Hydrovane Pro User manual

User Manual (Original Instructions)
HYDROVANE Pro
Electronic Controller
Stationary Air Compressors
GB
CC1092267A 04/2013

Attention: Important for RS compressors
Risk of electric shock from charged capacitors!
Always disconnect the system from the power supply
and then wait a further 10 minutes before touching
electrical components. The power capacitors take this
time to discharge.
Check the DC bus voltage at the system terminal strip
of the inverter by measuring between the +DC and -DC
terminals and the chassis. The exact position can be
found in the operating manual of the inverter, the
voltage must read zero for all three measurements.
Controller Ref: CC1054325 Single Speed (SS)
Software version HPro-V1.02
Controller Ref: CC1068566 Regulated Speed (RS)
Software version HPro-RS-V1.04
Hydrovane adopt a policy of continual product
development. The information in this handbook, whilst
fully up to date when issued, may be subject to change
without notice.

Contents
Contents
1
Operator Controls.................................................................................................................................................5
1.1
Keys...............................................................................................................................................................5
1.2
Status indicator (display / light signals).............................................................................................................5
1.2.1
Speed indicator in the display...............................................................................................................5
1.2.2
Status messages in display...................................................................................................................5
1.3
Displaying / changing values ...........................................................................................................................6
1.3.1
Selecting values...................................................................................................................................6
1.3.2
Changing values...................................................................................................................................6
1.4
Selecting language..........................................................................................................................................6
1.5
Setting pressure..............................................................................................................................................6
1.6
Setting time/date (timer) ..................................................................................................................................7
1.6
Menu structure (values are examples) .............................................................................................................8
2
Operating & Maintenance......................................................................................................................................9
2.1
Starting the unit...............................................................................................................................................9
2.2
Emergency stop button....................................................................................................................................9
2.3
Switching off the unit.......................................................................................................................................9
2.4
On-load/off-load..............................................................................................................................................9
2.5
Warning/fault messages..................................................................................................................................9
2.5.1
Warning messages...............................................................................................................................9
2.5.2
Fault messages....................................................................................................................................9
2.6
Maintenance.................................................................................................................................................10
2.7
Programming maintenance intervals..............................................................................................................10
2.8
Total/load hours counter................................................................................................................................10
3
Additional Functions...........................................................................................................................................11
3.1
[CONTROL MENU] sub-menu.......................................................................................................................11
3.1.1
Operating modes................................................................................................................................11
3.1.2
Second pressure range (p
2
)................................................................................................................11
3.1.3
Dryer pre-run......................................................................................................................................11
3.1.4
RS 485 communication.......................................................................................................................11
3.1.5
Automatic re-start...............................................................................................................................11
3.1.6
Unlimited autom. re-start after power loss............................................................................................12
3.2
[FAULT MEMORY]sub-menu.........................................................................................................................12
3.3
[TIMER CONTROL]sub-menu.......................................................................................................................12
3.3.1
Setting for timer units..........................................................................................................................12
3.3.2
Pressure changeover setting...............................................................................................................13
3.4
[LIMIT VALUES] sub-menu............................................................................................................................14
3.5
[OPTIONAL IN-/OUTPUTS] sub-menu...........................................................................................................14
3.5.1
Inputs.................................................................................................................................................14
3.5.2
Outputs..............................................................................................................................................15
3.6
Locking / unlocking code...............................................................................................................................16
3.7
Replacing the HYDROVANE Pro...................................................................................................................16
3.8
Remote control..............................................................................................................................................17
3.8.1
Remote control for pressure changeover.............................................................................................17
3.8.2
Enabling on-load operation.................................................................................................................17
3.8.3
On-load/off-load remote control...........................................................................................................18
3.8.4
Enabling on-load operation.................................................................................................................19
3.8.5
Remote start / stop.............................................................................................................................19
4
Error Rectification...............................................................................................................................................21
4.1
Safety Regulations........................................................................................................................................21
4.2
Warnings......................................................................................................................................................21
4.3
Faults...........................................................................................................................................................21
4.4
Checklist.......................................................................................................................................................21
4.5
Table of faults / warnings...............................................................................................................................21


1.0 Operator Controls
CC1092267A 5
1 Operator con trols / arr angeme nt
1.1 Keys
When power is applied the controller display illuminates
to show compressor output values and status
messages.
The two keys on the left above and below the green
and red LED’s have a single function:
Start key.
Stop key.
The three keys on the right next to the display have a
dual function:
+ Call up or exit menu / sub-menu.
Switch to next sub-menu / menu item, or
reduce a value.
Switch to previous sub-menu / menu item, or
increase a value.
Reset/Enter key.
In a menu / sub-menu, the reset key functions as
an enter key.
1.2 Status indicator (display / light
signals)
The controller is fitted with a three-row display.
The first row permanently displays compressor
discharge temperature and system pressure.
The following symbols may also be used in the 1st row:
p
2
Second pressure range
Remote start / stop activated
The second row is reserved for menu items, values like
the total service hours and set values like nominal
pressure are viewed here.
The third row shows status, fault and warning
messages.
The HYDROVANE Pro is fitted with two light signals (red,
green).
Flashing, system is ready, the motor may start up
automatically at any time.
Lit up permanently, the drive motor is running
Flashing slowly, warning, maintenance due
Flashing rapidly, fault, unit is stopped until fault has
been rectified
The red light signal only goes out once the warning or fault
has been rectified and confirmed using the Reset/Enter
key.
1.2.1 Speed indicator in the display
The speed is displayed in the 2nd row of the display. If the
menu navigation is displayed, the speed display is faded
out.
Examples of speed displayed:
[ _________❚___ ] 3290rpm
Speed in controlled range.
[ ❚____________ ] 1300rpm
Speed in lower controlled range,
minimum speed not yet reached.
[ |___________ ] 1280rpm
Minimum speed reached.
[ ___________| ] 3650rpm
Maximum speed reached.
1.2.2 Status messages in display
The status messages are shown in the 3rd row of the
display. With longer texts, the indication may 'alternate'.
Status messages:
INITIALIZATION VSD...
The compressor's supply voltage has been switched on.
The control system is being initialised and is setting up
communication to the inverter (VSD).
READY TO START
The unit is ready to start and can be switched on (see
Section 2.1).
WARNING START WITH ...
alternating with
... PRESSURE REQUIREMENT
The unit has been switched on and is ready. The unit starts
automatically following the pressure requirement from your
system.

1.0 Operator Controls
6 CC1092267A
WARNING START AFTER ...
alternating with
... DE-PRESSURISE
The unit has been switched on and is ready. However
the internal unit pressure is above the start-up
protection level. Once the unit has been de-
pressurised, the compressor starts automatically.
WARNING START WITH ...
alternating with
... TIMER CONTROL
The unit has been switched on and is ready. The
compressor is now waiting for start approval from the
timer (see Section 3.3)
WARNING START BY ...
alternating with
... REMOTE OPERATION
The unit has been switched on and is ready. Remote
unit operations have been activated in the control menu.
The unit starts via a remote signal (see Section 3.8).
WARNING START IN xxs
alternating with
... AFTER POWER LOSS
A power loss has caused the unit to shut down. The
'automatic restart' function has been selected in the
control menu. The unit now starts automatically after a
previously set time (see Section 3.1.5)
WARNING START IN
alternating with
... AFTER DRYER PRE-RUN
The unit has been switched on and is ready. The unit
starts automatically after the dryer pre-run (see Section
3.1.3).
MOTOR START PHASE
The unit has been switched on and the motor is starting
ON-LOAD
The compressor is on-load (see Section 2.4).
OFF-LOAD
The Compressor is running off-load (see Section 2.4).
OFF-LOAD XXs
Compressor is running off-load and will shut down in
XX seconds (see Section 2.4).
SOFT STOP TIME in xxs
The system has been switched off. The unit stops after
the soft-stop time of xx seconds.
FAULT: <fault text>
The unit has been shut down due to a fault. You will
find explanations of the fault texts in Section 4.
WARNING <warning text>
There is a warning in place. Ignoring a warning may result
in a fault and shut down the compressor. You will find
explanations of the warning texts in Section 4.5.
MAINTENANCE DUE
A maintenance interval is about to lapse or has already
done so, you will find more details in Section 2.6.
1.3 Displaying / changing values
1.3.1 Selecting values
You can display values, e.g. total hours, and set the control
system, e.g.cut-in and cut-out times, in the sub-menu.
To reach the main menu, you must press the + keys
at the same time.
Use the or keys to switch between the following sub-
menus:
[MAINTENANCE SCHED.]
[CONTROL MENU]
[FAULT MEMORY]
[TIMER CONTROL]
[LIMIT VALUES]
[OPTIONAL IN-/OUTPUTS]
Enter a sub-menu by pressing the
key
.
Use the or keys to go to a menu item.
To exit the sub-menu, you must press the + keys at
the same time.
To exit the main menu, you must press the + keys at
the same time again.
1.3.2 Changing values
Enter the sub-menu and then the menu item containing the
value you wish to change.
Press the key, the value flashes. Press the or
key to change the value, then press the key again to
confirm the value.
1.4 Selecting language
Change the language by pressing the + or +
keys. Press these keys at the same time until the right
language appears.
1.5 Setting pressure
Compressor control/speed is achieved using a pressure
transducer signal to the controller and/or inverter PID to
match output to system demand.
In the [CONTROL MENU] menu you have to set the
maximum pressure CUT-OUT POINT and the minimum
pressure CUT-IN POINT or TARGET PRESSURE.
In the range between the CUT-IN POINT or TARGET
PRESSURE and CUT-OUT POINT the output or speed of
the compressor is controlled or regulated to match the
compressed air requirement.
Example:
CUT-OUT POINT 8.5 bar (123 psi)
CUT-IN POINT (SS) 7.5 bar (109 psi)
TARGET PRESSURE (RS) 8.0 bar (116 psi)

1.0 Operator Controls
CC1092267A 7
The output of the compressor is controlled between
these points or speed is regulated so that the set
pressure of 8.0 bar (116 psi) is maintained.
When pressure reaches the CUT-OUT POINT of 8.5
bar (123 psi), the compressor switches to off-load.
If pressure falls to the CUT-IN POINT of 7.5 bar (109
psi), the compressor is switched back into on-load.
Maximum pressure is set in the [CONTROL MENU]-
sub-menu. The + keys have to be pressed at the
same time. You are then taken to the main menu. Use
the key to switch to the [CONTROL MENU] sub-
menu, then press the key.
The CUT-OUT POINT menu item now appears on the
display. Pressing the key causes the value to flash.
Increase or decrease this value using the or
keys, confirm the value set by pressing the key.
Note
The controller checks that the value set can be used.
The maximum pressure CUT-OUT POINT must be at
least 0.2 bar more than the CUT-IN POINT or TARGET
PRESSURE.
You may therefore have to set the minimum pressure
first. To keep the number of stop/starts to a minimum,
the difference between the CUT-OUT POINT and CUT-
IN POINT or TARGET PRESSURE should not be too
small.
Minimum pressure is set in the [CONTROL MENU]
sub-menu press the key to go to the CUT-IN POINT
or TARGET PRESSURE menu item.
Pressing the key causes the value to flash.
You can increase or decrease this value using the
or key, confirm the value set by pressing the key.
CUT-OUT POINT
CUT-IN POINT
TARGET PRESSURE
ON-LOAD
Fig. 1 Pressure Settings
1.6 Setting time/date (timer)
The HYDROVANE Pro will retain its settings after a power
loss lasting about two to three weeks. If power is lost for
longer periods, the timer's time and date are lost and have
to be re-entered.
Press the + keys at the same time. Use the key
to go to the [TIMER CONTROL] sub-menu and press the
key.
The date and time are displayed in the following format:
TU 30.10.07 12:10:34
Press the key, the left-hand value (day of the week)
starts to flash. Use the or keys to select, confirm by
pressing the key.
All values can now be set in succession using this
procedure. When the last value (seconds) has been set,
the timer is active, exit the menu by pressing the +
keys twice at the same time.

1.0 Operator Controls
8 CC1092267A
1.7 Menu structure (values are examples)
+
SS = SINGLE SPEED / RS = REGULATED SPEED
INPUT 1: FAN FAULT
INPUT 2-5 FREE:
OUTPUT 1 OFF
OUTPUT 2 FAN TEMP CONTROL
INTERNAL TRANSDUCER OFF
DESIGN PRESS 8.0bar
START PROTECT 2.0bar
HEAVY STARTUP (SS) 3.5bar
EXT. LIMIT (RS) 2000RPM
FINAL TEMP WARN 107ºC
FINAL TEMP MAX 110ºC
MIN START TEMP 0ºC
SOFT STOP 2s
MAX START PER HOUR 10
FAN ON TEMP 85°C
FAN OFF TEMP 75°C
FAN RUN ON 180s
STAR DELTA TIME (SS) 1s
SOFTWARE: HPro-Vx.xx
PROFILES 1-7 & p
2
1-7 NONE SET
TH 08.02.07 13:55:41
1 _______________________ 00:00 00:00:
7 _______________________ 00:00 00:00:
p
2
1 _____________________ 00:00 00:00:
p
2
7 ______________________00:00 00:00
ERRORS 1-20 READ ONLY
02!EM-STOP 12345h
01!EM-STOP 12300h
CUT-OUT POINT 8.5bar
CUT-IN POINT (SS) 7.5bar
TARGET PRESSURE (RS) 8.0bar
p
2
CUT-OUT POINT 8.5bar
p
2
CUT-IN POINT (SS) 7.5bar
p
2
TARGET PRESSURE (RS) 8.0bar
RUN ON TIME 60s
AUTOMATIC OPERATION
ENABLE REMOTE-START OFF
TIMER CONTROL OFF
p
2
TIMER CONTROL OFF
AUTO RESTART OFF
POWER LOSS TIME 2s
START-UP DELAY 5s
DRYER PRE-RUN 0min
RS485-PROTOCOL ModBus
RS485-BAUDRATE 19200
RS485-ADDRESS 1
[MAINTENANCE SCHED]
[CONTROL MENU]
[OPTIONAL IN-/OUTPUTS]
[LIMIT VALUES]
TOTAL RUNNING 12345h
LOADED HOURS 10987h
AIR FILTER IN 2000h
OIL FILTER IN 2000h
SEPARATOR IN 4000h
OIL CHANGE IN 4000h
OIL TYPE FF2000/CLEAR
SHUTDOWN DEACTIVATED
+
+
+
+
+
[TIMER CONTROL]
[FAULT MEMORY]

2.0 Operating & Maintenance
CC1092267A 9
2 Operations
2.1 Starting the unit
Caution
If the unit is ready, i.e. the green LED is flashing, the
compressor may automatically start at any time.
Use the isolator to switch the unit on.
If warning or fault messages appear in the third row of the
display, these first have to be rectified and confirmed
using the key.
Then start the unit by pressing the key on the
HYDROVANE Pro.
2.2 Emergency stop button
The EMERGENCY stop button is located below the
HYDROVANE Pro. Only use the emergency stop button
to shut down the unit in real emergencies. When shutting
down normally, always use the key.
2.3 Switching off the unit
The unit is switched off by pressing the key on the
HYDROVANE Pro. However the unit will only stop after a
2-second soft-stop.
The soft-stop is preset to protect the compressor.
2.4 On-load/off-load
Descriptions of the CONTINUOUS OPERATION and
AUTOMATIC OPERATION modes can be found in
section 3.1.1.
OFF-LOAD:
If there is no pressure requirement from the system with
the unit in CONTINUOUS OPERATION, it switches to
OFF-LOAD. This means that the motor and compressor
run but no air is delivered into the system.
The unit behaves differently in AUTOMATIC OPERATION
mode. If there is no pressure requirement, the compressor
switches to OFF-LOAD. The unit is switched off after a run-
on time that is shown on the display. If there is another
pressure requirement during the run-on time, the unit is
automatically switched on.
ON-LOAD:
If the unit is in ON-LOAD, air is delivered into the system.
2.5 Warning/fault messages
Warning and fault messages are shown in the third row of
the display. The red light signal flashes at the same time.
A table containing messages and suggestions for how to
remedy them is in Section 4.5.
2.5.1 Warning messages
If there are warnings, the red light signal flashes slowly.
The unit does not automatically shut down when there
are warnings. However ignored warnings may cause
faults.
Rectify what is causing the warning and press the key
to cancel the warning.
2.5.2 Fault messages
Fault messages result in the unit automatically shutting
down or do not permit the unit to be started.
Once you have rectified the problem, you must confirm
by pressing the key.

2.0 Operating & Maintenance
10 CC1092267A
2.6 Maintenance
Maintenance intervals are preset when the compressor is
supplied, more information is available in the unit's user
handbook.
It may be necessary to adjust maintenance intervals to
suit ambient conditions. For example, the air filter‘s level
of contamination depends on the compressor's intake
conditions.
The HYDROVANE Pro allows the operator to program
various maintenance intervals (see section 2.7).
If there is a maintenance interval at +200h (hours), the
compressor is not automatically shut down. The
MAINTENANCE DUE message appears on the display.
If you want the compressor to automatically shut down
when a maintenance interval is due, you have to set this
function.
Go to the [MAINTENANCE SCHED.] sub-menu. Go to
the last SHUTDOWN OFF menu item, press the key.
The OFF value starts to flash. By pressing the
key you
can change the value to ON, confirm by pressing the
key.
The compressor now automatically shuts down when the
-100h maintenance interval is displayed.
Once maintenance is complete the interval should be
reprogrammed back to 2000h. Confirm the maintenance
message using the key.
2.7 Programming maintenance intervals
To program a maintenance interval, go to the
[MAINTENANCE SCHED.] sub-menu. Here you can
program the maintenance intervals for:
AIR FILTER IN 2000h
OIL FILTER IN 2000h
SEPARATOR IN 4000h
OIL CHANGE IN 4000h
Go to the menu item required and press the key, the
value then starts to flash. Use the or key to set the
value to an interval of 0….9999, confirm your entry with
the key.
If you do not want the maintenance intervals to be
monitored, program the intervals to more than 9999
hours in the various menu items. ---- appears on the
display. The maintenance interval is then blocked.
Note
Values shown are examples only, those used in your unit
may be different.
2.8 Total/load hours counter
Press the + keys at the same time to reach the
main menu. Press the key, you are now in the
[MAINTENANCE SCHED.] sub-menu. Use the or
keys to go to the various menu items.
The total hours counter states the time for which your unit
has been in on-load and off-load.
The load hours counter states the time for which your unit
has been in on-load.
Note
The total and load hours are lost if the HYDROVANE Pro
is replaced.

3.0 Additional Functions
___________________________________________________________________________________________________
CC1092267A 11
3 Extendedf uncti ons
3.1 [CONTROL MENU] sub-menu
The most important parameters of the [CONTROL
MENU] menu have already been explained in Section
1.5 Operator Controls. This section simply contains an
overview and explanation of additional functions.
3.1.1 Operating modes
Go to the [CONTROL MENU] sub-menu, use the
key
to go to the AUTOMATIC OPERATION menu item.
Press the key, AUTOMATIC OPERATION starts to
flash. Use the key to switch to CONTINUOUS
OPERATION, confirm selection by pressing the key.
You can choose from two operating modes:
AUTOMATIC OPERATION is the most economical of
your compressor's operating modes. If there is no
system demand, the compressor is shut down after the
RUN-ON TIME. The control system automatically
recognises when compressed air is needed again. The
unit then starts up straight away.
CONTINUOUS OPERATION is only needed for some
special applications. When in this operating mode, the
motor is not shut down if there is no system demand.
The compressor runs continually in off-load mode when
there is no pressure requirement.
3.1.2 Second pressure range (p
2
)
The difference between the maximum and minimum
pressure is called the pressure range. The second
pressure range function allows you to use another
pressure range in addition to the pressure range
already set (see Section 1.5). This could be used for
example to implement night-time running at lower
pressures.
The settings for the second pressure range function are
in the [CONTROL MENU] sub-menu. Menu items are:
p
2
CUT-OUT POINT 8.5 bar (123 psi)
p
2
CUT-IN POINT (SS) 7.5 bar (109 psi)
p
2
TARGET PRESSURE (RS) 8.0 bar (116 psi)
p
2
TIMER CONTROL OFF
Use p
2
CUT-OUT POINT and p
2
CUT-IN POINT or p
2
TARGET PRESSURE to set the pressure switching
points. Use the p
2
TIMER CONTROL ON menu item to
activate the timer for the second pressure range.
You can also activate / deactivate the second pressure
range using an external potential-free contact (see
Section 3.5).
Section 3.3.2 contains a description of how to set the
timer for the second pressure range.
Note
Values shown are examples only, those used in your
unit may be different.
3.1.3 Dryer pre-run
If using an external dryer, you can provide the dryer
with a specified pre-run time. The compressor is then
only started after this pre-run time.
To set the pre-run time, go to the [CONTROL MENU] sub-
menu. From there use the
key to go to the DRYER
PRE-RUN 0min menu item. Once you have pressed the
key, the 0min value starts to flash. Use the or keys
to set the pre-run time you want, confirm your entry using
the key.
3.1.4 RS 485 communication
You can perform the settings for RS 485 communication in
the [CONTROL MENU] sub-menu.
These menu items are of relevance.
RS485-PROTOCOL ModBus
RS485-BAUDRATE 19200
RS485-ADDRESS 1
The HYDROVANE Pro has a serial RS485 interface. This
interface uses the ModBus RTU protocol.
ModBus interfaces and drivers are available from many
well-known manufacturers of programmable logic
controllers (PLC).
You can set the baud rate you want in the RS485-
BAUDRATE menu item.
You can set the participant number you want in the
RS485-ADDRESS menu item.
Note
Values shown are examples only, those used in your unit
may be different.
3.1.5 Automatic re-start
Caution
In this operating mode, the compressor may start
automatically at any time and after an unlimited length
of power loss.
Always fit the compressor with warning signs, lock the
room containing the compressor and instruct your
staff.
Fit the isolator specified by EN60204 and fit the
appropriate warning signs on it.
After a power loss that has not exceeded the preset time,
the unit can re-start automatically.
The settings needed must be undertaken in the [CONTROL
MENU] sub-menu. Menu items are:
AUTO RESTART OFF
POWER LOSS TIME Xs
START-UP DELAY Xs
Use the AUTO RESTART ON menu item to activate the
automatic re-start.
You can state the time for which a power loss may last and
after which the compressor is to automatically re-start in
the POWER LOSS TIME menu item. The time can be set
within a period of 2 - 999 seconds. If the power loss lasts
longer than the time you have set, the unit does not
automatically re-start. The POWER LOSS. fault message
then appears on the display

3.0 Additional Functions
12 CC1092267A
You can also program a start-up delay of 1 – 60 seconds.
This is set in the START-UP DELAY menu item and
ensures a staggered start-up if the installation features
several compressors. This ensures that the power supply
is not loaded unnecessarily.
3.1.6 Unlimited autom. re-start after
power loss
The control system can perform an automatic re-start
after any power loss period.
You must read and apply the following safety notices
before setting unlimited automatic re-start.
Caution
In this operating mode, the compressor may start
automatically at any time and after an unlimited
length of power loss.
Check the safety notices (e.g. EN1012-1, EN60204)
that apply in your country to find out whether you
can run an unlimited autom. re-start and what
safety precautions must be taken.
Always fit the compressor with warning signs, lock
the room containing the compressor and instruct
your staff.
Fit the isolator specified by EN60204 and fit the
appropriate warning signs on it.
To set unlimited automatic restart, proceed as follows:
1. Press the key for 5 seconds.
2. Use the or keys to enter code 8888.
3. Press the key to transfer the set code
The menu item for the max. power loss time can also
be programmed to [POWER LOSS TIME –s]. This is
the setting for an unlimited automatic re-start.
If you re-enter the code, you cancel the function.
Note
Details for locking sub menus by code can be found in
Section 3.6
3.2 [FAULT MEMORY]sub-menu
Warning messages and faults are stored in the fault
memory. The last warning message or fault recorded is
always at the top. In order to distinguish between faults
and warning messages, faults are marked with an
exclamation mark !.
Use the or key to switch between the individual
memory areas in the fault memory.
The faults are displayed as follows:
03! EM-STOP 000100h
a) b) c) d)
a) The same fault has occurred three times.
b) This relates to a fault.
c) Fault has occurred due to the emergency stop button
being pressed.
d) Fault occurred at 100 running hours.
03 HIGH TEMP 000100h
a) b) c)
a) The same warning has occurred three times.
b) Warning resulting from compressor temperature being
too high
c) Warning occurred at 100 running hours.
The last eight warning messages or faults recorded are
displayed in the fault memory. All messages and faults
occurring before that are retained in the long-term memory.
The frequency with which a warning or fault occurs is
therefore always recorded.
You can access more detailed information on warning
messages and faults that have been recorded in the fault
memory. The following are saved for every warning
message/fault recorded:
- time and date
- compressor status (e.g. on-load)
- speed (RS)
- compressor temperature and pressure
When accessed, these values flash to clearly show that
they are not the current display values.
Use the
or
key to go to the warning or fault message
of interest. Press the key, day of the week, date and
accurate time are now displayed (flashing) in the first row.
Press the key again, the status of the warning/fault of
the compressor is displayed (flashing) in the first row. If the
key is pressed again, the compressor temperature and
pressure are displayed (flashing) in the first display row.
Press the key again to return to the normal fault
memory view.
3.3 [TIMER CONTROL]sub-menu
Caution
When programming in standby, the compressor may
start up at any time.
The timer allows you to switch the compressor on and off at
permanently set (programmed) times. You can also change
over the pressure level (e.g. night-time running at lower
pressures).
3.3.1 Setting for timer units
You will have already set the time and date as described in
Section 1.6. This setting serves as the basis for accurate
timer operations.
Go to the [TIMER CONTROL] sub-menu, use the or
key to select from seven different timer units. The status
line of each switching unit is as follows:
a) b) c) d)
1 _______ 00:00 00:00
a) Unit no.
b) Days of the week [SMTWTFS] = Sunday, Monday.

3.0 Additional Functions
___________________________________________________________________________________________________
CC1092267A 13
c) Switch-in point.
d) Switch-out point
If there are no days of the week selected in the
switching unit line, the switching unit is not active. The
unit only becomes active when the day of the week is
set. When the key is pressed, the first underscore _
starts to flash. Use the key to set the first day of the
week (Sunday). Use the key to confirm the day of
the week, the next underscore _ starts to flash. If you
do not want to confirm a day of the week as set,
immediately press the key. Run through all seven
days of the week this way. Once you confirm the last
day of the week (Saturday), the first unit of the switch-in
point starts to flash, set this using or .
Once the last unit of the switch-out point has been
confirmed, the whole timer sequence is activated.
The next step is to go to the [CONTROL MENU] sub-
menu and then the TIMER CONTROL menu item. You
will see the default setting TIMER CONTROL OFF. If
you press the key, the OFF value starts to flash.
Use the key to change the value to ON. Then press
the key again to confirm the entry. The timer is now
switched on.
Timer sequence settings are explained by the examples
below.
Example 1:
Switching unit 1 not active:
1 _______ 00:00 00:00
Example 2:
The unit should run Monday to Friday between 7.30 am
and 4.15 pm.
2 _MTWTF_ 07:30 16:15
a) b) c)
a) Days of the week Monday to Friday
b) Switch-in point
c) Switch-off point
Example 3:
The unit is to run from Sunday 10 pm through
continuously to Saturday 2 pm. During the daily break
(12 midday to 12.30 pm), the unit is to be shut down.
You will now have to use various switching units. The
following settings would be needed in this case:
1 S______ 22:00 00:00 a)
2 _MTWTFS 00:00 12:00 b)
3 _MTWTF_ 12:30 00:00 c)
4 ______S 12:30 14:00 d)
5 _______ 00:00 00:00
6 _______ 00:00 00:00
7 _______ 00:00 00:00
a) Start of operating period
b) Operating period up until lunch break
c) Start of operation after lunch break
d) End of operating period.
3.3.2 Pressure changeover setting
Go to the [TIMERCONTROL] sub-menu. Use the or
key to select between various timer units. The timer units of
the 2nd (p
2
) pressure range are in the menu under the
normal timer units.
CUT-OUT POINT
CUT-IN POINT
TARGET PRESSURE
p2 CUT-OUT
p2 CUT-IN POINT
p2 TARGET PRESSURE
p2 TIMER CONTROL
ON-LOAD
Fig. 2 Pressure Changeover
Seven timer units are available for programming. Values
that you have set for the second pressure range supersede
the values for CUT-OUT POINT and CUT-IN POINT or
TARGET PRESSURE as soon as a switching unit is active.
The 1st row on the display then shows the p
2
symbol for
the second pressure range. If the switching unit becomes
inactive, the values for CUT-OUT POINT and CUT-IN
POINT or TARGET PRESSURE are used again.
The status line of each switching unit is as follows:
a) b) c) d) e)
p
2
1 _______ 00:00 00:00
a) 2nd pressure range
b) Unit no.
c) Days of the week [SMTWTFS] = Sunday, Monday...
d) Switch-in point
e) Switch-out point
When the key is pressed, the first underscore _ starts to
flash. Use the key to set the first day of the week
(Sunday). Use the key to confirm the day of the week.
The next underscore _ now flashes. If you do not want to
confirm a day of the week as set, immediately press the
key. Run through all seven days of the week this way.
Once you have confirmed the last day of the week
(Saturday), the first unit of the switch-in point starts to flash,
set this using the or key. Once the last unit of the
switch-out point has been confirmed, the whole switching
unit is activated.

3.0 Additional Functions
14 CC1092267A
Go to the [CONTROL MENU] sub-menu and then the
p
2
TIMER CONTROL menu item. You will now see the
p
2
TIMER CONTROL OFF default setting. If you press
the key, the OFF value starts to flash. Use the
key to change the value to ON. Then press the key
again to confirm the entry. The timer is now switched on
for the second pressure range. Refer to Section 3.1.2
for how to set the parameters for the 2nd pressure
range.
3.4 [LIMIT VALUES] sub-menu
Sub-menu [LIMIT VALUES] are the factory-set and
changeable parameters, SS or RS represent single or
regulated speed:
a) DESIGN PRESS 8.0 bar (116 psi)
b) START PROTECT 2.0 bar (29 psi)
c) HEAVY STARTUP (SS) 3.5 bar
d) EXT. LIMIT (RS) 2000RPM
e) FINAL TEMP WARN 107°C (225°F)
f) FINAL TEMP MAX 110°C (230°F)
g) MIN START TEMP 0°C (32°F)
h) RUN-ON TIME 60s
i) SOFT STOP 2s
j) STAR DELTA TIME (SS) 1s
k) SOFTWARE (SS) HPro-V1.xx
l) SOFTWARE(RS) HPro-RS-V1.xx
Note
Values shown are examples only, those used in your
unit may be different.
a) This is your unit's operating pressure. This is also
stamped on the compressor's rating plate.
b) As protection, the compressor only starts up when
the internal pressure is less than or equal to the set
value. If the internal pressure is higher when starting
up, the following appears in the display's third row.
WARNING START AFTER ...
alternating with
... DE-PRESSURISE
c) If the internal pressure builds up too quickly when
the compressor starts up, there is an error in the
unit. To protect the motor in the case of an error, the
compressor shuts down if pressure builds up too
quickly. FAULT HEAVY STARTUP appears in the
third row on the display.
d) If an input is programmed on the function [EXT.
RPM LIMIT] and its contact is closed, the speed of
the compressor will be restricted to the value set
here.
e) If the compressor temperature reaches 107°C
(225°F), WARNING HIGH TEMP appears in the
display's third row.
f) If the compressor temperature reaches 110°C
(230°F), the compressor shuts down. FAULT COMP
TEMP then appears in the third row on the display
g) If the compressor temperature is below 0°C (32°F ),
the compressor cannot start up.
h) If the compressor is in automatic mode and there is no
pressure requirement, the RUN-ON TIME xxxs
indication appears and the compressor goes into off-
load. After the run-on time (xxx), the compressor
automatically shuts down and is ready to start again. If
using the timer or the remote start / stop function, the
run-on time is also used.
i) In order to protect the compressor, once the key
has been pressed, the compressor is switched off 2
seconds later. If using the timer or the remote start /
stop function, the run-on timeis also used.
j) During the start-up phase, a change is made from star
to delta (contactors in starter panel) following the set
value.
k) Shows the software version of your single speed (SS)
electronic controller CC1054325.
l) Shows the software version of your regulated speed
(RS) electronic controller CC1068566.
3.5 [OPTIONAL IN-/OUTPUTS] sub-menu
3.5.1 Inputs
Attention
Only potential-free contacts may be connected to the
terminal strip. External voltages will destroy the
HYDROVANE Pro.
The potential-free contacts must not be more than 20
metres away from the terminal strip. If necessary
coupling relays must be fitted in the control cabinet.
The HYDROVANE Pro has programmable inputs, some
are already assigned (programmed) when supplied. Inputs
and their functions are shown in the circuit diagram of the
compressor.
Inputs are programmed in the [OPTIONAL IN-/OUTPUTS]
sub-menu. In the sub-menu press the key to display the
INPUT 1: menu item.
If you press the key, the function starts to flash. By
pressing the or key, you can change the function.
Once you have set the function you want, confirm using the
key. The input is now programmed.
You access all other programmable inputs by pressing the
or key.
Each input can be programmed with any of the functions
listed below.
Explanation of functions:
FREE
Input is not assigned (programmed).
EXT FAULT
If the contact is opened, the EXT FAULT fault message
appears on the display and the unit is shut down (shutting
down is delayed by 1sec.).
EXT WARNING
If the contact is opened, the EXTWARNING warning
message appears on the display (the indication is delayed
by 1sec.). This function does not result in the unit shutting
down.

3.0 Additional Functions
___________________________________________________________________________________________________
CC1092267A 15
DRYER FAULT
If the contact is opened, the DRYER FAULT fault
message appears on the display and the unit is shut
down (shutting down is delayed by 1sec.).
DRYER WARNING
If the contact is opened, the DRYER WARNING
warning message appears on the display (the indication
is delayed by 1 sec.). This function does not result in
the unit shutting down.
ENAB.REM.LOAD
For use and examples, see Section 3.8.3.
REMOTE LOAD
For use and examples, see Section 3.8.3.
EXT. RPM LIMIT
When the contact is closed the speed of the
compressor is restricted to the set speed in the menu
[LIMIT VALUES] in menu item EXT. LIMIT.
RTC OVERRIDE
The timer can be overridden using this input.
Example: The compressor has been shut down by the
timer. If the contact is now closed, the compressor
starts up.
2
nd
PR. RANGE
If the contact is closed, the system changes over to the
second pressure range. Also refer to section 3.1.2.
ENAB.REM-START
For use, see section 3.8.5.
OPERATE_B1
For use, see section 3.8.4.
3.5.2 Outputs
Attention
The maximum connected loads for the programmable
outputs (relay contacts) are 4,5A / 240V.
The HYDROVANE Pro has programmable outputs,
some are already assigned (programmed) when
supplied. Outputs and their functions are shown in the
circuit diagram of the compressor.
Outputs are programmed in the [OPTIONAL IN-
/OUTPUTS] sub-menu. In the sub-menu press the
key to display OUTPUT 1: menu item
If you press the key, the function starts to flash. By
pressing the or key, you can now change the
function. Once you have set the function you want,
confirm using the key. The output is now
programmed.
You access the other programmable output by pressing
the key.
Each output can be programmed with any of the
functions listed below.
Explanation of functions:
OFF
Output is not programmed.
OPERATING
The output (relay) is activated when the compressor's
motor is switched on or when the compressor is ready.
ON-LOAD
The output (relay) is activated when the compressor is in
on-load.
OFF-LOAD
The output (relay) is activated when the compressor is in
off-load.
FAULT
The output (relay) is activated when there are no faults on
the compressor.
WARNING
The output (relay) is activated when there are no warnings
on the compressor.
MAINT.DUE
The output (relay) is activated when there are no
maintenance messages on the compressor.
WARNING/MAINT.
The output (relay) is activated when there are no warnings
and no maintenance messages on the compressor.
WARN/MA/FAULT
The output (relay) is activated when there are no warnings,
no maintenance messages and no faults on the
compressor.
REM.STARTABLE
The output (relay) is activated when the compressor is
ready for the remote start.
RUNNING
The output (relay) is activated when the compressor's
motor is running (is switched on).
2nd PR. RANGE
The output (relay) is activated when the 2nd pressure
range is applicable.
TIMER
The output (relay) is activated when the compressor is
switched on by the internal timer.

3.0 Additional Functions
16 CC1092267A
3.6 Locking / unlocking code
Settings (sub-menus) can be locked using a code to
prevent unauthorised programming.
Limit values cannot be changed by the operator.
Locking
Press the key for 5 seconds, the following message
appears on the display:
CODE: UNLOCK (for 1 second) followed by CODE
INPUT 0000 (0000 value flashes)
Enter code: 3031, the following message appears:
CODE: LOCK (for 1 second)
The sub-menus are locked and cannot be changed.
If the wrong code is entered, the following message
appears:
CODE: UNLOCK (for 1 second)
The display then automatically jumps back to where it
started from.
Unlocking
If the code is to be unlocked again, either:
Press the key for 5 seconds when not in the menu
or when attempting to change a protected value in a
sub-menu.
The code prompt then appears:
CODE LOCK (for 1 second) followed by CODE INPUT
0000 (0000 value flashes)
Enter code: 3031.
If the code is entered correctly, the following message
appears:
CODE: UNLOCK (for 1 second)
If the code is entered incorrectly, the following message
appears:
CODE: LOCK (for 1 second)
The display then automatically jumps back to where it
started from.
3.7 Replacing the HYDROVANE Pro
Once a new HYDROVANE Pro has been fitted, switch
the isolator back on.
One of the following now appears on the display with
either the 6.0 BAR or KEB 400V flashing:
*** Hydrovane ***
SETUP PRESSURE: 6.0 BAR
*** Hydrovane ***
VSD-TYPE: KEB 400V
Use the key to select either the working pressure or a
KEB 460V/Mitsubishi VSD, press the key to confirm
your entry.
The following now appears on the display with the 07 figure
flashing (11 if Mitsubishi is selected):
***..Hydrovane..***
HV MODEL: 07RS
Use the key to select the required model, press the
key to confirm your entry, the following message appears
on the display.
INITIALIZATION VSD...
After a short delay the displayed message will change to
READY TO START
If the wrong selection is made, WRONG VSD MODEL
appears, hold the key to reach 2222 and press the
key to start again.
If the correct entry is made, the compressor automatically
switches to its delivery status.
The language has been reset to English. If you need a
different language, set as described in Section 1.4.
You now have to set the maximum and minimum supply
pressure as shown in Section 1.5.
You then have to repeat the individual programming for the
inputs and outputs. Consult your compressor's circuit
diagram, it shows how inputs and outputs are configured.
The [OPTIONAL IN-/OUTPUTS] Section 3.5 shows how to
program inputs and outputs.

3.0 Additional Functions
___________________________________________________________________________________________________
CC1092267A 17
3.8 Remote control
Caution
In this operating mode, the compressor may start
automatically at any time.
Attention
Only potential-free contacts may be connected to
the terminal strip. External voltages will destroy the
HYDROVANE Pro.
The potential-free contacts must not be more than
20 metres away from the terminal strip.
If necessary coupling relays must be fitted in the
control cabinet.
Important: The warnings above are applicable to all the
following items 3.8.1 to 3.8.5 inclusively.
3.8.1 Remote control for pressure
changeover
Sections 3.1.2 and 3.3.2 contain explanations of how to
set the second pressure range including timer
operations.
CUT-OUT POINT
CUT-IN POINT
TARGET PRESSURE
p2 CUT-OUT
p2CUT-IN POINT
p2 TARGET PRESSURE
p2 TIMER CONTROL
Input X:
2nd pressure range
ON-LOAD
Fig. 3 Remote Pressure Changeover.
You can also activate the second pressure range
remotely. This is done using a digital input X (Fig. 3) on
the HYDROVANE Pro (see Section 3.5.1 and circuit
diagram).
In the [OPTIONAL IN-/OUTPUTS] menu you have to
program the inputs using the 2nd PR. RANGE function.
A potential-free contact can now be connected to the
terminal strip of the programmable input. If this contact
is closed, the system changes over to the second
pressure range.
You can also use this contact to take the programmed
timer for the second pressure range out of service.
3.8.2 Enabling on-load operation
The HYDROVANE Pro controller allows the operator to
switch the compressor into off-load from a remote point
through the connection of a potential-free contact. This
function is needed when using an external control for
example.
CUT-OUT POINT
TARGET PRESSURE
p2 CUT-OUT
p2 TARGET PRESSURE
p2 TIMER
CONTROL
INPUT
X:
2nd PR.RANGE
INPUT X:
OPERATE_B1
ON-LOAD
Fig. 4 On-load/Off-load Remote Control
Go to the [OPTIONAL IN-/OUTPUTS] menu where you
must program one input with the OPERATE_B1 function
(Fig. 4). The unit can now be switched to off-load using the
input.

3.0 Additional Functions
18 CC1092267A
3.8.3 On-load/off-load remote control
The HYDROVANE Pro control system allows the
operator to switch the compressor into on-load or off-
load from a remote point through the connection of two
potential-free contacts. This function is needed when
using an external control for example.
Go to the [OPTIONAL IN-/OUTPUTS] menu where you
must program one input with the ENAB.REM.LOAD
function and another with the REMOTE LOAD function.
The unit can now be switched to on-load or off-load
using these two inputs.
In the circuit diagram (Fig. 5) we have assigned inputs
as follows:
INPUT 1:ENAB.REM.LOAD
INPUT 2:REMOTE LOAD
You can of course program the inputs any way you
choose.
If input 1 is activated, the unit can only be switched into on-
load or off-load by remote control. Both pressure ranges
and time control mode are interrupted (decoupled). If input
2 is now activated, the compressor is in on-load. If input 2
is not activated, the compressor is in off-load.
If the supply pressure exceeds the preset operating
pressure of 0.5 bar (7 psi), the WARNING LINE PRESS
indication appears on the display. Remote control is
deactivated at the same time. The unit now runs again
using one of the preset pressure ranges until the
WARNING LINE PRESS is acknowledged.
CUT-OUT POINT
CUT-IN POINT
TARGET PRESSURE
p2 CUT-OUT
p2 CUT-IN
p2 TARGET PRESSURE
INPUT X:
REMOTE LOAD
p2 TIMER CONTROL
INPUT X:
2
nd
PR. RANGE
INPUT X:
ENAB.REM.LOAD
WARNING
LINE PRESS
ON-LOAD
Fig. 5 On-load/Off-load Remote Control

3.0 Additional Functions
CC1092267A 19
3.8.4 Enabling on-load operation
The HYDROVANE Pro controller allows the operator to
switch the compressor into off-load from a remote point
through the connection of a potential-free contact. This
function is needed when using an external control for
example.
CUT-OUT POINT
TARGET PRESSURE
p2 CUT-OUT
p2 TARGET PRESSURE
p2 TIMER
CONTROL
INPUT
X:
2nd PR.RANGE
INPUT X:
OPERATE_B1
ON-LOAD
Fig. 6 On-load/Off-load Remote Control
Go to the [OPTIONAL IN-/OUTPUTS] menu where you
must program one input with the OPERATE_B1 function
(Fig. 6). The unit can now be switched to off-load using the
input.
3.8.5 Remote start / stop
This function allows the operator to externally switch the
compressor on and off. You have two ways of
implementing this function. The remote start / stop
function is permanently programmed, this relates to
terminals X10 and X12 (see circuit diagrams).
The unit continues to run while the potential-free contact
is closed. If the contact is opened, the soft-stop is
undertaken and the unit stops.
Note
The unit is controlled using the remote start / stop
function. If the unit is shut down during operations, e.g.
due to power loss, it does not automatically start up when
the power is restored. The potential-free contact must
first be re-opened and then closed to restart the unit.
1st option
The compressor is to be activated using a potential-free
contact.
Activate this function in the [CONTROL MENU] sub-
menu. Go to the ENABLE REMOTE-START menu item.
Once you have pressed the key, the OFF value starts
to flash. You can now use the key to change the value
to ON. The symbol appears in the first display row.
Connect the potential-free contact that you need for the
remote start / stop function to the X10 and X12 terminals
(see circuit diagram). This input is permanently
programmed for the remote start / stop function.
If the remote start / stop function is activated, you can no
longer control the compressor using the and keys.
Only the emergency stop button remains activated. The
compressor can now only be switched on and off using
the potential-free contact.
2nd option
A control room is to decide whether the enable for the
remote start / stop function is issued. The function for the
enable is implemented using a digital input. If the enable
is issued, the compressor can only be switched on and
off using the external potential-free contacts (X10 and
X12). If the enable is not issued, the compressor can only
be switched on and off on the HYDROVANE Pro.
Connect the potential-free contact for the remote start /
stop function to the permanently programmed X10 and
X12 terminals.
In the [OPTIONAL IN-/OUTPUTS] menu you now have to
program one input with the ENAB.REM-START function
(see Section 3.5.1).
The symbol appears in the first display row. In the
[CONTROL MENU] sub-menu behind the ENABLE
REMOTE-START menu item, EXT. appears.
If the input is closed, the unit can only be switched on
and off using the potential-free contact.
If the input is opened, the unit can only be switched on
and off using the HYDROVANE Pro.

Table of contents
Popular Controllers manuals by other brands

EuroLite
EuroLite SPX-405 DMX user manual

Belimo
Belimo HR series quick start guide

SmartVent
SmartVent LITE user manual

FUTABA
FUTABA PS-10 BR5.2 instruction manual

Mitsubishi Electric
Mitsubishi Electric MELSEC-F FX3U-232ADP-MB installation manual

Emerson
Emerson Vilter MicroVission Operation and service manual