Classic FF - Propane Installation 7
GENERAL
AIR SUPPLY
Detailed recommendations for air supply are given in BS.5440:2.
The following notes are for general guidance:
1. It is NOT necessary to have a purpose provided air vent in the
room or internal space in which the boiler is installed.
2. If the boiler is to be installed in a cupboard or compartment,
permanent air vents are required (for cooling purposes) in the
cupboard/compartment, at both high and low levels. The air vents
must either communicate with room/internal space, or be direct
to outside air. The minimum effective areas of the permanent
air vents, required in the cupboard/compartment, are specified
as follows and are related to maximum rated heat input.
3. Both air vents MUST communicate with the same room or
internal space or MUST be on the same wall to outside air.
4. In siting the air vents care must be taken to avoid the freezing of
pipework.
Refer to Table 4 for details of air vent position and sizing.
Table 4 - High and low vent areas
Boiler Air from room/internal Air direct
space cm2(in2) outside cm2(in2)
FF 250 P 170 (26) 83 (13)
FF 260 P 198 (31) 102 (16)
FF 275 P 264 (41) 132 (21)
WATER TREATMENT
These boilers incorporate a cast iron heat exchanger. As part of
the installation the central heating system should be thoroughly
flushed with appropriate water treatment in order to comply with
BS7593:1992.
Caradon Plumbing Ltd recommend the use of Fernox or Betz
Dearborn water treatment products which must be used in
accordance with the manufacturers instructions. For further
information contact :-
Fernox Manufacturing. Co. Ltd, Tandem House, Marlowe Way,
Croydon, Surrey CRO 4XS, tel 0870 5601 5000 or
Betz Dearborn Ltd, Widnes, Cheshire, tel. 0151 424 5351
Important: Any other treatment for this product will render the
guarantee of Caradon Plumbing Ltd INVALID.
Notes.
1. If an inhibitor is used, and in hard water areas where
treatment to prevent lime deposits is necessary, it is most
important that the water treatment MUST be maintained at the
correct concentrations recommended by the treatment
manufacturer.
2. Artificially softened water must not be used in the system,
under any circumstances.
THERMOSTATIC RADIATOR VALVES
Caradon Plumbing Limited recommend that heating systems
utilising full thermostatic radiator valve control of temperature in
individual rooms should also be fitted with a room thermostat
controlling the temperature in a space served by radiators not
fitted with such a valve as stated in BS. 5449.
When thermostatic radiator valves are used, the space heating
temperature control over a living / dining area or hallway having a
heating requirement of at least 10% of the boiler heat output
should be achieved using a room thermostat, whilst other rooms
are individually controlled by thermostatic radiator valves.
However, if the system employs thermostatic radiator valves on
all radiators or two port valves without end switches then a
bypass must be fitted to ensure a flow of water should all valves
be in the closed position.
ELECTRICAL SUPPLY
WARNING. The appliance MUST be efficiently earthed.
Wiring external to the appliance MUST be in accordance with the
current I.E.E. (BS 7671) Wiring Regulations and any local
regulations which apply.
The point of connection to the mains should be readily accessible
and adjacent to the boiler, except that for bathroom installations;
the point of connection to the mains MUST be situated outside of
the bathroom.
Note. Where a room sealed appliance is installed in a room
containing a bath or shower then the appliance and any electrical
switch or appliance control utilising mains electricity should be so
situated that it cannot be touched by a person using the bath or
shower.
WATER CIRCULATION SYSTEM
The boiler must NOT be used for direct hot water supply. For the
types of system and correct piping procedure refer to 'Introduction'
and Frame 1.
The central heating system should be in accordance with BS. 6798
and, in addition, for Smallbore and Microbore systems, BS. 5449.
The domestic hot water system, if applicable, should be in
accordance with the relevant recommendations of BS. 5546. Copper
tubing to BS. 2871:1 is recommended for water carrying pipework.
The hot water storage cylinder MUST be of the indirect type and
should preferably be manufactured of copper.
Single feed, indirect cylinders are not recommended and MUST
NOT be used on sealed systems.
The appliances are NOT suitable for gravity central heating, nor
are they suitable for the provision of gravity domestic hot water.
The hot water cylinder and ancillary pipework, not forming part of
the useful heating surface, should be lagged to prevent heat loss
and any possible freezing - particularly where pipes run through
roof spaces and ventilated under floor spaces.
The boiler must be vented (not on sealed system).
IMPORTANT
Draining taps MUST be located in accessible positions, which
permit the draining of the whole system - including the boiler and
hot water storage vessel. They should be at least 1/2" BSP
nominal size and be in accordance with BS. 2879.
The boiler is fitted with a special drain plug which is provided to
drain the BOILER ONLY in the event of the system drain plug
being unable to do so. The hydraulic resistances of the boilers, at
MAXIMUM OUTPUT with an 11oC (20OF) temperature differential,
are shown in Table 5.
Maximum boiler operating temperature should be 82 oC (180 oF).
Table 5 - Water flow rate and pressure loss
Boiler Size FF 250 P FF 260 P FF 275 P
Boiler kW 14.7 16.7 21.4
Output Btu/h 50 000 57 000 73 000
Water Flow l/min 19.0 22.8 30.3
Rate gal/h 250 300 400
Pressure mbar 31.5 41.7 77.0
Loss in w.g. 12.6 16.7 30.9