Hawkeye Mfg H908 User manual

6%2)3).$5342)%3
CURRENT MONITORING INSTALLATION GUIDE
Z201494-0E PAGE 1 ©2009 Veris Industries USA 800.354.8556 or 503.598.4564 / suppor[email protected] 05091
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Split-Core Current Switch, Adjustable Trip Point
Installer’s Specifications
Sensor Power Induced from monitored current
Insulation Class 600VAC RMS (UL), 300VAC RMS (CE)
Frequency Range 50/60Hz
Temperature Range -15° to 60°C (5° to 140°F)
Humidity Range 10-90% RH non-condensing
Amperage Range 2.5 - 135A Continuous
Output N.O. 1.0A@30VAC/DC, polarity insensitive
Hysteresis 10% of setpoint, typical
Terminal Block Maximum Wire Size 14 AWG
Terminal Block Torque (nominal) 4 in-lbs
Agency Approvals UL 508 open device listing
CE: EN61010-1:2001-02, CAT III, deg. 2, basic insulation
Specification Note: For CE compliance, conductor shall be insulated according to IEC 61010‑1:2001,
Installation Category III or equivalent.
The product design provides for basic insulation only.
)";"3%0'&-&$53*$4)0$,&91-04*0/03"3$'-"4)
t 'PMMPXTBGFFMFDUSJDBMXPSLQSBDUJDFT
4FF/'1"&JOUIF64"PSBQQMJDBCMFMPDBMDPEFT
t 5IJTFRVJQNFOUNVTUPOMZCFJOTUBMMFEBOETFSWJDFECZRVBMJmFEFMFDUSJDBMQFSTPOOFM
t 3FBEVOEFSTUBOEBOEGPMMPXUIFJOTUSVDUJPOTCFGPSFJOTUBMMJOHUIJTQSPEVDU
t 5VSOPõBMMQPXFSTVQQMZJOHFRVJQNFOUCFGPSFXPSLJOHPOPSJOTJEFUIFFRVJQNFOU
t 6TFBQSPQFSMZSBUFEWPMUBHFTFOTJOHEFWJDFUPDPOmSNQPXFSJTPõ
%0/05%&1&/%0/5)*4130%6$5'0370-5"(&*/%*$"5*0/
t 0OMZJOTUBMMUIJTQSPEVDUPOJOTVMBUFEDPOEVDUPST
'BJMVSFUPGPMMPXUIFTFJOTUSVDUJPOTXJMMSFTVMUJOEFBUIPSTFSJPVTJOKVSZ
%"/(&3
Wiring ExamplE
H908 908
DimEnsions
/05*$&
t 5IJTQSPEVDUJTOPUJOUFOEFEGPSMJGFPSTBGFUZBQQMJDBUJPOT
t %POPUJOTUBMMUIJTQSPEVDUJOIB[BSEPVTPSDMBTTJmFEMPDBUJPOT
t 5IFJOTUBMMFSJTSFTQPOTJCMFGPSDPOGPSNBODFUPBMMBQQMJDBCMFDPEFT
t .PVOUUIJTQSPEVDUJOTJEFBTVJUBCMFmSFBOEFMFDUSJDBMFODMPTVSF
quick install
Disconnect and lock out power to the conductor to be monitored.1.
Plan the installation:2.
Locate a mounting surface for the removable mounting bracket that will allow
the monitored conductor to pass through the iris, or “window” when it is installed
and keep the product at least ½” (13mm) from any uninsulated conductors (CE).
Determine cable routing for the controller connection, allowing wiring to reach
the mounting location.
Install mounting bracket3.
Drill holes to mount the bracket to the chosen surface using the included screws.
Wire the output connections between the sensor and the controller (solid-state4.
contact).
Snap the sensor over the wire to be monitored and clip the assembly to the5.
mounting bracket.
Calibrate the sensor (see page 2) with the load running normally.6.
Fan or Pump
CONTROLLER
Digital
Input
MOTOR
Insulated Conductor
CONTACTOR
Removable Mounting Bracket
Self-gripping
Iris
1.0”
(25 mm)
0.8”
(21 mm)
1.1”
(26 mm)
3.1”
(79 mm)
2.8”
(70 mm)
Ø = 0.3”
(8 mm)
1.4”
(36 mm)
2.5”
(64 mm)
3.0”
(76 mm)
Bracket can be mounted
on either side for added
installation flexibility.
Use DIN Rail
Mounting clip
(Veris part
number AH01) to
mount on stan‑
dard DIN rail.

6%2)3).$5342)%3
INSTALLATION GUIDE
H908
Z201494-0E PAGE 2 ©2009 Veris Industries USA 800.354.8556 or 503.598.4564 / suppor[email protected] 05091
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
opEration
The H908 is a current-sensitive switching device that monitors current (amperage) in
the conductor passing through it. A change in amperage in the monitored conductor
that crosses the switch (setpoint) threshold plus the hysteresis value will cause
the resistance of the FET status output to change state, similar to the action of a
mechanical switch. In this model, the setpoint is adjustable through the action of a
twenty (20) turn potentiometer (see the CALIBRATION section). The status output is
suitable for connection to building controllers or other appropriate data acquisition
equipment operating at up to 30 volts. The H908 requires no external power supply
to generate its output.
The H908 housing offers unprecedented mounting flexibility. The mounting bracket
can be attached in three different places. Additionally, the bracket is compatible with
the Veris AH01 DIN Rail clip, allowing DIN mounting.
notEs
troublEshooting
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center hole and around the sensor body
to produce multiple turns through the "window." This increases the current measured
by the transducer.
4x
1A
DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's instructions.
Terminate the CT secondary before applying current.
H68xx‑5A CT
240A
300A:5A
4A
> 135A (H908 max.)
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) Current Transformer (CT) as shown.
Problem Solution
No Reading at Controller • Check sensor calibration (see above)
• Check for amperage in monitored conductor (> 2.5A)
• Assure that sensor core mating surfaces are clean and
that the core clamp is completely closed
Setpoint screw has no stops The setpoint screw has a slip-clutch at both ends of its
travel to avoid damage.Twenty turns CCW will reset
the sensor to be most sensitive. Repeat calibration
above.
Both LEDs are lit Setpoint screw is too far clockwise. See solution above.
CAUTION
RISK OF EQUIPMENT DAMAGE
t %FSBUFUIFQSPEVDUTNBYJNVNDVSSFOUGPSUIFOVNCFSPGUVSOT
UISPVHIUIFTFOTJOHXJOEPXVTJOHUIFGPMMPXJOHGPSNVMB
3BUFE.BY"NQT/VNCFSPG5VSOT.BYNPOJUPSFE"NQT
FH"5VSOT"NQTNBYJONPOJUPSFEDPOEVDUPS
t 'BJMVSFUPGPMMPXUIFTFJOTUSVDUJPOTDBOSFTVMUJOPWFSIFBUJOH
BOEQFSNBOFOUFRVJQNFOUEBNBHF
calibration
A. To monitor under-current (belt loss, coupling shear, status)
"
OK!
!
1. Turn setpoint screw
clockwise until Status OPEN
LED turns ON.
2. Slowly turn the screw counter-clockwise until the Status CLOSED LED just
turns ON.
3.Turn the screw an
additional ¼ turn
counter-clockwise for
operational margin.
B. To monitor over-current (mechanical problems, seized impeller)
"
OK!
!
3. Turn the setpoint
screw an additional
¼ turn clockwise for
operational margin.
1.Turn setpoint screw
counter-clockwise until Status
CLOSED LED turns ON.
2. Slowly turn the setpoint screw clockwise until the Status OPEN LED just turns ON.
OK!
45"564
OK!
45"564
4FUQPJOU
4UBUVT
0QFO
4501
4FUQPJOU 4UBUVT
$MPTFE
4501
4FUQPJOU
+
4FUQPJOU 4UBUVT
$MPTFE
4501
4FUQPJOU
4UBUVT
0QFO
4501
+
4FUQPJOU
Before beginning calibration, establish normal load conditions.
OK!
"
OK!
Then choose either A or B below.
Controller must be
programmed to account for the
extra turns. e.g., if four turns
pass through the sensor (as
shown) the normal controller
reading must be divided by 4.
< 2.5 A (Sensor Min.)
Table of contents
Other Hawkeye Mfg Switch manuals