Imac NGS 1000 Guide

INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS FOR
NGS 1000 NATURAL GAS SCRUBBERS
10 AND 25 SCFM UNITS
Natural Gas Scrubber
Figure 1. NGS 1000
Natural Gas Scrubber
Two sizes available NGS-4 and NGS-12
APPLICATION
Designed specifically for industrial applications with natural gas
supply lines such as:
· Cata-Dyne™ Series MKII, WX, and BX heaters
·Enclosure systems
·Instrument gas pre-heaters
STANDARD PRODUCT FEATURES
· CRN Certified (#0H6573.213) to 250 psi and 200°F
·Two sizes available
SIZE 4, 10 SCFM, ؼ” NPT
SIZE 12, 25 SCFM , Ø ¾” NPT
MOUNTING OPTIONS
With appropriate brackets, the NGS 1000 natural gas scrubber can
be installed in an existing piping system or it can be bolted to a
wall/panel using the factory supplied stainless steel wall mounting
kit.
FEATURES
CRN CERTIFIED #0H6573.213
Max. Pressure = 250 psi
Max. Temperature = 200°F
Min. Temperature = -40°F
Flow Rates: 10 SCFM to 25 SCFM
SAE/ORB o-ring design.
BENEFITS
Extend the life of your Cata-Dyne™ infrared heater if sour gas or
moisture is present.
Low-pressure drop at rated flow.
Table 1. Natural Gas Scrubber, Cartridge, and Mounting Kit Coded Numbering System.
Gas Scrubber Cartridge Mounting Kit
NGSNGS NGC- - -4 4 K
A Leader in Advanced Heating Solutions
NEW
PRODUCT
NGS-12
25 SCFM
NGS-4
10 SCFM
Outlet
Outlet
Inlet
Inlet
10001000
Natural Gas
Scrubber
Natural Gas
Scrubber
Natural Gas
Cartridge
K = Mounting
Kit
4 = 10 SCFM
12 = 25 SCFM
4 = 10 SCFM
12 = 25 SCFM
IMAC Systems, Inc.
90 Main Street, PO Box 1605
Tullytown, PA 19007
1-800-955-4GAS
Phone: (215) 946-2200
Fax: (215) 943-2984

INSTALLATION & MAINTENANCE INSTRUCTIONS
WARNINGS
NGS 1000
Natural Gas Scrubbers
1. Read and follow all instructions contained in this manual before
installing, operating, and maintaining this equipment. Failure to
do so could void the warranty, damage the equipment, or cause
severe injury or death.
2. Relieve all pressure before dismantling unit.
NGC - Cartridges
1. Do not use cartridge if the package has been damaged or seal is
broken.
2. Store cartridges at room temperature in a dry/dark place.
3. Avoid contact with eyes or exposed skin.
4. Contents may be harmful if swallowed or inhaled as dust.
5. Spilled or discarded product should be disposed of in accordance
with all applicable government regulations.
6. Contents may become hot if exposed to water.
HOW TO ORDER
Natural Gas Scrubber cartridge and mounting kit coded numbering system
is presented in Table 1, while the parts list is in Table 2.
INSTRUCTIONS
INSTALLATION PROCEDURE
A. Read and follow all instructions contained in this manual before
installing, operating, and maintaining this equipment. Failure to do so
could void the warranty, damage the equipment, or cause severe injury
or death.
B. Review Figure 2 for NGS 1000 scrubber component nomenclature.
Refer to Figure 3 for mounting dimensions and NGS scrubber general
arrangement. Install scrubber units only in vertical position shown.
C. Install the NGS 1000 scrubber using appropriate mounting hardware.
Optional (factory supplied) universal mounting brackets are available.
D. Relieve and block all pressure before installing, maintaining, or
dismantling the NGS 1000 scrubber.
E. Remove the NGS 1000 scrubber cover (Item 3). Carefully inspect the
spring (item 6), the o-ring (item 8), and the cover/housing threads.
Remove any dirt, contaminants, or residue from the cover/housing
threads prior to final assembly.
F. Read the label on the NGC Natural Gas Cartridge (Item 1) then remove
the cartridge from the factory-sealed bag. Ensure the contents of the
NGC cartridge are never exposed to water.
G. Insert the NGC cartridge (Item 1) into the scrubber housing (Item 2).
To help with this process you may choose to insert a sheet of rolled
paper or transparency into the scrubber housing (Item 2) prior to
inserting the NGC cartridge. Remember to remove the paper or
transparency once the NGC cartridge has been installed.
H. Re-install the NGS cover (Item 3) using a wrench (see Table 3(b) for
hex size) and ensure the cover has completely bottomed out and there
is zero gap between the cover and the housing. CAUTION: DO NOT
OVERTIGHTEN the cover or thread damage may occur. Contact
the factory if threads are damaged, corroded, stripped, or galled.
I. Ensure all fittings are installed and sealed in accordance with the
manufacturer's specifications.
J. Verify that the drain cock (Item 7) is in the fully closed position
(clockwise hand tight) before pressurizing the system.
MAINTENANCE PROCEDURE
I. Refer to Table 4 to determine the suggested change-out
frequency for your Cata-Dyne™ heater application.
II. Relieve and block all pressure before installing, maintaining,
or dismantling the NGS 1000 scrubber.
III. Release and contain any residual water/ contaminates from the
drain bowl by opening the drain cock (Item 7) counterclockwise.
IV. Repeat step E of the Installation Instructions.
V. Remove and properly dispose of used or contaminated cartridges
in accordance with all applicable government regulations.
VI. Repeat steps F through J of the Installation Instructions.
Figure 2. NGS 1000 Gas Scrubber and NGC Cartridge
Table 2. Parts List
A Leader in Advanced Heating Solutions
* ADD SUFFIX-G FOR Ø1/8” NPT GAUGE PORT OPTION
ITEM DESCRIPTION
NGS-4* NGS-12*
1SCRUBBER HOUSING B16135-01 B16138-01
2CARTRIDGE NGC-4 NGC-12
3THREADED COVER B16142-01 B16143-01
4THREADED BASE B16142-02 B16143-02
5BAFFLE A16146-01 A16146-02
6CONICAL SPRING
7DRAIN COCK
8ORING A10069-42 A10069-43
9SNAP RING A16154-01 A16154-02
10 MOUNTING BRACKET
11 LABEL
PART NUMBER
B16158-01
NGS-K
A16150-01
A16149-01

Figure 3. NGS 1000 General Arrangement
WARNING
NGC-12
1-800-661-8529
1-780-468-5904
EDMONTON, AB, CANADA
NATURAL GAS CARTRIDGE
CARTRIDGE NO.
DO NOT USE IF PACKAGE IS DAMAGED OR SEAL IS BROKEN.
STORE AT ROOM TEMPERATURE IN A DRY/DARK PLACE.
CONTENTS MAY BECOME HOT IF EXPOSED TO WATER.
AVOID CONTACT WITH EYES OR EXPOSED SKIN.
CONTENTS MAY BE HARMFUL IF SWALLOWED OR INHALED AS DUST.
SPILLED OR DISCARDED PRODUCT SHOULD BE DISPOSED OF IN ACCORDANCE
WITH ALL APPLICABLE GOVERNMENT REGULATIONS.
When contacting the factory for service, replacement parts, supplies, or technical information, provide the model number of the scrubber and the
cartridge. Typical labels for the scrubbers and cartridges are shown in Figure 4. Also, include the purchase order number, and the date of purchase (if
available).
Figure 4 (b). Typical Gas Cartridge Nameplate
Figure 4 (a). Typical Gas Scrubber Nameplate
A Leader in Advanced Heating Solutions
0H6573.213
BATCH NO.
1234
Table 3. Dimensions & Information
Model # Inlet
Side
A
Overall
Length
B
Overall
Width
C
Port to
Port
D E F G Pipe
Size
Replacement
Cartridge #
Bed
Volume
(in.) (in.) (in.) (in.) (in.) (in.) (in.) (NPT) (Cu. In.)
NGS-4 Right 9” 3-1/4" 4-7/8" 4-1/2" 1-7/16" 5-1/4" 2-1/2" Ø1/4" NGC-4 12.56
NGS-12 Left 12-3/4” 4" 8-1/8" 5-1/4" 3-1/16" 6" 3-1/4" Ø3/4" NGC-12 30.78

CCI Thermal warrants to the purchaser of each new product that any part thereof which proves to be defective in material or workmanship under
normal use within 12 months of the date of shipment will be repaired or replaced without charge. Any such defect should be brought to the attention of
the company's office from which the product was purchased, which is authorized to furnish repair or replacement within the terms of this warranty.
The company will not be responsible for any expenses incurred in installation, removal from service, transportation cost, or for damages of any type
whatsoever, including incidental or consequential damages. Some states or provinces do not allow exclusion or limitation of incidental or consequential
damages, so the preceding exclusion or limitation may not be applicable to you.
Since we cannot anticipate or control the conditions under which our products may be used, we accept no responsibility for the safety and suitability of
our products when used alone or in combination with other products. Tests for safety and suitability of the products should be done by the user.
This warranty will not apply if, in the judgment of the company, damage or failure has resulted from accident, alteration, misuse, abuse, or operation on
an incorrect installation. The foregoing is in lieu of other warranties expressed or implied. CCI Thermal Technologies neither assumes nor authorizes
any person to assume for it any other obligation or liability in connection with the said product.
Natural Gas Scrubbers are not guaranteed against damage caused by corrosion.
WARRANTY
Table 4 shows cartridge change-out frequencies in days for each model
heater and gas scrubber for H S and moisture.
2
To determine the cartridge change-out frequency in days for other H S or
2
moisture concentrations, use the formulas provided in the following
examples:
Example 1: Sour Gas H S
2
Your installation has a Cata-Dyne™ heater, model
WX 12 x 24, 8,000 BTU/hr (2.343 kW/hr) natural gas using a model NGC-
4 cartridge.
·The concentration of H S in your gas supply is 25 ppm.
2
·The change-out frequency for 10 ppm is 87 days (derived from
Table 4).
·COF = 87 days x 10ppm / 25 ppm = 34.8 days.
·The NGC-4 scrubber cartridge should be changed once every
35 days.
Example 2: Moisture
Your installation has a Cata-Dyne™ heater, model
WX 12 x 24, 8,000 BTU/hr (2.343 kW/hr) natural gas using a model NGC-
4 cartridge.
·The concentration of moisture in your gas supply is 25 ppm.
·The change-out frequency for 50 ppm is 69 days (derived from
Table 4).
·COF = 69 days x 50 ppm / 25 ppm = 138 days.
·The NGC-4 scrubber cartridge should be changed once every
138 days.
Change-out Moisture in Gas Supply
# DAYS
(Table 3) X[]
Frequency =
50 ppm
H S in Gas Supply
[
X
# DAYS
(Table 3)
Change-out
Frequency =]
10 ppm
2
CHANGE-OUT FREQUENCY
Printed in Canada
M20412-008
A Leader in Advanced Heating Solutions
WX Series Rating NGC-4 NGC-12 NGC-4 NGC-12
Heater (Btu/hr) Days Days Days Days
6 x 6 1,000 696 936 552 752
6 x 12 2,000 348 468 276 376
6 x 24 4,000 174 234 138 188
8 x 8 2,333 298 401 237 322
10 x 12 3,333 209 281 166 226
12 x 12 4,000 174 234 138 188
12 x 24 8,000 87 117 69 94
12 x 36 12,000 58 78 46 63
12 x 48 16,000 44 59 35 47
12 x 60 20,000 35 47 28 38
12 x 72 24,000 29 39 23 31
18 x 24 12,000 58 78 46 63
18 x 36 18,000 39 52 31 42
18 x 48 24,000 29 39 23 31
18 x 60 30,000 23 31 18 25
18 x 72 36,000 19 26 15 21
24 x 24 16,000 44 59 35 47
24 x 30 20,000 35 47 28 38
24 x 36 24,000 29 39 23 31
24 x 48 32,000 22 29 17 24
24 x 60 40,000 17 23 14 19
24 x 72 48,000 15 20 12 19
SOUR GAS H2S MOISTURE
(10 ppm) (50 ppm)
Table 4 NGC Cartridge Change Schedule in Days
4
4
Popular Scrubber manuals by other brands

Hakko Electronics
Hakko Electronics FA-430 instruction manual

Cleanfix
Cleanfix MasterCraft RA-300 Safety, operation and maintenance manual

Lamona
Lamona LAM2543 User's installation guide

KENT
KENT C4-100A Maintenance & Repair Manual

Tennant
Tennant 800 Operator's manual

Electrolux
Electrolux EFC 9650 user manual