HB HBLC-Fgas User manual

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 1
Wire and Flex are intelligent liquid level sensors which can be installed in a vessel or in a standpipe. For the Wire sensor the
sensor element is a stainless steel wire insulated with PTFE and for the Flex sensor the element is a stainless steel wire
mounted with steel tube elements to increase the sensivity. Both sensors can to be mounted directly in a stand pipe. If they
need to be installed in a vessel they need an inner pipe. Both sensors measure between the wire/tube elements and the sur-
rounding pipe.
The sensor can be installed in refrigeraon systems and similar demanding applicaons with high pressures and aggressive
uids. The sensor emits a 4-20mA analog signal, which is proporonal to the liquid level.
Introducon
Manual for all exible level sensors and wire sensors delivered be-
fore October 15th 2021
Covers: HBLT & HBSLT
• Wire sensor suited for liquids like NH3, and HFC/HFO refrigerants
• Flex sensor suited for liquids like CO2 and Hydro carbons
Can be used in refrigeraon systems and similar demanding systems.
ATEX/Ex versions included

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 2
Table of contents
Introducon...............................................................................................1
Safety Instrucons .....................................................................................2
Applicaon Examples..............................................................................3-5
Installaon Wire.........................................................................................6
Installaon Flex..........................................................................................7
Connecon diagrams ............................................................................8-12
Analog output ..........................................................................................12
Use the HB-tool for seng up the sensor ..........................................13-16
LED indicaon ..........................................................................................17
Calibraon on the sensor.........................................................................17
Fault detecon.........................................................................................18
Sensor Repair...........................................................................................18
Further Informaon.................................................................................18
Safety Instrucons
CAUTION! Always read the instrucon manual before commencing work! Heed all warnings to the leer! Installaon of the
sensor requires technical knowledge of both refrigeraon and electronics. Only qualied personnel should work with the
product. The technician must be aware of the consequences of an improperly installed sensor and must be commied to
adhering to the applicable local legislaon.
If changes are made to type-approved equipment, this type approval becomes void. The product's input and output, as well
as its accessories, may only be connected as shown in this guide. HB Products assumes no responsibility for damages re-
sulng from not adhering to the above.
Explanaon of the symbol for safety instrucons. In this guide, the symbol below is used to point out important safety
instrucons for the user. It will always be found in places in the chapters where the informaon is relevant. The safety in-
strucons and the warnings in parcular, must always be read and adhered to.
Intended use, condions of use. The level sensor is designed
for connuous measurement of liquids, but please note the
sensor design and setup has to comply with the liquid. The
table show how sensors comply to liquids. It can be used in
refrigeraon systems and similar environments. If the sensor
is to be used in a dierent way and if the operaon of the
product in this funcon is determined to be problemac,
prior approval must be obtained from HB Products.
Prevenon of collateral damage Make sure that qualied
personnel assess any errors and take necessary precauons
before aempng to make replacements or repairs, to avoid
collateral damage.
Disposal instrucons: The sensor is constructed so that the
modules can easily be removed and sorted for disposal.
CAUTION! Refers to a possible limitaon of funconality or risk in usage.
NOTE! Contains important informaon about the product and provides further ps.
The person responsible for operaon must commit to adhering to all the legislave requirements,
prevenng accidents, and doing everything to avoid damage to people and materials.
Comply
Not comply

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 3
Standpipe should be insula-
ted to avoid boiling in stand-
Drainpipe most be placed at
an angle of 5-10°, to avoid oil
pockets in standpipe.
Sensor must have a minimum
of 50 mm between the sen-
sor weight end and the
boom of the pipe.
The following applies to the design of the system:
• It must be installed in a vercal posion
• Sensor must have a minimum of 50 mm between the sensor weight end and the boom of the pipe.
• The sensor must be installed in an overow or standpipe where the ow stream and turbulence are minimized.
• The sensor must be mounted in a standpipe bigger than DN25. Standpipe must be insulated to avoid boiling of refrig-
erant.
• The outlet pipe from standpipe shall be mounted in an angle of 5-10 degree from horizontal to secure drainage and oil
pockets in refrigeraon systems.
• The sensor is installed and is supplied with a standard non-shielded cable.
If EMC is greater than described in EN 61326, a shielded cable must be used.
The wire sensor is designed for level measurement of liquids in vessels like,
tanks, pump separators and receivers . The sensor can be mounted in a
standpipe from 1” (25mm) up to 4” (100mm) diameter or directly in a vessel
with an inner pipe from 1” (25mm) up to 4” (100mm) diameter. The inner
pipe is needed to create sucient measuring signal and to avoid a swinging
wire in a lively uid. To reduce wire movements in larger pipes a special
weight can be used.
Installaon Instrucons—wire sensor
Special weight for mounng in turbulent
condions. The steel spacer “star” can be
shortened, using a simple n cung shear,
to t the standpipe. Allow 2 mm play be-
tween inner pipe diameter and “star” di-
ameter

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 4
Stand pipe: DN32..…DN65.
Recommended pipe standard: DIN 10220
Recommended bending: DIN 2615-1/Type 3
Recommended TEE: DIN 2615-1
Standpipe: DN65…DN100.
Recommended pipe standard: DIN 10220
Recommended bending: DIN 2615-1/Type 3
Site pipe can be designed in smaller pipe e.g. o.5 x DN.

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 5
Standpipe should be insula-
ted to avoid boiling in stand-
Drainpipe most be placed at
an angle of 5-10°, to avoid oil
pockets in standpipe.
Sensor must have a minimum
of 50 mm between the sen-
sor weight end and the
boom of the pipe.
The following applies to the design of the system:
• It must be installed in a vercal posion
• Sensor must have a minimum of 50 mm between the sensor weight end and the boom of the pipe.
• The sensor must be installed in an overow or standpipe where the ow stream and turbulence are minimized.
• The sensor must be mounted in a standpipe DN25 orDN32. The standpipe must be insulated to avoid boiling of refrig-
erant.
• The outlet pipe from standpipe shall be mounted in an angle of 5-10 degree from horizontal to secure drainage and oil
pockets in refrigeraon systems.
• The sensor is supplied and can be is installed with a standard non-shielded cable.
If EMC is greater than described in EN 61326, a shielded cable must be used.
The Flex sensor is designed for level measurement of liquids in
vessels like, tanks, pump separators and receivers . The sensor
can be mounted in a standpipe 1” (25mm) or 1 ¼” (32mm) diam-
eter or directly in a vessel with an inner pipe 1” (25mm) or 1
¼” (32mm) diameter. The inner pipe is needed to create su-
cient measuring signal and to avoid a swinging wire in a lively
uid.
Installaon Instrucons—Flex sensor

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 6
Wire adjustment—Wire sensor
The sensor is installed in the standpipe or directly in the tank. The sensor length is determined by standpipe length or tank
height. Cut the insulated steel wire to desired length with a wire cuers or bolt cuer in the end where the weight is in-
stalled. The weight is xed by the 2 screws. Liquid sealant is applied to the thread.
When sealing the conical thread, you must use liquid conducve sealant, which creates
a ground connecon between the standpipe/tank and the sensor, since the sensor uses
the standpipe/tank as reference. If Teon is used, it must only be used on part of the
thread so that the ground connecon is established. If you are in doubt regarding the
ground connecon, measuring the resistance between the tank and sensor is recom-
mended. This should be approx. 0 ohms.
An aluminum sealing/washer has been included for the sensor with cylindrical thread.
To install HBLT-wire, you must use a 2.5
mm Allen key, shiing spanner, and
gasket, depending on the type of
thread.
Separate the electronic part from the
mechanical part
Remove the insulaon 18 +/-2 mm
Dene the required length of sensor
from standpipe. Shorten the wire with
wire cuer.
Make sure that wire is in boom of
the hole.
Tighten the 2 set screws to x the wi-
re.Turn the top cover plasc part on
the metal part (right-hand thread)
L = Programmable sensor length
L= Wire length + 86 mm
Allow for 50 mm clearance below
the weight to the boom of the
tank—if relevant.
18

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 7
Installaon instrucon—Flex sensor
The sensor can be shortened to t the standpipe length or vessel height. The sensor consist of a 5 mm steel wire ed with
a stainless steel weight at the boom, plasc spacers and aluminum pipes. The purpose of the plasc spacers is to keep the
metal parts away from the pipe and the aluminum pipe increase the sensivity of the sensor.
The sensor length can be reduced to desired
length by reducing the wire length and removing
the aluminum pipes and spacers. Shorten the wire
by using a heavy wire cuer or bolt cuer in the
end where the weight is installed.
Allow for the wire to be inserted 25 mm into the
weight and a 50 mm clearance below the weight
to the boom of the vessel. You can have up to 50
mm free wire at the top or shorten one of the
aluminum pieces to get to the desired length.
When sealing the conical thread, you must use liquid conducve sealant, which cre-
ates a ground connecon between the standpipe/tank and the sensor, since the sen-
sor uses the standpipe/tank as reference. If Teon is used, it must only be used on
part of the thread so that the ground connecon is established. If you are in doubt
regarding the ground connecon, measuring the resistance between the tank and
sensor is recommended. This should be approx. 0 ohms.
An aluminum sealing/washer has been included for the sensor with cylindrical thread.
The sensor with all elements removed from the wire. To shorten HBSLT/HBLT-Flex, you only need
to remove the necessary elements. A large wire cuer is needed for the wire.

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 8
+24V DC or AC
- Common
DO, Alarm output
AO, 4-20 mA level
Communicaon only
1
5
4
3
2
PLC
+
-
DI
AI
DO
Connecon diagram for sensors without control
cable. With and without temperature compensa-
on
Suited for
• HBLT and HBLT-wire & Flex
• HBLC
How to connect the sensor
Two dierent type of sensors
• A pure sensor version with 4-20 mA output
• A controller version with both cable for direct valve control and analog output
All sensors can provide a signal for a PLC via the M12 connection. The M12 connection is also used for power supply.
Some versions are able to control a valve directly. They have a cable, which can be connected directly to the valve.
PLC
Controller and
sensor version
HBSLT
HBSLC
PLC (oponal)
or
Power supply
Sensor only version
• HBLT
• HBLC
Digital output on pin 3
The sensor versions without a cable has an alarm out-
put on pin 3. Remote setpoint is not available

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 9
+24V DC or AC
- Common
AI Remote set point 4-20 mA
AO, 4-20 mA level
Run in signal
1
5
4
3
2
PLC
+
-
AO
AI
DO
Color coding
A+ = yellow(2)
A- = white (4)
B- = green (1)
B+= brown (3)
The sensor has a build in controller for a stepper valve. The sensor pro-
vides both the analog output via the cable to control the valve. The lev-
el measurement signal for the PLC comes via the M12 plug .
On pin 3 it is possible to send an analog 4-20 mA signal to the controller
and change the setpoint. The signal is scaled linear like analog output.
The cable is connected according to the drawing and the parameters
are set as shown in the next secon.
For the stepper motor setup a
special menu is acvated
Connecon diagram for sensors with control ca-
ble for all common stepper motor valves — here
shown with Carel E2V
Suited for
• HBSLT/S and HBSLT–wire & Flex/S
• HBSLC/S

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 10
+24V DC or AC
- Common
AI Remote set point 4-20 mA
AO, 4-20 mA level
Run in signal
1
5
4
3
2
PLC
+
-
AO
AI
DO
Connecon diagram for sensors with control ca-
ble for pulse modulang valve — here shown
with Danfoss AKV/AKVA
The sensor has a build in controller for a pulse modulang valve. The
sensor provides both the analog output via the cable to control the
valve. The level measurement signal for the PLC comes via the M12
plug .
On pin 3 it is possible to send an analog 4-20 mA signal to the controller
and change the setpoint. The signal is scaled linear like analog output.
The cable is connected according to the drawing and the parameters
are set as shown in the next secon.
Suited for
• HBSLT/PWM and HBSLT–wire & Flex/
PWM
• HBSLC/PWM
Wiring using cable
Brown: + when using DC
White: - common when using DC
The cable can supply AC as well

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 11
+24V DC or AC
- Common
AI Remote set point 4-20 mA
AO, 4-20 mA level
Run in signal
1
5
4
3
2
PLC
+
-
AO
AI
DO
Connecon diagram for sensors with control ca-
ble for modulang valve — here shown with Sie-
mens MVS661
The sensor has a build in controller for a pulse modulang valve. The
sensor provides both the analog output via the cable to control the
valve. The level measurement signal for the PLC comes via the M12
plug .
On pin 3 it is possible to send an analog 4-20 mA signal to the controller
and change the setpoint. The signal is scaled linear like analog output.
The cable is connected according to the drawing and the parameters
are set as shown in the next secon.
Suited for
• HBSLT/C and HBSLT–wire & Flex/C
• HBLC/C
AO = Grey , 4-20 mA
Motor valve: 4-20 mA 24 V DC, max 24 W
3 wire connecon
-common
+ supply
mA input
mA output posion
Open/Close valve
G0
G
Y
M
U
ZC
+ = Brown Supply
- = White common
Manual open/close
Close
Open
MVS661 motor valve

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 12
The sensor with ATEX approval use a two wire connecon.
This means only two pins in the M12 connector are acve
and the output is a 4-20 mA analog signal.
Barrier
+24V DC
Not used
Not used
AO, 4-20 mA level
Not used
1
5
4
3
2
PLC
+
AI
AO
AI
DO
Connecon diagram for sensors without control
cable. With and without temperature compensa-
on
Suited for
• HBLT and HBLT-wire & Flex
• HBLC
Scaling and oseng the output
Scaling the analog output
The output is scaled linear from minimum to maxi-
mum and it is done in the HB-tool.
Oseng minimum and maximum
If your sensor height doesn’t match your vessel height
it is possible move the minimum level and maximum
level beyond the physical sensor by adjusng the o-
set value in the HB-tool. It is also possible to make the
oset by making a calibraons to known levels also in
the tool.
Analog output
mA
Level
Maximum level
4
20
Minimum level

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 13
Setup — level or control
The sensor can operate in two dierent modes
• As sensor input to a PLC, computer or other device that
uses the analog sensor signal
• A direct controller of an electrically controlled expansion
valve version with a cable output that can be set up as a
controller
Select Control/Level to select the mode
Seng up the sensor
The HB tool has three pages of sengs. Some elds
will be shown in grey when they are not relevant/
acve with the seng chosen. Detailed
explanaons of the individual elds will
show up when the mouse is moved
over the eld. Only the latest version
of the tool has this feature.
When you like to change a seng ,you
just type in a new value or select in the
drop down. Aer changing the value
you store the data by clicking “save to
sensor”. The data is then saved and
stored in the sensor and remains there
even when the power supply is discon-
nected.
Use the HB tool for seng up the sensor
Connecng the sensor
All sensor are connected to a PC using an USB/M12 cable
Setup using a splier box
When using a splier box it is possible to run the refrigeraon system
and connect a PC to the sensor at the same me. The splier box is
not suited for normal operaon, but only for installaon and modi-
caon. The splier box is connected to the M12 plug on the HBX sen-
sor and then both the pc and the normal M12 plug can be connected. The USB cable and the splier box

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 14
Basic sengs
Here you make the primary sengs of the sensor
Here you set the parame-
ters for the control func-
on.
When “Run in signal” is
set to o the sensor con-
trol connuously when set
to on, control only when
signal is applied on pin5
Here you set the alarm
level. This is only for
versions without cable
for valve control
Here you set the pa-
rameters for the sen-
sor
Filter me averages
the output over a peri-
od and reduce uctua-
ons
Here you can adjust
minimum and maxi-
mum
Zero & span. When o
is selected the “R”
buon can’t be used
Select remote setpoint
if you use that.
Setpoint level in % (control mode only) Desired level: Shows the percentage level that one wants to remain in the container or
the level indicator.
P-band in % (control mode only) Proporonal band: Control area that describes how much the valve should open, dependent
upon the deviaon from the desired level. If proporonal band is set to 10%, for example, a liquid level that is under 5% will
make the valve open 50%; the valve will open to 100% if the level is under 10%. Small proporonal band results in a system
which reacts quickly, while a large proporonal band results in a system that reacts more slowly.
Filter me const. in sec. Filter funcon: Averages the measurement so that the control funcon is performed based on an av-
erage measurement in a programmable me span (in seconds). This is increased if there are brief uctuaons in the measure-
ment which lead to unstable control.
Run in signal remote acvaon: with this funcon it is possible to acvate centralized control. If one does not want this, the
funcon must be set to OFF, otherwise the sensor's control funcon will not work (power LED will ash when run-in signal is
acve or if this funcon is deacvated).
Zero & span cal. Funcon Calibrang funcon: ON in case calibraon of the sensor is allowed. Aer start-up and possibly the
rst calibraon, the tool can be connected and is deacvated.
Alarm seng in % Alarm, H/L: Indicates the desired alarm level. It is given in % of max measurement range.
Alarm delay in sec Delay – alarm: The delay from when the liquid level falls/rises to under/over the selected alarm, indicated in
seconds.
Oset max/min level in mm. here you can adjust for a sensor smaller than the vessel at max level and min level
Select mechanical type: select the type of sensor you have
Refrigerant: Indicates the type of refrigerant the sensor shall measure on.
Measurement length in mm Measurement in mm: Indicates the length of the sensor in mm typically printed on the electrical
part

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 15
Here you set the parame-
ters for the alarm func-
on.
Only available for sensors
without cable
Here you can adjust
parameters for the
valve control
Advanced sengs
Here you make the advanced sengs of the sensor
Alarm relay funcon: Here, the relay funcon is indicated, depending upon
the instrucons – NO or NC (normally open/normally closed). Here the signal
can be changed from alarm on below or above the alarm setpoint
Output direcon: Here you select either LP-mode (low pressure control) or HP
-mode (high pressure control). In LP-mode, the container is lled so that the
level is maintained, and in HP-mode the container is emped so that the level
is maintained. LP-mode = 4-20 mA. HP-mode = 20-4 mA.
Set mA or digital 2 output Select the sensor output digital or analog
Digital 2 alarm in %: set the alarm setpoint
Digital Hysteresis in %: %: Indicates the deviaon required before the alarm is
deacvated, following acvaon of the alarm. Alarm hysteresis in percent of
the probes calibrated span 0 and 100%.
Alarm seng is as well in % of the probes calibrated span 0 and 100%.
E.g. alarm seng = 80%, Alarm hysteresis = 25%
Set LED indicaon: Determines the funcon LED lighng has.

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 16
Here you can see and change the zero
calibraon.
The value is normally calculated based
on an automac calibraon and should
not be changed
Here you can see
the actual meas-
urement value
Visualizaon of the
control signal and the
level
Here you can see and change the SPAN
which is a part of the calibraon
The value is normally calculated based
on an automac calibraon and should
not be changed
Use this buon to
make the zero
calibraon
Use the buon and the eld to
make a calibraon to a known level
between 1 and 100%
Diagnosc (calibraon of sensor)
Here you make the calibraon of the sensor. If the sensor is operang in one of the predened liquid it is delivered with a
calibraon and does normally not need further calibraon. If you need higher accuracy the sensor can be calibrated

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 17
LED indicaon
• Green LED indicates 24 V DC supply; it ashes during operaon. If "run-in" is not used, this funcon must
be deacvated in the tool.
• Yellow LED indicates control.
The ashing sequence indicates if the valve is closing or opening.
• Red LED indicates high- or low-level alarm, depending upon the set-
up.
3-digit display: (not available on /S stepper motor control version.)
Showing 0…100 % linearly corresponding to 4…20 mA.
Calibraon on the sensor
Calibraon instrucons:
0% or 100% for calibraon can be carried out independent of each other. We recommend only calibrang at 0% if a high
degree of accuracy is desired.
Note: To use this funcon the “Zero & span cal. Funcon “ eld found under basic sengs have to be on - default is o
Instrucon for 0% calibraon:
• Connect the supply cable
• Empty the vessel
• Acvate "R" for 5 seconds to acvate calibraon mode = Yellow LED is on (ON) during the 5 second acvaon and
turns o (OFF) when calibraon mode is acvated.
• Acvate "R" once = Yellow LED ash once. Aerwards, the green LED ashes to conrm calibraon.
Instrucon for 100% calibraon:
• Fill the vessel to 100%.
• Acvate "R" for 5 seconds to acvate calibraon mode = Yellow LED is on (ON) during the 5 second acvaon and
turns o (OFF) when calibraon mode is acvated.
• Follow the instrucons under "Conguraons Instrucons" regarding the installaon of drivers in the program.
• Acvate "R" twice = Yellow LED ashes twice. Aerwards, the green LED ashes to conrm calibraon.
LED Signal ON/OFF/Frequency Funconality
Green ON Supply voltage connected
Flash Run In start signal / in operaon.
OFF No supply voltage
Yellow ON Acvaon of valve control / and during calibraon
OFF Valve control not acve
Red ON Alarm, high or low level, depending upon the setup.
Flash slow No contact to sensor probe or sensor probe shorted
Flash fast USB cable connected and communicaon acve
OFF No alarm
Yellow + Red Flash Insucient Power supply
All Flash USB cable connected and communicaon acve
OFF No alarm

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 18
Sensor Repair
In case of faults with the sensor, it will typically only be necessary to replace the electronics.
Please contact your local distributor about how to handle complaints.
Further Informaon
For further informaon, please visit our website, www.hbproducts.dk, or send an email to: supp[email protected].
Fault detecon
General: In case of fault, it is normally enough to replace the electronic part.
NOTE! Fault detecon and/or changing the electronic funcon can be carried out without releasing
pressure from the system or disassembling the mechanical part of the sensor.
Fault Reason Correcon of fault
No LED is on / not operang. No supply to the sensor or defecve
cable/plug
Check and nd faults in the power
supply, or replace the supply cable.
Yellow and red LED ash. Power supply is not sucient. Install proper power supply.
Valve open and close to fast. Refrigerant is boiling in the stand-
pipe
Increase “lter” sengs and eventu-
ally increase P-band as well.
No contact acvaon
There may be dirt between the elec-
tronic housing and the mechanical
housing.
Separate the two parts and clean the
spring p. Remember to apply sili-
cone grease to the spring p so as to
avoid problems with moisture
Delay in sensor acvaon May be caused by gas and bubbles
in the system.
Check if the sensor is placed opmal-
ly so that gas is avoided.
The valve is not performing the
control funcon well enough.
Oil has accumulated in the level indi-
cator glass which cannot escape.
Drain the level indicator of oil and, if
necessary, clean the oil from the rod.
There is no alignment between the
output signal and the level in the
level indicator.
The sensor is incorrectly calibrated. Perform calibraon.

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 19

Wire and Flex level sensor manual 04 October 2021 HBproducts.dk 20
Quick guide
Installaon
The sensor is installed in the vessel using liquid sealant or PTFE tape like shown in the manual and the electrical unit is
connected. If the electronic unit has the threaded union, make sure it is rmly ghtened to secure good electrical con-
necon.
Setup
The sensor is delivered pre-calibrated for the liquid you specied when ordering and ready for use. To obtain a more
accurate measurement you need to calibrate the sensor as described in the complete manual. You need a computer
and a USB/M12 cable to do the calibraon and more advanced setup. The setup is done in the HB-tool which is down-
loaded from the HBproduct web page www.hbproducts.dk
Measurement signal
The sensor output is a 4-20mA provided on pin 4 in the M12 plug. The signal grow linear to the level. More advanced
wiring and wiring of sensors controlling a valve is described in the complete manual.
+24V DC or AC
- Common
AO, 4-20 mA level
1
4
2
LED Signal ON/OFF/Frequency Funconality
Green ON Supply voltage connected
Flash Run In start signal / in operaon.
OFF No supply voltage
LED indicaon
When the sensor is operang the green LED should the green LED should be on or ashing
This manual suits for next models
9
Table of contents
Popular Accessories manuals by other brands

Gared
Gared MINI-EZ Installation, operation and maintenance instructions

SAGEMCOM
SAGEMCOM Fast PLUG 500 premium user guide

Honeywell
Honeywell CRIR-E1 user guide

Waeco
Waeco CoolFun CA-35 instruction manual

PCB Piezotronics
PCB Piezotronics Y351B03 Installation and operating manual

Myron L
Myron L TechPro ARH1 Replacement instructions

ekwb
ekwb EK-FC970 GTX Strix Backplate Installation and mounting manuals

S+S Regeltechnik
S+S Regeltechnik AERASGARD ACO2-W Operating Instructions, Mounting & Installation

SECURENET
SECURENET OKO DB3A quick start guide

Spinshot
Spinshot SPINSHOT plus user manual

DPM
DPM DT01 manual

PCB Piezotronics
PCB Piezotronics JM352C66 Installation and operating manual