Huasun Wireless H3G-TA Installation and operation manual

H3G-TA
ENGINEERING MANUAL
(With CM-02N)
Hangzhou Huasu Technology Co., Ltd
2nd & 3rd Floor of No.3 Building, No.1418-50 Moganshan Road ,Hangzhou
City, Zhejiang Province, P.R. China 310000
TEL: 86-571-87967915 FAX:86-571-87968969
http://huasu-tech.com//

H3G-TA Engineering Manual (CM-02N) B2
Hangzhou Huasu Technology Co., Ltd HTTP://HUASU-TECH.COM// TEL:0571-87967915 ii
Note
·This manual is for HUASU company use only.
·It must be approved by Huasu Technology Department when it is provided to any other
company or individual.
Hangzhou Huasu Technology Co., Ltd
Add: 2nd & 3rd Floor of No.3 Building, No.1418-50 Moganshan Road, Hangzhou City,
Zhejiang Province, P.R. China 310000
The contents of this manual may be modified without notice.
H3G-TA Engineering Manual (CM-02N), P/N HA-0024AAA1,REV.B2。
©2003-2018HuasuTech,2nd&3thFloor of No.3Building,No.1418-50 Moganshan Road,
Hangzhou City, Zhejiang Province, P.R. China 310000
This manual may be copied in whole or in part.
Printed in china

H3G-TA Engineering Manual (CM-02N) B2
Hangzhou Huasu Technology Co., Ltd HTTP://HUASU-TECH.COM// TEL:0571-87967915 iii
Content
Tools required for installation and Debugging...........................................................................................4
1Overview..........................................................................................................................................7
2System Components and Module Description .................................................................................8
2.1 System Components........................................................................................................................8
2.2 TA Module........................................................................................................................................9
2.3 CM Module.....................................................................................................................................10
2.4 TC Module......................................................................................................................................11
3Installation......................................................................................................................................12
3.1 Numbering the Batteries.................................................................................................................12
3.2 TA Test Cable Installation..............................................................................................................13
3.3 TA Module Installation....................................................................................................................15
3.4 Address Setting for TA/TC Module.................................................................................................17
3.5 CT And TC Module Installation, Wiring, Address Setting...............................................................21
3.6 CM Module Installation and Wiring with TA and TC Modules.........................................................22
3.7 Complete Cable and Marking.........................................................................................................23
4Wiring Diagram ..............................................................................................................................24
5Start-up Operation..........................................................................................................................25
5.1 Easy Setup.....................................................................................................................................25
5.2 Real-time Data Query.....................................................................................................................26
5.3 Alarm Query...................................................................................................................................27
5.4 Internal Resistance Test and Setting .............................................................................................27
5.5 Voltage Internal Resistance Temperature Accuracy Checking Method .........................................28
6Access to a Third-Party Monitoring System ...................................................................................29
6.1 Access Via Series Port...................................................................................................................29
6.2 Access Via Network Port................................................................................................................29
6.3 Access Via Dry Contact..................................................................................................................29
7Advanced setting............................................................................................................................29
7.1 Alarm Limits Modified.....................................................................................................................30
7.2 Internal Resistance Setting ............................................................................................................30
7.3 Connect Multiple Strings TA Modules to The Same COM Port......................................................30
7.4 Online Updating Firmware..............................................................................................................30
7.5 Turn on Capacity Estimation Function (Optional)...........................................................................32
7.6 Setting Method for Each String More Than 200 Cells ....................................................................33
8Menu Description ...........................................................................................................................34
9Appendix 1: Correspondence table between ampere-hour and internal resistance of VRLA
batteries..................................................................................................................................................35

H3G-TA Engineering Manual (CM-02N) B2
Hangzhou Huasu Technology Co., Ltd HTTP://HUASU-TECH.COM// TEL:0571-87967915 4
Tools required for installation and Debugging
NO
Picture
Name
Installation tools
1
Socket wrench
12902
Socket head
12307/309/311
2
Multimeter
VC9807A+
3
Clamp Meters
VC3266D
4
Stripper
91108
5
Phillips-head
screwdriver
61213

H3G-TA Engineering Manual (CM-02N) B2
Hangzhou Huasu Technology Co., Ltd HTTP://HUASU-TECH.COM// TEL:0571-87967915 5
6
Flat-head screwdriver
61311
7
Phillips-head
screwdriver
61211
8
Needle nose pliers
70124A
9
Diagonal pliers
70221A
10
Multifunctional network
cable pliers CP-
376TR
11
Scissors
03131

H3G-TA Engineering Manual (CM-02N) B2
Hangzhou Huasu Technology Co., Ltd HTTP://HUASU-TECH.COM// TEL:0571-87967915 6
12
Wrench
47222
Debugging tools
13
Lap top
14
485 Converter and wire
15
Engineering manual
(this manual)

H3G-TA Engineering Manual (CM-02N) B2
Hangzhou Huasu Technology Co., Ltd HTTP://HUASU-TECH.COM// TEL:0571-87967915 7
1Overview
The H3G-TA battery monitoring system consists of TA module, TC module and
control module. The control module with an LCD display and can upload data via
RS485 or network port. During remote monitoring, a computer can be connected to
the battery monitoring device through the network or serial port. Special monitoring
service software needs to be installed on the computer to provide data viewing and
remote control. In addition, according to the specific situation on site, it may also
include installing cabinets, etc.
Figure 1-1-1
The H3G-TA standard configuration has the following features and functionality:
- Online monitoring of cell voltage, internal resistance, cell temperature, overall
voltage, charge and discharge current and ambient temperature.
- Automatic over-limit alarm
- Displays data on CM module
- Key data can be saved on CM module, and a remote computer or a device can
access CM module to pool out the data through a RS485 port or Ethernet port
- Comes standard with two dry contact outputs on CM module
Optional features:
- 7 inch, 10 inch display;
Huasu technology provides its users with installation solutions, engineering
drawings, device configuration, wiring methods and wiring diagram.
Installation steps are as follows:
1 Check inventory of equipment and accessories according to the packing list
upon arrival
2 Installation solutions. Determine the installation location and wiring method

H3G-TA Engineering Manual (CM-02N) B2
Hangzhou Huasu Technology Co., Ltd HTTP://HUASU-TECH.COM// TEL:0571-87967915 8
of the equipment according to the engineering drawings and site conditions,
and explain to the user and obtain user approval.
3 Mounting equipment
4 Wiring
5 Testing
6 Check before approval
7 Training
The above contents will be described in detail below.
2System Components and Module Description
2.1 System Components
Standard configuration below:
No.
Picture
Name
1
TA Module
2
Control Module
CM-02N
3
TC Module
4
Current
Transformer (CT)
5
TA Test Cable
6
TC Test Cable
7
Communication
Cable
8
Power Cable

H3G-TA Engineering Manual (CM-02N) B2
Hangzhou Huasu Technology Co., Ltd HTTP://HUASU-TECH.COM// TEL:0571-87967915 9
Optional parts:
No.
Picture
Name
1
Monitoring Module
MM-07
2
Monitoring Module
MM-10
TA module is for monitoring cell voltage, cell internal resistance and cell
temperature. TC module is for monitoring battery string charge and discharge current
and ambient temperature, and is connected to the control module through the UART
bus. The control module is connected to the server through the serial port or network
port to achieve remote centralized management.
The system topology is as follows:
Figure 2-1-1
2.2 TA Module
TA module can monitor cell voltage, cell internal resistance and temperature, and
upload the data to the control module through the communication port. TA module
itself does not with an alarm judgment function. It should be noted that the 2V module

H3G-TA Engineering Manual (CM-02N) B2
Hangzhou Huasu Technology Co., Ltd HTTP://HUASU-TECH.COM// TEL:0571-87967915 10
can only be used to monitor 2V batteries, and 6V and 12V module also the same,
otherwise it will damage the module.
The ports description is as shown in the figure below.
Figure 2-2-1
Name
Description
J1 port
Test port, connects with battery negative and positive
poles.
COM1/COM2 port
This is an internal parallel UART port, which are used in
communication between TA Modules.
LEDs
A double colors LED with a red and green light, green light is
power light and red light is communication light.
2.3 CM Module
CM module can read the monitoring values one by one from the TA and TC
modules, and perform analysis, processing and display. One CM module can monitor
up to six battery strings. The specific functions are as follows:
a、Read the monitoring data from each TA and TC module;
b、With LCD display, it can query real-time monitoring data and historical alarm
records
c、Can set parameters for operation limitations.
d、Automatic alarm function. In the event of an alarm, an LED light will flash and
a buzzer will sound, the corresponding dry contact will automatically shut off.
e、Connects to a host computer through an RS485 or a Ethernet port.

H3G-TA Engineering Manual (CM-02N) B2
Hangzhou Huasu Technology Co., Ltd HTTP://HUASU-TECH.COM// TEL:0571-87967915 11
Figure 2-3-1
Name
Description
LCD display
Two lines of text are displayed, 122X32.
Button
Total of four buttons, “Esc” for exit,“▲”“▼”for page
up/page down,“Enter” for confirmation.
LED
P is the power light, which is always on after power on; when
USB is on, it indicates that the device is failture; E1: indicates
a communication error; E2: indicates a battery alarm; R1 /
T1: COM1 is sending and receiving data; R1: receiving data;
T1: sending data, and R2 / T2, R3 / T3, R4 / T4, and R5 / T5:
correspond to COM2, COM3, COM4, and COM5.
Ground
Connects to the ground.
Power input
100~240VAC input.
External input
IN1, IN2, two external digital quantities can be input.
Dry contact
J1 for module or communication alarm, J2 for battery
alarm, DC220V/1A.
COM5 port
Data upload port that connects to a remote computer through
an RS485, Pin9 is - and Pin5 is +, the baud rate is
19200BPS.
LAN port
Direct access to LAN network, support MODBUS / TCP and
SNMP protocol.
COM1A-COM4A
Connects to TA module or TC module, one port is able to
communicate with 240 modules, Max. support 960 modules
in total.
DC12V output port
12V power output port, pin 3 is +, pin 4 is-, pin 1 and 2 are
empty.
2.4 TC Module

H3G-TA Engineering Manual (CM-02N) B2
Hangzhou Huasu Technology Co., Ltd HTTP://HUASU-TECH.COM// TEL:0571-87967915 12
The TC module monitors charge and discharge current and ambient temperature
for one string. And it can communicate with the CM module through the UART port.
One string needs one TC Module. The ports description are shown below.
Figure 2-4-1
Name
Description
J1 port
Connects to the current transformer and the ambient temperature
sensor.
LED
A double colors LED with a red and green light, the green is power
light, the red is communication light.
COM1/COM2
port
This is an internal parallel UART port, which are used in
communication with TA Module and converter.
VIN port
Power input,DC8-13V,where the left is + and right is -,
powered by the CM Module, where the maximum power
is less than 1W.
3Installation
3.1 Numbering the Batteries
Before connecting the TA Modules to the batteries, the batteries should be
numbered and labeled correctly by using a label to paste on the surface of the battery
where the labels are easy to be seen. The first battery, or, battery NO.1 must be the
first one on the string positive terminal, the NO.2 is the battery following the NO.1
battery, and so on. The last battery is the one attached closest to the string negative
terminal. The batteries must be numbered in accordance with this method.

H3G-TA Engineering Manual (CM-02N) B2
Hangzhou Huasu Technology Co., Ltd HTTP://HUASU-TECH.COM// TEL:0571-87967915 13
Figure 3-1-1
Figure 3-3-1
3.2 TA Test Cable Installation
Each battery should be connected to one TA test cable on its poles. Put the red
cable on the positive pole of the battery (See (1)), and the black ones for the negative
pole (See (2)).

H3G-TA Engineering Manual (CM-02N) B2
Hangzhou Huasu Technology Co., Ltd HTTP://HUASU-TECH.COM// TEL:0571-87967915 14
Figure 3-2-1
It should be noted that the TA test cable must be installed outside the
connection bar (cable) between the batteries, and it is not allowed to be
sandwiched between the battery pole and the connection bar, starting from the
near battery end, in this order: battery pole → connection strip → battery
monitoring terminal → flat gasket → spring gasket → nut, as shown below:
Figure 3-2-2
Figure 3-2-3
After all installation and commissioning work is completed, the tightness of each

H3G-TA Engineering Manual (CM-02N) B2
Hangzhou Huasu Technology Co., Ltd HTTP://HUASU-TECH.COM// TEL:0571-87967915 15
battery pole screw must be checked and marked, the specific method is as follows:
After confirming that the bolts are tightened with a torque wrench, use a marker
to mark the screws as shown below.
Figure 3-2-3
When adjusting and loosening the bolts of the battery pole connection strip
and restoring the battery string breakpoint, the module and the test cable must
be disconnected first. It is forbidden to perform the above operations when the
module and the test cable are connected, otherwise themodule will bedamaged.
The following sequence must be followed when installing and removing
modules:
When installing: install the test cable first, then connect the module
When disassembling, first disconnect the module from the test cable, and
then remove the test cable.
3.3 TA Module Installation
Choose a suitable location to install the TA module. Generally, it is directly
attached to the side or front of the battery through the back double-sided adhesive. To
ensure the firmness, it is recommended to use glass glue to reinforce it. Note that
when mounted on the front, it cannot be stuck on the safety valve (as shown in the
following figure (1)).

H3G-TA Engineering Manual (CM-02N) B2
Hangzhou Huasu Technology Co., Ltd HTTP://HUASU-TECH.COM// TEL:0571-87967915 16
Figure 3-3-1
Generally, the TA module can be fixed in the following three positions:
Position
Installation and
description
Application
Battery side
The module is fixed
with 3M double-sided
tape, which is often
used when the battery
is placed in two rows on
the battery rack or
there is enough space
between the battery
and the battery to
install the module (it is
recommended to use
glass glue to
strengthen)
Battery top
Use the module with
3M double-sided tape
to fix it, which is often
used when there is not
enough place on the
side of the module to
install the module

H3G-TA Engineering Manual (CM-02N) B2
Hangzhou Huasu Technology Co., Ltd HTTP://HUASU-TECH.COM// TEL:0571-87967915 17
Battery rack
Use an electric drill to
punch holes in the
battery rack, and fix it
by screwing the ears of
the module with its own
ears. It is often used
when there is not
enough space on the
side and top of the
battery to install the
module
Insert the TA test cable plug to the TA module's J1 port, and connect one end of
the TA communication cable to the COM2 port of the module, and the other end to the
COM1 port of the next module after setting the address. The COM1 and 2 of TA
module functions are completely the same, no need to distinguish; at this time, the TA
module has been powered on and the green light should be always on.
Although the TA module consumes only a very small current, if the battery
is not charged for a long time (more than one month) after installation, it is
recommended to unplug the TA test cable from J1 port.
3.4 Address Setting for TA/TC Module
Method 1: Using TA address modifier to set TA/TC module address
Take the 2 strings and 32 cells per string as an example,
TA address of string 1 is set to: 1 ~ 32, and the TC address is set to: 241
TA address of string 2 is set to: 1 ~ 32, and the TC address is set to: 241.
After the address modification is completed, connect the first string to the
COM1A port of the control module, and the second string to the COM2A port.
Address Setting For TA Module
Turn on the side switch → connect the TA module with a communication cable →
press the "▲ ▼ key" to set the address → press the "Enter" key to confirm the
modification → the status light turns green to indicate that the modification was
successful, and the red light indicates that the modification failed
Address Setting For TC Module
Turn on the side switch → connect the TC module with a communication cable →
press the “ESC” key, set the address via the “▲ ▼ key” → jump to the “H-A” interface

H3G-TA Engineering Manual (CM-02N) B2
Hangzhou Huasu Technology Co., Ltd HTTP://HUASU-TECH.COM// TEL:0571-87967915 18
by pressing the “Enter” key → select “H-C” via the “▲ ▼ key” → press "Enter" to jump
to the "96" interface → press "Enter" to jump to the address interface → press "Enter"
to confirm the modification.
Note:
1. "H-A" means to modify the TA address, turn on the side power switch, and
modify the TA address by default.
2. "H-C" means to modify the TC address, it needs to be changed to the TC
address mode according to the above operation.
3. "96" is the baud rate, modify the TA and TC address, baud rate is all 9600.
4. The factory address of the TA module is 1, and the factory address of the TC
module is 1.
Figure 3-4-1
The TA address modifier can be used to modify the addresses of TA and TC
modules more conveniently and quickly, especially when mass modifying. If you need
TA address modifier, you can contact us directly for purchase.
After the address modification is successful, replace the next module and press
Enter to continue the modification.
The address modification method of TC module is the same as TA module, just
change module type H-A to H-C module.
Method 2: Use the control module to modify the TA and TC module
addresses
Take the 2 strings and 32 cells per string as an example, the TA address of string
1 is set to: 1 ~ 32, and the TC address is set to: 241 (The default addresses of TA and
TC are both 1). TA address of string 2 is set to: 1 ~ 32, and the TC address is set to:
241. After the address modification is completed, connect the first string to the COM1A
port of the control module, and the second string to the COM2A port.

H3G-TA Engineering Manual (CM-02N) B2
Hangzhou Huasu Technology Co., Ltd HTTP://HUASU-TECH.COM// TEL:0571-87967915 19
When modifying the TA and TC module addresses, only one TA or TC module can
be connected to the COM1A port of the control module each time, and only one
module address can be modified at a time.
First connect a TA module to the positive and negative poles of the battery, then
connect the COM1 port of the TA module to the COM1A port of the control module,
and modify it according to the following steps:
ESC → D Setup (password: 2022) → 4 addr Wr → 4.3 mod addr
Note:The module type is HG-TA and the target address is 2
Note:1 → 2 indicates that the address modification is successful, and
the address is changed from 1 to 2
After the address modification is successful, replace the next module and press
Enter to continue the modification.
The modification method of the TC module address is the same as the TA module,
just change the module type H3G-TA to TC module.
Method 3: Use "H3G-TA Debugging Tool" to modify the addresses of TA
C. Hist Alarm
D. Setup
Enter PIN:
2022
3 Setup
4 Addr Wr
4.2 Read
4.3 Mod addr
COM1,TA Mod, 001
COM1,H3G-TA,002
COM1,H3G-TA, 003
H3G-TA, 1→2

H3G-TA Engineering Manual (CM-02N) B2
Hangzhou Huasu Technology Co., Ltd HTTP://HUASU-TECH.COM// TEL:0571-87967915 20
and TC modules
Ifthereis noTA address modifieror CMmodule,computerscanbe usedtomodify
TA and TC module addresses.
First, connect the TA module to the positive and negative poles of the battery,and
connect them as shown in the following figure. Connect only one TA or TC module at
a time:
Figure 3-4-2
After connecting, open and run the "H3G-TA Debugging Tool" software, correctly
set the corresponding equipment type and computer serial port number, and click the
"Open Serial Port" button to confirm whether the serial port is normally opened.