Infinite Transtector DCPDU2B Series User manual

Installation Manual
© 2021 Innite Electronics, Inc. Transtector is a registered trademark of Innite Electronics, Inc. | DCPDU2B-M Rev. 1
DCPDU2B Series Power Distribution Units

Installation Manual | DCPDU2B Series Power Distribution Units
2+1 (208) 635-6400 | www.transtector.com
REV DESCRIPTION CHK’d & APPR’d / DATE
1 Production Release DR / 01-29-21
Contents
1.0 INTRODUCTION...............................................................................................................4
2.0 FEATURES........................................................................................................................4
3.0 PRODUCT LINE................................................................................................................5
4.0 SAFETY & INDUSTRY STANDARDS...............................................................................6
5.0 WARRANTY (summary)....................................................................................................6
6.0 DESCRIPTION OF OPERATION......................................................................................7
7.0 SPECIFICATIONS.............................................................................................................8
8.0 FRONT PANEL DESCRIPTION ........................................................................................8
9.0 BACK PANEL DESCRIPTION...........................................................................................9
10.0 UNPACKING AND INSPECTION ....................................................................................13
11.0 INSTALLATION................................................................................................................14
13.0 SETUPAND TESTING....................................................................................................18

3
+1 (208) 635-6400 | www.transtector.com
FIGURES
Figure 1. DCPDU2B DC Power Distribution Panel........................................................................4
Figure 2. Block Diagram..................................................................................................................7
Figure 3. Front Panel View.............................................................................................................8
Figure 4. Back Panel View..............................................................................................................9
Figure 5. Input Bus Bar Detail........................................................................................................9
Figure 6. Output Barrier Strip Detail............................................................................................10
Figure 7. Alarm Connection Detail...............................................................................................11
Figure 8. Form-C Relay Schematic ..............................................................................................11
Figure 9. Chassis Ground Connection..........................................................................................12
Figure 10. Series Connection of Multiple Panels .........................................................................14

Installation Manual | DCPDU2B Series Power Distribution Units
4+1 (208) 635-6400 | www.transtector.com
OPERATING MANUAL
DCPDU2B SERIES DC POWER DISTRIBUTION PANELS
1.0 INTRODUCTION
DCPDU2BSeries circuitbreakerpanels providedistributionand overloadprotectionfor 1to20 circuits
with circuit breakers that can be eld installed/exchanged using a supplied puller tool. The panels
are only two mounting positions (3.5 inches) high.
The panels provide up to 20 breakers single bus 450A or 10A+10B 450A+450A distribution and
alarm capabilities. The A and B sections of the dual-bus panel are fully isolated, can be separately
congured for 24/48 volts and are polarity neutral. Breaker capacities range from 2.5 to 200 amperes.
Breaker alarm is indicated by a dual color LED (green/red) and Form C relay contacts for each bus.
Figure 1. DCPDU2B DC Power Distribution Panel
2.0 FEATURES
48/24V Tapered entry for easy insertion
POLARITY NEUTRAL NO or NC alarm contacts
450A bus bar inputs Alarm LEDs
Single or Dual Feed Power Fail form-C alarm
Rear panel safety cover standard 19” & 23” mounting brackets

5
+1 (208) 635-6400 | www.transtector.com
3.0 PRODUCT LINE
3.1 Congurations
The following table lists the 5 available congurations of the DCPDU2B series.
STANDARD DUAL FEED CONFIGURATIONS
MODEL
NUMBER VOLTS
EACH FEED INPUT
FEEDS MAX. #
BREAKERS AMPS
EACH FEED TOTAL
AMPS
DCPDU2B-D-2X10-450 48/24 - 48/24 2 10 A side
&
10 B side 450 900
OPTIONAL SINGLE FEED CONFIGURATIONS
MODEL
NUMBER VOLTS
EACH FEED INPUT
FEEDS MAX. #
BREAKERS AMPS
EACH FEED TOTAL
AMPS
DCPDU2B-S-X20-450 48/24 1 20 450 450
3.2 Available Breakers1
AMPS PART NUMBER AMPS PART NUMBER
2.5 DCBKR2B-2.5 50 DCBKR2B-50
5 DCBKR2B-5 60 DCBKR2B-60
10 DCBKR2B-10 80 DCBKR2B-80
15 DCBKR2B-15 100 DCBKR2B-100
20 DCBKR2B-20 1252 DCBKR2B-125
25 DCBKR2B-25 1502 DCBKR2B-150
30 DCBKR2B-30 2002 DCBKR2B-200
40 DCBKR2B-40
NOTES:
1. Breakers need to be ordered individually and are shipped separately.
2. Require two positions. Includes paralleling bars to connect output load terminals.
3. Breakers are magnetic-hydraulic plug-in type with auxiliary contacts (Normally Open) and mid-trip
function. Only the following types may be installed.
2.5A to 100A:
CBI D-Frame Series single pole,
D-2A23XANBSXXXXLXB-XXXXXWDVAX2-X
or
Carling C-Series Handle single pole, CT1-B2-14-XXX-A11-MJ
125A to 200A:
CBI D-Frame Series, parallel pole,
D-2A23XBNBSXXXXLAM-XXXXXWDVAX3-X
or
Carling C-Series Handle Parallel pole, CT2-P2-04-XXX-A11-MK

Installation Manual | DCPDU2B Series Power Distribution Units
6+1 (208) 635-6400 | www.transtector.com
4.0 SAFETY & INDUSTRY STANDARDS
4.1 DCPDU2B Series power distribution panels meet the following safety requirements:
STANDARD
UL60950-1, 2nd Edition
CSA22.2 No. 60950-1, 2nd Edition
EN60950-1, 2nd Edition
4.2 DCPDU2B Series power distribution panels are CE marked to indicate conformance
to the European Union’s Low Voltage Directive.
4.3 These Distribution Panels operate at voltages that could potentially be hazardous.
Furthermore, inadvertent short circuiting of the system battery and/or rectier by mis-
connection or other error could be harmful. This product should be handled, tested
and installed only by qualied technical persons who are trained in the use of power
systems and are well aware of the hazards involved.
4.4 When operating this Distribution Panels the chassis ground terminal must be
connected to the system frame ground or other proper safety ground for the protection
of personnel.
4.5 Allconnectionsto theDistributionPanelsshould becarefullychecked forerrorsbefore
applying power to them.
4.6 The internal voltages may be at hazardous potentials. The top cover should not be
removed. There are no user-serviceable components in these units. Removing the
top cover will void the warranty.
5.0 WARRANTY (summary)
DCPDU2B Series power distribution panels are warranted for two (2) years from date of
shipment against defects in material and workmanship. This warranty does not extend
to products which have been opened, altered or repaired by persons other than persons
authorized by the manufacturer or to products which become defective due to acts of God,
negligence or the failure of customer to fully follow instructions with respect to installation,
application or maintenance.
For a complete text of Transtector’s warranty conditions please request a copy from your
local Sales Oce.

7
+1 (208) 635-6400 | www.transtector.com
6.0 DESCRIPTION OF OPERATION
6.1 Power Distribution Circuits. A simplied schematic diagram of the distribution
panels is shown in Figure 2. The battery input to each load connects to a high-current
copper bus bar from which the individual fuses or circuit breakers distribute power to
the loads. The return input connects to a similar bus bar to which the individual loads
terminate. The A and B loads are totally independent and isolated with the exception
of models incorporating the ‘S’ option.
CIRCUIT
BREAKERS
BATT.
BATT.
INPUT
RET.
INPUT
RET.
HI-CURRENT BUS BAR HI-CURRENT BUS BAR
HI-CURRENT BUS BAR HI-CURRENT BUS BAR
LOADS LOADS
1 2 3... N
A SIDE
ALARM
CIRCUITS
B SIDE
ALARM
CIRCUITS
A SIDE B SIDE
-S OPTION
-S OPTION
1 2 3... N
Figure 2. Block Diagram
6.2 Alarm Circuits. The alarm circuits detect a tripped circuit breaker and, in this event,
turn on the red part of the LEDs. The alarm circuits also each drive Form C relay
contacts. If one or more circuits open or if there is an input power failure, the relays
are de-energized and the contacts are used to control external audible or visual alarms.
The A and B alarm circuits are also independent and isolated from each other.
LED & RELAY STATE MEANINGS
LED State Relay State Meaning
Green Energized (N.O. is closed) OK
Red De-energized
(N.O. is open) Breaker Trip
OFF No Input Power

Installation Manual | DCPDU2B Series Power Distribution Units
8+1 (208) 635-6400 | www.transtector.com
7.0 SPECIFICATIONS
The following specications are typical at 25°C unless otherwise noted.
INPUT/OUTPUT
Panel Capacity
@35°C..............................................................................450A per Bus
@40°C..............................................................................400A per Bus
@50°C..............................................................................320A per Bus
@70°C..............................................................................200A per Bus
Conguration ..................................450A Single Bus with 1 to 20 Breakers
900A Dual Bus 1 to 10 Breakers Each Bus
Breaker Capacity 1................................................................. 2.5A to 200A
Voltage 1.....................................................................................21-60VDC
Polarity ............................................Neutral, Positive or Negative Ground
ALARMS
Alarm Indicator ....................................................Dual Color LED Per Bus
LED Status Indication........................................................Green = Normal
Red = CB Trip Alarm
O = No Power
Alarm Relays.............................................. Form C Contacts for each Bus
SAFETY.................... UL60950-1 2nd Ed., CSA22.2 No. 60950-1 2nd Ed.,
EN60950-1 2nd Ed.
ENVIRONMENTAL
Operating Temp. Range ..................................................... -10°C to +70°C
Storage Temp. Range........................................................ -40°C to + 85°C
Humidity........................................................ 0% to 95%, Non-Condensing
PHYSICAL SPECIFICATIONS
Case Material ......................................................................................Steel
Finish............................................................................Powder Coat Black
Case Dimensions, Inches (mm) ........................3.45 H x 17.16 W x 5.98 D
(87.6 x 435.9 x 151.9
Weight (approx.)........................................................... 12.5 lbs. (5.67 kg.)
Rack Mounting...................................................................... 19 or 23 Inch
CONNECTIONS
Input Connections...........................................................................Bus Bar
Output Connections...............................................1/4-20 Stud, 2-hole lugs
Chassis Ground Connection..................................1/4-20 Stud, 2-hole lugs
Alarm Relay Connections...................Spring Clamp Terminals,16-26AWG
Notes:
1. See ordering guide to specify.
8.0 FRONT PANEL DESCRIPTION
The front panel of the DCPDU2B, shown in Figure 3 below, consists of the A and B sides
and a center section. The A and B sides can each accommodate up to 10 eld installed/
replaceable hydraulic magnetic circuit breakers rated from 2.5A to 200A. The center section
has two green/red LEDs, one for the A side (left) and the other for the B side (right). At the
bottom of this center section is a slot for a wallet and designator card. This card permits the
recording of each output circuit by number.
A - ALM B - ALM
123456789 10
A BUS - 450A MAX/100A MAX PER CB
123456789 10
B BUS - 450A MAX/100A MAX PER CB
NO-C-NC NO-C-NC
ALM-B
ALM-A
NO-C-NC NO-C-NC
1098765432 1
0.63
(16.0)
0.76
(19.3)
0.42
(10.7)
0.25
(6.4)
1/4-20 stud
length = 0.50 (12.7),
0.625 (15.88) spacing
1/4-20 stud
length = 0.38 (9.7),
0.625 (15.88) spacing
0.57
(14.5)
0.37
(9.4)
0.90
(22.9)
ø 0.306 (7.8)
0.49 (12.5) x
0.31 (7.9) slot
3.50
(88.9)
1.25
(31.8)
5.98
(151.9)
0.60
(15.2)
17.16
(435.9)
0.76
(19.3)
1.725
(43.82)
0.56
(14.2)
0.21
(5.3)
1.13
(28.7) 0.22
(5.6)
3.45
(87.6)
A - BUS OUTPUT FEEDB - BUS OUTPUT FEED
A - BUS RETURNB - BUS RETURN
B - BUS FEED BREAKERS
A - BUS FEED BREAKERS
Alarm connector
Chassis GND
(1/4-20 THREAD)
A - BUS INPUT
FEED
B - BUS INPUT
FEED
1098765432 1
Shorting Bus (-S Models)
OUTLINE OF SAFETY COVER
(blue dotted line)
4.60
(116.8)
0.625
(15.88)
0.500
(12.70)
0.750
(19.05)
4.642
(117.91)
Figure 3. Front Panel View

9
+1 (208) 635-6400 | www.transtector.com
9.0 BACK PANEL DESCRIPTION
9.1 Back View. Figure 4 shows the back of the DCPDU2B distribution panel. Inputs are
at the left and right ends of the back panel. Side B outputs are at two rows of barrier
terminal strips on the left side, and side A outputs are the same on the right side.
At the center of the back panel are two spring clamp terminal blocks for the Form C
relay contact outputs.
Below these is a chassis ground terminal.
A - ALM B - ALM
123456789 10
A BUS - 450A MAX/100A MAX PER CB
123456789 10
B BUS - 450A MAX/100A MAX PER CB
NO-C-NC NO-C-NC
ALM-B
ALM-A
NO-C-NC NO-C-NC
1098765432 1
0.63
(16.0)
0.76
(19.3)
0.42
(10.7)
0.25
(6.4)
1/4-20 stud
length = 0.50 (12.7),
0.625 (15.88) spacing
1/4-20 stud
length = 0.38 (9.7),
0.625 (15.88) spacing
0.57
(14.5)
0.37
(9.4)
0.90
(22.9)
ø 0.306 (7.8)
0.49 (12.5) x
0.31 (7.9) slot
3.50
(88.9)
1.25
(31.8)
5.98
(151.9)
0.60
(15.2)
17.16
(435.9)
0.76
(19.3)
1.725
(43.82)
0.56
(14.2)
0.21
(5.3)
1.13
(28.7) 0.22
(5.6)
3.45
(87.6)
A - BUS OUTPUT FEEDB - BUS OUTPUT FEED
A - BUS RETURNB - BUS RETURN
B - BUS FEED BREAKERS
A - BUS FEED BREAKERS
Alarm connector
Chassis GND
(1/4-20 THREAD)
A - BUS INPUT
FEED
B - BUS INPUT
FEED
1098765432 1
Shorting Bus (-S Models)
OUTLINE OF SAFETY COVER
(blue dotted line)
4.60
(116.8)
0.625
(15.88)
0.500
(12.70)
0.750
(19.05)
4.642
(117.91)
Figure 4. Back Panel View
9.2 Input Connections. See Figure 5. The DC power inputs to the distribution panel
are made by means of crimp type lugs to two copper bus bars on side A and side B.
The upper bus bar is the battery connection (whether + or -) and the lower bus bar
is the return (whether + or -).
0.37
(9.4)
0.90
(22.9)
ø
0.306 (7.8)
0.49 (12.5) x 0.31 (7.9) slot
0.76
(19.3)
1.12
(28.4)
0.56
(14.2)
1.13
(28.7)
Figure 5. Input Bus Bar Detail

Installation Manual | DCPDU2B Series Power Distribution Units
10 +1 (208) 635-6400 | www.transtector.com
9.3 Recommended Input Cable Sizes and Lugs
The following table details the recommended cable size for various input current.
MAXIMUM
CURRENT CONDUCTOR
SIZE PANDUIT CORP.
PART NUMBER TORQUE
1/4 x 20 BOLT
450A 350KCMIL LCC350-14BW-X 62 in-lbs
400A 300KCMIL LCCX250-14B-X 62 in-lbs
320A 4/0 AWG LCCX4/0-14B-X 62 in-lbs
200A 3/0 AWG LCCX3/0-14B-X 62 in-lbs
150A 1/0 AWG LCCX1/0-14B-X 62 in-lbs
9.4 Output Connections. Output connections for A and B loads are shown in Figure 4.
There are 10 sets of bus bar terminals for each side, Aand B. The connections are
numbered to correspond with the numbers of the front panel breakers. The upper
strip connections are from the battery (FEED) through the breakers; the lower strip
connections are the RETURNS. Side B is on the left and side A on the right when
viewed from the rear.
All connections use 1/4-20 threaded studs and are rated up to 100 amperes. Maximum
wire size is 2 AWG. Transtector recommends using FLEX wire with either Panduit
LCDXN2-14A-E or LCDXN2-14AF-E (90deg angle) lugs. When 125A, 150A or 200A
breakers are installed two positions are utilized. Figure 6 below shows detailed
spacing of the terminals.
A - ALM B - ALM
123456789 10
A BUS - 450A MAX/100A MAX PER CB
123456789 10
B BUS - 450A MAX/100A MAX PER CB
NO-C-NC NO-C-NC
ALM-B
ALM-A
NO-C-NC NO-C-NC
1098765432 1
0.63
(16.0)
0.76
(19.3)
0.42
(10.7)
0.25
(6.4)
1/4-20 stud
length = 0.50 (12.7),
0.625 (15.88) spacing
1/4-20 stud
length = 0.38 (9.7),
0.625 (15.88) spacing
0.57
(14.5)
0.37
(9.4)
0.90
(22.9)
ø 0.306 (7.8)
0.49 (12.5) x
0.31 (7.9) slot
3.50
(88.9)
1.25
(31.8)
5.98
(151.9)
0.60
(15.2)
17.16
(435.9)
0.76
(19.3)
1.725
(43.82)
0.56
(14.2)
0.21
(5.3)
1.13
(28.7) 0.22
(5.6)
3.45
(87.6)
A - BUS OUTPUT FEEDB - BUS OUTPUT FEED
A - BUS RETURNB - BUS RETURN
B - BUS FEED BREAKERS
A - BUS FEED BREAKERS
Alarm connector
Chassis GND
(1/4-20 THREAD)
A - BUS INPUT
FEED
B - BUS INPUT
FEED
1098765432 1
Shorting Bus (-S Models)
OUTLINE OF SAFETY COVER
(blue dotted line)
4.60
(116.8)
0.625
(15.88)
0.500
(12.70)
0.750
(19.05)
4.642
(117.91)
Figure 6. Output Barrier Strip Detail
The following table lists a range of cable sizes with matching lugs that will t the output
terminals. The indicated current rating is the maximum assuming that the cables are
bundled/conned.

11
+1 (208) 635-6400 | www.transtector.com
MAXIMUM
CURRENT CONDUCTOR
SIZE PANDUIT CORP.
PART NUMBER TORQUE
1/4 x 20 BOLT
200A (2 pos) 3/0 AWG LCDX3/0-14A-X 62 in-lbs
150A (2 pos) 1/0 AWG LCDX1/0-14A-X 62 in-lbs
125A (2 pos) 1 AWG LCDX1-14A-X 62 in-lbs
100A (1 pos) 2 AWG LCDXN2-14A-E 62 in-lbs
80A (1 pos) 4 AWG LCDX4-14A-L 62 in-lbs
60A (1 pos) 6 AWG LCDX6-14A-L 62 in-lbs
50A (1 pos) 8 AWG LCDX8-14A-L 62 in-lbs
9.5 Form C Relay Contact Outputs. The center of the back panel has connections to
the Form C relay contact outputs for connection to external audible or visual alarm
circuits. See Figure 7 below.
ALM-B
ALM-A
NO-C-NC NO-C-NC
Figure 7. Alarm Connection Detail
Connection is made via two Phoenix Contact spring clamp terminal blocks. J3 is for
the Form C relay contact of side B and J4 is for the Form C relay contact of side B.
Terminals 1, 2 and 3 viewed from left to right are the normally open (NO) common
(C) and normally closed (NC) contacts, respectively. See gure 8 below.
“Normally Closed” and “Normally Open” are dened with the distribution panel powered
and providing power to all outputs, i.e., no circuit breakers tripped.
The ratings of the relay contacts are 0.6A at 125VAC or 2A at 30VDC. The spring
clamp terminals accept wire sizes nos. 16 to 26 AWG.
When the input power is connected to a side (A or B), the Form C relay of that side
is energized. If there is either loss of input power, one or more circuit breakers trip or
the relay is de-energized, the normally open contacts close and the normally closed
contacts open. See gure 8 below.
RELAY
C
ONTACTS
OUTPUTS
NC
C
NO
Figure 8. Form-C Relay Schematic

Installation Manual | DCPDU2B Series Power Distribution Units
12 +1 (208) 635-6400 | www.transtector.com
9.6 Chassis Ground Connection. Thisis locatedonthe leftsideof thechassis asshown
in gure 9 below and is a pair of 1/4-20 bolts.
A - ALM B - ALM
123456789 10
A BUS - 450A MAX/100A MAX PER CB
123456789 10
B BUS - 450A MAX/100A MAX PER CB
NO-C-NC NO-C-NC
ALM-B
ALM-A
NO-C-NC NO-C-NC
1098765432 1
0.63
(16.0)
0.76
(19.3)
0.42
(10.7)
0.25
(6.4)
1/4-20 stud
length = 0.50 (12.7),
0.625 (15.88) spacing
1/4-20 stud
length = 0.38 (9.7),
0.625 (15.88) spacing
0.57
(14.5)
0.37
(9.4)
0.90
(22.9)
ø 0.306 (7.8)
0.49 (12.5) x
0.31 (7.9) slot
3.50
(88.9)
1.25
(31.8)
5.98
(151.9)
0.60
(15.2)
17.16
(435.9)
0.76
(19.3)
1.725
(43.82)
0.56
(14.2)
0.21
(5.3)
1.13
(28.7) 0.22
(5.6)
3.45
(87.6)
A - BUS OUTPUT FEEDB - BUS OUTPUT FEED
A - BUS RETURNB - BUS RETURN
B - BUS FEED BREAKERS
A - BUS FEED BREAKERS
Alarm connector
Chassis GND
(1/4-20 THREAD)
A - BUS INPUT
FEED
B - BUS INPUT
FEED
1098765432 1
Shorting Bus (-S Models)
OUTLINE OF SAFETY COVER
(blue dotted line)
4.60
(116.8)
0.625
(15.88)
0.500
(12.70)
0.750
(19.05)
4.642
(117.91)
Figure 9. Chassis Ground Connection
The recommended cable size for this connection is 2/0 AWG terminated with a Panduit
LCDN2/0-14A-X or equivalent lug. Torque bolts to 62 in-lbs.
NOTE THAT IT IS ESSENTIAL THAT THIS TERMINAL IS CONNECTED TO THE
SYSTEM FRAME GROUND TO ENSURE SAFE OPERATION.
retaining screws
extraction tab

13
+1 (208) 635-6400 | www.transtector.com
10.0 UNPACKING AND INSPECTION
10.1 This DCPDU2B Series power distribution panel was carefully tested, inspected and
packaged for shipment from our factory. The unit and circuit breakers are shipped
separately. Upon receipt of the unit it should be carefully unpacked and inspected
for any damage in shipment.
10.2 If there is evidence of damage, do not attempt to test the unit. The freight carrier
should be notied immediately and a claim for the cost of the rectier system should
be led with the carrier for direct reimbursement. Be sure to include the model and
serial number of the damaged unit in all correspondence with the freight carrier. Also
save the shipping carton and packing material as evidence of damage for the freight
carrier’s inspection.
10.3 Transtector will cooperate fully in case of any shipping damage investigation.
10.4 Always save the packing materials for later use in shipping the unit. Never ship the
unit without proper packing.

Installation Manual | DCPDU2B Series Power Distribution Units
14 +1 (208) 635-6400 | www.transtector.com
11.0INSTALLATION
11.1 Mounting. This distribution panel can be mounted in either 19- or 23-inch racks by
using the supplied reversible brackets. Mount it from the front of the rack using the
correct osets to align with existing rack-mounted equipment. The bracket osets
are every quarter inch from front to back.
A minimum air clearance of 1.5” above and below the unit must be maintained after
installation in the rack. Care should be taken not to compromise the stability of the
rack by the installation of this unit.
11.2 Connections. Input connections should be made with two-terminal crimp type lugs.
See Sections 9.2 and 9.3.
Connection to Supply
a) Connect to a reliably grounded 24VDC to 48VDC SELV source.
b) The branch circuit over-current protection shall be sized appropriate to the input
current and shall not exceed 600A.
c) Use minimum 350Kmcm copper conductors for max. rated input current.
d) A readily accessible disconnect device that is suitably approved and rated is
recommended to be incorporated in the eld wiring.
e) To be installed in a Restricted Access Location.
NOTE: Single feed models have both left and right side input bus bars tted. It is
only necessary to connect the input feed to one side for correct operation.
The unused side is directly connected to the live input feed and can be used for
supplying additional panels. See gure 10 below.
CAUTION: The total load must not exceed 450A on any one pair of bus bars in the
chain.
450A MAX. FEED
RETURN
Figure 10. Series Connection of Multiple Panels
Output connections are made to individual output bus bars and common return. See
Section 9.4 and Figure 6.

15
+1 (208) 635-6400 | www.transtector.com
The Form C relay contact output connections are made to the spring clamp terminal
blocks. See Section 9.5. The chassis ground connection is made to the 1/4-20 studs.
See Section 9.6. This safety ground connection should be made before operating
the panel.
11.3 Checking Connections. Carefully check the polarity of input connections to the
distribution panel and output connections to the load before operating the panel.
Reverse connections will not harm the distribution panel which is POLARITY
NEUTRAL but may cause serious harm to the load. Check to make sure that the
chassis safety ground connection is made. Make sure that all connections are clean
and secure to minimize contact resistance.
11.4 Rear Safety Cover. Once all of the above have been completed, t the clear plastic
safety cover to the back of the unit using the supplied mounting studs and screws.
Instruction for tting the mounting studs the panel are included in the accessory kit.

Installation Manual | DCPDU2B Series Power Distribution Units
16 +1 (208) 635-6400 | www.transtector.com
12.0 INSTALLING CIRCUIT BREAKERS
The DCPDU2B Series employs pluggable circuit breakers that can be easily installed, removed
or replaced using the supplied puller tools. This operation is carried out without the need to
dismount the unit from it’s installation.
Installation,removal or replacement of acircuit breakerand connectionor disconnection ofa
load circuit should be carried out only by only by qualied technical persons who are trained
in the use of power systems and are well aware of the hazards involved.
Although it may be necessary on some occasions to carry out this operation while power
remains applied to the panel, it is always preferable to switch o the power if possible before
proceeding.
12.1 Removing the cover plate. To remove the cover plate undo the two knurled retaining
screws at the left and right side of the unit and pull forward.
12.2 Removing a breaker or blanking panel. To remove a breaker pull the toggle switch
handle using the supplied puller tool until the breaker comes free. To remove a
blanking panel lever it out at the top or bottom using a at bladed screwdriver.
12.3 Installing a breaker or blank panel. To insert a breaker carefully push the breaker
rmly into the socket and make sure that it is fully seated. To t a blanking panel use
the two supplied retaining screws to t it into position.
Repeat the above procedure from 12.2 to 12.3 for all positions and then replace the
cover plate.
12.4 Conditions for breaker positioning. For thermal reasons, when operating the panel
continuously at the current ratings stated in note (2) on page 15, the circuit breaker
current shall not exceed the continuous rating as dened in the table.
Adjoining gaps on each side of the circuit breaker must be provided for current ratings
70A to 200A. None are required for 2.5A to 60A.
Circuit Breaker Gap Requirements
CB Current
Rating Number
Poles Max. Continuous
Load Adjoining Gap
(each side)
2.5A to 60A 1 80% of CB rating
(70% @ 70°C) NO
70A to 100A 1 75% of CB rating
(50% @ 70°C) YES
125A to 200A 2 62.5% of CB rating
(37.5% @ 70°C) YES

17
+1 (208) 635-6400 | www.transtector.com
The above table is based on the following:
1) Use of Carling (C Series) breakers or CBI (D Frame) breakers. Breakers in these
series are equivalent in t, form, and function and can be used interchangeably
within the same system.
2) The DCPDU2B panel is rated for continuous operation at a maximum input of
450A per side @ 35C max., 400A per side @ 40C max., 320A per side @ 50C
max., and 200A per side @ 70C max.
12.5 Connecting or disconnecting load circuits. In cases where a breaker has been
installed follow the instructions in section 9.4 to connect the new output wiring. Ensure
that the breaker is in the OFF position until all connections have been made and
thoroughly checked.
Remember that if any 125A, 150A or 200A breakers have been tted these will require
that the supplied link bar is tted across the associated output bus bars.
Note that if power remains applied to the panel during breaker installation the
alarm LED will show red and the alarm relay will be activated until the new
cables have been connected and the breaker set to the ON position.

Installation Manual | DCPDU2B Series Power Distribution Units
18 +1 (208) 635-6400 | www.transtector.com
13.0SETUP AND TESTING
13.1 It is not necessary to have the distribution panel mounted in a rack for initial testing.
This can be done on a bench. It is also not necessary to have loads connected to
the panel for this testing.
13.2 With the input power source o, connect the input wires to the A side of the distribution
panel. Connect ground to the chassis ground terminal. Set all circuit breakers to on.
13.3 Turn on the input power source. The A side LED should be green. If it is red, one
of the circuit breaker is tripped. If the LED is o, there is no input power to the unit.
Check the output voltage at each set of output terminals with a digital voltmeter.
13.4 With the A side LED green, use an ohmmeter to check the Form C relay contact
outputs. On J4 measure the resistance between pins 1 and 2. This should read
“open”. Measure the resistance between pins 2 and 3. This should read “short”.
13.5 On the A side trip circuit breaker no. 1. The A side LED should turn red. On J4
measure the resistance between pins 1 and 2. This should read “short”. Measure the
resistance between pins 2 and 3. This should read “open”. Reset the circuit breaker.
13.6 On the A side check each succeeding breaker by tripping it, and verify that the LED
turns red. It is not necessary to recheck the Form C relay contacts.
13.7 Repeat the same tests of Sections 13.2 through 13.6 on the B side of the distribution
panel, use J3 to check the Form-C relay operation.
13.8 The distribution panel may now be connected to its intended application.
13.9 If the distribution panel did not operate properly in the above tests, go back and double
check the connections and the polarity of the input source to make sure it is correct.
Please note that there are no user serviceable parts inside either the modules or the
shelves and that opening either will void the warranty.

Installation Manual | DCPDU2B Series Power Distribution Units
19 +1 (208) 635-6400 | www.transtector.com
This document is believed to be correct at time of publication and TRANSTECTOR accepts no responsibility for
consequences from printing errors or inaccuracies. Specications are subject to change without notice.
About Transtector Systems:
Transtector Systems, an Infinite Electronics brand, leads the industry with a comprehensive product
portfolio and specialized expertise in consulting, design and manufacturing of AC, DC, data and signal
surge protection, communications power cabinets, and EMP protection.
Transtector provides valuable end-to-end power and signal integrity solutions for markets that include
telecommunications, medical imaging, transportation, energy, security and the military. Our goal is to
support the urgent surge-protection requirements of our customers with responsive customer service,
technical support and a wide-range of quality AC, DC and data line surge protection products in-stock and
available for same-day shipping.
Contact us at +1 208 635 6400 or online at www.transtector.com.
About Infinite Electronics:
Infinite Electronics is a leading global supplier of electronic components serving the urgent needs of
engineers through a family of highly recognized and trusted brands. Our portfolio brands are specialists
within their respective product set, offering broad inventories of engineering-grade product, paired with
expert technical support and same day shipping. Over 100,000 customers across a diverse set of markets
rely upon Infinite Electronics to stock and reliably ship urgently needed products every day.
Product support can be obtained using the following addresses and telephone numbers.
TRANSTECTOR
10701 N Airport Rd
Hayden, ID 83815
United States
Phone: +1.208.635.6400
Toll Free: 1.800.882.9110
Web site – www.transtector.com
Table of contents
Other Infinite Power Distribution Unit manuals
Popular Power Distribution Unit manuals by other brands

Sonorous
Sonorous Energy Saver-ES-05 operating instructions

Flintec
Flintec KPK-4 Technical manual

environmental potentials
environmental potentials EP-2000 Series Installation and maintenance manual

Godrej
Godrej S.M.A.R.T. Installation and operational manual

Gude
Gude Expert PDU basic 8110 manual

Lanberg
Lanberg PDU 03 Series user manual

Xtreme Power Conversion
Xtreme Power Conversion SPD-0215 User & installation manual

EuroLite
EuroLite SB-4 user manual

Compaq
Compaq 252663-B24 - PDU Power Distribution Strip installation instructions

M-system
M-system M6DBS instruction manual

Omicron
Omicron CMC 850 user manual

Nibe
Nibe ICP 10 Installation and maintenance instructions