intatec Intamix Pro V 61022CPB User manual

Thermostatic Mixing Valves
61022CPB & 61028CPB
Intamix Pro V
Installation and Maintenance Instructions
In this procedure document we have endeavoured to make the
information as accurate as possible.
We cannot accept any responsibility should it be found that in
any respect the information is inaccurate or incomplete or
becomes so as a result of further developments or otherwise.
Intatec Ltd
Airfield Industrial Estate
Hixon
Staffordshire
ST18 0PF
Tel: 01889 272 180
Fax: 01889 272 181
email: [email protected]
web: www.intatec.co.uk
© Intatec Ltd. 2021

© Intatec Ltd 2021 1
Introduction
A thermostatic mixing valve (TMV) is used in domestic hot water systems.
It’s function is to maintain the temperature of the mixed water, supplied to the user, constant at
the set value when there are variations in the supply pressure and temperature of the incoming
hot and cold water or in the flow rate.
The Intamix Pro V TMV has been designed specifically for systems requiring high flow rates,
for example group showing.
Systems of this nature require precise, stable temperature control, especially when there are
variations in the flow rates drawn off by the users.
It is recommended, especially in hard water areas, that a water softener such as the ActivFlo or
ActivFlo lite be fitted to reduce the risk of calcium deposits forming.
Products
Intamix Pro V 22mm with isolating unions 61022CPB
Intamix Pro V 28mm with isolating unions 61028CPB
Technical Data
Temperature range: 30 to 65˚C
Max. working pressure: 14 bar - Static
5 bar - Dynamic
Min. working pressure: 0.2 bar
Max. inlet temperature: 85˚C
Max. inlet ratio (H/C or C/H): 2:1
Min. temperature differential to ensure
failsafe between hot and mixed supplies: 10˚C
Accuracy: ±2%
Minimum flow rate required to maintain
stable temperature: 61022CPB 8.3 l/min
61028CPB 13.0 l/min
Kv value: 61022CPB 4.0 m3/hr
61028CPB 4.5 m3/hr
Connections: 22mm & 28mm compression for copper pipe
Note: Use BS EN 1057 R250 (half hard) copper pipe with compression joints to BS EN 1254-2

© Intatec Ltd 2021 2
Dimensions
Safety
If the thermostatic mixing valve is not installed, commissioned and maintained properly,
according to the instructions contained in this manual, it may not operate correctly and could
endanger the user.
Make sure the connecting pipework to the TMV is not mechanically over-stressed, appropriate
support/fixing should be used. Over time this could cause a fracture, with consequential water
loss which, in turn, could cause harm to property or people.
Water temperatures higher than 50˚C can cause serious scalding.
During installation, commissioning and maintenance take the necessary precautions to
ensure that such temperatures do not endanger people.
In the case of highly aggressive water, arrangements must be made to treat the water
before it enters the thermostatic mixing valve, in accordance with current legislation.
Otherwise, the TMV may become damaged and not operate correctly.
Product Code A B C D E
61022CPB 22 200 300 74 98
61028CPB 28 200 304 74 99
ØA
ØA
B
C
DE
2
MAX
MIN
7
1

© Intatec Ltd 2021 3
Installation
If the thermostatic mixing valve is not installed, commissioned and maintained properly,
according to the instructions contained in this manual, it may not operate correctly and may
endanger the user.
Before installation the system must be thoroughly flushed and checked to ensure that it’s
operating conditions are within the range of the valve; eg the supply temperatures, pressures
and flow rates.
Systems must be flushed to remove any dirt or debris, which may have accumulated during
installation, which may affect its performance and the manufacturer’s product guarantee.
The installation of filters, of appropriate capacity, at the inlet from the mains supply is always
advisable.
In the case of highly aggressive water, arrangements must be made to treat the water
before it enters the thermostatic mixing valve, in accordance with current legislation.
Intamix Pro V TMV must be installed strictly in accordance with the Water Supply (Water Fitting)
Regulations 1999, any local authority regulations and the diagrams in this manual.
They can be installed in any orientation, either vertically or horizontally.
The following are shown on the mixer body:
~ hot water inlet, denoted by the letter ‘H’.
~ cold water inlet, denoted by the letter ‘C’.
It is essential that access to the valve or connections is totally unobstructed for any maintenance
which may be required.
The pipework to or from the valve must not be used to support the valve unless adequately
supported.

© Intatec Ltd 2021 4
Commissioning
After installation, the valve must be tested and commissioned in accordance with the
instructions given below, taking into account current applicable standards and Codes of
Practice.
1. Ensure that the system is clean and free from any dirt or debris before commissioning.
2. It is recommended that the temperature is set using a suitable calibrated digital
thermometer. The valve is commissioned by measuring the temperature of the mixed water
emerging at the point of use.
3. The maximum discharge temperature from the valve must be set to take account of
fluctuations due to simultaneous use.
Allow conditions to stabilise before measuring the temperature and commissioning
4. Adjust the temperature using the adjusting knob on the valve.
5. This valve setting is only applicable to current site conditions at the current location in the
system.
Setting the Temperature
The temperature is set to the required value by means of the adjusting knob with the
graduated scale located at the top of the valve.
1. Using a suitably sized screwdrive unscrew the knob retaining screw.
2. Note the position of the lug on the body and the corresponding recess inside the knob.
Application
Hot Water
Mixed
Water
Cold Water
2
MAX
MIN
7
1

© Intatec Ltd 2021 5
Setting the Temperature Continued
3. Temporarily refit the knob onto the splined section of
the stem and rotate the stem to alter the mixed water
temperature.
To increase the temperature, rotate the spindle
anti-clockwise.
To decrease the temperature, rotate the spindle
clockwise.
4. Allow the outlet temperature to stabilize for 60
seconds and once again take a temperature
reading. Repeat the procedure until the desired
temperature has been reached.
5. Check the circulating water temperature is stable.
Preset Locking
Position the adjusting knob to the temperature required.
Unscrew the retaining screw.
Remove the knob by pulling away from the valve and reposition on the splined shaft so
that the internal slot locates on the position indicator on the knob frame.
Re fit and tighten the retaining screw.
Maintenance
In service, tests should be carried out regularly to monitor the TMV’s performance, as
deterioration could indicate that the valve and/or the system require maintenance.
If during these tests, the temperature of the mixed water has changed significantly when
compared with the previous test, the details given in the Installation and Commissioning
sections should be checked and maintenance carried out.
The following should be checked regularly to ensure that the optimum performance levels of the
valve are maintained.
Every 12 months or more often if necessary.
1. Check and clean the system filters.
2. Check that any non-return valves positioned upstream of the TMV are operating correctly
and free from debris.
3. Limescale can be removed from internal components by immersion in a suitable
de-scaling fluid.
4. When the components have been checked and maintained, the mixed water outlet
temperature should be checked using a thermometer following the procedure detailed in
the Commissioning section.
M
I
N
M
A
X

© Intatec Ltd 2021 6
Problem Solving
The following details are supplied for on site queries, should you require any further assistance
our Technical Department can be contacted directly on 01889 272 199.
1 Hot water at cold outlet
i. Operation of the insert check valves is hindered, check the valve is seated correctly.
ii. Check Valves not fitted.
iii. Unbalanced hot/cold supply pressure.
2Fluctuating mixed water temperature
i. Erratic supply temperatures at the inlets of the valve.
ii. Starvation of the water supplied at the inlets of the valve.
iii. Incorrect commissioning of the valve.
3 Erratic flow
i. Insufficient water supplies.
ii. Fluctuations in the supply pressures/temperatures.
iii. Adverse effect created by other draw off points on the system.
4 No flow/reduced flow from valve
i. In line filters are blocked.
ii. Insufficient supply pressure.
iii. Debris obstructing valve operation.
iv. Valve requires servicing.

© Intatec Ltd 2021
Intatec Ltd
Airfield Industrial Estate
Hixon
Staffordshire
ST18 0PF
Tel: 01889 272 180
Fax: 01889 272 181
email: [email protected]
web: www.intatec.co.uk
E & O.E
26-04-21
Notes
To activate your product warranty please visit
www.intatec.co.uk
and click on Product Registration
Please leave this Manual for the User
This manual suits for next models
1
Table of contents
Popular Plumbing Product manuals by other brands

Hans Grohe
Hans Grohe Vivenis 75445 7 Series Instructions for use/assembly instructions

AbodeFit
AbodeFit Zen Ultimate Far user manual

Helvex
Helvex EP-95 installation guide

Signature Hardware
Signature Hardware PERDITA 948400 manual

Allen + Roth
Allen + Roth WSWS-PB1C manual

Omnires
Omnires Y1244SUGLB Installation and Maintenance