Hawk Intelligent 2000-SAN Series User manual

Overview
Gladiator Acoustic Switch Series
A Higher Level of Performance
Instruction Manual (“HART”)
www.hawkmeasurement.com
For more information, please visit >
Series 2000 - SAN
Series 2000
Series CER - 2000
Series 2000 - Hydrobar
“Intelligent”
Pressure and Level Transmitters

2
Overview
Series 2000 HART
Table of Contents
1. Introduction 3
1.1 Description Series 2000-SAN 3
1.3 Description Peramic “S” (Series CER 2000) 3
1.2 Description Series 2000 3
1.4 Description HYDROBAR (Series 2000 - Hydrobar) 3
1.5 Barometric Reference 3
2. Dimensional Drawings 4
2.1 2000-SAN 4
2.2 2000 4
2.3 CER 2000 4
2.4 2000-Hydrobar 5
3. Installation transmitter 6
3.1 Installing Weld-On Nipple 6
3.2 Installing Transmitter Series 2000-SAN 6
3.3 Installing Transmitter Series 20006
3.4 Installing Transmitter Series CER-2000 7
3.5 Mounting Position 7
3.6 Mounting Position Effect
(Series 2000 and Series 2000-SAN) 7
3.7 Installing Transmitter Series 2000-Hydrobar 7
3.8 Calibration 7
3.9 Wiring 7
4. Remaining 8
4.1 Digital Local Indicator 8
4.2 CE / EMC - RULES 8
4.3 External Load 8
4.4 Intrinsically Safe and NON SPARKING (Ex version) 8
4.5 Special Instructions for Safe Use 10
4.6 Tracebility Year of Manufacturing 10
4.7 Software Revisions 10
5. Function of Push Buttons 11
6. Programming Points (P101 - P114) 12
7. Reading On The Display 12
8. Explanation Programming Points P101 to P114 13
P101 Zero Adjustment (4 mA) 13
P102 Span Adjustment (20 mA) Without Test Pressure 13
P103 Cancel Mounting Position Effect 14
P104 Adjustment Pressure Unit On Display
(See Conversion Table) 14
P105 Reverse Output (20 - 4mA) 15
P106 Adjustment Samping (0 till 25 sec) 15
P107 Indication of Process Temperature
(Read Out On Display) 15
P108 Temperature In oC OR oF 15
P109 Read Out On Display 15
P110 Simulation of Current (4 - 20 mA) 16
P111 Linearisation 17
Linearization horizontal tank (Elliptical) 18
Linearisation Vertical Tank With Cone 18
Linearisation Vertical Tank With Spherical Cone
(From Software Revision 3) 18
P112 Specific Density 19
P113 Write Protection 19
P114 Response Time From Push Buttons 19
P115 Service Menu 19
P116 Service Menu 19
9. Programming The Series 2000 20
9.1 Programming With The Hand Held Terminal 20
9.2 Programming With DTM 20
9.3 Programming With PDM 20
10. Specications 21
11. Precautions and Warnings 22
Attachment: EC-Declaration of conformity 22

Overview
Gladiator Acoustic Switch Series
3
1. Introduction
The SERIES 2000 and SERIES 2000-SAN are solid-state pressure- and level transmitters based upon a bridge resistive silicon
sensor, with a very high burst pressure. The sensor element is mounted in a stainless steel foot. A very strong stainless steel
“flush” diaphragm protects the sensor from the process medium. Special oil fills the chamber surrounding the sensor and transfers
pressure from the flush mounted diaphragm to the sensor.
Pressure exerted on the sensor element creates a very small deflection of the silicon substrate and bridge network. The resulting
strain in the silicon resistors causes a change in the bridge resistance that is proportional to the pressure applied. The transmitter
electronics detects this change in bridge resistance and converts it into 4-20 mA. The amplifier system is based on a single
Integrated Circuit, which ensures a perfect linearity in the 4-20 mA output.
Together with the Flush Diaphragm Technology (FDT) the long term stability is perfect.
The Series CER-2000 are “All Stainless” pressure transmitters based on a ceramic pressure cell, with very high burst pressure.
These transmitters do not have oil filling.
Series 2000 HART
1.1 Description Series 2000-SAN
The SERIES 2000-SAN are specially
designed with a flush mounted
diaphragm so they fully meet the
needs of the food, chemical and
pharmaceutical industries.
The Series 2000-SAN is available
as 3-A version (Sanitary Standard -
Option G153) and EHEDG (Sanitary
standard – Option G150).
Standard the wetted parts are made of
SS 316 , other materials are available.
Various process connections can be
delivered, such as Tri-Clamp(1,5”, 2”
and 3”), SMS (1,5” and 2”), dairy milk
couplings (NW25,40 and 50), flanges
and very sanitary weld-on nipples (ø
62 and 85 mm).
1.2 Description Series 2000
The SERIES 2000 are specially
designed for the pulp- and paper
industry or similar, where clogging
is a problem. The very compact
construction of the SERIES 2000
permits flush installation with the tank-
or pipe wall. Standard the wetted parts
are made of SS 316, other materials are
available.
All transmitters are fully temperature
compensated, which means that
various process temperatures have
nearly no effect on the accuracy of the
output signal. When a failure occurs,
the transmitter is repairable. However,
for optimum accuracy the transmitter
has to be send back to the factory.
1.3 Description Peramic “S” (Series CER 2000)
The Series CER-2000 are pressure
transmitters based on a ceramic
pressure cell, which can be used for
all gauge- and absolute pressure
measurement on steam (with syphon),
liquids and gases.
These transmitters do not have oil
filling.
1.4 Description HYDROBAR (Series 2000 - Hydrobar)
The series 2000-Hydrobar is a complete range of submersible
level transmitter for top mounting. The 2000-Hydrobar can be
used in fluids like waste water, mud, pulp and chemicals. As
standard the cable material is polyethylene. The connections for
the wetted parts from the 2000-Hydrobar to the cable are from
Viton® FKM.
1.5 Barometric Reference
The SERIES 2000-SAN are “relative transmitters” which means
that barometric changes will not affect the zero (4 mA). The
venting (4) is placed at the side of the electronic housing and is
the barometric reference to atmospheric. The venting must be
kept clean.
Series 2000-SAN
Series 2000
Series CER 2000

Overview
Gladiator Acoustic Switch Series
4
Overview
2. Dimensional Drawings
2.1 2000-SAN
Parts Descriptions Material
1. Cover SS 304
2. Pushbutton + Display
3. Cover with venting SS 304
4. Venting PA
5. PG9 Cable Gland
6. O-ring (2 pcs) EPDM
7. Electronics housing SS 304
8. Foot SS 316
9. Lock ring SS 304
10. Weld-on nipple SS 316 L
11. Packing PTFE
12. Diaphragm SS 316 L
2.2 2000
Parts Descriptions Material
1. Cover SS 304
2. Pushbutton + Display
3. Cover with venting SS 304
4. Venting PA
5. PG9 Cable Gland
6. O-ring (2 pcs) EPDM
7. Electronics housing SS 304
8. Foot with cooling fins SS 304
9. O-ring Viton
10. O-ring Viton
11. M8 bolt SS 316
12. Diaphragm and ring SS 316
13. Weld-on nipple ø 33 mm SS 316 L
Parts Descriptions Material
1. Cover SS 304
2. Pushbuttons + Display
3. Cover with venting SS 304
4. Venting PA
5. PG9 Cable Gland
6. O-ring (2 pcs) EPDM
7. Electronics housing SS 304
8. Foot with cooling fins SS 316
9. Ceramic sensor Al2O3 (96%)
10. Process connection ½ “ BSP (M)
DIN 16288 SS 316
NOTE The ceramic sensor is sealed with an O-ring (VITON).
Other O-ring materials can be applied (on request).
2.3 CER 2000
Series 2000 HART

5
Overview
2.4 2000-Hydrobar
Parts Descriptions Material
1. Cover SS 304
2. Push buttons + Display
3. Cover with venting SS 304
4. Venting PA
5. PG9 Cable Gland
6. 2x O-ring EPDM
7. Electronics housing SS 304
8. 2x Connection to cable SS 316
9 Cable with venting tube PE
10 Foot SS 316
11. Diaphragm protection cap PE
12. Diaphragm SS 316L
13. Mounting bracket (2 holes ø 6,5 mm) SS 304
NOTE The wetted parts of the 2000-hydrobar are sealed with an O-ring (VITON).
Other O-ring materials can be applied (on request).
Series 2000 HART

6
Overview
3. Installation transmitter
The diaphragm of the transmitter is protected with a special protection cap. Protect the diaphragm until installation takes place.
* DO NOT DAMAGE THE DIAPHRAGM. *.
3.1 Installing Weld-On Nipple
A skilled machinist or certified welder should perform installation of the weld-on nipple.
Weld Argon, MIG or TIG with the smallest welding pin.
1. Cut a hole in the process vessel/pipe to accept the weld-on nipple. The hole should produce a tight fit when coupled with the
weld-on nipple.
2. Prepare the vessel hole by beveling the edge to accept filler material.
3. Remove the weld-on nipple from the transmitter.
4. Remove the PTFE packing of the SERIES 2000-SAN.
5. Position the weld-on nipple in the vessel hole and tack six places. The weld sequence is shown in the figure above.
6. Weld the weld-on nipple in place using 0,03 to 0,045 in. (0,762 to 1,143 mm) stainless rod as filler material in the beveled area.
Adjust amperage for penetration.
7. Remove mandrel after the welding operation.
WARNING
Improper installation may result in distortion of the weld-on nipple.
Excessive heat will distort the weld-on nipple. Weld in sections as shown
in the figure left. Allow adequate cooling between passes. To reduce the
chances of distortion to the weld-on nipple, use a mandrell.
(SERIES 2000-SAN Part.nr. 1019)
(SERIES 2000 Part.nr. 1016)
The position of the electronic housing (SERIES 2000) is fixed by the
welding position of the weld-on nipple. Before welding, locate weld-on
nipple so that the cable entry and the venting are in the right direction.
3.2 Installing Transmitter Series 2000-SAN
1. Improper installation at the packing can cause a process leak.
2. Make sure to correctly locate the packing within the weld-on nipple.
3. Position the transmitter into the weld-on nipple and begin engaging threads. The transmitter can be rotated prior to seating
enabling the user to optimize access to calibration adjustments, cable entry, and local indicator.
4. Once Lock ring (9) has been hand tightened, it must be tightened with an additional turn with adjustable pliers (± 1/8”).
3.3 Installing Transmitter Series 2000
1. After welding, clean up edges, take care of the inside nipple wall.
2. Make sure the O-rings (10) and (11) are properly located. Improper installation at the O-ring can cause a process leak.
3. Apply silicone grease to the O-ring(10), diaphragm ring and the hole inside wall of the weld-on nipple, this prevents galvanic cell
corrosion between transmitter and nipple inside.
4. Install the transmitter and fix it with the SS M8 bolt.
Series 2000 HART

7
Overview
3.4 Installing Transmitter Series CER-2000
The position of the electronic housing is depends on the welding position of the weld-on nipple. Before welding, locate weld-on nipple
so that the cable entry and the venting are in the right direction.
* DO NOT DAMAGE THE THREAD. *.
3.5 Mounting Position
When the transmitter is mounted horizontally, the cable gland MUST be pointed downwards.
3.6 Mounting Position Eect (Series 2000 and Series 2000-SAN)
All transmitters are calibrated in vertical position.
If the transmitter is mounted in a different position, there will be a little zero shift.
If the transmitter is mounted up, there is a zero shift (e.g. 4,03 mA instead of 4mA). If the transmitter is mounted down, there is
a zero shift (e.g. 3.97 mA instead of 4mA). After installation of the transmitter the zero must be set to 4.00 mA with “P103” in the
programming mode.
This will not affect the span.
3.7 Installing Transmitter Series 2000-Hydrobar
The diaphragms are protected by a special protection cap (PE). Do not remove this cap. When clogging is a problem, please contact
HAWK for other solutions. DO NOT DAMAGE THE DIAPHRAGM.
3.8 Calibration
All transmitters are fully calibrated at the factory, to the conditions stipulated in users order. When the buyer has not requested
calibration, the transmitter will be calibrated at the maximum span.
3.9 Wiring
The push buttons “Zero”, “Span” and “Prog” are under the other cover (1).
External loads must be placed in the negative leg of the 2-wire loop.
The figure right shows the wiring connection of the transmitter. The 2-wires must
be connected to 3(-) and 4 (+) of the terminal board.
The transmitter must always be connected to earth.
The transmitter must be connected with standard two wire shielded cable.
Do NOT run signal wiring in open trays with power wiring, or near “heavy” electrical
equipment (E.g.: Frequency controller or heavy pumps). Shielding must always
be connected at the side of the power supply. In case the process connection is
already connected to ground (e.g. via the tank or pipe line) Do not connect the
instrument to ground. Please ensure that the instrument is not connected to ground
twice to prevent an ‘earth loop’. In applications with synthetic process connections,
the enclosure (internal or external) must be connected to ground. ensure that the
instrument is not connected to earth twice to prevent the occurrence of an ‘earth
loop’.
Note: In applications with synthetic mounting positions the case ground terminal
(internal or external) must be connected to earth.
Care must be taken to assure that the polarity of the power supply is correct, a
reversal of wiring polarity will not damage the transmitter, but it will not function
until the wiring is connected correctly.
+
-
+
-
Connection
Transmitter
4-20 mA
External
Load
Series 2000 HART

8
Overview
4. Remaining
4.1 Digital Local Indicator
All transmitters from the Series 2000 are standard equipped with a digital display.
In the standard execution the covers are “closed”. The three push buttons and the display are behind the cover (3).
As an option a transparent cover can be delivered to achieve the display can be used as a local display in the process. The full-scale
point may be set to any value between 0000 and 9999 (4 digit). (Option: “I” extra price).
4.2 CE / EMC - RULES
All transmitters are manufactured in accordance with the RFI / EMC directives and comply with the CE standard. All transmitters are
fitted with RFI filters, which provide optimum, trouble-free operation. Our products are in conformity with EMC-Directive 2004/108/EC
based on test results using harmonized standards.
4.3 External Load
The minimum power supply is based on the total circuit resistance.
The maximum permissible load(Ri max.) in case of 24 Vdc is 600 Ω (Ohm).
By increasing the power supply, the external load can be increased to 1200 Ohm / 36 Vdc.
RI max. = Power Supply - 12 Vdc
20 mA
4.4 Intrinsically Safe and NON SPARKING (Ex version)
The Series 2000, Series 2000-SAN, Series CER-2000 and Series 2000-Hydrobar-cable are also available for intrinsically safe
(Zone 0). The Series 2000, Series 2000-SAN, Series 2000- Cable and Series 2000-SAN-Cable are also available for Non-
Sparking (Zone 2).
Series 2000 HART
!With a loop resistance of 250 Ω a power supply of at least 17 Vdc must be used.
ATEX – KEMA 03ATEX1092 X
II 1G Ex ia IIC T4 Ga
II 1D Ex ia IIIC T100°C Da (option G100, extra price)
II 3G Ex nA IIC T100°C Gc (option G180, extra price)
IECEx – DEK 14.0079X
Ex ia IIC T4 Ga
Ex ia IIIC T100°C Da (option G100, extra price)
Ex nA IIC T100°C Gc (option G180, extra price)
For detailed explanation see “EC-Declaration of conformity” on the last page of this manual.
For use in a non-sparking area, the transmitter can be installed without the use of a (intrinsic safe) barrier.
The transmitter can be connected with the following nominal value’s:
UN = 12O26.5 Vdc; IN = 4O20 mA; PN = 0,28 W.
For use in an intrinsically safe area, use a certified power supply in an intrinsic safe area, from 12 - 26,5 Vdc.
Installation of this device has to be carried out by a qualified mechanic / installer.

9
Overview
Series 2000 HART
Transmitter type and options Equipment category Ambient temperature range
Pressure / Level Transmitter
Series 2000, Series 2000-SAN, Series 2000-Cable,
Series 2000-SAN-Cable, Series CER-2000,
Series 2000-Hydrobar-Cable and
Series 2000-Hydrobar-EXTD
II 1 G -20ºC………70ºC
With transparent indicator cover (Option I) II 1 G -20ºC………70ºC
Pressure / Level Transmitter
Series 2000, Series 2000-SAN, Series 2000-Cable
And Series 2000-SAN-Cable.
With closed covers, Option G180
II 3 G -20ºC………70ºC
Process temperature range:
-20 °C to +100 °C
Pressure / Level Transmitter
Series 2000, Series 2000-SAN, Series 2000-Cable,
Series 2000-SAN-Cable, Series CER-2000,
Series 2000-Hydrobar-Cable, Series 2000-Hydrobar-
EXTD and Temperature Transmitter Type TT-2000
With closed covers, Option G100
II 1G
and
II 1D
-20 °C to +70 °C
The maximum surface temperature of the enclosure T 100ºC is based on a maximum ambient temperature of 70ºC, and maximum
process temperature of 100°C. This temperature is determined with a dust layer of maximum 5 mm.
Electrical data for Ex transmitters
Pressure / Level Transmitter Series 2000, Series 2000-SAN, Series 2000-Cable, Series 2000-SAN-Cable, Series CER-2000, Series
2000-Hydrobar-Cable, Series 2000-Hydrobar-EXTD and Temperature Transmitter Type TT-2000:
Supply/output circuit (terminals 3 ‘-’ and 4 ‘+’): in type of protection intrinsic safety Ex ia IIC, or
Ex ia lllC only for connection to a certified intrinsically safe circuit, with the following maximum values: Ui = 26,5 Vdc; Ii = 110 mA; Pi =
0,9 W (linear source); Li = 1,4 mH; Ci = 63 nF (without cable between terminals 3 ‘-’ and 4 ‘+’).
Cable length
The maximum length of the cable for the Series 2000-Cable, 2000-SAN-Cable and 2000- Hydrobar-Cable is 100 m. Electrostatic
charging of the cable and the protection cap by the flow of non-conductive media (e.g. in stirring vessels or pipes) shall be avoided.
Special conditions for Safe use in Zone 0
As category 1G equipment may be applied directly in the process, electrostatic discharge from the cable and the protection cap
of Pressure / Level Transmitter Series 2000-Hydrobar-Cable by the flow of non-conductive media (e.g. in stirring vessels or pipes)
should be avoided.
Special Instructions for Safe use in Zone 2
For use in non-sparking areas (Zone 2), the following should be taken into consideration:
• As standard the transmitter is supplied without a certified cable gland. The cable entry is fitted with a PE blanking plug for protection
during transport. Remove the blanking plug after installing the transmitter. When using a gland make sure it is certified and
complying with applicable protection level of the transmitter.
• Always use the covers supplied by Klay Instruments B.V.
• All transmitters from Klay Instrument are designed to last for at least 10 years under normal process and environmental conditions.
The gaskets and seals for the series 2000 are successfully tested according to IEC 60079-0 for temperature endurance (heat and
cold), resistance to impact and ingress protection by DEKRA Certification. In harsh process and environmental conditions the
lifetime of gaskets and seals may be reduced.
Hawk Measurement strongly advises to inspect these yearly and replace them when necessary.

10
Overview
Series 2000 HART
4.5 Special Instructions for Safe Use
For use in a potentially explosive atmosphere caused by air/dust mixtures the following should be taken into consideration:
• The dust layer may not exceed a thickness of 5 mm.
• as standard a transmitter is supplied with a certified cable gland (PG). When using a different gland make sure it is certified and
complying with applicable protection level of the transmitter.
• Always use the covers supplied by Klay Instruments B.V.
WARNING
DO NOT REMOVE THE SCREW COVERS WHEN AN EXPLOSIVE ATMOSPHERE MAY BE PRESE.
4.6 Tracebility Year of Manufacturing
The year of manufacturing of the transmitter can be traced as follows: take the first two numbers from the serial number that is
engraved in the transmitter and add 1970 to it.
For example: if the serial number is 4309036. The year of manufacturing is 1970 + 43 = 2013.
4.7 Software Revisions
Due to the improvements on the Series 2000, there are several software versions (revisions). For this reason it is possible the
transmitter you are working with does not support some options, which are discussed in this manual. This instruction is applicable
from software revision V9.17. After powering up, the transmitter will show the revision number on the display.

11
Overview
5. Function of Push Buttons
The Series 2000 can be programmed easily by use of the 3 front panel
pushbuttons (See picture right). The display can show engineering units of:
mH2O, inH2O, bar and PSI.
The functions of the three pushbuttons will be explained below.
This button has 2 functions:
1. It can be directly used for adjusting the zero (zero / 4mA), with or without a test pressure.
When the zero (4 mA) must be adjusted at 0 (atmospheric pressure), the button must be held
until the word “ZERO” appears on the display. The transmitter is now set to 4 mA.
2. Secondly, this button must be used for stepping down in the programming menu or to
decrease a value (-).
Note: For canceling the mounting position effect you have to use P103.
This button has 2 functions:
1. It can be directly used for adjusting the span (20 mA), when using a test pressure (air). When
a test pressure (e.g. 2 bar) is supplied to the transmitter, the button must be held until the
word “SPAN” appears on the display. The transmitter is now adjusted at 20 mA. The span can
also be adjusted without test pressure (see P102).
2. Secondly, this button must be used for stepping up in the programming or to increase
a value (+).
This button has 2 functions:
1. It is used to adjust the 14 Programming Points (P101 to P114). Push it once and P100 is
displayed, use the h(SPAN) to step to P101 etc.
2. This button must also be used for confirming the adjustments (enter).
For example if you want to change the adjustment in bars (P104), the following steps
must be taken:
1. Push on [PROG] until “100” appears on the display.
2. Push on [SPAN] 4 times to go to point “P104” (adjustment pressure unit).
3. Push [PROG] to confirm this.
4. Push several times on the h(SPAN) to reach 3 (= bar). See also the conversion table (page 12).
1 = mWC, 3 = bar, 5 = PSI, 11 = inch WC
5. Confirm this by pushing once at [PROG].
The transmitter is now adjusted to read in “bar”.
Series 2000 HART
ZERO SPAN
PROG
PROG
ZERO
SPAN
mH20
inH20
bar
psi
ZERO SPAN
PROG
PROG
ZERO
SPAN
mH20
inH20
bar
psi
ZERO
ZERO SPAN
PROG
PROG
ZERO
SPAN
mH20
inH20
bar
psi
SPAN
ZERO SPAN
PROG
PROG
ZERO
SPAN
mH20
inH20
bar
psi

12
Overview
6. Programming Points (P101 - P114)
The following points can be adjusted by means of the
three push buttons.
For an explanation of these points see page 11 to 18 of
this manual.
To change one of these points you have to push on [PROG] until
“100” appears on the display.
To go to from a lower program (P101) to a higher one (P102),
push on the h(SPAN).
To confirm the adjustments you always have to press on [PROG].
*) Standard adjustments ex works.
Programming points:
P101 Zero adjustment (4 mA)
P102 Span adjustment (20 mA)
P103 Cancel mounting position effect
P104 Adjustment pressure unit (See Conversiontable)
P105 4-20 mA *)
20-4 mA (Reverse output)
P106 Adjustment damping (0 to 25 sec)
P107 Indication of process temp. (Read out on display)
P108 0 = °C (*)
1 = °F
P109 Read out on display:
Curr (0) = current (4 - 20 mA) (*)
Unit (1) = pressure unit (conversiontable)
PerC (2) = percentages
TenP (3) = temperature
Hect (4) = hectoliters
CB n (5) = Cubic meters
Ltr (6) = Liters
P110 Simulation of current
P111 Linearisation
0 = no linearisation (*)
1 = cylindrical tank
2 = vertical tank with cone
3 = vertical tank with spherical cone
P112 Specific density
P113 Write Protection
P114 Response time from push buttons
7. Reading On The Display
On the standard built-in display several values can be shown.
During the programming of the transmitter the display shows all
the information that is needed.
When the transmitter is in the process the display gives all the
information of the process pressure or temperature.
On the display the following units can be showed: mH2O, inH2O,
bar and PSI (see also P104 and P109).
N.B.: The standard transmitter is supplied with two “closed”
covers shielding the buttons and the display. As an option an
“open” cover (IP 65) can be fitted. The display can then be used
as a local process display. (Option: “I” extra price). The full scale
can be set between -9999 and 9999 (4 digit).
Series 2000 HART
ZERO SPAN
PROG
PROG
ZERO
SPAN
mH20
inH20
bar
psi

13
Overview
8. Explanation Programming Points P101 to P114
Zero Adjustment (4 mA)
The transmitter as standard is adjusted to 4.00 mA at atmospheric pressure. It is also possible to adjust a zero-
suppression or elevation.
For example: zero elevation of 1 mWK.
1. Push at [PROG] until “100” is shown on the display.
2. Push h/ SPAN button once until “101” shows.
3. Confirm this by pushing [PROG].
4. Now the display will show 0.00 mH2O. Push h[SPAN] until 1.00 mH2O is on the display.
5. Confirm with [PROG].
6. The output of the transmitter will be lower than 4 mA. The output at atmospheric pressure will be for example 3.68 mA.
When a pressure of 1 mWC is applied on the diaphragm the output will be 4.00 mA.
The elevation can be canceled by pushing at [ZERO] till zero disappears out of the display. The transmitter is now adjusted
at 4 mA at atmospheric pressure.
P101
Span Adjustment (20 mA) Without Test Pressure
Before adjusting the span take care the right pressure unit is selected. (See also P104 and P109).
Example: Adjustment of the span at 0 - 2 bar.
First off all, the pressure unit must be adjusted at “bar”. (See P104 and P109).
1. Push [PROG] untill “100” is shown on the display.
2. Push h/ SPAN twice until “102” is on the display.
3. Confirm this by pushing [PROG].
4. Push [SPAN] (+) or [ZERO] (-) to select the measuring range that is required.
5. Confirm by pushing [PROG]. The transmitter is adjusted now.
N.B.: P102 is the adjustment of the total span. When a “compound” range must be adjusted (for example -1 till +3 bar), a
span of 4 bar must be programmed. At P101 (ZERO,4 mA), -1 bar must be adjusted. Now the transmitter is adjusted at: - 1
bar = 4 mA and +3 bar = 20 mA.
N.B.:
It is not possible to show values larger than ‘9999’ or smaller than ‘–9999’ on the display. In this case the display will show:
- - - - For values larger than ‘9999’.
- - - - For values smaller than ‘–9999’.
As long as the display shows “- - - - “, the value will not be saved by pressing “PROG”.
P102
Series 2000 HART

14
Overview
Cancel Mounting Position Eect
All transmitters are calibrated vertically. When a transmitter of the Series 2000 or 2000-SAN is installed horizontally, there
will be a small “mounting effect” on the zero
(4 mA). For example the transmitter shows 4.03 mA instead of 4.00 mA. This can be easily canceled with P103. In P103
there are three options:
1. ESC:
Nothing will be changed.
Leave without doing anything. (confirm with PROG).
2. RESET:
Use this option when you are not sure if P103/SET has been performed properly. (confirm with PROG). when using this
option the original factory setting will be valid.
3. SET:
Canceling mounting position effect. (confirm with PROG).
When “SET” is selected the transmitter is automatically adjusted to 4.00 mA. The span will not be affected.
CAUTION: Do not apply pressure while executing “cancel mounting position effect”
N.B.:
From revision 2 the description above is valid. Transmitters working with software revision 1 will direct process cancel
mounting position.
P103
Adjustment Pressure Unit On Display (See Conversion Table)
P104
104 Conversion Factor Display
11.000 mH2O (mWC)*
21000 m H2O (mm WC)
30.09806 bar*
498.0665 mbar
51.4223 PSI*
60.0967 Atm
79.80665 KPa
80.009807 MPa
90.1 Kgf/cm2
10 73.556 mm HG
11 39.37 inH20 (“WC)*
12 2.895906 “HG
Several engineering units can be shown on the display
by using a conversion factor. (See conversion table).
Four engineering units will light up on the display
(mH2O, inH2O, bar and PSI).
N.B.: To show one of the engineering units, P109 must
be adjusted at 1 (= pressure unit).
This will be explained with an example (e.g. bar):
1. Push [PROG] until “100” is shown on the display.
2. Push h4 times, go to [P104].
3. Push [PROG] to confirm.
4. Push at h/ [SPAN] and adjust at 3 (= bar).
1 = mH2O (=mWC), 3 = bar, 5 = PSI, 11 = inch WC.
5. Confirm with [PROG].
The transmitter will now read out in bar.
Conversion Table:
*) Pressure units that can be shown on the display. When
the value of the highest range is larger than 9999, “NA” will
appear in the display (Not Applicable). Another unit must be
chosen.
Series 2000 HART

15
Overview
Reverse Output (20 - 4mA)
The transmitter as standard is adjusted to 4-20 mA.
Push on [PROG] and go to P105.
Push hto change the output to 20-4 mA (Reverse output).
Push [PROG] to confirm this.
Now the transmitter will give 20 mA at atmospheric pressure
P105
Adjustment Samping (0 till 25 sec)
In P106 an electronic damping can be adjusted between 0 and 25 seconds.
This can be done with the push buttons h(up) and i(down).
Always confirm by pushing once at [PROG].
P106
Indication of Process Temperature (Read Out On Display)
1. Push [PROG] until “100” is shown on the display.
2. Push h7 times, go to [P107].
3. Push [PROG] to confirm this. Now the process temperature appears on the display (Indication: +/-2oC).
This will remain on the display. To get the actual pressure back on the display you have to push again on P107 until the
actual pressure appears on the display again.
P107
Temperature In oC OR oF
The temperature of the transmitter is standard adjusted at oC (“DEGR”). When pushing hin P108, this will change into oF
(“FAHR”).
Always confirm by pushing once at [PROG].
P108
Read Out On Display
Curr (0) = current (4 - 20 mA)
Unit (1) = pressure unit (See conversion table)
PErC (2) = percentages (0 - 100%)
TEnP (3) = temperature (oC of oF)
HECt (4) = hectoliter (only in combination with P111)
Cb n (5) = Cubic meter (only in combination with P111)
Ltr (6) = Liters (only in combination with P111)
As standard the transmitter is delivered with read out in mA (0). To change this, follow the next steps:
1. Push [PROG] until “100” is shown on the display.
2. Push h/ SPAN 9 times untill “109” appears on the display.
3. Confirm with [PROG].
4. Push once at h.
5. Push [PROG] to confirm this.
The transmitter will now read mH2O (mWC).
The pressure unit can be changed with the conversion table in “P104”.
1 = mH2O (=mWK), 3 = bar, 5 = PSI, 11 = inch WK.
Also the read out can be 0 - 100%. In this case select “P109”, option 2.
P109
Series 2000 HART

16
Overview
Simulation of Current (4 - 20 mA)
The transmitter can be used as a simulator of a current between 4 - 20 mA.
This can be done in P110 with the push buttons hand i.
The user can perform a current simulation (Curr) or a pressure simulation (Unit).
Current-simulation (Curr)
To perform a current-simulation follow the next steps:
1. Push [PROG] until “100” is shown on the display.
2. Push h/ SPAN 10 times until “110” appears on the display.
3. Confirm with [PROG].
4. The display will readout ‘Curr’
5. Confirm with [PROG].
6. The display shows ‘4.00’. Push [PROG] and the output changes to 4.00 mA.
7. By pushing h/ SPAN or i/ ZERO, you can change the value on the display. The output value will change as soon as
the h/ SPAN OR i/ ZERO button is released.
8. Pressing the [PROG]-button again will exit the simulation.
Pressure-simulation (Unit)
To perform a pressure-simulation follow the next steps:
1. Push [PROG] until “100” is shown on the display.
2. Push h/ SPAN 10 times until “110” appears on the display.
3. Confirm with [PROG].
4. The display will readout ‘Curr’
5. Press h/ SPAN once
6. The display will readout ‘Unit’.
7. Confirm with [PROG].
8. The display shows a pressure value. Push [PROG] and the output changes to a mA-output corresponding with the
range entered in menu P101 and P102.
9. By pushing h/ SPAN or i/ ZERO, you can change the value on the display. The output value will change as soon as
the h/ SPAN OR i/ ZERO button is released.
10. Pressing the [PROG]-button again will exit the simulation.
Note:
• The values that can be entered using the pressure-simulation are related to the adjustments in menu P101 and P102.
These values are also the minimum and maximum values.
• For HART-transmitters: this menu will not work when the device is operating in multi-drop mode.
P110
Series 2000 HART

17
Overview
Linearisation
0 = no linearisation
1 = cylindrical tank (horizontal)
2 = tank with bottom cone
3 = tank with spherical bottom
As standard the transmitter is delivered without linearisation (= 0). However, for a horizontal tank or a tank with a bottom
cone, a linearisation can be applied to achieve the current signal (mA) is equal to the level in the tank. All values must be
programmed in meters.
P111
Cylindrical horizontal tank Cylindrical tank with cone-shaped ends
Linearisation horizontal tank (Cylindrical)
1. Push [PROG] until “100” is shown on the display.
2. Push h/ SPAN 11 times until “111” appears. (Confirm with [PROG])
3. Push honce. (Confirm with [PROG])
4. Enter the height (H1) of the tank in meters. (Confirm with [PROG])
5. Enter the same height (H2) of the tank in meters. (Confirm with [PROG])
6. Enter the length (L) of the tank. For a “ball” or cone shaped tank, take the cylindrical length plus the length of 1 “ball”
cone. (Confirm with [PROG])
7. Enter H3 in meters if the transmitter is installed like in the left picture. Enter 0m when the transmitter is installed like in
the right picture.
8. Enter the percentage of the actual “full” level (for example 80%).
(Confirm with [PROG]).
Note
If the height (H) of the tank is 1 meter and the maximum level in the tank is 0.8 meter the percentage (point 5) must be set
at 80%. The calibration at P102 must be adjusted at: 1 meter (if s.g. equals 1).
Series 2000 HART

18
Overview
Linearisation Vertical Tank With Cone
1. Push [PROG] till “100” appears on the display.
2. Push h/ SPAN 11 times until “111” appears. (Confirm with [PROG])
3. Push htwice. (Confirm with [PROG])
4. Enter height (H1) of the tank (= actual level).
(Confirm with [PROG]).
5. Enter diameter (D) of tank. (Confirm with [PROG])
6. Enter height (H2) of cone. (Confirm with [PROG])
7. Enter the height (H3) from the bottom of the tank to the topside
of the diaphragm (or weld-on nipple). (Confirm with [PROG]).
8. Enter the percentage of the actual “full” level (for example 80%).
(Confirm with [PROG]).
Linearisation Vertical Tank With Spherical Cone
(From Software Revision 3)
1. Push [PROG] till “100” appears on the display.
2. Push h/ SPAN 11 times until “111” appears. (Confirm with [PROG])
3. Push hthree times. (Confirm with [PROG])
4. Enter height (H1) of the tank (= actual level).
(Confirm with [PROG]).
5. Enter diameter (D) of tank. (Confirm with [PROG])
6. Enter height (H2) of cone. (Confirm with [PROG])
7. Enter the height (H3) from the bottom of the tank to the topside
of the diaphragm (or weld-on nipple). (Confirm with [PROG]).
8. Enter the percentage of the actual “full” level (for example 80%).
(Confirm with [PROG]).
Note
When the specific gravity of the fluid is unequal to 1 and you do not want to use option 4, you must take care of it by defining the
calibration of the transmitter.
Calibration (see P102) = Height of the level x Specific Gravity.
Series 2000 HART
Linearization horizontal tank (Elliptical)
1. Push [PROG] until “100” is shown on the display.
2. Push h/ SPAN 11 times until “111” appears. (Confirm with [PROG])
3. Push honce. (Confirm with [PROG])
4. Enter the height (H1) of the tank in meters. (Confirm with [PROG])
5. Enter the height (H2) of the tank in meters. (Confirm with [PROG])
6. Enter the length (L) of the tank. For a “ball” or cone shaped tank,
take the cylindrical length plus the length of 1 “ball” cone. (Confirm
with [PROG])
7. Enter H3 in meters if the transmitter is installed like in the
left picture. Enter 0m when the transmitter is installed like
in the right picture.
8. Enter the percentage of the actual “full” level (for example
80%). (Confirm with [PROG]).

19
Overview
Specic Density
If the specific gravity of the medium differs from 1 kg/dm3, you can enter the real density of the medium in P112. When this
option is used, in menu P102, the ‘true’ height of the tank must be entered.
P112
Write Protection
The Series 2000 with HART-Protocol can be protected for writing (Write Protection). This is possible for two kinds of
writings:
- Changes via the Display (“Lo.Pr” = Local Protection).
- Changes via external HART configuration software by the Hand-held terminal or the P.C. (“Co.Pr.”= Communication
Protection).
Standard, the transmitter is set to no-write protection.
Adjustment Local Protection
1. Push [PROG] till “100” appears on the display.
2. Push h/ SPAN 13 times until “113” appears on the display.
3. Push [PROG] to confirm. (“Lo.Pr.” appears on the display).
4. Push h/ ifor adjusting to “ON” or “OFF”.
5. Push [PROG] to confirm.
Adjustment Communication Protection
1. Push [PROG] till “100” appears on the display.
2. Push h/ SPAN 13 times untill “113” appears on the display.
3. Push [PROG] to confirm. (“Lo.Pr.” appears on the display).
4. Push once more at [PROG]. (“Co.Pr.” appears on the display).
5. Push h/ ifor adjusting to “ON” or “OFF”.
6. Push [PROG] to confirm.
N.B. When Lo.Pr. is set to “ON”, the display shows 104, 105, 107, 108, 109 and 111 and the adjusted values of the
parameters. Afterwards “PROT” (Protected) is shown.
Both protections can be adjusted at the same time, independent from each other.
P113
Response Time From Push Buttons
This option can only be used from software version 8.01. The response time from the push buttons can be adjusted from
0,0 till 5,0 seconds.
P114
Service Menu
Permission from manufacturer needed to access menu.
P115
Service Menu
Permission from manufacturer needed to access menu.
P116
Series 2000 HART

20
Overview
9. Programming The Series 2000
9.1 Programming With The Hand Held Terminal
The series 2000 can be programmed very easily with the Hand Held Terminal (HHT) from the “HART Foundation” or the HHT from
Rosemount or Yokogawa (type 275 Hart Communicator).
The HART (Highway Addressable Remote Transducer) Communicator provides a common communication link to all HART-
compatible, microprocessor-based instruments.
WARNING: When using a HHT to function properly, a minimum resistance of 250 Ohms must be present in the loop of the 2-wire
system. (See figure below).
9.2 Programming With DTM
There is an instruction manual available which is a guide for installing and using the Klay Series 2000 HART DTM. This DTM is
developed to make configuration changes of the Series 2000 HART transmitters easy.
This DTM can be used with almost every FDT-container.
To be able to install the DTM Klay Series 2000 HART on your system, download the installation file. This file can be downloaded from
the HAWK Instruments site or via the following link: www.hawkmeasure.com
The installation can be started by opening the “DTM Klay Series 2000 HART V1-2-0-1.zip” and continue by opening the “DTM Klay
Series 2000 HART V1-2-0-1.exe” file.
9.3 Programming With PDM
There is also a Device Description (DD) available for the Series 2000 HART. This DD can be used for configuring a Series 2000
HART transmitter using Simatic PDM. You can download this DD (in zip file) from the following link: www.hawkmeasure.com.
To install the DD, unzip the KLAY_PDM_HART_REV8.ZIP file and run DeviceInstall.exe.
Series 2000 HART
Option 1: HART ® Handheld terminal connected across the transmitter.
Option 2: HART ® Handheld terminal connected across the loop resistor.
This manual suits for next models
3
Table of contents
Other Hawk Transmitter manuals
Popular Transmitter manuals by other brands

ULFA TECHNOLOGY
ULFA TECHNOLOGY JANITOR PLT Series instruction manual

AMC
AMC CU800 Installer manual

NIVELCO
NIVELCO AnaCONT LE-100 Installation and programming manual

Vaisala
Vaisala HUMICAP HMT130 quick guide

M-system
M-system M6SPA instruction manual

Emerson
Emerson Micro Motion 2500 Configuration and Use Manual