Icon Electronics D3-VMD0-T User manual

Description:
ThisdeviceisusedtodisplayandmonitorDCvoltage.Maximum&Minimumvaluesareloggedfor24hours(updatedevery60min).
The relay(s) may be used for over and / or under protection. The latch facility may be de-activated for one or both the relays
allowing one relay to be used for control (not latched), and the other as a latched alarm. Use the “ScAL” parameter for calibratio
n
purposes, or to change the number of decimal places displayed (see notes). Other features include adjust able signal damping,
adjustable start-up and reaction delays, the ability to swap the relay’s functionality.All settings may be locked & code protected
toavoidchanges from being made byunauthorisedpersonnel.
0RELAY
This device is used to display DC voltage.
1RELAY
Thevoltageappliedisdisplayedaccordingtothescalespecified.The relay remains energised while the input signal is betwee
n
the upper and lower set points. Once de-energised, the signal must change in the opposite direction by the hysteresis amou
nt
before the relay will re-energise. The relay’s action may be swapped to energise when the setpoint is reached. Note: the relay
will NOT re-energise while the latch pins are shorted. The latch pins can also be used as a reset.
2RELAY
The voltage applied is displayed according to the scale specified. The relays remain energised while the input signal is betwee
n
the upper and lower set points. Once de-energised, the signal must change in the opposite direction by the hysteresis amou
nt
before the relay will re-energise. Either relay’s action may be swapped to energise when the setpoint is reached. Note: the
relay will NOT re-energise while the latch pins are shorted. The latch pins can also be used as a reset.
Adjustable parameters:
P
lease note: Depending on the model of the device purchased, some of the parameters listed below may not be available
·Upper limit for relay 1 “Hi 1” (default: disabled)
When the input rises above this value, the relay changes state until the signal drops by the hysteresis amount
(see“HYS.1”setting)
·Lower limit for relay 1 “Lo 1” (default: disabled)
When the input drops below this value, the relay changes state until the signal rises by the hysteresis amount
(see“HYS.1”setting)
DC VOLTAGE MONITOR
incl 4-20mA or 0-10V re-transmit
D3-VMD 0/1/2-T
P44-VMD 0/1/2-T
P49-VMD 0/1/2-T
EXAMPLE:D3-MD0-T=0RELAY
Operating instructions and Guarantee Certificate
www.iconelectronics.co.za
ReTransmit devices (-T)
T
he 4 -20mA re-transmitted signal is optically isolated from the input signal. By default the re-transmittion parameters are set so that th
e
o
utput follows the full scale input.
D3
53mm
DINrailmount
P44
48mmx48mm
panel mount
P49
48mmx96mm
panel mount

·Hysteresis value for relay 1 “HYS.1 “ (default: 0.5 )
Oncetheset-pointisreached, (&relay changedstate),theinputsignal mustchange (intheoppositedirection)by thisvalue beforetherela
y
will return to its original state.
· Start-up delay for relay 1 “St.d.1“(default: 0.0 Sec, max: 100.0 Sec)
Delay(afterpower-up) beforemonitoringstarts (toallowthe signaltostabilize).
·Reaction delay for relay 1“rE.d.1 “ (default: 0.0 Sec, max: 100.0 Sec)
A fault condition must occur for longer than this period before the relay changes state.
(Toallowfaultconditionsforshortperiodsof time)
·Relay 1 function “rE.F.1 “ (default: De-energise)
Relaystatewhen thesetpointisreached “dE.En”=de-energise,“EnEr”= energise.
·Latch enable for Relay “LAt.1 “ (default: Enable)
Whenthe setpointisreached, &the relayhaschanged state,therelay willNOT revertbackto theoriginalstate whilethe latch pins are
shorted(withthisparameterenabled),evenifthemeasuredvaluedropsbelowthesetpoint&hytesresislevel.Thelatchpinscanalsobeused
toresetrelay1ifenabled.Ifdisabled,thelatchpinsdoNOTaffectrelay1’sfunctionality.“En.Ab”=enabled,“diS.A”=disabled.
·Upper limit for relay 2 “Hi 2” (default: disabled)
·Lower limit for relay 2 “Lo 2” (default: disabled)
·Hysteresis value for relay 2 “HYS.2 “ (default: 0.5)
·Start-up delay for relay 2 “St.d.2“(default: 0 Sec, max: 100.0 Sec)
·Reaction delay for relay 2 “rE.d.2 “ (default: 0 Sec, max: 100.0 Sec)
·Relay 2 function “rE.F.2 “ (default: De-energise)
·Latch enable for Relay 2“LAt.2 “ (default: Enable)
·Fault indication “indi” (default: on)
Duringfaultconditionsthedisplayindicateswhetherthevalueisaboveorbelowthesetpointvalues(“r1.Hi”,”r1.Lo”,“r2.Hi”,”r2.Lo”).If
a
fault condition exists, but the relay is being held energised by the start-up or reaction delay timers, “-r1-” or “-r2-” is displayed.
Changingthis setting to “off”,disables these messages. Note:Thissettingdoes not affectthe “Er.Hi” and “Er.LO” messages. (see
notes)
·Lower display value “diSP”
Select the valueto be displayedon thelower LED display.“Hi1”,“Lo1” or “off”
·24 hour Minimum “24h.L”
Displaythelowestvaluemeasuredduringthepast24hours(Press“SELECT”toclear)
·24 hour Maximum “24h.h”
Displaythehighestvaluemeasuredduringthepast24hours(Press“SELECT”toclear)
·Display Span “SCAL” (default value:100.0)
Thisvalueis displayed when 150V is applied to the input. (or rated input if specified otherwise. See label on device)
·Decimal pointer “dEci” (default value: 100.0)
Use this setting to adjust the decimal point to the desired position.(0.000/0.00/0.0/0)
·Software damping filter “FiLt” (default value:6)
Adjust from 1 to 15 to increase the amount of signal damping.
·Re-transmitoutput Offset “rt.OS’ (default value: programmed display offsetvalue)
When the display indicates this value, 4mA will be transmitted.(see notes)

·Re-transmit output SPan “rt.SP’ (default value: programmed display span value)
When the display indicates this value PLUS the offset value (“rt.SP’+”rt.OS”), 20mA is transmitted. (see notes).
·Reset “RESt”
By selecting this setting, the device is reset to the factory defaults press “S”&“T” or “+” & “-” together to select.
DUALDISPLAYDEVICE PROGRAMMING Example 1:
Setthe device to de-energise relay 1 when the voltage is below 10.0V and above 90.0V
IfallofthefollowingsettingsareNOTavailable,exitthemenuandactivatetheadvancedmenu.
Press “4” to display “Hi 1”.
Use “T” and“S”buttons to change thevalueto“90.0”.
Press “4” to display “Lo 1”.
Use “T” and“S”buttons to change thevalueto“10.0”.
Press and hold “4” for 3 seconds to exit the menu.
DUALDISPLAYDEVICE PROGRAMMING Example 2:
Set the device to display 0-100% for a voltage of 0-50V
ie: 0V=0%, 50V=100%
IfallofthefollowingsettingsareNOTavailable,exitthemenuandactivatetheadvancedmenu.
Press “4” repeatedly until “SCAL” is displayed.
Use“T”and“S”buttonstochangethevalueto“3000”.(ignoredecimalpointer)
150V(fullscalevoltage)/50V(newfullscalevalue)x100(displayvalueatnewfullscalevaluevalue)
Press “4” to display “dEci”.
Use “T” and“S”buttons to move the decimal pointer to the desired position.
SINGLE DISPLAYDEVICE PROGRAMMING Example 1:
Setthe devicetode-energise relay 1 when thevoltage is below 10.0V and above 140.0V
IfallofthefollowingsettingsareNOTavailable,exitthemenuandactivatetheadvancedmenu.
Press “MENU” to display “Hi 1”.
Press“SELECT” andchange thevalue to“140.0”.
Press “ENTER”. “Lo 1” is displayed.
Press“SELECT” andchange thevalueto“10.0”.
Press“ENTER”.
Press “BACK” to exit the menu.
SINGLE DISPLAYDEVICE PROGRAMMING Example 1: Set the device to display 0-100% for a voltage of 0-50V
ie: 0V=0%, 50V=100%
Press“MENU” repeatedly until “SCAL” is displayed.
Changethevalue to 3000.
150V(fullscalevoltage)/50V(newfullscalevalue)x100(displayvalueatnewfullscalevaluevalue)
Notes:
· Whenevertheinputsignalisabove orbelow the“CAL.O”or“CAL.S”valuesby more than3%.The displayindicates“Er.Hi”or“ER.Lo”.
· Certainsettingsare resettodefaultwhenthedevice isre-configured.Re-checkall settingstoensure theyarecorrectbefore
commissioning.(usetheadvancedmenu)
· The maximum & minimum values are NOT updated during the first 30 seconds after power up. This allows the input signal to
stabilize first.
Specifications:
Display scale: 10 to 9999
Display resolution: 0.01 to 1 (adjustable)
Maxinputvoltage 103% of rated input
(155Vonstd device)
Measurementresolution: 0.15V
Accuracy ±0.3% @ 25°C (% of full scale)
Inputvoltage: ±15% of rated input

P
lease Note ( for 1 and 2 relay devices ONLY):
·
As a power saving feature, the display dims if settings are not being made.
·
Even though the device seems to operate correctly, the relay(s) will not energise if the input voltage is below the operating
voltage.
12 Month guarantee:
Ourproductis guaranteed for a 12 (twelve) month period fromdateofpurchase. This guarantee is valid for defects arisingfrom
failureduringspecifiedconditions. This guarantee does not cover damage duetoabuse,tampering or improper installation. Our
company does not accept liability for any consequential damage or loss arising from product malfunction. Should this product
provetobe defective, kindly return for inspection or repair.
R
elay specifications:
C
ontactrating: 10A 250 VAC 2500VA
M
echanicallife: 30million operations
E
lectrical life: 250000operations(atmaximumload)
For furtherinformation, please visitus at: www.iconelectronics.co.za
Menu operation (single display):
All adjustments are made via the three front mounted buttons.
Press the “MENU” button repeatedly until the desired setting is reached, press “SELECT” to display the current value of the
selectedparameter,or sub menu (if applicable).
The“+”and“-”buttonsareusedtochange the value.
“ENTER”willreturnthedeviceto the menu.
The “BACK” button will exit the menu.
Menu operation (dual display):
Press the menu “4” button repeatedly until the desired setting is reached.
The“S”and“T” buttons are usedtochange the value.
“4” will display the next menu item.
To exit the menu hold “4” button for 3 seconds.
Menu options:
Exitthemenubeforemakingthefollowingadjustments.
Lock / unlock parameters:
(default: unlocked)
Press “BACK” (“T”), then “ENTER” (“4”) and hold the 2 buttons until the desired option is displayed.
Thedisplaycyclesbetween“Loc”(nochangesallowed)&“u.Loc”(parametersmaybeadjusted)
Full / reduced menu (default: Full)
Press “SELECT”(“S”), then “ENTER”(“4”) and hold the 2 buttons until the desired option is displayed.
The display cycles between “rEdu” (limited menu) & “Full” (all parameters are accessible)
Access Code: (default: no code)
Oncetheaboveoptionshavebeensetasrequired,Press “BACK” and “SELECT” (“T”and “S”) simultaneously until “CODE” is
displayed.
Now use the “+” & “-” (“S” and “T”) to enter a code.
Once a code is entered, access to the options above is not permitted.
To clear the code, re-enter the same code again.
If the code is forgotten. Press and hold “+” & “-” (“S”and “T” ) until “CODE” is displayed while re-applying power to the device.
re-transmit Notes:
· The output 4-20mAis dependant on the value being displayed, and is set up in a similar manner to the display.The offset
parameter determines when 4mA is output, and the span is the amount required for the output to increase by an additional
12mAie. 20mAis output when the value displayed = re-transmit OFFSET+SPAN
· To set the re-transmittion signal to follow the input signal (the output 4-20mAfollows the 4-20mAreceived), set the re-tx offset
and span settings to the same value as the display offset and span settings.
· To set the re-transmittion signal to invert the input signal (the output = 4mAwhen the input = 20mA), set the re-tx offset = (display
offset+span)andre-txspan = (display span x -1).
· Whenever the input signal is above or below the “CAL.O” or “CAL.S” values by more than 3%.The display indicates “Er.Hi” or
“ER.Lo”.
· Certain settings are reset to default when the device is re-configured. Re-check all settings to ensure they are correct before
commissioning.(usethe advanced menu)

This manual suits for next models
8
Table of contents
Other Icon Electronics Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Bartington
Bartington MS3 Operation manual

FW Murphy
FW Murphy TDX6 Installation and operation instructions

Sontex
Sontex Supercal 739 Instruction guide

Thies CLIMA
Thies CLIMA First Class Advanced X Instructions for use

RD Instruments
RD Instruments WorkHorse Sentinel user guide

AST
AST A250+ PL/TL/Video user manual