V. Installation Instructions
5.2 Locating Unit
For optimal performance, the HealthyAir® Ceiling-Mount Aerosol Extractor
should be located such that the Hood of the Extraction Arm can be strategically
positioned about 6”-12” from the emission source.
The unit base should also be installed where it can be easily accessed and
opened for periodic filter replacement. Refer to Section 9.2 for filter
replacement details.
5.2.1 The base unit is designed to be installed in place of a standard 2'x2’
ceiling tile, and it must be securely attached to the building structure for
adequate support.
5.2.2 Depending on the type of building structure, and whether the ceiling has
I-Beam or concrete construction, follow the appropriate protocol for
proper installation and support of the unit.
5.3 Locating Extraction Arm
The Articulating Extraction Arm is specifically designed to work with the
HealthyAirâ Ceiling-Mount Source Captureâ unit model HA-CMSC-G2.
Together, this system will enable effective capture and filtration of ultra-fine
airborne aerosols generated in various procedures.
The Articulating Extraction Arm is to be installed to the main structure in the
ceiling (above the drop ceilings) on either side of the chair or work area. The
exact and optimal location of the arm depends on the specific layout of the site
and the presence of other equipment.
In general, the Articulating Extraction Arm should be located within a radius of
36” from the area where work is performed. The arm is equipped with (3)
adjustable joints and a 360° swivel ring, that enable it to be maneuvered to
position the capture hood within 6” of the breathing zone.
The Ceiling-Mount Source Captureâ unit is to be located 4-6’ from the
Articulating Extraction Arm and connected to the arm via a Flex Hose.