ICT Protege PRT-RDM2-PCB User manual

PRT-RDM2-PCB
Protege Mini 2 Reader Expander
Installation Manual

2PRT-RDM2-PCB Protege Mini 2 Reader Expander Installation Manual | March 2015
The specifications and descriptions of products and services contained in this document were correct at the
time of printing. Integrated Control Technology Limited reserves the right to change specifications or withdraw
products without notice. No part of this document may be reproduced, photocopied, or transmitted in any form
or by any means (electronic or mechanical), for any purpose, without the express written permission of
Integrated Control Technology Limited. Designed and manufactured by Integrated Control Technology Limited.
Protege® and the Protege® Logo are registered trademarks of Integrated Control Technology Limited. All other
brand or product names are trademarks or registered trademarks of their respective holders.
Copyright © Integrated Control Technology Limited 2003-2015. All rights reserved.
Publication Date: March 2015

PRT-RDM2-PCB Protege Mini 2 Reader Expander Installation Manual | March 2015 3
Contents
1Introduction_______________________________________________________________ 5
1.1Document Conventions.................................................................................................5
2Installation________________________________________________________________ 6
2.1Location and Mounting .................................................................................................6
2.2Cabinet Tamper Switch.................................................................................................6
2.3DC Power and Encrypted Module Network ..................................................................7
3Door Access Control_______________________________________________________ 8
3.1Reader Connection........................................................................................................8
3.2Multiple Wiegand Reader Connection...........................................................................9
3.3Magnetic Reader Connection......................................................................................10
3.4Door Contact Connection ...........................................................................................10
3.5Door Lock Connection ................................................................................................11
4Zone Inputs______________________________________________________________ 12
4.1Zone Inputs .................................................................................................................12
4.2Trouble Zone Inputs ....................................................................................................13
5Programmable Outputs ___________________________________________________ 14
5.1Lock PGM Outputs (1 and 2).......................................................................................14
5.2Standard PGM Outputs (3 To 8)..................................................................................14
5.3PGM Beeper Outputs Special Functions (5 and 8) .....................................................15
6Configuration Switch______________________________________________________ 16
6.1Address Configuration.................................................................................................16
7Status Indication _________________________________________________________ 17
7.1Status Indicator ...........................................................................................................17
7.2Fault Indicator..............................................................................................................17
7.3RLY 1/RLY 2 Indicators ...............................................................................................17
7.4RDRMON Indicator......................................................................................................17
7.5R1 and R2 Data Indicator ............................................................................................17
8Error Code Indication _____________________________________________________ 18
8.1Error Code Display ......................................................................................................18

4PRT-RDM2-PCB Protege Mini 2 Reader Expander Installation Manual | March 2015
9Technical Specifications___________________________________________________ 19
10New Zealand and Australia ________________________________________________ 20
11European CE and EN 50131 _______________________________________________ 21
12Ordering Information ______________________________________________________ 23
13Warranty ________________________________________________________________ 24
14Contact _________________________________________________________________ 25

PRT-RDM2-PCB Protege Mini 2 Reader Expander Installation Manual | March 2015 5
1 Introduction
Thank you for purchasing the Protege Mini 2 Reader Expander by Integrated Control Technology. The Protege
System is an advanced technology security system designed to provide integration with building automation,
apartment complex control and HVAC in one flexible package. Communication is over a proprietary high speed
protocol across an encrypted local area network and AES Encrypted Proprietary RS-485 module network.
Using modular-based hardware design, system installers have the flexibility to accommodate any installation
whether it's small, large, residential or commercial.
The Reader Expander extends the number of card reader inputs on the system by 2 or 4 when using Multiple
Reader mode, number of zone inputs by 8 (four zones used for door monitoring and control and up to eight can
be used for extended functionality) and the number of PGM outputs by 8 (includes 2 relay lock control outputs).
Flexible module network architecture allows large numbers of modules to be connected to the RS-485 Module
Network. Up to 250 modules can be connected to the Protege System in any combination to the network, over
a distance of up to 900M (3000ft). Further span can be achieved with the use of a network repeater module.
Locking a network prevents the removal, substitution or addition of modules to the module network effectively
preventing any tampering with the system.
The current features of the Reader Expander include:
4 Wiegand Reader Mode For 2 Entry/Exit Doors Per Reader Expander
Secure encrypted RS-485 module communications
8 Zone Inputs
2 lock FORM C Relay PGM outputs
6 open collector PGM outputs (Reader Control outputs)
Smart reader missing/tamper monitoring
Online and remote upgradeable firmware
When receiving this product you should find the kit contains the items listed below. If you do not have the
correct contents, please contact your distributor immediately.
Reader Expander Printed Circuit Board
Protege Mini 2 Reader Expander Installation Manual
18 1K Ohm resistors
2 1N4007 lock reverse EMF protection diodes
6 Plastic mounting standoffs
For more information on the Protege Mini 2 Reader Expander and other Integrated Control Technology products
please visit the ICT website (http://www.ict.co).
1.1 Document Conventions
Indicates a warning or cautionary message
i
Indicates an important note or advisory information
Indicates a hint or suggestion
[TEXT] Bold text enclosed in brackets is used to show a section number or address of a programmable
option or information on programming shortcut sequences

6PRT-RDM2-PCB Protege Mini 2 Reader Expander Installation Manual | March 2015
2 Installation
2.1 Location and Mounting
The Reader Expander is available as a PCB Only (Printed Circuit Board) or complete unit supplied with a metal
cabinet. We recommend that the cabinet is used wherever possible as this provides the best mounting and
installation solution as well as the required cable entry and termination space.
When installing the Reader Expander ensure that there is adequate clearance around all sides of the enclosure
and air flow to the vents of the enclosure are not restricted.
We recommend the Reader Expander is installed in a location that will facilitate easy access for wiring. We also
recommend that the Reader Expander is installed in electrical rooms, communication equipment rooms, closets
or in an accessible area of the ceiling.
1. Insert the plastic stand-offs in to the locations to mount the PCB board.
2. Calculate the location and position of the enclosure and mark the holes for the keyhole points in the top left
and right locations. This will allow you to screw in the screws and then hang the box on them adjusting the
location to suit.
3. Ensure a solid fixing point and screw in the two screws. Before tightening the top screws insert the tamper
bracket in the slot provided on the right side of the enclosure.
4. Fix the enclosure securely using the remaining mounting holes on the bottom left, right and centre of the
enclosure.
5. Insert the PCB in to the enclosure and mount using the plastic standoffs inserted during step one.
i
Install the enclosure when the circuit board is NOT installed on the plastic stand-offs. This will reduce
the risk of damage caused by debris during the installation process.
2.2 Cabinet Tamper Switch
The enclosure tamper input signals to the monitoring station or remote computer that the Reader Expander
enclosure has been opened. The tamper input switch shall be mounted into the steel bracket provided and
connected to the tamper connection terminals as shown in the diagram below. The tamper input opens and
closes trouble zone RDxxx:01 on the Reader Expander.
Bracket
Tamper Switch
N+ N- NA NB TP TP
Tamper Input Connection

PRT-RDM2-PCB Protege Mini 2 Reader Expander Installation Manual | March 2015 7
2.3 DC Power and Encrypted Module Network
The Reader Expander incorporates encrypted RS-485 communications technology, and both module and
network power are supplied by the N+ and N- terminals.
Network communicationsinput
from the Protege Integrated
System Controller or previous
Protege module
N+ N- NA NB TP TP
Standard Communication Connection
Connection of the communications and DC supply should be performed according to the diagram shown
above. It is important that the N+ Network Communications Power be 12VDC supplied from an independent
battery backed power supply unit such as the PRT-PSU-DIN or a networked module capable of supplying the
required voltage to all devices on the RS485 network.
Warning:
The 12V N+ and N- Communication input must be supplied from only ONE point. Connections
from more than one 12V supply may cause failure or damage to the Reader Expander or device
supplying network power.
Under no circumstances should you power the locking devices that are connected to the Reader
Expander from the N+ and N- network communication power supply. A separate power supply
MUST be used to power the locking devices.
EOL OFF EOL ON
EOL Jumper
i
The EOL (End Of Line) jumper should be placed in the ON position when the Reader Expander is
inserted as the FIRST or LAST module on the RS485 network. EOL is ON when the jumper is placed
closest to the EOL text.

8PRT-RDM2-PCB Protege Mini 2 Reader Expander Installation Manual | March 2015
3 Door Access Control
The Reader Expander allows the control of two separate access controlled doors used for entry or exit only, and
a single access controlled door using entry/exit.
3.1 Reader Connection
The Reader Expander allows the connection of 2 magnetic clock and data reading devices or 4 Wiegand
reading devices and the ability to control 2 doors (entry or exit only) or 1 door (entry and exit). The following
diagram shows the connection of a standard Wiegand Reader with the Reader Expander controlling an access
door and entry/exit door.
+ - DO L2D1 L1 BZ
RED
BLACK
GREEN
WHITE
ORANGE
BROWN
BLUE
YELLOW
SHIELD
R1 R1 R1 R1 R1 R1 R1
Standard Reader Connection
Warning: The shield connection on the card reading device that is connected to the reader port should
NOT be connected to the R1-, R2- or a 0V connection. Do not join the shield and black wires at the
card reading device. The shield should not be connected to any shield used for isolated
communication. Always refer to the card reader manufacturer for detailed installation guidelines.
i
The beeper output on the Reader Expander provides diagnostic information to the end user and
installer when access is denied or the unit is operating offline. Refer to PGM Beeper Outputs Special
Function Operation (see page 15) for further details.

PRT-RDM2-PCB Protege Mini 2 Reader Expander Installation Manual | March 2015 9
3.2 Multiple Wiegand Reader Connection
When operating in multiple reader mode the Reader Expander allows the connection of 4 reading devices for
entry/exit control of doors per reader input.
When connecting Wiegand readers in multiple reader mode the secondary reader that is connected will have all
connections wired to the same port as the primary card reader with the DATA 1 connection wired to the
opposite reader connection DATA 1 input.
RED
BLACK
GREEN
WHITE
ORANGE
BROWN
BLUE
YELLOW
SHIELD
RED
BLACK
GREEN
WHITE
ORANGE
BROWN
BLUE
YELLOW
SHIELD
Entry Reader
Exit Reader
Data
+ - DO L2D1 L1 BZ
R1 R1 R1 R1 R1 R1 R1
+ - DO L2D1 L1 BZ
R2 R2 R2 R2 R2 R2 R2
Multiple Reader Interface
Warning: The shield connection on the card reading device that is connected to the reader port
should NOT be connected to the R1-, R2- or a 0V connection. Do not join the shield and black wires
at the card reading device. The shield should not be connected to any shield used for isolated
communication. Always refer to the card reader manufacturer for detailed installation guidelines.
i
The secondary reader when connected will ALWAYS function as the exit reader.

10 PRT-RDM2-PCB Protege Mini 2 Reader Expander Installation Manual | March 2015
3.3 Magnetic Reader Connection
The Reader Expander allows the connection of standard magnetic track 2 format cards and provision is made in
the software for a large number of formats. Formats include BIN number for ATM access control and first 4, 5
and 6 card numbers.
YELLOW
GREEN
RED
BROWN
ORANGE
OUT COM IN
INLINE +5v REGULATOR
50mA MAX OUTPUT
+5V +12V
0V 0V
+ - DO L2
D1 L1 BZ
R1 R1 R1 R1 R1 R1 R1
Magnetic Card Reader Interface
i
Magnetic card readers are typically operated by 5 volts. Before connecting the magnetic card reader
to the Reader Expander, ensure that the supply voltage is correct and if required insert the inline 5 Volt
regulator as shown in the diagram above.
3.4 Door Contact Connection
The Reader Expander allows the connection of up to 4 contacts for monitoring and controlling access control
doors. Each zone on the Reader Expander can be used for the door function that is automatically assigned and
as a normal zone input on the system. The following example shows the connection of a normally closed door
position monitoring contact to monitor the open, closed, forced and alarm conditions of the door.
Z1
DOOR1
Z2
Z3
Z4
COM
REX1
SENSE1
REN1
DOOR CONTACT
NORMALLY CLOSED
REQUEST TO EXIT
NORMALLY OPEN
Standard Door Contact Inputs
i
When connected the REX input can be programmed to operate regardless of the door contact state.
The REX input can also be programmed to recycle the door alarm time to prevent nuisance alarms
when the door is held open to permit longer entry.

PRT-RDM2-PCB Protege Mini 2 Reader Expander Installation Manual | March 2015 11
3.5 Door Lock Connection
The Reader Expander provides two lock output relays that can be used to switch electric locks.
+
-
1N4007 Diode
12VDC Electric
Locking Device
+
-
Power Supply for
Locking Devices
Max 30VDC
NO COM NC
Contact Rating 7A,
30VDC or 30VAC
Door Lock Outputs
i
When using a door with an entry and exit reader, the LOCK output should be connected to LOCK
1, and enable the swap lock option for the second reader input to allow the reader LED's to
display the correct status.
The 1N4007 diode shown in the above diagram is supplied with the Reader Expander and MUST
be installed at the electric strike terminals.

12 PRT-RDM2-PCB Protege Mini 2 Reader Expander Installation Manual | March 2015
4 Zone Inputs
The Reader Expander has 8 zone inputs. The Reader Expander also monitors 16 trouble zones used to report
trouble conditions such as module communication problems.
4.1 Zone Inputs
The Reader Expander can monitor the state of up to 8 zone inputs EOL monitored or dry contact devices such
as magnetic switches, PIR motion detectors and temperature thermostats. Devices connected to these zones
can be installed to a maximum distance of 300m (1000ft) from the Reader Expander when using 22 AWG wire.
Each zone input may be individually configured for normally opened and normally closed configurations with or
without EOL resistors for tamper and short condition monitoring.
When using a zone with the EOL resistor configuration, the controller generates an alarm condition when the
state of a zone changes between open and closed and generates a tamper alarm condition when a wire fault
(short circuit) or a cut wire (tampered) in the line occurs.
When using the EOL resistor configuration, the EOL resistor option must be enabled in the zone programming
so that the tamper and short states can be monitored (for details, refer to the Zones Section in the Protege
Reference Manual).
N.C Zone Contact
N.C Tamper 1K 1K
Z1
DOOR1
Z2
Z3
Z4
COM
REX1
SENSE1
REN1
EOL Resistor Zone Configuration
Each zone input can use a different input configuration. When using the No Resistor configuration, the system
controller only monitors the opened and closed state of the connected input device generating the (OPEN)
Alarm and (CLOSED) Sealed conditions.
N.C Zone Contact
Z1
DOOR1
Z2
Z3
Z4
COM
REX1
SENSE1
REN1
Normally Closed Zone Configuration No Resistors

PRT-RDM2-PCB Protege Mini 2 Reader Expander Installation Manual | March 2015 13
4.2 Trouble Zone Inputs
Each Reader Expander can monitor up to 16 trouble zones. Trouble zones are used to monitor the status of the
Reader Expander and in most cases are not physically connected to an external zone. The following table
details the trouble zones that are configured in the system and the trouble type and group that they activate.
Zone Number Description Type Group
RDxxx:01 Module Tamper System Tamper System
RDxxx:02 AC Failure Power Fault General
RDxxx:03 Reserved None None
RDxxx:04 Aux Failure Power Fault General
RDxxx:05 Reserved None None
RDxxx:06 Door 1 Forced Forced Door Access
RDxxx:07 Door 2 Forced Forced Door Access
RDxxx:08 Door 1 Left Open Left Open Access
RDxxx:09 Door 2 Left Open Left Open Access
RDxxx:10 Reserved None None
RDxxx:11 Reserved None None
RDxxx:12 Reader 1 Tamper System Tamper System
RDxxx:13 Reader 2 Tamper System Tamper System
RDxxx:14 Door 1 Lockout Attempts Access
RDxxx:15 Door 2 Lockout Attempts Access
RDxxx:16 Module Offline Module Offline System
Replace 'xxx' with the appropriate address of the Reader Expander that you are programming.

14 PRT-RDM2-PCB Protege Mini 2 Reader Expander Installation Manual | March 2015
5 Programmable Outputs
The Reader Expander has 8 Programmable Outputs (PGMs). These PGMs are used to activate bell sirens,
lighting circuits, door locks, relay accessory products, and other automation points.
5.1 Lock PGM Outputs (1 and 2)
Relays are provided on PGM output 1 and 2. These are used for the Lock 1 (PGM1 RD001:01) and Lock2
(PGM2 RD001:02) functions and are used to control electric door strikes and other lock control devices. The
lock relay will switch a maximum current of 7A resistive.
+
-
1N4007 Diode
12VDC Electric
Locking Device
+
-
Power Supply for
Locking Devices
Max 30VDC
NO COM NC
Contact Rating 7A,
30VDC or 30VAC
Lock Output PGM1/2 Connection
5.2 Standard PGM Outputs (3 To 8)
The PGM outputs 3, 4, 5, 6, 7 and 8 on the Reader Expander are open collector outputs and switch to a
ground connection.
The PGMs have a default pre-programmed function as detailed in the following table and are used to control the
indicator and audible outputs on the attached reading device. These functions may be disabled by programming
the appropriate setting in the reader expander configuration.
PGM Number Description
RDxxx:03 LED 1 (Green) Reader 1
RDxxx:04 LED 2 (Red) Reader 1
RDxxx:05 BEEPER Reader 1
RDxxx:06 LED 1 (Green) Reader 2
RDxxx:07 LED 2 (Red) Reader 2
RDxxx:08 BEEPER Reader 2

PRT-RDM2-PCB Protege Mini 2 Reader Expander Installation Manual | March 2015 15
Replace 'xxx' with the appropriate address of the Reader Expander that you are programming.
1K5 OHM
LED
+ - DO L2
D1 L1 BZ
R1 R1 R1 R1 R1 R1 R1
Example Open Collector Output Connection (LED)
Warning: The PGM outputs 3 to 8 can switch to a maximum capacity of 50mA each. Exceeding this
amount will damage the PGM output.
5.3 PGM Beeper Outputs Special Functions (5 and 8)
The PGM beeper outputs 5 and 8 on the Reader Expander provide special diagnostic information when a card
is presented. The following table shows the beeper modes of operation.
Function Description
2 Beeps Access Granted. The lock will activate and allow access to the door the card has been
presented.
4 Beeps Offline Access Granted. This is generated ONLY if the reader expander is operating
offline and the mode of offline operation allows access.
1 Long Beep Offline Access Denied. This is generated ONLY if the reader expander is operating offline
and the mode of offline operation prevents this card from being allowed access.
1 Long Beep
1 Short Beep
Access Denied Card Number Not Known. The card number is not known in the system.
The card that has been presented to the reader could not be matched to a valid user in
the system.
1 Long Beep
2 Short Beeps
Access Denied Door Group. The user is denied access because they do not have
access to the door. This error will also be generated if the door group is not set or the
door group schedule is not valid.
1 Long Beep
3 Short Beeps
Access Denied Area Group. The user is denied access because they do not have
access to the area that is being controlled by the door. If the area that the door is
associated with is armed, and the user does not have this area in their area disarm
group, they will be denied access. This also depends on the area group settings for the
door.
1 Long Beep
4 Short Beeps
Access Denied Access Level. The user is denied access because they do not have a
valid access level or the access level they are assigned is currently outside the
programmed schedule.

16 PRT-RDM2-PCB Protege Mini 2 Reader Expander Installation Manual | March 2015
6 Configuration Switch
The addressing of the Reader Expander allows up to 128 devices to be connected to the system controller. The
'CONFIG' configuration DIP switch allows each Reader Expander to have a unique address.
6.1 Address Configuration
The settings of the switch positions (1 to 7) determine the address assigned to the Reader Expander, a value
from 1 to 128. When setting an address the Reader Expander must be powered down and restarted for the
new address to take effect. When changing the address the Reader Expander will automatically default the
internal configuration and require a network update. See the Protege System Reference Manual for information
on performing a module update.
1ADDRESS 1
2 ADDRESS 2
3 ADDRESS 4
4 ADDRESS 8
5ADDRESS 16
6ADDRESS 32
7 ADDRESS 64
8DEFAULT/RUN
ONOFF
Reader Expander CONFIG Switch Functions
The device address is determined by adding the value of each switch (1 to 7) that is set in the ON position and
then adding 1 to this value. In the following example, the device address is determined by performing the
addition (64 + 8 + 4 + 2) + 1 = 079. Setting all address switches to OFF results in the default address of 001.
1ADDRESS 1
2 ADDRESS 2
3 ADDRESS 4
4 ADDRESS 8
5ADDRESS 16
6ADDRESS 32
7 ADDRESS 64
ADDRESS 079
Reader Expander Configured for Address 079

PRT-RDM2-PCB Protege Mini 2 Reader Expander Installation Manual | March 2015 17
7 Status Indication
The Reader Expander includes comprehensive diagnostic indicators that can aid the installer in diagnosing faults
and conditions. In some cases an indicator may have multiple meanings depending on the status indicator
display at the time.
7.1 Status Indicator
The Status indicator displays module status of the Reader Expander. FLASHING rapidly at 250ms intervals
indicates that the Reader Expander is attempting registration with the controller. FLASHING at 1 second
intervals will indicate that the Reader Expander has successfully registered with the controller.
i
When the fault indicator is on, the status indicator is used to show an error code. Refer to the Error
Code Display section for more information.
7.2 Fault Indicator
The Fault indicator is lit any time the module is operating in a non-standard mode. When the Fault indicator is
FLASHING the Reader Expander is operating in boot mode awaiting firmware update. When the Fault indicator
is ON the Reader Expander is in error state and will flash an error code with the Status indicator. Refer to the
Error Code Display section to determine the error.
7.3 RLY 1/RLY 2 Indicators
The RLY 1 and RLY 2 indicators will show the status of the respective lock output relays.
ON Relay output is ON.
OFF Relay output is OFF
7.4 RDRMON Indicator
Reader/Auxiliary voltage is supplied to the R1+ and R2+ outputs through the auxiliary fuse. If the reader/auxiliary
supply is normal then the RDRMON indicator will be ON. If the fuse is damaged, the indicator will be OFF.
7.5 R1 and R2 Data Indicator
The R1 and R2 data indicators display the status of the data being received on their respective reader terminals.
A short FLASH (<250 Milliseconds) on the R1/R2 data indicators will show that data was received but was not
in the correct format. A long FLASH (>1 Second) indicates that the Reader Expander has read the data and the
format was correct.

18 PRT-RDM2-PCB Protege Mini 2 Reader Expander Installation Manual | March 2015
8 Error Code Indication
When the Reader Expander attempts to register or communicate with the system controller a registration error
can be generated indicating that it was not successful.
8.1 Error Code Display
The following table is only valid if the FAULT indicator is CONSTANTLY ON and the STATUS indicator is
FLASHING RED.
If the fault indicator is FLASHING the Reader Expander requires a firmware update or is currently in firmware
update mode.
The status indicator will FLASH RED with the error code number. The error code number is shown with a
250ms ON and OFF period (duty cycle) with a delay of 1.5 seconds between each display cycle.
Flash Error Description
1
Unknown Error Code
The error code returned by the system controller could not be understood by the Reader
Expander. Contact Integrated Control Technology.
2
Firmware Version
The firmware version on the Reader Expander is not compatible with the system controller.
To clear this error, update the module using the module update application.
3
Address Too High
The Reader Expander address is above the maximum number available on the system
controller. To clear this error change the address to one within the range set on the system
controller, restart the Reader Expander by disconnecting the power.
4
Address In Use
The Address is already in use by another Reader Expander. To clear this error set the
address to one that is not currently occupied. Use the view network status command to list
the attached devices, or the network update command to refresh the registered device list.
5
Controller Secured Registration Not Allowed
Controller is not accepting any module registrations. To allow module registrations use the
network secure command to change the secure setting to not secured.
6
Serial Number Fault
The serial number in the device is not valid. Return the unit to the distributor for
replacement.
7
Locked Device
The Reader Expander or system controller is a locked device and cannot communicate on
the network. Return the unit to the distributor for replacement.

PRT-RDM2-PCB Protege Mini 2 Reader Expander Installation Manual | March 2015 19
9 Technical Specifications
The following specifications are important and vital to the correct operation of the Reader Expander. Failure to
adhere to the specifications will result in any warranty or guarantee that was provided becoming null and void.
Integrated Control Technology continually strives to increase the performance of its products. As a result these
specifications may change without notice. We recommend consulting the ICT website (http://www.ict.co) for the
latest documentation and product information.
Power Supply
DC Input Voltage 12VDC (+/-10%)
R1/R2 DC Output Voltage 12VDC 700mA (Typical) Electronic Shutdown at 1.1A
Operating Current 40mA (Typical) 110mA (Max, All Relays Activated)
Low Voltage Cut-out 8.7VDC
Low Voltage Restore 10.5VDC
Communication
RS-485 Isolated Module Network
Outputs
Lock Outputs 2 FORM C Relay Outputs, 7A 250V Max
PGM Outputs 6 (50mA Max) Open Collector
Inputs
Zone 8 (10ms to 1hr Input Speed Programmable)
Tamper Dedicated Hardware Tamper Input
Trouble Zone 16
Dimensions
PCB Dimensions 96mm X 217mm (3.78" X 8.54")
Weight 156g (5.50oz)
Temperature
Operating 5˚- 55˚ Celsius (41˚ - 131˚ Fahrenheit)
Storage -10˚- 85˚ Celsius (14˚ - 185˚ Fahrenheit)
Humidity 0%-85% (Non-Condensing)
i
It is important that the unit is installed in a dry cool location that is not affected by humidity. Do not
locate the unit in air conditioning or a boiler room that can exceed the temperature or humidity
specifications.

20 PRT-RDM2-PCB Protege Mini 2 Reader Expander Installation Manual | March 2015
10 New Zealand and Australia
The C-Tick compliance label indicates that the supplier of the device asserts that it complies with all applicable
standards. The SCN establishes a traceable link between a device and the supplier responsible for placing it on
the Australian market.
N30659
Table of contents
Other ICT Network Hardware manuals