ICT Protege PRT-RDE2-PCB User manual

PRT-RDE2-PCB
Protege Ethernet 2 Reader Expander
Installation Manual

2PRT-RDE2-PCB Protege Ethernet 2 Reader Expander Installation Manual | June 2017
The specifications and descriptions of products and services contained in this document were correct at the
time of printing. Integrated Control Technology Limited reserves the right to change specifications or withdraw
products without notice. No part of this document may be reproduced, photocopied, or transmitted in any form
or by any means (electronic or mechanical), for any purpose, without the express written permission of
Integrated Control Technology Limited. Designed and manufactured by Integrated Control Technology Limited.
Protege® and the Protege® Logo are registered trademarks of Integrated Control Technology Limited. All other
brand or product names are trademarks or registered trademarks of their respective holders.
Copyright © Integrated Control Technology Limited 2003-2016. All rights reserved.
Publication Date: June 2017

PRT-RDE2-PCB Protege Ethernet 2 Reader Expander Installation Manual | June 2017 3
Contents
1Introduction_______________________________________________________________ 5
2Installation________________________________________________________________ 6
2.1Package Contents .........................................................................................................6
2.2Location and Mounting .................................................................................................6
2.3Cabinet Tamper Switch.................................................................................................7
2.4Earth Ground Connection..............................................................................................7
2.5AC Power ......................................................................................................................8
2.6Backup Battery..............................................................................................................8
2.7Status Indicator .............................................................................................................9
2.8Ethernet 10/100 Network Connection...........................................................................9
2.9Encrypted Module Network.........................................................................................10
2.10Slave Device Network .................................................................................................12
2.11RS-485 Biasing Settings .............................................................................................14
3Communication Setup ____________________________________________________ 15
3.1Keypad Programming..................................................................................................15
Network Mode.............................................................................................................15
Controller Connection .................................................................................................16
DHCP Configuration....................................................................................................16
Network UDP Port .......................................................................................................16
Module IP Address ......................................................................................................16
Module IP Subnet Mask ..............................................................................................17
Module IP Gateway .....................................................................................................17
Controller IP Address ..................................................................................................17
3.2Web Programming ......................................................................................................17
User Login ...................................................................................................................18
Setup ...........................................................................................................................18
Network Setup.............................................................................................................18
Statistics......................................................................................................................19
Users ...........................................................................................................................19
4Door Access Control______________________________________________________ 20
4.1Reader Connection......................................................................................................20
4.2Multiple Wiegand Reader Connection.........................................................................21
4.3Magnetic Reader Connection......................................................................................22
4.4Door Contact Connection ...........................................................................................22
4.5Door Lock Connection ................................................................................................23

4PRT-RDE2-PCB Protege Ethernet 2 Reader Expander Installation Manual | June 2017
5Zone Inputs______________________________________________________________ 24
5.1Zone Inputs - Reader ..................................................................................................24
5.2Trouble Zone Inputs ....................................................................................................26
6Programmable Outputs ___________________________________________________ 27
6.1Lock PGM Outputs (1 and 2).......................................................................................27
6.2Standard PGM Outputs (3 to 8)...................................................................................28
6.3PGM Beeper Outputs Special Functions (5 and 8) .....................................................29
7Configuration Switch______________________________________________________ 30
7.1Address Configuration.................................................................................................30
8Status Indication _________________________________________________________ 31
8.1Status Indicator ...........................................................................................................31
8.2Fault Indicator..............................................................................................................31
8.3Charge/Test Indicator..................................................................................................31
8.4Auxiliary OK Indicator..................................................................................................31
8.5AC OK Indicator ..........................................................................................................31
8.65V Isolated Power Indicator ........................................................................................32
8.7Lock 1/Lock 2 Indicators.............................................................................................32
8.8Network RX/TX Indicator.............................................................................................32
8.9R1 and R2 Power Indicator .........................................................................................32
8.10R1 and R2 Data Indicator ............................................................................................32
9Error Code Indication _____________________________________________________ 33
9.1Error Code Display ......................................................................................................33
10Technical Specifications___________________________________________________ 34
11New Zealand and Australia ________________________________________________ 35
12European Standards ______________________________________________________ 36
13Ordering Information ______________________________________________________ 38
14Warranty ________________________________________________________________ 39
15Contact _________________________________________________________________ 40

PRT-RDE2-PCB Protege Ethernet 2 Reader Expander Installation Manual | June 2017 5
1 Introduction
The ICT Protege System is a powerful integrated alarm and access control management system designed to
provide integration with building automation, apartment complex control and HVAC in one flexible package.
Communication is over a proprietary high speed protocol across an encrypted local area network and AES
Encrypted Proprietary RS-485 module network. Using modular-based hardware design, system installers have
the flexibility to accommodate any installation from small to large, residential or commercial.
The PRT-RDE2-PCB Protege Ethernet Reader Expander extends the number of card reader inputs on the
system by 2, number of zone inputs by 8 (4 zones used for door monitoring and control and up to eight can be
used for extended functionality) and the number of PGM outputs by 8 (includes 2 monitored lock control
outputs).
Flexible module network architecture allows large numbers of modules to be connected to the RS-485 Module
Network. Up to 250 modules can be connected to the Protege System in any combination to the network up to
a distance of 900M (3000ft). Communication beyond this distance requires the use of a RS-485 Network
Extender or the Slave Communications Port on a PRT-RDI2-PCB Protege Intelligent Reader Expander.
The current features of the Protege Ethernet 2 Reader Expander include:
4 Wiegand Reader Mode for 2 Entry/Exit Doors Per Reader Expander
Secure Encrypted RS-485 Module Communications
8 Zone Inputs
2 Monitored Lock Control PGM Outputs
6 Open Collector PGM Outputs (Reader Control Outputs)
1.5A Switching Power Supply
Intelligent Battery Charge and Monitoring
Smart Reader Missing/Tamper Monitoring
Online and Remote upgradeable firmware
For more information on the Protege Ethernet 2 Reader Expander and other Integrated Control Technology
products please visit the ICT website (http://www.ict.co).

6PRT-RDE2-PCB Protege Ethernet 2 Reader Expander Installation Manual | June 2017
2 Installation
2.1 Package Contents
When receiving the PRT-RDE2-PCB Protege Reader Expander you should find the kit contains the items listed
below. When receiving this product, you should find the kit contains the items listed below. If you do not have
the correct contents, please contact your distributor immediately.
PRT-RDE2-PCB - Protege Reader Expander PCB Only
Reader Expander Printed Circuit Board
6 X Plastic Mounting Standoffs
20 X 1K Ohm Resistors
2 X 1N4007 Lock Reverse EMF Protection Diodes
Red/Black Backup Battery Wires
2.2 Location and Mounting
The Reader Expander is available as a PCB Only (Printed Circuit Board) or complete unit supplied with a metal
cabinet. We recommend that the cabinet is used wherever possible as this provides the best mounting and
installation solution as well as the required cable entry and termination space.
When installing the Reader Expander ensure that there is adequate clearance around all sides of the enclosure
and air flow to the vents of the enclosure are not restricted.
We recommend the Reader Expander is installed in a location that will facilitate easy access for wiring. We also
recommend that the Reader Expander is installed in electrical rooms, communication equipment rooms, closets
or in an accessible area of the ceiling.
1. Insert the plastic stand-offs in to the locations to mount the PCB board.
2. Calculate the location and position of the enclosure and mark the holes for the keyhole points in the top left
and right locations. This will allow you to screw in the screws and then hang the box on them adjusting the
location to suit.
3. Ensure a solid fixing point and screw in the two screws. Before tightening the top screws insert the tamper
bracket in the slot provided on the right side of the enclosure.
4. Fix the enclosure securely using the remaining mounting holes on the bottom left, right and centre of the
enclosure.
5. Insert the PCB in to the enclosure and mount using the plastic standoffs inserted during step one.
i
Install the enclosure when the circuit board is NOT installed on the plastic stand-offs. This will reduce
the risk of damage caused by debris during the installation process.

PRT-RDE2-PCB Protege Ethernet 2 Reader Expander Installation Manual | June 2017 7
2.3 Cabinet Tamper Switch
The enclosure tamper input signals to the monitoring station or remote computer that the Reader Expander
enclosure has been opened. The tamper input switch shall be mounted into the steel bracket provided and
connected to the tamper connection terminals as shown in the diagram below. The tamper input opens and
closes trouble zone RDxxx:01 on the Reader Expander.
Bracket
Tamper Switch
AC AC ST TP TP
Tamper Input Connection
2.4 Earth Ground Connection
The Reader Expander has a connection for earth ground. For best results a cold water pipe should be used with
a pipe wiring clamp. If a cold water pipe is not available, connect to a suitable ground connection in the
installation. A minimum 14AWG solid copper wire shall be used from the Reader Expander's earth connection
point to the clamp on the cold water pipe. If other earth clamps are present at the same connection point
connect the clamp below the existing units.
To other earth connecons already
aached to the earth peg or water
pipe
Cold water pipe grounding earth
peg grounding rod
AC AC ST TP TP
Main Earth Ground Connections

8PRT-RDE2-PCB Protege Ethernet 2 Reader Expander Installation Manual | June 2017
2.5 AC Power
The Protege PGM Expander should be supplied by a dedicated electrical power source rated for a minimum
10Amp Load and have a dedicated circuit breaker. Do not use a switch controlled breaker or a switched
electrical point to supply electrical power. Connect the primary of a 16.5VAC, 50/60Hz, 40VA Transformer to
the electrical circuit and run the secondary to the AC input on the controller terminals.
Transformer
Mains Input
AC AC ST TP TP
AC Transformer 16VAC, 50/60Hz, 40VA MAX
Specific regional regulations may allow the transformer to be mounted inside the enclosure. In this case wire the
electrical circuit to the electrical termination point inside the enclosure and the secondary wires of the
transformer to the AC Input on the controller.
i
Termination of wiring to the PGM Expander while power is applied or the battery is connected may
cause serious damage to the PGM Expander and will VOID ALL WARRANTIES OR GUARANTEES.
Power the PGM Expander ONLY after all wiring, configuration and jumper settings are completed and
verified.
2.6 Backup Battery
It is recommended that a minimum of a 4Ah battery is used as the main backup battery. From the accessory
bag provided, connect the RED and BLACK battery termination wires to the B+ and B- terminals. Connect the
spade terminals to the battery as shown below. Connection of the battery in reverse will not damage the Reader
Expander but will cause the battery fuse (5A Fast Blow) to blow and require replacement.
Gel Cell Backup Baery
+
-
AC AC ST TP TP
+_
BATT
Battery Connection

PRT-RDE2-PCB Protege Ethernet 2 Reader Expander Installation Manual | June 2017 9
The battery test procedure uses a special algorithm to prevent deep discharge and increase battery endurance.
A dynamic battery test is performed every ten minutes when AC power is present and a battery condition alarm
will be generated if the battery is either disconnected or shows poor capacity. Battery fault conditions will
activate the battery trouble zone associated with the address assigned to the Reader Expander.
If AC is not present the Protege Reader Expander will monitor the battery for a low voltage level and will activate
the battery trouble zone. The next dynamic battery test will occur 30 minutes after AC power has been restored.
This delay allows the battery to achieve optimal charging during the first 30 minutes when power is initially
restored to the unit. Once the first test is completed the dynamic battery testing will return to 10 minute
intervals.
When power is first applied to the Protege Reader Expander a dynamic battery test will be performed after 30
seconds, this allows the status and condition of the battery to be detected. On completion of this first test the
normal testing period of 10 minutes will be resumed.
2.7 Status Indicator
The status output will activate according to the status indicator on the Protege Reader Expander and can be
used to provide signalling or indication of the Reader Expander status outside the enclosure. The following
diagram shows the connection of an LED indicator to the status output.
1K5 OHM
LED
AC AC ST TP TP
+12V AUX
External Status LED Connection
2.8 Ethernet 10/100 Network Connection
The communication between the PRT-RDE2 and the Protege System Controller can be via a 10/100 Ethernet
network operating the encrypted UDP protocol suite. The IP address of the controller can be configured using
the LCD Keypad Terminal or web interface. The default IP address for the PRT-RDE2 is set to a static IP
address of 192.168.1.3 with a subnet mask of 255.255.255.0, and the default controller IP address the
PRT-RDE2 will try to communicate on is 192.168.1.2.
i
Installing the Protege Reader Expander on an active network requires knowledge of the configuration
and structure for the network. Always consult the network or system administrator and ask them to
provide you with a fixed IP address that can be assigned to the Protege Reader Expander.

10 PRT-RDE2-PCB Protege Ethernet 2 Reader Expander Installation Manual | June 2017
When installing an Ethernet connection, the Protege Reader Expander should be interfaced using a standard
segment (<100M in length) and should be connected to a suitable Ethernet hub or switch.
Ethernet 10/100 Switch Hub Connection
Temporary direct connections can be used for onsite programming by using a standard Ethernet crossover
cable.
Ethernet 10/100 Direct Connection
2.9 Encrypted Module Network
The Protege Reader Expander incorporates encrypted RS-485 communications technology. The isolated
communications interface offers full galvanic isolation to prevent ground loop noise and cross phase ground
differential between network devices.
NAN+ N- NB
Network communicaons input
from the Protege Integrated
System Controller or previous
Protege module
Standard Communication Connection

PRT-RDE2-PCB Protege Ethernet 2 Reader Expander Installation Manual | June 2017 11
Connection of the communications should be performed according to the diagram shown above. It is important
that the N+ Network Communications Power be supplied from an independent battery backed power supply
unit or a networked module capable of supplying the required voltage to all devices on the RS485 network.
Always connect the Reader Expanders NA and NB terminals to the NA and NB terminals of the communication
network. The N+ and N- must go to a 12V power supply source as shown in the following diagram and
connected at ONLY one +12V power source.
NAN+ N- NB
NAN+ N- NB
NAN+ N- NB
+AUX- Z1 COM COMZ2 Z3 Z4
Protege Integrated System
Controller or module supplying
power to networked devices
AUX power from Module or
external power supply
Next modules
on network
Network Power Supplied By Network Module
Warning: The 12V N+ and N- Communication input must be supplied from only ONE point.
Connections from more than one 12V supply may cause failure or damage to the Reader Expander or
device supplying network power.
i
The EOL (End Of Line) jumper setting MUST be set in the ON position for the LAST module on the
RS485 network. EOL is ON when the jumper is closest to the EOL text.

12 PRT-RDE2-PCB Protege Ethernet 2 Reader Expander Installation Manual | June 2017
2.10 Slave Device Network
The Protege Reader Expander incorporates a secondary encrypted RS-485 communication interface that can
be used to expand the functionality of the Reader Expander for the purpose of High Rise Elevator Control. A
floor control module PRT-PX16 Protege 16 PGM Expander, set as a floor control device, is attached to the
slave communication interface.
Connection of the communications shall be performed according to the following diagram. It is important that
the S+ Slave Communications Power be supplied from an independent battery backed power supply unit or a
module connected to the slave communication interface capable of supplying the required voltage to all devices
on the slave RS485 network.
SAS+ S- SB
Slave Communications Connection
Always connect the Reader Expanders SA and SB terminals to the SA and SB terminals of the slave devices.
The S+ and S- must go to a 12V power supply source as shown in the following diagram.
SAS+ S- SB
NAN+ N- NB
NAN+ N- NB
+AUX- Z13 COM COMZ14 Z15 Z16
AUX Power from Module or
external power supply
Slave devices connected to the Reader Expander Slave
interface use their N+, N-, NA, NB terminals
Reader Expander
Slave Network
Slave Power Supplied by Module
The above diagram shows a power connection taken from the auxiliary power outputs on the Reader
Expander's zone terminals. This connection is suitable for smaller systems provided that the:
Maximum total output current,
AUX DC output current,
B1/B2 DC output current, and
Total combined current
are ALL lower or equal to the values outlined in the Technical Specifications section. If these currents are
exceeded, a separate power supply shall be used.

PRT-RDE2-PCB Protege Ethernet 2 Reader Expander Installation Manual | June 2017 13
UL
ULC
If an external power supply is required, a UL 603 or UL 294 listed power-limited power supply must be
used to comply with UL installation standards, and a CAN/ULC-S318 or CAN/ULC-S319 listed
power-limited power supply must be used to comply with ULC installation standards.
Warning: The 12V S+ and S- Communication input must be supplied from only ONE point.
Connections from more than one 12V supply may cause failure or damage to the Reader Expander or
device supplying slave communication power.
The recommended module network wiring specifications are:
CAT5e / CAT6 are also supported for data transmission when using ground in the same cable.
24AWG twisted pair with characteristic impedance of 120ohm
Belden 9842 or equivalent.
Maximum total length of cable is max 900m (3000ft)
Warning: Unused wires in the cable must not be used to carry power to other devices.
Shielded Cables
Shielded cables can be used in noisy environments (with RF and electromagnetic interference).
If a shielded cable is used, the shield must be connected at only one end of the cable. DO NOT connect a
shield at both ends. Refer to the following diagram for the recommended shield connection.
External Power Supply
or AUX Supply Out
NAN+ N- NB NAN+ N- NB NAN+ N- NB
Shield isframe
grounded at
one point
Shieldsare
connected together
and Isolated
Shielded Cable
Product #1 Product #2 Product #3
Shielded Cable
Shield not
connected
Recommended Shield Connection
i
The EOL (End Of Line) jumper setting MUST be set in the ON position for the LAST slave module on
the RS485 network. EOL is ON when the jumper is closest to the EOL text.
EOL OFF EOL ON
EOL Jumper

14 PRT-RDE2-PCB Protege Ethernet 2 Reader Expander Installation Manual | June 2017
2.11 RS-485 Biasing Settings
The Protege Reader Expander has biasing settings for the module network. Biasing can be configured for either
high or low (L indicates a low bias and H indicates high bias configuration). Both jumpers MUST be set to the
same bias type.
i
Biasing shall only be set to LOW on ONE point on any single segment of the RS-485 network. All
other devices on the same segment shall be set to the middle position which is no biasing.
By default, the PRT-CTRL System Controller has the jumpers for the biasing set to low and the
EOL jumper on. This is also the same default configuration for the slave communication port on
the PRT-RDI2 Protege Intelligent Reader Expander.

PRT-RDE2-PCB Protege Ethernet 2 Reader Expander Installation Manual | June 2017 15
3 Communication Setup
Before the Protege Reader Expander can communicate with the Protege System Controller the communications
need to be setup. These settings are available from either a web interface or by using a Protege LCD Keypad.
To program the reader expander using the web interface the IP address must be known.
3.1 Keypad Programming
To setup the basic communication parameters for the Protege Ethernet Reader Expander using a Protege LCD
Keypad (PRT-KLCD) power the Reader Expander up with DIP Switch 8 turned on as shown below.
1
2
3
4
5
6
7
8
OFF ON
ADDRESS 1
ADDRESS 2
ADDRESS 4
ADDRESS 8
ADDRESS 16
ADDRESS 32
ADDRESS 64
DEFAULT/RUN
DIP Switch Setting for Keypad Configuration
Connect a PRT-KLCD module to the primary RS-485 port (NA and NB) that has a module address of 200 or
greater. Make sure there are no other modules attached to this network, as in this mode the Reader Expander
will simulate a Protege System Controller when in this programming mode.
Once the Keypad has registered with the Reader Expander the following screen will be displayed.
Network Mode
The network mode defines what communication method the Protege Reader Expander will use to communicate
with the Protege System Controller. When Ethernet is selected the primary RS-485 port can be used as a
network repeater and all received Protege communication will be sent to the System Controller of the Ethernet
link.
Network Mode
Ethernet
Use the [1] and [3] keys to scroll the network mode selection and press [ENTER] to select the mode displayed.

16 PRT-RDE2-PCB Protege Ethernet 2 Reader Expander Installation Manual | June 2017
Controller Connection
The controller connection defines how the reader expander finds the Protege System Controller on the network.
This can be done either dynamically where the reader expander will find an available controller to connect to or
statically. When connecting statically the Controller IP Address must be set (see below).
CTRL Connect
Static
Use the [1] and [3] keys to scroll the connection selection and press [ENTER] to select the connection displayed.
i
Do not use a dynamic controller connection when there is more than one controller on the network the
reader expander is being connected to. You cannot guarantee which controller the reader expander
will connect to.
DHCP Configuration
The Reader Expander can use DHCP to obtain an IP address. To use this feature select Enabled.
DHCP Usage
Disabled
Use the [1] and [3] keys to scroll the connection selection and press [ENTER] to select the connection displayed.
Network UDP Port
The Network UDP port defines the port the Reader Expander uses to connect to the Protege System Controller.
This must be set the same as Protege System Controller.
Network UDP
port: 09450
Enter a network UDP port (00000 - 65535).
Module IP Address
The reader expander has a built in TCP/IP Ethernet Device and it must be programmed with a valid TCP/IP
Address to allow it to connect to the system controller. By default the IP address is set to 192.168.1.2.
Programming an IP address requires knowledge of the network and subnet that the system controller will be
connected to. ALWAYS consult the network or system administrator before programming these values.
IP Address
192.168.001.003
To modify the IP address use the decimal entry from (000 to 255), use the keypad as explained in section
Entering Decimal Numbers in the Protege System Controller Reference Manual and press [ENTER].
i
When the Reader Expander is configured with DHCP enabled an IP address does not have to be
entered. Once a DHCP address has been obtained it will be displayed. An IP address of
000.000.000.000 will be shown while the Reader Expander is trying to find a DHCP server.

PRT-RDE2-PCB Protege Ethernet 2 Reader Expander Installation Manual | June 2017 17
Module IP Subnet Mask
In conjunction with the IP Address a netmask must be configured to allow access to the appropriate node on
the subnet. By default this is set to a value of 255.255.255.0.
Programming an IP Netmask requires knowledge of the network and subnet that the system controller will be
connected to. ALWAYS consult the network or system administrator before programming these values.
Subnet
255.255.255.000
To modify the subnet mask use the decimal entry from (000 to 255), use the keypad as explained in section
Entering Decimal Numbers in the Protege System Controller Reference Manual and press [ENTER].
Module IP Gateway
In conjunction with the IP Address a gateway can be configured to allow access to a router for external
communications beyond the subnet to which the reader expander is connected. By default this is set to a value
of 0.0.0.0 to prevent any external communication.
Programming a, IP Gateway requires knowledge of the network and subnet that the system controller will be
connected to. ALWAYS consult the network or system administrator before programming these values.
Gateway
000.000.000.000
To modify the IP gateway use the decimal entry from (000 to 255), use the keypad as explained in section
Entering Decimal Numbers in the Protege System Controller Reference Manual and press [ENTER].
Controller IP Address
If the reader expander has been configured to connect to the Protege System Controller using a static IP
address then this IP address of the Controller must be entered in this field. If a dynamic connection is being
used the controller’s IP address can be confirmed by viewing this field.
Controller IP
192.168.001.002
To modify the IP address use the decimal entry from (000 to 255), use the keypad as explained in section
Entering Decimal Numbers in the Protege System Controller Reference Manual and press [ENTER].
3.2 Web Programming
The Protege Reader Expander can be programmed using an internal web interface. To access this, open a web
browser (such as Internet Explorer or Firefox) and type the IP address of the module into the address bar.
i
When attempting to view the webpage of the Reader Expander from a network that uses a Proxy
Server, ensure the browsers connections options recognise local addresses.

18 PRT-RDE2-PCB Protege Ethernet 2 Reader Expander Installation Manual | June 2017
User Login
To access to the reader expander programming you must login. By default the username is adminand the
password admin. For maximum security, modify the password before competition of the installation.
Web Programming User Login Page
Setup
Once logged in the main page (index.php) will be displayed. Click the Setup link on the menu on the left to
navigate to the setup page (setup.php).
All the options that are available through the keypad can be modified through the web page. Enter the details as
appropriate.
Protege Reader Expander Basic Setup
Network Setup
The IP address, Subnet Mask and Gateway settings can also be programmed through the web pages. Click the
Network link on the menu on the left to access this programming.
The reader expander will need to be restarted for any of these changes to take place.

PRT-RDE2-PCB Protege Ethernet 2 Reader Expander Installation Manual | June 2017 19
Statistics
The statistics web page displays the reader expander's serial number and firmware versions.
Users
To restrict access to the reader expander it is recommended to change the password of the default user.
Select the checkbox of the user to be modified and click the Edit button as shown below. Up to two users can
be programmed.
i
Once setup is complete turn DIP switch 8 off before restarting Reader Expander.
Web page User Programming

20 PRT-RDE2-PCB Protege Ethernet 2 Reader Expander Installation Manual | June 2017
4 Door Access Control
The Reader Expander allows the control of two separate access controlled doors used for entry or exit only, and
a single access controlled door using entry/exit.
4.1 Reader Connection
The Protege Reader Expander allows the connection of 2 reading devices or 4 Wiegand reading devices and
the ability to control 2 doors (Entry or Exit Only) or 1 door (Entry and Exit). The following diagram shows the
connection of standard Wiegand Reader with the Protege Reader Expander controlling an Access Door and
Entry/Exit Door.
+AUX- DO L2D1 L1 BZ
Shield isframe
grounded at
one point
Shielded Cable
RED
BLACK
GREEN
WHITE
ORANGE
BROWN
BLUE
YELLOW
SHIELD
Shield not
connected
Standard Card Reader Connection
The card reader must be connected to the Controller port using a shielded cable. Always refer to the card
reader manufacturer for detailed installation guidelines. The shield connection must only be connected at one
end of the cable in the metallic enclosure(frame grounded). The beeper output on the Controller provides
diagnostic information to the end user and installer when access is denied or the unit is operating offline.
Warning:
Do not connect the shield to a AUX- or 0V connection.
Do not join the shield and black wires at the reading device.
Do not connect the shield to any shield used for isolated communication.
UL
ULC
Compatible access control card reader communication formats are: 26-, 34-, 37-Bit Wiegand,
RS-232, RS-485, and Smart RS-485.
Table of contents
Other ICT Network Hardware manuals