INTRONICS
P/N 170195-000E Rev. 00 3
2.7 KEYBOARD LOCK
To lock/unlock the keyboard is by pressing and at the same time for 3 seconds.
2.8 SENSOR ERROR
qIf the temperature sensor is failed (open or short circuit), the alarm E1 is displayed and the
compressor will be turned on 5 minutes and turned off 5 minutes in sequence.
qIf the defrost sensor is failed (open or short circuit), the alarm E2 is displayed.
2.9 MEMORY
All setting parameters are kept in the non-volatile memory.
3. PROGRAMING
There are 10 programs for parameter setting.
Program Description Range
01 Lowest temperature setting ³–50 °C
02 Highest temperature setting £40 °C
03 Hysterisis temperature setting (Thys)1 –9 °C
04 Defrost cycle time setting 0 –15 hours (0 = not activate)
05 Defrost duration setting 5 –60 minutes
06 Stop-defrost temperature setting 0 –15 °C
07 Fan delay time setting after defrost 0 –10 minutes
08 Compressor delay time 1 –5 minutes
09 Heater installed or
10 Fan mode (Auto or continuous) or
Programing can be done as follows :
a) Press and hold and buttons at the same time for 3 seconds, the display will show ProG,
b) Press button, the display will show Program Number, such as P01,
c) Press or button until the Program Number required is shown,
d) Press button,
e) Press or button for parameter setting,
f) Press button to confirm, the display will show next Program Number,
g) Repeated (c) to (f) for other parameter setting.
Note : If no button is pressed within 10 seconds, it will automatically exit from the programing process.