Isimet FLA Series Installation manual

Application:
The FLA Series Controller operates as a dual output controller to operate fuel gas outlets as well as electrical devices
located within the kitchen in a Fire Station. Input terminals equipped with a delay function will turn OFF all connected
appliances when a notification signal is received for a fire or other emergency response.
ISIMET FLA Series
Fire House Controller
Dual Output Circuit Ver 4.6 pcb
Installation, Operations, Start-up and
Maintenance Instructions
Table of Contents:
Page
Warranty………………………………………………………….. 2
Enclosure Specifications and Dimensions………………………... 3
Model Numbers…………………………………………………… 3
Mounting Instructions (Flush)….………………………………… 4
Mounting Instructions (Casework)..……………………………… 4
Mounting Instructions (Surface Mount)..………………………… 4
Wall Panel Mounting Instructions..………………………………. 4
Wiring Schematics ……………………….………………………. 5
Circuit Board Configurations ……………………….……………. 5
Installing the Electrical Conduit………………………….………. 6
Wiring the Unit……………………………………………………. 6
Output Wiring Configurations.. ………………………………….. 6
Optional Input Connections………………………………………. 6
Operation of Unit…………………………………………………. 7
Equipment Maintenance………………………………………….. 7
March 2014
DOC# 18012

2
ISIMET FLA Series Utility Controller
Installation, Maintenance, Operations, and Startup Instructions
Copyright © 2014 ISIMET, LLC.
All rights reserved.
Patent 6,757,589 B1
6,990,393 B2
This document is copyrighted. This document may not, in whole or part, be copied, duplicated, reproduced,
translated, electronically stored, or reduced to machine readable form without prior written consent from
ISIMET, LLC.
Although the material contained herein has been carefully reviewed, ISIMET, LLC does not warrant it to be
free of errors or omissions. ISIMET reserves the right to make corrections, updates, revisions, or changes to
the information contained herein.
Warranty:
ISIMET will repair or replace any defective parts or workmanship of this product for a period of one
year from date of installation. The P.C. Board has a two year limited warranty. Damage caused by
incorrect installation or improper usage is not warranted. Failure to follow recommended installation,
operation, and/or maintenance procedures listed in this manual may void product warranty. Recovery
rights shall be limited to the total sum of the amounts paid for the product by the purchaser.
EXTENDED WARRANTY:
ISIMET will extend the warranty of this product to a period of two years from date of installation
when installation complies with all start up and routine maintenance procedures and Start up has been
performed by an authorized factory representative. Refer to Extended Warranty Policy.
Limits of Liability:
ISIMET's liability shall be limited to costs of repair or replacement parts. The Laboratory Service
Panel and Utility Controller are not intended for usage other than those expressly described in this
manual. ISIMET shall not be liable for damage or injury caused by the improper use of the product.
ISIMET does not warrant against or assume liability for failure of operation or lack of notification to
secondary integrated monitoring systems. The system should be thoroughly tested and adjustments
made at time of initial operation. Periodic testing should be conducted by the user to assure that all
components function and operate according to specifications.
Care should be taken in the installation of this product. ISIMET shall not be liable for damage or
injury caused from the improper installation of the product.
Warranty is Subject to Compliance with Specific Installation Requirements.
DISCLAIMER OF IMPLIED WARRANTY:
THERE ARE NO WARRANTIES THAT EXTEND BEYOND THE DESCRIPTION HEREIN.
SELLER DISCLAIMS ANY IMPLIED WARRANTY OF MERCHANTABILITY OF THE GOODS
OR OF THE FITNESS OF THE GOODS FOR ANY PURPOSE, AND BUYER AGREES THAT THE
GOODS ARE SOLD “AS IS.”
NOTE: Only qualified craftsmen licensed within the governing jurisdiction to perform the work
associated with this installation should install and/or service this equipment.

3
Specifications:
Control Panel - Stainless Steel 16 gauge
9.875 X 16
9.875 X 18 * where 12 vdc output is provided
Wall Box –16 gauge powder coated sheet metal
6.0 X 12.25 X 4.0
6.0 X 14.25 X4.0 * where 12 vdc output is provided
* all dimensions are in inches
Output Reset Switch: (Where Provided)
Reset Switches are specifically rated to
accommodate output load requirements.
Style: Units are intended for use as a Safety Shut OFF for Kitchens in Fire Stations.
Single Source –Unit provides an Operation Station with control over up to two solenoid valves to operate fuel gas
as well as 120-vac convenience outlets. A single switch controls all output circuits.
All Standard Styles are provided with Panic Button Assembly and Push Button Reset.
A 10 amp, fused, 120 vac circuit is available to operate the wall plug at the gas range
Units may be ordered with Keyed Reset.
Optional Alarm OverRide Switch allows users to Stop an Alarm Signal from turning OFF the Unit.
A Remote Operator can be added in order to control an outdoor gas grill.
3 amp Transformer ratings.
Styles
# Output
Circuits
Panel
Fuse
120 V
Output
Fuse
Pcb
Fuse 1
Relays
Solenoid Outputs
FLA –2XX5
1 @ 120 vac
1 @ 24 vac
15 amp
10 amp
3 amp
10 amp @ 120 vac
2 amp @ 24 vac
2 @ 0.2 amp @ 120 vac
2 @ 1 amp @ 24 vac
FLA –2XX6
1 @ 120 vac
1 @ 24 vac
15 amp
10 amp
3 amp
10 amp @ 120 vac
1.5 amp @ 24 vac
1 @ 1.5 amp @ 120 vac
1 @ 1.5 amp @ 24 vac
Output fuse on PCB, FUSE 1 is Slow Blow. PCB circuit fuse, FUSE 3 is 500 mA Fast Acting
120 V Output fuse is Fast Acting
Transformer Rating –3 amp

4
Mounting Instructions: Flush Wall Mount
Two mounting flanges with screws are provided with the
unit. Attach flanges as shown. Flanges can be affixed to
any two corners of the unit. Then, fasten unit between two
(2) wall studs. The face of the box should be even with the
face of finished wall surface. After mounting unit, protect
interior of box from construction debris.
CAUTION: Provided mounting hardware must be used.
Mounting Instructions: Casework Mount
Two mounting flanges with screws are provided with unit.
Holes are slotted to permit adjustments for variations in
cabinet material thickness. Attach flanges as shown in
figure above. Make cutout in desired location in casework
to permit wall unit to pass easily into opening. From within
the cabinet fit into opening and fasten unit to back of
casework. Face of wall box should be even with face of
cabinet. After mounting unit, protect interior of box from
construction debris.
CAUTION: Provided mounting hardware must be used.
Mounting Instructions: Surface Mount
In order to surface mount the unit, it is necessary to attach
the provided brackets to the rear of the housing. Care should
be taken to verify that the mounting means securely fastens
the unit to the wall surface. A stainless skirt is provided in
order to conceal the wall box from view.
CAUTION: Provided mounting hardware must be used
Mounting the Wall Panel
Verify that Unit is wired with junction box cover in
place.
With the Door open, position the Wall Panel over the
Wall Box as shown.
Holding panel in front of box, affix panel to box using
four (4) 8-32 stainless screws
Close the panel and lock.
CAUTION! Do not install the panel until all wall finishes
are complete.
Wall

5
Alarm Input- JP6
Configuration Jumpers
@ Alarm Input @ CON 4.B
2 jumpers across each pair of posts
= dry-contact input
1 jumper across center two posts
= vdc input
Place Jumper @ JP7
if Alarm Input is
5vdc, Remove if
24vdc or dry-contact
@ Alarm Input
Adjust dial to shorten or lengthen
Alarm Delay Timing.
NOTE:
The PCB may be provided with a microchip processor (not shown).
Do not attempt to remove this processor or it’s adapter PCB.
Where Solenoids are provided
by others or by ISIMET within
a S-Series Enclosure.
24 or 120 vac Solenoids
are provided
by ISIMET
CAUTION:
If Alarm Input is 24vdc or jumpers @ JP6 are
set to “dry-contact”, placing a Jumper
@ JP 7 will cause damage to the pcb.
Circuit Board (pcb)
Configurations
Wiring Schematics
NOTE:
Connect circuit for 120-vac Range outlet
@ Posts 1 and 2 where required by application.

6
Installing the Electrical Conduit:
Knockout holes for connecting the electrical conduits are located at the top left and right of the Wall Box.
Connect rigid conduit for the required 120-vac electrical service.
Connect conduit for the operating power to the upper left top of the enclosure at the junction box.
Connect conduit for the operating power for the output to the upper right top of the enclosure.
Wiring the Unit:
Important!
Verify that the electrical supply is disconnected prior to connecting wiring to the Utility Controller.
To wire the Controller:
1. Remove the junction box cover.
2. Make final connections to the 120-vac electrical service to wiring within the junction box. Verify that
line wiring (Black), neutral (White), and ground wire (Green) are correctly connected. Minimum
recommended wire size is 14 AWG.
3. Replace the junction box cover before activating or testing the unit.
Output Wiring Configurations:
Output Style 5-R: Units are configured to permit two 24-vac and two 120-vac outputs.
Output Style 5: Units are configured to permit one 24-vac and one 120-vac output.
Output Style 6-R: Units are factory configured to permit one 24-vac and one 120-vac output.
Additionally, a single 120-vac output rated at 10 amps for connection of a Gas Range Electric Outlet is
provided. Refer to drawings on page 5 for specifics. Do not attempt to modify the unit to accept other than
voltage outputs as specified for the unit. To replace a PC Board not configured correctly for a specific
application, contact the factory or a local representative.
Backup Battery is intended for use where 12-vdc Latching Solenoids are utilized for fuel gas services.
Optional Input Control circuit:
A 5-vdc or 24-vac/vdc Alarm Input will turn OFF all outputs. An integral timing function permits the user to
set a delay of up to five (5) minutes from time the signal is received until the system is turned OFF. This
feature will avoid cancelled alarms from shut down of the kitchen. Optionally this input may be configured
in order to utilize a dry-contact from the Alarm Signal source. Refer to circuit board configuration on page 5.
Optional Remote Panic Input Connection:
An optional input from an ISIMET Remote Panic Assembly can be connected to the PCB at CON 4-a.
Connection of the Wall Panel Plug:
The Unit is equipped with a 9 pin d-sub connector
Turn counter-clockwise the two retaining clips at the top of the Panel, and open.
Insert plug onto circuit header on PCB.
Turn Power ON.
Close the panel and lock.
CAUTION! Do not install the panel until all wall finishes are complete. Verify that the plug is configured
correctly. Incorrect insertion will prevent operation of unit.
Important!
All local codes must be followed when installing the unit and connected outputs and when connecting
the conduit to the service panel and making wiring connections. Do not install wiring or cable for
integrated systems, remote panic assemblies or other interface wiring within conduit for either 24-vac
control or 120-vac line voltage. Each wiring system including outputs should be housed in independent
conduit and not bundled with wiring for other systems. Failure to comply with these wiring specifics
may create transient voltage at the pc board and cause system malfunction and/or failure. Only
qualified craftsmen licensed within the governing jurisdiction to perform the work associated with this
installation should install and/or service this equipment.

7
Operation of the Unit:
CAUTION: Having outlets such as Gas Outlets Open when Services are activated can result in injury or
death. Verify that these outlets are closed prior to activating the unit.
With the panel service switch ON, press the Service Button. The circuits will activate and the panel Green
LED will illuminate to indicate that the services are active. After turning the switch OFF, it will be necessary
to re-press the Service Button in order to reactivate the services.
After turning the switch OFF, it will be necessary to press the service button in order to reactivate the service.
The Red LED below the switch will illuminate when the services are OFF.
Pressing the panic button will deactivate the services, requiring re-press of the Service Button to again
reactivate service. All Panel lights should illuminate with Panic.
Receipt of an Alarm Signal will deactivate the services. If the Unit is provided with the OverRide Switch
and the Alarm circuit is set for delay response, pressing the OverRide Button will stop the Shutdown of
service. If not, all Panel LEDs will illuminate and all output circuits will turn OFF. If the Alarm Signal is
withdrawn before the time elapses then services will continue to operate once the Service Button is pressed.
If no OverRide Switch is provided, after Alarm Timing elapses all Panel LEDs will illuminate and all output
circuits will turn OFF. If timing is set to “0” this OFF will occur immediately
NOTICE: If OverRide is accomplished, the Service Button should be pressed to cancel OverRide. Where
units are provided with a Key Switch in lieu of the standard Service Button the engaging this switch results in
the same function as the Service Button.
Once in Panic or Alarm Modes the Service Button must be pressed in order to reactivate service. The Alarm
Signal must be withdrawn prior to reactivation.
Equipment Maintenance:
The FLA Series Controller should have semi-annual inspections.
ISIMET recommends that you periodically conduct a brief test of the system to verify that the output
circuit performs as intended.
If examination of the unit indicates tampering, ISIMET recommends that you first review the
installation and wiring portions of this manual prior to placing the unit in service.
ISIMET recommends that when solenoids are operated by the unit, the piping systems be thoroughly
flushed and cleaned and tested for leaks prior to placing the system into use. Periodic testing of these
solenoids will assure that the piping system continues to function properly.
If you have any questions regarding the operation and maintenance of the Utility Controller, please contact
an ISIMET Service Representative.
The enclosure has a NEMA 1 rating. It is not intended for use in wet areas. Exercise caution to prevent
exposure of the interior compartment of the enclosure to moisture. If moisture is present within the
enclosure, ISIMET recommends that the control switch be turned OFF, power be disconnected from the unit
until the source of the moisture is determined, and all moisture is removed from the compartment.
The electronic controller (PCB) is sensitive to dust and other air-borne particles. Do not expose the interior
compartment of the enclosure to dust. During the semi-annual inspection, if dust or other material is present,
ISIMET recommends that you remove all foreign matter before operating the unit.
If the Unit fails to operate, ISIMET recommends that you check the power supply to the unit. With the
control switch in the ON position, pcb LED 1 should illuminate. If not, check the service breaker.
If the fuse is not damaged and the unit still does not function, contact ISIMET or your local Service
Representative.

8
PO Box 129 (Mailing)
103 W. CJ Wise Pkwy
Naples, Texas 75568-0129
Phone (866) 897-0737
Fax (903) 897-0740
www.ISIMET.com
Innovative Systems
Integrating
Mechanical and Electrical
Technology
This manual suits for next models
3
Table of contents
Other Isimet Fire Alarm manuals
Popular Fire Alarm manuals by other brands

Panasonic
Panasonic 6362 quick start guide

System Sensor
System Sensor FL2011EI Quick installation guide

Ampac
Ampac ZoneSenseDH4 Installation, commissioning & operation

Fire-Lite
Fire-Lite LDM-32F instruction manual

Evonicfires
Evonicfires DOUBLE SIDED E810 DS instruction manual

Secutron
Secutron MRM-800MP Series installation instructions