PAGE 2 15 MAY 2006 MAN0808-01
HE-XE102 Specifications / Installation
4 Wiring and Jumpers
Wire according to the type of inputs / outputs used, and select the
appropriate jumper option.
a. Wiring Examples
J1 Orange
Terminal
Connector
XE102
Name
I1 IN1
I2 IN2
I3 IN3
I4 IN4
I5 IN5
I6 IN6
I7 IN7
I8 IN8
H1 HSC1 /IN9
0V Ground
A1 Analog IN1
A2 Analog IN2
A3 Analog IN3
A4 Analog IN4
0V Ground
J2 Black
Terminal
Connector
XE102
Name
C6 Relay 6 COM
R6 Relay 6 NO
C5 Relay 5 COM
R5 Relay 5 NO
C4 Relay 4 COM
R4 Relay 4 NO
C3 Relay 3 COM
R3 Relay 3 NO
C2 Relay 2 COM
R2 Relay 2 NO
C1 Relay 1 COM
R1 Relay 1 NO
H4 HSC4 / IN12
H3 HSC3 / IN11
H2 HSC2 / IN10
b. I/O Jumpers Settings (JP1 - JP2)
c. External Jumpers Settings
5 Safety
Warning: Consult
user documentation.
Warning: Electrical
Shock Hazard.
WARNING: To avoid the risk of electric shock or burns,
always connect the safety (or earth) ground before making
any other connections.
WARNING: To reduce the risk of fire, electrical shock, or
physical injury it is strongly recommended to fuse the voltage
measurement inputs. Be sure to locate fuses as close to the
source as possible.
WARNING: Replace fuse with the same type and rating to
provide protection against risk of fire and shock hazards.
WARNING: In the event of repeated failure, do not replace
the fuse again as a repeated failure indicates a defective
condition that will not clear by replacing the fuse.
WARNING: Only qualified electrical personnel familiar with
the construction and operation of this equipment and the
hazards involved should install, adjust, operate, or service this
equipment. Read and understand this manual and other
applicable manuals in their entirety before proceeding.
Failure to observe this precaution could result in severe bodily
injury or loss of life.
All applicable codes and standards need to be followed in the
installation of this product.
Adhere to the following safety precautions whenever any type
of connection is made to the module:
Connect the safety (earth) ground on the power connector first
before making any other connections.
When connecting to electric circuits or pulse-initiating
equipment, open their related breakers.
Do not make connections to live power lines.
Make connections to the module first; then connect to the
circuit to be monitored.
Route power wires in a safe manner in accordance with good
practice and local codes.
Wear proper personal protective equipment including safet
glasses and insulated gloves when making connections to
power circuits.
Ensure hands, shoes, and floor are dry before making an
connection to a power line.
Make sure the unit is turned OFF before making connection to
terminals.
Make sure all circuits are de-energized before making
connections.
Before each use, inspect all cables for breaks or cracks in the
insulation. Replace immediately if defective.
Note: The Cscape Module Setup configuration must match the
selected I/O (JP) jumper settings.
001XLE026
JP1 Digital DC In / HSC
Positive Negative
Logic Logic
Default 001XLE027
A1
A2
A3
A4
JP2 Analog In (A1 – A4)
Current Voltage
(20 mA) (10 V)
Default
When found on the product, the
following symbols specify:
J1 JP2
JP1
J2
001XLE025
Location of I/O jumpers (JP)
and wiring connectors (J1
and J2).
I1
0V
001XLE036
12-24VDC
I1
0V
Positive Logic In Negative Logic In
Positive Logic vs. Negative Logic Wiring
The XLE can be wired for Positive Logic inputs or
Negative Logic inputs.
001XLE015
0V ON J1
12-24VDC
R2
C2
R3
C3
R6
C6
R4
C4
R5
C5
R1
C1
H4
H2
H3
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
LOAD
230VAC
OR
25VDC
N
L
XE102 J2 Black
Positive Logic
Digital In / Relay Out
Wiring Specifications
For I/O wiring (discrete), use the
following wire type or equivalent:
Belden 9918, 18 AWG or larger.
For shielded Analog I/O wiring,
use the following wire type or
equivalent: Belden 8441, 18
WG or larger.
For CAN wiring, use the
following wire type or equivalent:
Belden 3084, 18 AWG or larger.
The External Jumpers are used fo
termination of the RS-485 ports.
The XLE is shipped unterminated.
To terminate, select one of the
umpers shipped with the product
and insert it based upon the option
that is desired.
Factory Use
(default – none)
MJ2 Termination
(default – none)
MJ1 Termination
(default – none)
001XLE037
s seen when looking at the top of the XLE unit. Refer to
Section 3 for the location of the External Jumpers.
XE102 J1 Orange
Positive Logic In
Digital In /
20 mA Analog In
I1
I2
I3
I4
0V
A1
A2
0V
I5
I6
I7
I8
A3
A4
H1
001XLE017
12-24VDC
LOOP PWR
20mA
0-10VDC