STV75 ed 01/08 VICTRIX 75
Air-gas adjustments.
Calibration of the total pre-mix combustion system envisages,
whenever there is the need, adjustment of the nominal heat
output and air-gas ratio (o-set).
With the exception of the nominal output adjustment which
must nonetheless be done also during the initial inspection,
the two operations are normally only required after a gas
conversion, after extraordinary maintenance work (replacing
a component part of the air-gas circuit, replacing the integrated
board, etc.) or when the appliance needs recalibrating.
Nominal and minimum heat output regulation
e availability of maximum output is related to the length
of the air inlet and exhaust pipes. If this is extended, we have
a slight reduction in the quantity (ow) of air at the inlet and
consequently, also of burnt gas pressure.
e boiler is factory set for operation with a horizontal con-
centric kit, 80/125 Ø, 0.5 m and consequently the use of ue
accessories with higher or lower head losses requires the control
and, if necessary, adjustment of nominal output in accordance
with the table below.
e operation must be performed in the following way, observ-
ing the values given in the heat output adjustment table:
- start the boiler in the chimneysweep mode simultaneously
pressing the “MODE” and “+” keys for two seconds, the
letter “H” followed by a two-digit number indicating the
primary circuit temperature appears on the display; now
control maximum speed (with the burner on);
- after at least 5 minutes check, modifying if necessary, the
value of parameter No. 22 “Max. fan rpm in central heat-
ing”, after having entered the technician’s code, to obtain the
relative value (fan RPM) for nominal output (see technical
data);
- press the “MODE” and “-” keys simultaneously for two
seconds; this forces the boiler at minimum and the letter
“L” followed by a two-digit number indicating the primary
circuit temperature appears on the display;
- check, modifying if necessary, the value of parameter No.
26 (“Min fan rpm in central heating”) to obtain the relative
value (fan RPM) for nominal output (see technical data).
To exit the chimneysweep function press the “+” and “-”
keys simultaneously for two seconds.
Air-gas ratio adjustment (o-set).
e correct air-gas ratio adjustment (1:1) is factory set and
needs resetting only when carbon dioxide (CO2) values in
the ue do not correspond to optimum values.
For this purpose, during the initial inspection or after
extraordinary maintenance jobs, a ue analysis must be
performed at maximum output and at minimum output
that certies combustion complies with the values indicated
in the following table:
G 31
G 30
G 20
CO2at nominal
output
CO2at minimum
output
8.90 % ± 0.2
11.30 % ± 0.2
9.70 % ± 0.2
9.25 % ± 0.2
12.10 % ± 0.2
10.50 % ± 0.2
To check correctly and if necessary adjust the air-gas ratio,
proceed as follows:
DUNGS GB-GD 057 Gas valve.
Calibrating maximum CO2.
- Switch the boiler on and set to chimneysweep mode by press-
ing and holding the "MODE" and "+" buttons simultane-
ously for two seconds. is forces the boiler to operate at
maximum power and the letter "H" appears on the display,
followed by a two gure number indicating the primary
circuit temperature;
- perform a combustion product sampling by inserting the
test probe as far as it will go;
- check that the measured carbon dioxide (CO2) value matches
the value corresponding to nominal output power in the table
above;
- if the values are incorrect, bring them back to the limits
with the gas valve ow adjustment screw (12).
Turn clockwise to reduce the CO2, turn counterclockwise to
increase it.
G20 G30 G31
Single boiler
Max RPM 5700 Max RPM 5100 Max RPM 5700
Min RPM 1400 Min RPM 1350 Min RPM 1450
Flue manifold kit with ue
adjusting device
Max RPM 5700 Max RPM 5100 Max RPM 5700
Min RPM 1700 Min RPM 1650 Min RPM 1750