4 Modbus
The EasyTronic EC can be integrated into the building management system via
Modbus RTU. The Modbus slave protocol is implemented in the controller. It uses
an RS485 interface for communication with a Modbus master.
The parameters are accessible as holding registers. Read and write operations
must be carried out with the appropriate function codes (FC 03 / 06 / 16).
Up to 125 variables can be read in one operation. Depending on the baud rate,
select a suitable timeout between the read operations:
Baud rate 38400 ................ 1.0 s
Baud rate 19200 / 9600 ..... 1.5 s
Baud rate 4800 / 2400 ..... 2.0 s
4.1 Parameters for controller status
Register Address Parameter Description Min Max R/W
207 206 DAMPER_FEEDBACK_AI3 Feedback Air-Injector actuator
displayed value = Volt ×100 (for ex.: 655 = 6.55 V)
-999 9999 R
208 207 STATE_REL_FAN Enable fan
0 = deactivated / 1 = activated
0 1 R
209 208 STATE_REL_PUMP_VALVE Enable pump/valve
0 = deactivated / 1 = activated
0 1 R
213 212 OUT_SUPPLY_FAN Fan control signal
displayed value = Volt ×10 (for ex.: 80 = 8.0 V)
0100 R
214 213 OUT_DAMPER Air-Injector control signal
displayed value = Volt ×10 (for ex.: 80 = 8.0 V)
0100 R
216 215 WORKING_TEMP Actual value room temperature
displayed value = °C ×10 (for ex.: 200 = 20 °C)
In the event of a fault, the following values are displayed:
Sensor open: -200
Sensor in short circuit: 970
-200 900 R
219 218 CURRENT_WORKING_SET Currently valid room temperature setpoint, depending on operating
mode and operating state
displayed value = °C ×10 (for ex.: 200 = 20 °C)
see
parameters
see
parameters
R
220 219 FLAG_STA_WORKING Heating/cooling changeover
0 = heating / 1 = cooling
0 1 R
221 220 FLA_CURRENT_MODE_REG Current operating mode
0 = normal operation without week programme
1 = normal operation within week programme
3 = ECO mode
4 = setback operation
0 4 R
223 222 YEAR Current year 2012 2100 R
224 223 MONTH Current month 112 R
225 224 DAY Current day 131 R
226 225 DAY_NAME Current weekday
0 = Su / 1 = Mo / 2 = Tu / 3 = We / 4 = Th / 5 = Fr / 6 = Sa
0 6 R
227 226 HOUR Current hour 023 R
228 227 MIN Current minute 059 R
229 228 SEC Current second 059 R
230 229 FLAG_DOOR_POSITION Door contact
0 = door open / 1 = door closed
0 1 R
231 230 FLAG_ALARM_FAN Alarm Fan
0 = no alarm / 1 = alarm
0 1 R
232 231 FLAG_ALARM_DAMPER Alarm Air-Injector
0 = no alarm / 1 = alarm
0 1 R
Table 4: Modbus parameters for controller status
10
EasyTronic EC
Modbus