Hochiki HCVX User manual

Hochiki HCVX Fire Control Panel Issue Date: June 2016
Installation and Operation Manual
Man-1194HA, Revision E01.04
HCVX
Fire Control Panel
Installation and Operation Manual

Hochiki HCVX Fire Control Panel
Installation and Operation Manual
Man-1194HA, Revision E01.04
Underwriters Laboratories (UL)
Fire Alarm Equipment
Hochiki HCVX Fire Control Panel
Models of the HCVX Fire Control Panel are suitable as follows:
Without integrated dialer and conventional detection for 2 Zone (HCVX-2R/115V or 230V), 4 Zone (HCVX-4R/115V or 230V) or
8 Zone (HCVX-8R/115V or 230V)
With integrated dialer and conventional detection for 2 Zone (HCVXD-2R/115V or 230V), 4 Zone (HCVXD-4R/115V or 230V) or
8 Zone (HCVXD-8R/115V or 230V)
Non-coded Signaling, DACT requires Integrated Dialer
Local Signaling Unit
Commercial protected-premises control unit
Style Y for Notification Appliance Circuits
Types of signaling services are NFPA 72 conventional IDC Class B and Style C or Class B, Class A Style D, Class A Style E,
Style B, automatic fire alarm, manual fire alarm
Compatibility identifier AXT0110
Install detectors with spacing as specified in section 90.19 of UL 864, 9th edition where units employing the multiple detector operation shall
include guidelines for installing of a minimum of two detectors in each protected space and to reduce the detector installation spacing to 0.7
times the linear spacing in accordance with National Fire Alarm Code, NFPA 72. Also reference 55.3.1 and 55.3.2 of UL 864, 9th edition for
these detector spacing requirements.

Hochiki HCVX Fire Control Panel
Installation and Operation Manual
Man-1194HA, Revision E01.04
Copyright © 2016 by Hochiki America
All rights reserved.
Hochiki is a registered trademark of Hochiki America
All other product or service names are property of their respective owners.

i
Hochiki HCVX Fire Control Panel
Installation and Operation Manual
Man-1194HA, Revision E01.04
Contents
TableofContents
Contents ......................................................................................................i
Introduction................................................................................................5
Using This Manual ............................................................................................................... 6
Related Documentation........................................................................................................ 6
Document Conventions........................................................................................................ 7
Part Numbers ........................................................................................................................................7
Writing Styles........................................................................................................................................7
If You Need Help....................................................................................................................................7
ContactingHochiki America Technical Support..................................................................................7
RMA Returns Required.........................................................................................................................8
Warranty Returns..................................................................................................................................8
Product Return Address.......................................................................................................................8
Overview...................................................................................................11
Hardware Features............................................................................................................. 13
Internal Power Supply........................................................................................................................14
Power Outputs ....................................................................................................................................14
NAC Outputs.......................................................................................................................................14
Panel Controls and Indicators...........................................................................................................15
Field Terminals ...................................................................................................................................21
Optional Dialer Board.........................................................................................................................23
Installation................................................................................................24
General Installation Checklist............................................................................................ 24
Before You Begin............................................................................................................... 25
Determining System Current Draw..................................................................................... 26
Standby-Battery Capacity..................................................................................................................26
Operating Constraints........................................................................................................................26
Mounting the Fire Control Panel........................................................................................ 26
Preparing.............................................................................................................................................26
Removing the Fascia..........................................................................................................................27
Mounting..............................................................................................................................................27
Separation of Circuits........................................................................................................ 28
AC Cabling......................................................................................................................... 29
Standby-Battery Cabling.................................................................................................... 30
Field Cabling.......................................................................................................................................32

ii
Hochiki HCVX Fire Control Panel
Installation and Operation Manual
Man-1194HA, Revision E01.04
Detection Zones..................................................................................................................................32
ALM RES..............................................................................................................................................33
Notification Appliance Circuits (NAC)s.............................................................................................33
NAC 1 and NAC 2................................................................................................................................34
Relay Outputs .....................................................................................................................................35
Optional Dialer Board.........................................................................................................................35
TELCO Line Connections...................................................................................................................38
Aux 24V................................................................................................................................................39
ALM RES..............................................................................................................................................39
RS485...................................................................................................................................................39
Connecting the HCVX Annunciator...................................................................................................39
Testing the Installation ...................................................................................................... 40
Troubleshooting................................................................................................................. 40
Programming and Operating ..................................................................42
Programming the Fire Control Panel.................................................................................. 44
Open the Menu....................................................................................................................................44
Navigate the Menu..............................................................................................................................45
Configuration Codes ..........................................................................................................................48
Control Operation...............................................................................................................................56
Single Zone Fire Condition................................................................................................................56
Silence/Resound Fire Drill .................................................................................................................57
Reset....................................................................................................................................................57
Zone Trouble.......................................................................................................................................57
NAC Trouble........................................................................................................................................57
Power Trouble.....................................................................................................................................57
System Trouble...................................................................................................................................57
General Trouble ..................................................................................................................................57
Lamp Test............................................................................................................................................57
Test Mode............................................................................................................................................58
Disablements ......................................................................................................................................59
Alarm Delays.......................................................................................................................................60
Relay Operation ..................................................................................................................................61
Maintenance and Repair..........................................................................62
Cleaning the External Cabinet and Fascia-Door..............................................................................62
Inspecting Batteries............................................................................................................................62
Replacing Standby-Batteries.............................................................................................................62
Removing the Standby-Batteries ......................................................................................................62
Installing the Standby-Batteries........................................................................................................63
Replacing Fuses .................................................................................................................................63
Battery Fuse........................................................................................................................................63
Transformer Fuse ...............................................................................................................................64
AC Input Fuse .....................................................................................................................................65

iii
Hochiki HCVX Fire Control Panel
Installation and Operation Manual
Man-1194HA, Revision E01.04
Replacing Cabinet Components........................................................................................................66
Specifications...........................................................................................67
Electrical............................................................................................................................ 67
AC Line Connection............................................................................................................................67
Power Supply......................................................................................................................................67
Ground Trouble Indication.................................................................................................................67
Maximum Current Draw......................................................................................................................68
Rechargeable Battery Circuit.............................................................................................................68
Field Wiring.........................................................................................................................................70
Initiating Device Circuit (IDC) Ratings ..............................................................................................72
Notification Appliance Circuit (NAC).................................................................................................72
Relay Ratings......................................................................................................................................73
AUX 24V...............................................................................................................................................73
ALM RES..............................................................................................................................................73
Dialer Board ........................................................................................................................................73
Cabling.................................................................................................................................................74
Operating Environment...................................................................................................... 74
Physical Specifications...................................................................................................... 74
Equipment List.........................................................................................75
Hochiki HCVX Fire Control Panel HCVX Fire Control Panels ............................................. 75
Supporting Components and Replacements...................................................................... 76
Compatibility Identifier.......................................................................................................................78
Detectors ........................................................................................................................... 78
Hochiki.................................................................................................................................................78
Notification Appliances...................................................................................................... 79
Amseco Compatible NAC Devices.....................................................................................................79
Gentex Compatible NAC Devices ......................................................................................................82
System Sensor Compatible NAC Devices.........................................................................................84
Cooper/WheelockCompatible NAC Devices.....................................................................................86
Calculations..............................................................................................91
Determining the Amp-Hour Rating..................................................................................... 91
Current-Load.......................................................................................................................................92
NAC Wiring Length.............................................................................................................................93
Operating Instructions.............................................................................96
InspectingBatteries............................................................................................................................99
Replacing Standby-Batteries.............................................................................................................99
RelatedDocumentation......................................................................................................................99

iv
Hochiki HCVX Fire Control Panel
Installation and Operation Manual
Man-1194HA, Revision E01.04
Index........................................................................................................100

5
Hochiki HCVX Fire Control Panel
Installation and Operation Manual
Man-1194HA, Revision E01.04
Section 1
Introduction
This manual describes conventional detection models of the Hochiki HCVX Fire Control. These models can
include or exclude dialer communication.
Models including dialer communication are the 2 zone HCVXD-2R, 4 zone HCVXD-4R and 8 zone HCVXD-
8R.
Models excluding dialer communication are the 2 zone HCVX-2R, 4 zone HCVX-4R and 8 zone HCVX-2R.
Power supply options of these models are available for 115 VAC or 230 VAC and cabinet colors are available
in red.
Reference Appendix B, Equipment list of this manual for a complete description of features available for the
HCVX Fire Control Panel.
This section describes:
Using This Manual
Related Documentation
Document Conventions
If You Need Help
The figure below illustrates the HCVX Fire Control Panel:
Figure 1-1
HCVX Fire Control Panel

6
Hochiki HCVX Fire Control Panel
Installation and Operation Manual
Man-1194HA, Revision E01.04
Using This Manual
The following sections provide instructions for installing, testing and troubleshooting the HCVX Fire Control
Panel:
Section 1 Introduction provides document conventions, the technical help-line, repair and return
information.
Section 2 Overview provides a summary of features for the HCVX Fire Control Panel.
Section 3 Installation describes how to setup, install, test and troubleshoot the HCVX Fire Control Panel.
Section 4 Operation describes how to open security functions for Access Level 2 or Access Level 3, identify
Alarm Conditions, Controls and Indicators, understand Relay Contacts and how to Configure
Ancillary Circuit Boards.
Section 5 Maintenance and Repair describes how to maintain and repair the HCVX Fire Control Panel.
Appendix A Specifications provide characteristics of the HCVX Fire Control Panel.
Appendix B Equipment List provides model numbers for Hochiki HCVX Fire Control Panel HCVX Fire Control
Panels, loop devices, accessories, replacement parts and compatible Notification Appliances.
Appendix C Calculations provides calculations for determining load capacity, battery rating, and wiring length
of the HCVX Fire Control Panel.
Appendix D Operating Instructions provides an overview of HCVX Fire Control Panel status and control
instructions.
Related Documentation
The following documentation shall be used for installing and operating models of the HCVX Fire Control
Panel:
Installation and Operation Manual, Man-1194HA, Revision E01.XX
Operating Instructions, Man-1195HA, Revision E01.XX
UL Compliance Label, HA1864-00, Revision E01.XX

7
Hochiki HCVX Fire Control Panel
Installation and Operation Manual
Man-1194HA, Revision E01.04
Document Conventions
This document contains conventions for part numbers and writing style.
Part Numbers
Part numbers are provided in Section 1, Appendix B and Appendix D of this manual. Refer to Appendix D,
Door Label for a diagram summary of this manual. Refer to Appendix B, Equipment List for a complete list of
part numbers required for completing this installation.
Writing Styles
Before you begin using the HCVX Fire Control Panel, familiarize yourself with the stylistic conventions used
in this manual:
Italic type Denotes a displayed variable, a variable that you must type, or is used for emphasis.
Courier font Indicates text displayed on a computer screen.
If You Need Help
If you need technical support contact Hochiki at (800) 845 - 6692 or e-mail technicalsupport@hochiki.com.
Technical support is available Monday through Friday, 7:00 AM to 5:00 PM, Pacific Standard Time.
Contacting Hochiki America Technical Support
On-site technicians familiar with the product issue should contact Technical Support and include the:
Product part number
Purchase order number
Product serial number
Current function of the product
Expected function of the product
Installation of the product

8
Hochiki HCVX Fire Control Panel
Installation and Operation Manual
Man-1194HA, Revision E01.04
RMA Returns Required
A Return Material Authorization (RMA) must be assigned to all products returning to Hochiki America.
Technical
Support will assign an RMA to a returning product after recording information collected from the
on-site technician.
Hochiki America cannot not accept product-returns that do not include an accompanying
RMA number.
An RMA number is assigned when:
•
A product issue is acknowledged by a Hochiki America’s Technical Support representative
•
A product was damaged during shipping
•
An incorrect product was shipped
•
An order was placed using an incorrect part number *
•
An order was placed using an incorrect part quantity *
•
An order is no longer required *
* Restocking fees may apply.
Warranty Returns
Technical Support can replace a defective product when the original purchase is within the warranty period
defined in
the sales contract. Check your sales-contract for more information or contact your Hochiki
America’s sales representative about the warranty period described in your sales-contract or terms and
condition.
Warranty products that have been placed in service will be repaired or replaced by Hochiki America..Warranty
products that have not been placed in service will be returned to Hochiki America stock and an equivalent
credit will be provided to the contractor.
Product Return Address

9
Hochiki HCVX Fire Control Panel
Installation and Operation Manual
Man-1194HA, Revision E01.04
Prominently display the RMA number on all packages sent to Hochiki America Corporation for return.
Ship
all return products to:
Attention: RMA #
Hochiki America Corporation
7051
Village Drive, Suite 1oo
Buena
Park, CA 90621

10 of 105
Overview 2
Hochiki HCVX Fire Control Panel
Installation and Operation Manual
Man-1194HA, Revision E01.04
This page intentionally left blank

11 of 105
Overview 2
Hochiki HCVX Fire Control Panel
Installation and Operation Manual
Man-1194HA, Revision E01.04
Overview
The HCVX Fire Control Panel is a conventional fire control panel with features for operating detection
zones, Notification Appliance Circuits (NACs), relays and auxiliary 24 volt power.
Models of the HCVX Fire Control Panel support synchronization protocols from Wheelock, Gentex,
Amseco and System Sensor.
These models are UL864 listed for operating:
Detection devices from Hochiki
UL listed conventional initiation devices
Notification devices from Gentex, Wheelock, System Sensor and Amseco
The fire control panel provides Class B zone detection under default conditions and Class A loop
detection on one zone when configured. Default zones of the HCVX Fire Control Panel can operate as
NFPA 72 Class B, Style C or NFPA 72, Class B, Style B.
The functions of Style C provide trouble conditions for direct-shorts and opens on zone loops. The
functions of Style B provide alarm conditions for direct-shorts and trouble conditions for opens on zone
loops.
A Dialer Board can be installed as an optional feature to provide alarm and trouble reporting. The
Optional Dialer Board provides Contact ID or SIA format reporting through a standard POTS connection.
Models of the HCVX Fire Control Panel provide a resettable, unregulated and special application 24 VDC
power output suitable for powering 4 wire detectors on eight zones. These models also include two
unregulated solid state NAC outputs.
Relays are provided on these fire control panels for Trouble, Supervisory and Fire.
Access levels are provided for controls and programming on the HCVX Fire Control Panel. Access Level
1 provides restricted controls, Access Level 2 provides less restricted controls with limited programming
and Access Level 3 provides unrestricted controls and programming.

12 of 105
Overview 2
Hochiki HCVX Fire Control Panel
Installation and Operation Manual
Man-1194HA, Revision E01.04
The figure below illustrates Class B field wiring terminations of the HCVX Fire Control Panel:
Figure 2-1
Field Wiring Terminations
Models of the HCVX Fire Control Panel provide:
Zone Testing Zone testing provides the automatic resetting of zones in alarm for testing
purposes.
NAC Delay Delay on NAC outputs allows alarm to be verified before premises is evacuated.
Voltage Free Relay Contacts Voltage free relay contacts provide fire, supervisory and trouble reporting for local
control and signaling.
Power All models accept standby-batteries and contain a power supply with an
internal battery charger.
Models of the HCVX Fire Control Panel accept 7 AH or 12 AH valve-regulated, lead-acid batteries and
operate in special application modes for power inputs of 115 VAC or 230 VAC.

13 of 105
Overview 2
Hochiki HCVX Fire Control Panel
Installation and Operation Manual
Man-1194HA, Revision E01.04
Hardware Features
The figure below illustrates hardware features of the HCVX Fire Control Panel:
Figure 2-2
Hardware Features
Key Item Description
1 Main Terminal Block
and Fuse Holder The Main Terminal Block accepts input power and transformer primary
connections. The Main Terminal Block contains a 3.15 Amp slow-blow
fuse rated for 250 VAC. Connections from the primary of the
transformer to the Main Terminal Block are pre-wired at the factory.
Terminals of the Main Terminal Block are designated Line, Neutral
and Ground.
2 Field Terminals Field terminals provide connections for Zones, NACs, Relay Outputs
and AUX 24V.
3 Fascia The front fascia of the HCVX Fire Control Panel is populated with
controls and indicators for programming and operating the fire control
panel.
4 Standby-Batteries The HCVX Fire Control Panel accepts two 12 VDC, 7 AH or
12 AH batteries for operating during an AC power failure.

14 of 105
Overview 2
Hochiki HCVX Fire Control Panel
Installation and Operation Manual
Man-1194HA, Revision E01.04
Internal Power Supply
The internal power supply of the HCVX Fire Control Panel meets UL 864, 9th edition and provides a 4
Amp, linear power-source for operating FACP functions as well as charging the standby batteries.
Reference Appendix C, Calculations to determine load current limitations of the 4 Amp power supply.
Features of the internal power supply include:
Battery-Backup Provides battery power to the load when the AC input of the power
supply falls below the rated level. The voltage at the load remains
within the specified range during these switching-transitions.
Short-Circuit Protection Provides a shut down on the load side of the power supply when the
load-current exceeds the maximum level.
Status The AC input to the power supply is supervised by the HCVX Fire
Control Panel. The control panel provides an LED status display for
normal and trouble conditions. Normal conditions occur when the power
supply is operating in an acceptable range. Trouble conditions occur
when the power supply is not operating in an acceptable range.
Power Outputs
The HCVX Fire Control Panel provides power outputs to the terminals of NAC 1, NAC 2, and AUX 24V
terminals.
Reference Section 3, Installation and Appendix A, Specifications for further information concerning NAC
and AUX 24V outputs of the HCVX Fire Control Panel.
NAC Outputs
NAC outputs of the HCVX Fire Control Panel are programmable and can be operated in regulated or
special application mode.
Reference Appendix A, Specifications for constraints and operating levels of these NAC output modes.

15 of 105
Overview 2
Hochiki HCVX Fire Control Panel
Installation and Operation Manual
Man-1194HA, Revision E01.04
Panel Controls and Indicators
The fascia of the HCVX Fire Control Panel is divided into sections for controls and indicators.
The figure below illustrates controls and indicators of the HCVX Fire Control Panel:
Figure 2-3
Controls and Indicators
Key Description Key Description
A Upper Indicators D Upper Controls
B Central Controls E Lower Controls
C Lower Indicators
General System Status
Disabled
NAC Trouble
Mode
(+1)
Trbl.
(+10)
Trbl.
Trouble/Test/Disablement
Trouble/Test/Disablement
Enter
Trbl.
Select
Trbl.
Mode
Trbl.
Reset
Trbl.
Enable Access
Test M ode On
Delay On
AC Power On
Alarm Silenced
Supervisory
Disablement
System Trouble
General Trouble
Lamp Test
Trbl.
Silence/Resound
Fire Drill
Trbl.
Silence Buzzer
Trbl.
8765
4321
Fire
Alarm In Zone
Alarm In Zone
Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.
NAC1 NAC2Sys.FuseEarth
Trbl.Trbl.Trbl.Trbl.Trbl.
Comms
Low
Batt.
Trbl.
Aux.24V
Trbl.
CPU
Fail
Batt.
Fail
Mains
W/Dog
Reset
Processor
Reset
Write
Enable
Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.Trbl.
A
B
C
A
B
C
D
E

16 of 105
Overview 2
Hochiki HCVX Fire Control Panel
Installation and Operation Manual
Man-1194HA, Revision E01.04
Upper Indicators
The figure below illustrates upper indicators of the HCVX Fire Control Panel:
Figure 2-4
Upper Indicators
The table below describes upper indicators of the HCVX Fire Control Panel:
Key Upper Indicators LED Color
A General System Status
Fire Red
AC Power On Green
Delay On Yellow
Test Mode On Yellow
Disablement Yellow
Supervisory Yellow
NAC Trouble Disabled Yellow
General Trouble Yellow
System Trouble Yellow
Alarm Silenced Yellow
General System Status
Disabled
NAC Trouble
Mode
Trouble/Test/Disablement
Trouble/Test/Disablement
Enable Access
Test M ode O n
Delay On
AC Power On
Alarm Silenced
Supervisory
Disablement
System Trouble
General Trouble
8765
4321
Fire
Alarm In Zone
Alarm In Zone
AA
BB C
C
D

17 of 105
Overview 2
Hochiki HCVX Fire Control Panel
Installation and Operation Manual
Man-1194HA, Revision E01.04
Key Upper Indicators LED Color
B Alarm In Zone
1 Trouble/Test/Disablement Yellow
Alarm Red
2 Trouble/Test/Disablement Yellow
Alarm Red
3 Trouble/Test/Disablement Yellow
Alarm Red
4 Trouble/Test/Disablement Yellow
Alarm Red
C Alarm In Zone
5 Trouble/Test/Disablement Yellow
Alarm Red
6 Trouble/Test/Disablement Yellow
Alarm Red
7 Trouble/Test/Disablement Yellow
Alarm Red
8 Trouble/Test/Disablement Yellow
Alarm Red
D Two Seven-Segment LEDs
Mode The Mode display contains two seven-segment LEDs for
programming configurations and identifying status conditions.
This manual suits for next models
12
Table of contents
Other Hochiki Control Panel manuals
Popular Control Panel manuals by other brands

Steamist
Steamist TC-135 Installation and operating instructions

Haes
Haes ELAN HS-5000 Series user manual

Extron electronics
Extron electronics TLP Pro x25M Series Setup guide

vds
vds EURO380 M1 instruction manual

BFT
BFT THALIA P installation manual

Ptotec
Ptotec 3300 Installation, commissioning and maintenance manual