isobus TeeJet IC18 User manual

IC18 SPRAYER/NH3
JOB COMPUTER
OEM MENU SETUP
Software version 1.09

ii www.teejet.com
IC18 Sprayer/NH3 OEM options
Table of Contents
OEM SETUP OPTIONS 1
Sensor Presence ..................................................................................................................................................................................... 3
Flow Sensor...........................................................................................................................................................3
Liquid Pressure Sensor..........................................................................................................................................3
Fill Flow Sensor (Sprayer Mode) ...........................................................................................................................3
Tank Sensor (Sprayer Mode).................................................................................................................................3
Implement Parameters........................................................................................................................................................................ 3
Sprayer Mode ........................................................................................................................................................3
Number of Sections ...............................................................................................................................................3
Circulation (Sprayer Mode)....................................................................................................................................3
Valve Setup .............................................................................................................................................................................................. 4
Regulation Valve Type ...........................................................................................................................................4
Section Valve Behavior..........................................................................................................................................4
Section Valve Type (Sprayer Mode).......................................................................................................................4
Tank Setup................................................................................................................................................................................................ 4
Maximum Content..................................................................................................................................................4
Minimum Content...................................................................................................................................................4
Auto Filling (Sprayer Mode) ...................................................................................................................................4
Auto Filling Offset (Sprayer Mode).........................................................................................................................4
Regulation Details ................................................................................................................................................................................. 5
Minimum Regulation Pressure...............................................................................................................................5
Maximum Regulation Pressure..............................................................................................................................5
Regulation Valve Time ...........................................................................................................................................5
Minimum Regulation Voltage .................................................................................................................................5
Regulation Dead Band...........................................................................................................................................5
Regulation Backlash ..............................................................................................................................................5
Anticipation Factor .................................................................................................................................................5
Default Valve Position............................................................................................................................................5
Regulation Valve Capacity.....................................................................................................................................5
Regulation Start Delay...........................................................................................................................................6
Minimum Speed.....................................................................................................................................................6
Manual Regulation Speed......................................................................................................................................6
Restrictor Plate Flow (Sprayer Mode)....................................................................................................................6
Clear Total Counters.............................................................................................................................................................................. 6
Area .......................................................................................................................................................................6
Volume...................................................................................................................................................................6
Time .......................................................................................................................................................................6
CHANGES ON OPERATION SCREEN 7
LIQUID PRESSURE SENSOR ACTIVATED (NH3 MODE) 7
Operation Mode Overview ................................................................................................................................................................ 7
Section and Icon Descriptions .........................................................................................................................................7
Application Rate Options.................................................................................................................................................................... 8
Target Rate Percentage Increase/Decrease....................................................................................................................8
Target Rate ......................................................................................................................................................................8
With Switchbox ......................................................................................................................................................8
Without Switchbox .................................................................................................................................................8

1
98-05267-EN R3
IC18 Sprayer/NH3 OEM options
OEM SETUP OPTIONS
Main Setup Mode congures the Counters, Job Parameters, Machine, User Interface, Communication and Help options. The
OEM options will dene the options available in the OEM menu.
NOTE: The menu structure on your display might vary from the one displayed in this User Manual depending on the universal
terminal being used.
Figure 1-1: Soft Keys
Home Key
Back One Screen
Up One Selection
Down One Selection
Forward One Screen
MAIN SETUP MODE MENU STRUCTURE
||||||
Counters Job Parameters Machine User Interface Communication Help
Filling
Operation
Implement parameters
Calibrations
Alarm congurations
OEM – Sensor presence
Implement parameters
Valve setup
Tank setup
Regulation details
Clear total counters

2www.teejet.com
IC18 Sprayer/NH3 OEM options
The OEM setup menu is password protected and the settings in this menu are directly related to the tted OEM equipment. Once the OEM
Menu is unlocked, it will remain unlocked until the IC18 is powered off.
To access the OEM screens:
Figure 1-2: Machine to OEM
Figure 1-3: OEM Unlock
1. From the Main Setup Screen , select MACHINE.
2. Select OEM.
3. Select the Access Code Entry Box to the right of the menu option.
4. Use the number pad or slide bar to enter the access code.
5. Select the ACCEPT KEY to complete the unlock process.
6. Select from:
►Sensor presence – used to establish sensors for Flow, Liquid Pressure, Fill
Flow and the Tank
►Implement parameters – used to establish the Sprayer Mode, Number of
Sections and Circulation
►Valve setup – used to establish the Regulation Valve Type, Section Valve
Behavior and Section Valve Type
►Tank setup – used to establish maximum and minimum tank content, Auto
Filling mode and Auto Filling Offset value
►Regulation details – used to adjust the control of the regulation valve
►Clear total counters – used to delete the Total Count system counter for
Area, Volume and Time back to the default settings
NOTE: Settings are NOT automatically saved when selected. The
ACCEPT KEY must be selected to save the setting. Select the
ESCAPE KEY to escape without saving settings and return to
the previous menu. OEM

3
98-05267-EN R3
IC18 Sprayer/NH3 OEM options
Sensor Presence Figure 1-4: Sensor Presence - Sprayer Mode
Figure 1-5: Sensor Presence - NH3 Mode
Figure 1-6: Implement Parameters - Sprayer Mode
Figure 1-7: Implement Parameters - NH3 Mode
Sensor Presence establishes sensors for Flow, Liquid Pressure, Fill Flow and the
Tank. If the tted sensors are not registered here, the sensor options will not be
available in the calibration menus.
Flow Sensor
Flow Sensor sets the associated sensor availability to yes or no.
• To set the Flow Sensor, select an option from the drop down menu or use the
UP/DOWN ARROWS to highlight the option.
Liquid Pressure Sensor
Liquid Pressure Sensor sets the associated sensor availability to yes or no.
• To set the Liquid Pressure Sensor, select an option from the drop down menu
or use the UP/DOWN ARROWS to highlight the option.
Fill Flow Sensor (Sprayer Mode)
Fill Flow Sensor sets the associated sensor availability to yes or no. Available only
in Sprayer Mode.
• To set the Fill Flow Sensor, select an option from the drop down menu or use
the UP/DOWN ARROWS to highlight the option.
Tank Sensor (Sprayer Mode)
Tank Sensor sets the associated sensor availability to yes or no. Available only in
Sprayer Mode.
• To set the Tank Sensor, select an option from the drop down menu or use the
UP/DOWN ARROWS to highlight the option.
Implement Parameters
Implement Parameters establishes the Sprayer Mode, Number of Sections and if
there is tank Circulation.
Sprayer Mode
Sprayer Mode sets the implement parameter to either Crop Sprayer, Turf or NH3.
• To set the Sprayer Mode, select an option from the drop down menu or use
the UP/DOWN ARROWS to highlight the option.
NOTE: When sprayer mode is changed, power must be cycled before all settings
will be displayed correctly.
Number of Sections
Number of Sections establishes how many sections are on the boom.
NOTE: The number established here affects options under Main -> Implement
Parameters -> Section Width -> Boom Section Width and on the
Operations Screen.
• To set the Number of Sections, use the number pad or slide bar.
Circulation (Sprayer Mode)
Circulation sets if there is No, Semi or Full tank circulation. Available only in
Sprayer Mode.
• To set the Circulation, select an option from the drop down menu or use the
UP/DOWN ARROWS to highlight the option.
NOTE: For this option to appear, Sprayer Mode must be set to Crop Sprayer.

4www.teejet.com
IC18 Sprayer/NH3 OEM options
Valve Setup Figure 1-8: Valve Setup - Sprayer Mode
Figure 1-9: Valve Setup - NH3 Mode
Figure 1-10: Tank Setup - Sprayer Mode
Figure 1-11: Tank Setup - NH3 Mode
Valve Setup establishes the Regulation Valve Type, Section Valve Type and
Section Valve Behavior.
Regulation Valve Type
Regulation Valve Type sets the vale type to either Throttle or Bypass.
• To set the Regulation Valve Type, select an option from the drop down menu
or use the UP/DOWN ARROWS to highlight the option.
Section Valve Behavior
Section Valve Behavior sets the valve to either Independent or Follow Master.
• To set the Section Valve Behavior, select an option from the drop down menu
or use the UP/DOWN ARROWS to highlight the option.
Section Valve Type (Sprayer Mode)
Section Valve Type sets the valve type to either 2-way or 3-way. Available only in
Sprayer and Turf Mode.
• To set the Section Valve Type, select an option from the drop down menu or
use the UP/DOWN ARROWS to highlight the option.
Tank Setup
Tank Setup establishes maximum and minimum tank content, Auto Filling mode
and Auto Filling Offset value.
Maximum Content
Maximum Content establishes the maximum tank volume.
• To set the Maximum Content, use the number pad or slide bar.
Minimum Content
Minimum Content establishes the minimum tank volume at which the tank agitation
should automatically be shut off.
• To set the Minimum Content, use the number pad or slide bar.
Auto Filling (Sprayer Mode)
Auto Filling sets the automatic lling mode to either on or off. Available only in
Sprayer Mode.
• To set the Auto Filling mode, select an option from the drop down menu or use
the UP/DOWN ARROWS to highlight the option.
Auto Filling Offset (Sprayer Mode)
Auto Filling Offset establishes the volume that will still run into the tank after the ll
valve has started shutting. Available only in Sprayer and Turf Mode.
• To set the Auto Filling Offset volume, use the number pad or slide bar.

5
98-05267-EN R3
IC18 Sprayer/NH3 OEM options
Regulation Details Figure 1-12: Regulation Details
Regulation Details adjust the control of the regulation valve.
Minimum Regulation Pressure
Minimum Regulation Pressure establishes the minimum pressure. The working
pressure will not drop lower than this level, even if a lower pressure is required
by the regulation system (the controller). If the actual pressure on the sprayer
becomes lower than this value, the regulating system will continue to increase the
pressure until the minimum pressure level has been reached.
• To set the Minimum Regulation Pressure, use the number pad or slide bar.
Maximum Regulation Pressure
Maximum Regulation Pressure establishes the maximum pressure. The working
pressure will not rise higher than this level, even if a higher pressure can be
obtained by the regulation system (the controller). If the actual pressure on the
sprayer becomes higher than this value, the regulating system will continue to
decrease the pressure until the maximum pressure level has been reached.
• To set the Maximum Regulation Pressure, use the number pad or slide bar.
Regulation Valve Time
Regulation Valve Time establishes the time, in seconds, for the regulation valve to
go from fully closed to fully open (or vice versa).
• To set the Regulation Valve Time, use the number pad or slide bar.
NOTE: The time is determined by the type of regulation valve used and should be set to the recommendations included with the regulation
valve.
Minimum Regulation Voltage
Minimum Regulation Voltage establishes the lowest voltage at which the regulation valve will start to move. The controller uses variable
voltage to control the valve; the closer the actual rate is to the target rate, the lower the voltage sent to the valve is. The minimum voltage
must therefore be found when the valve is under pressure, as this affects the force required to move the valve.
• To set the Minimum Regulation Voltage, use the number pad or slide bar.
Regulation Dead Band
Regulation Dead Band establishes an acceptable regulation dead band in percent. Regulation will stop when the difference between the
target rate and the actual rate is lower than the entered dead band (percent of the target rate). This is to prevent the valve from oscillating
when the actual rate is near the target rate.
• To set the Regulation Dead Band, use the number pad or slide bar.
Regulation Backlash
Regulation Backlash establishes the time in seconds it takes before the valve starts moving after a direction change.
• To set the Regulation Backlash, use the number pad or slide bar.
Anticipation Factor
Anticipation Factor establishes the anticipation factor to ensure that the regulation valve is in a suitable position when switching the master
valve on (when turning at headland).
►0 = Off. The regulation valve remains stationary at the position when the main valve is switched off.
►100 = Full. The regulation valve will move completely to the calculated position.
The number of boom sections open, the target rate, the average forward speed, the regulation valve time and the maximum reg. valve
capacity are used to calculate a theoretical position of the regulation valve when the master valve is off (when turning at headland).
• To set the Anticipation Factor, use the number pad or slide bar.
Default Valve Position
Default Valve Position establishes the percentage value for the valve position.
• To set the Default Valve Position, use the number pad or slide bar.
Regulation Valve Capacity
Regulation Valve Capacity establishes the capacity of the regulation valve in volume per minute.
• To set the Regulation Valve Capacity, use the number pad or slide bar.

6www.teejet.com
IC18 Sprayer/NH3 OEM options
Regulation Start Delay
Regulation Start Delay establishes the delay in seconds from when the main valve is switched on until regulation starts.
• To set the Regulation Start Delay, use the number pad or slide bar.
Minimum Speed
Minimum Speed establishes the forward speed at which the system should automatically switch the master valve off.
• To set the Minimum Speed, use the number pad or slide bar.
Manual Regulation Speed
Manual Regulation Speed establishes the percentage of the regulation valve controlling the speed at which the regulation valve should
move in manual operation mode.
• To set the Manual Regulation Speed, use the number pad or slide bar.
Restrictor Plate Flow (Sprayer Mode)
Restrictor Plate Flow establishes the capacity of the restrictor plate in volume per minute and is to be used when working with return ow
(circulation). Available only in Sprayer Mode.
• To set the Restrictor Plate Flow, use the number pad or slide bar.
Clear Total Counters Figure 1-13: Clear Total Counters - Sprayer Mode
Figure 1-14: Clear Total Counters - NH3 Mode
Figure 1-15: Confirm Total Counter Clearance
Clear Total Counters deletes the Total Count system counter for Area, Volume and
Time back to the default settings of "0".
• To clear the total counters, select TRASH CAN KEY . A conrmation
screen will be displayed.
Area
Displays total applied area for all trips.
Volume
Displays total volume of material applied during all trips.
Time
Displays total time traveled for all trips.

7
98-05267-EN R3
IC18 Sprayer/NH3 OEM options
CHANGES ON OPERATION SCREEN
The Operation Screen accesses the working aspects of the IC18 including boom section control, rate control and trip/count/
application information. When OEM options are turned on or off, different Operations screen options become available. This
chapter details these changes.
NOTE: The menu structure on your display might vary from the one displayed in this User Manual depending on the virtual
terminal being used.
LIQUID PRESSURE SENSOR ACTIVATED (NH3 MODE)
The following options will be made available when the Liquid Pressure Sensor is installed and turned on in the OEM setup menu while in
NH3 mode.
Operation Mode Overview
Information on the Operation screen will vary depending on the parameters set by the user and the OEM.
Figure 1-16: Operation Mode Screen Overview
Pressure Range
Target Rate Percentage Increase/Decrease
Target Rate Indicator
Current Pressure Rate
Section and Icon Descriptions
Section or Icon Description
Application Rate Displays the actual application rate per hectare/acre
NOTE: When the Master is “On” the actual application rate per hectare/acre will be displayed. When the
Master is “Off” the target rate is displayed and the TARGET RATE ICON appears
Pressure Range This information section displays the pressure range and the current
working pressure. 2.8
bar
Current Working
Pressure
Displays the current working pressure
NOTE: This pressure range should not exceed
the recommended pressure range.
IMPORTANT! ALWAYS REFER TO THE RECOMMENDED NOZZLE PRESSURE VALUES WHEN
SETTING NOZZLE PRESSURE.
Current Pressure
Rate
Displays the current pressure on the system. 2.8
bar

8www.teejet.com
IC18 Sprayer/NH3 OEM options
Application Rate Options
Target Rate Percentage Increase/Decrease Figure 1-17: Target Rate Percentage Increase/
Decrease
Target Rate Percentage Increase/Decrease Keys increase/decrease the
application target rate per the established percentage set in the Machine
Operation setup screen under Application Rate Step. Automatic regulation
mode will automatically adjust the application rate based on the current speed in
reference to the target rate. Preset Application Rates dene up to ve (5) target
rates of product being applied per hectare/acre. These can be toggled using the
Toggle Preset Target Rate Key on the Operation Screen or Home Screen.
• To adjust the Target Rate, press the BOOST/STEP % INCREASE/DECREASE
KEYS .
Target Rate
Preset Application Rates dene up to ve (5) target rates of product being applied
per hectare/acre. These settings will set the same for all active trips. Target rates
set to “0.0” will not be included in the toggle preset target rate options on the
Operation Screen or Home Screen.
If a switchbox is being used to control the boom sections, current target application
rate can be set on the Operation Screen.
When a switchbox is not connected to the system current target application rate
needs to be established on the Home Screen before entering Operation Mode.
With Switchbox Figure 1-18: Target Application Rate
• To toggle between Target Application Rates, press the TOGGLE PRESET
TARGET RATE KEY .
Without Switchbox Figure 1-19: Target Application Rate
• To toggle between Target Application Rates, press the TOGGLE PRESET
TARGET RATE KEY .

COPYRIGHTS
© 2016 TeeJet Technologies. All rights reserved. No part of this document or the computer programs described in it may be reproduced,
copied, photocopied, translated, or reduced in any form or by any means, electronic or machine readable, recording or otherwise, without
prior written consent from TeeJet Technologies.
TRADEMARKS
Unless otherwise noted, all other brand or product names are trademarks or registered trademarks of their respective companies or
organizations.
LIMITATION OF LIABILITY
TEEJET TECHNOLOGIES PROVIDES THIS MATERIAL “AS IS” WITHOUT WARRANTY OF ANY KIND, EITHER EXPRESSED OR
IMPLIED. NO COPYRIGHT LIABILITY OR PATENT IS ASSUMED. IN NO EVENT SHALL TEEJET TECHNOLOGIES BE LIABLE FOR
ANY LOSS OF BUSINESS, LOSS OF PROFIT, LOSS OF USE OR DATA, INTERRUPTION OF BUSINESS, OR FOR INDIRECT,
SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES OF ANY KIND, EVEN IF TEEJET TECHNOLOGIES HAS BEEN ADVISED OF
SUCH DAMAGES ARISING FROM TEEJET TECHNOLOGIES SOFTWARE.
To ensure optimal use of the equipment, please read this manual thoroughly. Please contact TeeJet Technologies Customer Support or an
authorized TeeJet Technologies dealer if additional support is required.

IC18 SPRAYER/NH3
JOB COMPUTER
OEM MENU SETUP
www.teejet.com
98-05267-EN-A4 R3 English
© TeeJet Technologies 2016
SOFTWARE VERSION 1.09
This manual suits for next models
1
Table of contents