MODULE FOR SINGLE LAMP SELECTION AND MONITORING
Switching of one selected light in the electric circuit
SET010 select
DIP-switch 1
ON for non-maintained mode
OFF for maintained mode (Default)
DIP-switch 2
OFF for lighting address 1-16 (Default)
ON for lighting address 17-32
Indicator LED
Rotary coding switch
for setting the exact lamp adress DIP-switch 3 (OFF)
Attention!
Connect L and N correctly!
Exchanging L and N causes malfunction.
The address range 17 to 32 can be selected by setting DIP switch 2 to ON.
By means of a suitable control, it is possible with the aid of the SET010 select to determine whether the
lamp connected to it is ready for use or faulty.
Function
In the mixed operation circuit, the connected lamp can also be additionally set in non-maintained mode
or maintained mode (DIP Switch 1).
Settings
Setting the lighting address is carried out by a rotary coding switch that is easily accessible from the
outside.
Lighting addresses 1 to 16 can be slected when DIP switch 2 is set at OFF.
The module is already prepared for administering a total of 32 lighting addresses.
(DIP switch 2 = ON and rotary coding switch = 1 is equivalent to lighting address 17 etc.)
Technical description
Cross section:
Temperature:
Dimensions (L x W x H in mm) 78 x 30 x 20
2
Max: 1.5mm
-30°C up to +60°C, T =+75°C
cmax
SET010 select
Prewired