])
4. Enter height (H1) of the tank (= actual level).
(Confirm with [PROG]).
5. Enter diameter (D) of tank. (Confirm with [PROG])
6. Enter height (H2) of cone. (Confirm with [PROG])
7. Enter the height (H3) from the bottom of the tank to the topside
of the diaphragm (or weld-on nipple). (Confirm with [PROG]).
8. Enter the percentage of the actual “full” level (for example 80%).
(Confirm with [PROG]).
Linearisation Vertical Tank With Spherical Cone
(From Software Revision 3)
1. Push [PROG] till “100” appears on the display.
2. Push 11 times at [h] till “111” appears. (Confirm with [PROG])
3. Push three times at [h]. (Confirm with [PROG])
4. Enter height (H1) of the tank (= actual level).
(Confirm with [PROG]).
5. Enter diameter (D) of tank. (Confirm with [PROG])
6. Enter height (H2) of cone. (Confirm with [PROG])
7. Enter the height (H3) from the bottom of the tank to the topside
of the diaphragm (or weld-on nipple). (Confirm with [PROG]).
8. Enter the percentage of the actual “full” level (for example 80%).
(Confirm with [PROG]).
Note
When the specific gravity of the fluid is unequal to 1 and you do not want to use option 4, you must take care of it by defining the
calibration of the transmitter.
Calibration (see P102) = Height of the level x Specific Gravity.
SERIES 2000-RANGE-VALVE

15
Overview
Specic Density
If the specific gravity of the medium differs from 1 kg/dm3, you can enter the real density of the medium in P112. When this
option is used, in menu P102, the ‘true’ height of the tank must be entered.
P112
Write Protection
The Series 2000-RANGE-VALVE with HART-Protocol can be protected for writing (Write Protection). This is possible for
two kinds of writings:
- Changes via the Display (“Lo.Pr” = Local Protection).
- Changes via external HART configuration software by the Hand-held terminal or the P.C. (“Co.Pr.”= Communication
Protection).
Standard, the transmitter is set to no-write protection.
Adjustment Local Protection
1. Push [PROG] till “100” appears on the display.
2. Push [h] / SPAN 13 times till “113” appears on the display.
3. Push [PROG] to confirm. (“Lo.Pr.” appears on the display).
4. Push [h]/[i] for adjusting to “ON” or “OFF”.
5. Push [PROG] to confirm.
Adjustment Communication Protection
1. Push [PROG] till “100” appears on the display.
2. Push [h] / SPAN 13 times till “113” appears on the display.
3. Push [PROG] to confirm. (“Lo.Pr.” appears on the display).
4. Push once more at [PROG]. (“Co.Pr.” appears on the display).
5. Push [h]/[i] for adjusting to “ON” or “OFF”.
6. Push [PROG] to confirm.
N.B. When Lo.Pr. is set to “ON”, the display shows 104, 105, 107, 108, 109 and 111 and the adjusted values of the
parameters. Afterwards “PROT” (Protected) is shown.
Both protections can be adjusted at the same time, independent from each other.
P113
Response Time From Push Buttons
This option can only be used from software version 8.01. The response time from the push buttons can be adjusted from
0,0 till 5,0 seconds.
P114
Service Menu
Use only under order of manufacturer.
P115
Service Menu
Use only under order of manufacturer.
P116
SERIES 2000-RANGE-VALVE

16
Overview
Programming The Series 2000-RANGE-VALVE
Programming With The Hand Held Terminal
The Series 2000-RANGE-VALVE can be programmed very easily with the Hand Held Terminal (HHT) from the “HART Foundation” or
the HHT from “Rosemount” (type 275 Hart Communicator).
The HART (Highway Addressable Remote Transducer) Communicator provides a common communication link to all HART-
compatible, microprocessor-based instruments.
WARNING: When using a HHT to function properly, a minimum resistance of 250 Ohms must be present in the loop of the 2-wire
system. (See figure below).
Programming With DTM
There is an instruction manual available which is a guide for installing and using the HAWK Series 2000-RANGE-VALVE (option - ‘H’ HART)
DTM. This DTM is developed to make configuration changes of HAWK Series 2000-RANGE-VALVE (option - ‘H’ HART) transmitters
easy.
This DTM can be used with almost every FDT-container.
To be able to install the DTM HAWK Series 2000-RANGE-VALVE (option - ‘H’ HART) on your system, you have to download the installation
file. This file can be downloaded from the HAWK Instruments site or via the following link: www.hawkmeasure.com
The installation can be started by opening the “DTM HAWK Series 2000 HART V1-2-0-1.zip” and continue by opening the “DTM
HAWK Series 2000 HART V1-2-0-1.exe” file.
Programming With PDM
There is also a Device Description (DD) available for the Series 2000-RANGE-VALVE (option - ‘H’ HART). This DD can be used for
configuring a Series 2000-RANGE-VALVE (option - ‘H’ HART) transmitter using Simatic PDM. You can download this DD (in zip file) from the
following link: www.hawkmeasure.com.
SERIES 2000-RANGE-VALVE

Overview
Gladiator Acoustic Switch Series
Overview
All company or product names are registered trademarks or trademarks of their respective owners.
Additional product warranty and application guarantees upon request.
Technical data subject to change without notice.
SERIES 2000-RANGE-VALVE
Precautions and Warnings
We herewith give a list of some precautions and warnings concerning the application and installation of the electronic pressure – and
level transmitters, SERIES-RANGE-VALVE
• Check if the specifications of the transmitter meet the needs of the process conditions
BE SURE THE VALVE IS CLOSED WHEN TRANSMITTERIS RETRACTED FROM VALVE
• When the Series 2000-RANGE-VALVE is used as a level transmitter, be aware of the place where the transmitter is mounted. Here
are some suggestions:
1. DO NOT mount a level transmitter in- or near filling or discharging pipes.
2. In case of automatic cleaning systems or hand cleaning: never point the water jets on the diaphragm, take necessary steps
to avoid this. Guarantee will not be granted.
• When the Series 2000-RANGE-VALVE is used as a pressure transmitter, be aware of the following points:
1. Rapid closing valves in combination with high flow velocity will cause water hammer(spikes) and can destroy the transmitter.
DO NOT mount a transmitter near such valves, always a few pipe bends away up or down stream (avoid suction).
2. Install a pressure transmitter a few pipe bends away from pumps, as well on the suction or pressure side of the pump
• WELDING ADVISEMENT:
When using the SERIES 2000-RANGE-VALVE the welding advisements on page 4/5/6 must be followed exactly. This is very
important to prevent distortion of the weld spud.
• The diaphragm of the SERIES 2000-RANGE-VALVE is protected with a special protection cap. Protect the diaphragm until
installation takes place, to prevent damaging of the diaphragm.
• As soon as the wiring is brought inside through the PG9 cable gland and connected to the terminal board, make sure the cable
gland is tightly fixed, so that moisture cannot enter into the electronic housing.
• NEVER unscrew the venting(3), because it is especially designed to prevent moisture from entering into the electronic housing. If the
ambient conditions are very wet, we advise to use a venting through the cable. A special vented cable can be delivered on request.
• Avoid high pressure water-jets pointed at the venting.
• Turn the cover (1) hand-tight, so that moisture cannot enter into the electronic housing.
• WARRANTY: The warranty is 1 year from purchase date.
HAWK does not accept liability for consequential damage of any kind due to use or misuse of the Series 2000. Warranty will be
given, to be decided by the manufacturer. Transmitter must be shipped prepaid to the factory on manufacturers authorization.
• NOTE: HAWK reserves the right to change its specifications at any time, without notice. HAWK is not an expert in the customer’s
process (technical field) and therefore does not warrant the suitability of its product for the application selected by the customer.
Hawk Measurement Systems
(Head Oce)
15 - 17 Maurice Court
Nunawading VIC 3131, AUSTRALIA
Phone: +61 3 9873 4750
Fax: +61 3 9873 4538
Hawk Measurement
5010 Gateway Drive, Medina, OH 44256, USA
Phone: +1 888 HAWKLEVEL (1-888-429-5538) /
+1 978 304 3000 / +1 877-356-5463
Fax: +1 978 304 1462 / +1 330-331-7172
For more information and global representatives: www.hawkmeasurement.com
Table of contents
Other Hawk Transmitter manuals
Popular Transmitter manuals by other brands

BD Sensors
BD Sensors DX14A-DMK 456 operating manual

BWI Eagle
BWI Eagle AIR-EAGLE FM2 43-1000-RB-N4-120VAC Product information bulletin

Consult IX
Consult IX CellWizard WTX-05 user manual

Magnetrol
Magnetrol Kotron RF 2-Wire Series Instruction manual and parts list

SkyZone
SkyZone RC832 instruction manual

Bacharach
Bacharach GDX-350 instructions

Aventura
Aventura FBR-4V2AS-TX instruction manual

Inovonics
Inovonics EchoStream ShatterPro EE1247 Installation and operation

GRAUPNER
GRAUPNER S1031 manual

AudioLink
AudioLink JM-STU01 Quick start user guide

Rosslare
Rosslare SA-26 installation instructions

Johnson Controls
Johnson Controls H -68P3 Series installation instructions