ITI 60-770 - Security SuperBus 2000 4-Zone Output... User manual

1
SuperBus® 2000 4-Relay Output Module
Installation Instructions
Product Summary
Each SuperBus 2000 4-Relay Output module adds four pro-
grammable relay outputs to a compatible panel.
Examples of module uses include:
❑Turning on a CCTV camera during a burglary alarm.
❑Turning on exit lights during a fire alarm.
❑Activating backup cellular phones or long-range radios
if primary communications are inoperable.
Each module comes complete with mounting hardware.
Power for the module is provided by the panel.
Advent®panels can be expanded to a total of 124 (24 pre-
programmed) output points.
UltraGard®and Concord™panels can be expanded to a total
of 32 output points.
For additional security, the plastic case accommodates a
magnetic reed switch to provide tamper protection. Simply
connect a UL listed reed switch to the module built-in zone
input or to one of the fire/security panel hardwire input
zones.
SuperBus 2000 vs. SuperBus
SuperBus 2000 panels have the ability to auto-address mod-
ule unit numbers. When the panel is initially powered up,
the panel automatically reads the unique SuperBus 2000
device ID number and assigns a unit number to the module.
This eliminates manually setting DIP switches and the
chance of identical unit number conflicts.
SuperBus 2000 Panels
❑Advent
❑Concord (software versions 2.0 and later)
SuperBus panels communicate with SuperBus 2000 mod-
ules but require the module unit number to first be set man-
ually with DIP switches.
SuperBus Panels
❑UltraGard
❑Concord (software versions 1.0–1.6)
Module Components
Figure 1 shows the main module components and Table 1
describes them.
Figure 1. Module Circuit Board Components
Table 1: Module Component Descriptions
Component Function
Unit Number DIP
Switches Used for manually setting module unit
number (SuperBus panels).
BUS LED (Red) Flashes to indicate normal
communication with the panel.
POWER LED
(Green) Indicates module power status.
Output Relays Form C (dry contact) output relays rated
4A @ 24VDC, 4A @ 24VAC, 1A @
70VAC maximum.
SuperBus 2000
Device ID Number
Label
Identifies the unique device ID
(SuperBus 2000).
Software Version
Label Identifies the installed software version.
Wiring Terminals Used for power, bus, and output wiring
connections. All terminals are Class 2
power limited.
POWER LED
(GREEN)
SOFTWARE
VERSION LABEL
UNIT NUMBER
DIP SWITCHES
WIRING
TERMINALS
9710G01A.DSF
BUS STATUS LED
(RED)
OUTPUT RELAYS (4)
SUPERBUS 2000
DEVICE ID
NUMBER LABEL
SuperBus
®
2000
4-Relay Output Module
8557109A.DS4
ITI Part No. 60-770
Document Number: 466-1608 Rev. B
November 2000

2SuperBus® 2000 4-Relay Output Module
Installation Guidelines
Installation Guidelines
❑For the maximum number of bus devices and
touchpads per panel see Table 2.
❑Do not exceed the panel total DC output power rating
when using panel power for bus devices and hardwired
detectors (see specific panel Installation Instructions).
❑Do not exceed the maximum wire length from the
panel to the module (see Table 3).
❑When using self or remotely powered devices with an
Advent panel, do not exceed the maximum recom-
mended wire length of 4000 feet using 22-gauge or
larger wire.
❑Maximum module current draw with all outputs ener-
gized is 180 mA. Each module draws 12 mA typical
when outputs are not energized (idle).
❑Do not exceed the module output relay contact ratings
(4A @ 24VDC, 4A @ 24VAC, 1A @ 70VAC maximum).
Tools and Supplies Needed
❑Screwdrivers
❑Drill with bits
❑Wire cutters/strippers
❑3/8-inch #6-32 self-tapping screws (included)
❑22-gauge or larger stranded wire (18-gauge or larger
for commercial applications)
❑1/4-inch press-fit reed switch and magnet (not
included) for cover tamper
❑1/4-inch #6-32 self tapping screws (not included) for
Advent cabinet mounting
❑Support standoff (included with Concord cabinet)
Installation
The relay output module can be mounted:
❑On a wall.
❑Inside an Advent cabinet.
❑Inside a Concord cabinet.
❑Inside a SuperBus Module cabinet (60-698). Refer to
the cabinet Installation Instructions for installation
procedures.
CAUTION
To prevent damaging the panel or card, disconnect the
panel AC Power and backup battery(s) before
installation.
CAUTION
You must be free of all static electricity when handling
electronic components. Touch a bare metal surface
before touching the circuit board.
Mounting the Module
Note
If connecting the module to an UltraGard panel it must
be mounted on a wall. The module will not fit in the
UltraGard cabinet.
Mounting the Module on a Wall
1. Remove the module cover and set it aside (Figure 2).
Figure 2. Removing the Cover
2. Place the back-plate on the wall and mark the mount-
ing holes (Figure 3).
3. Drill holes and insert appropriate anchors.
4. Secure the back-plate to the wall with included
screws.
Table 2: Maximum Bus Devices Per Panel
Panel Maximum Bus
Devices
Advent 62
UltraGard 8
Concord
(software versions 2.0 and later) 16
Concord
(software versions 1.0–1.6) 16
(up to eight 4-Relay
Output modules)
Table 3: Maximum Wire Lengths
Panel Maximum Wire Length
Advent 22 ga. 200 ft./18 ga. 500 ft.
UltraGard 22 ga. 500 ft./18 ga. 1000 ft.
Concord 22 ga. 350 ft./18 ga. 900 ft.
PRESS DOWN
HERE AND PULL
AWAY FROM BASE
8557G47B.DS4

3
SuperBus® 2000 4-Relay Output Module
Installation
Figure 3. Mounting Holes
Mounting the Module in an Advent Cabinet
1. Remove panel AC power and disconnect the backup
battery(s).
2. Remove the module cover and set it aside (Figure 2).
3. Turn the module upside down and line up the holes on
the back-plate at the desired location (Figure 4).
4. Secure the back-plate to the cabinet using three ¼-inch
#6-32 self-tapping screws (not included).
Figure 4. Mounting Module in Advent Cabinet
Mounting the Module in a Concord Cabinet
1. Remove AC panel power and disconnect the backup
battery.
2. Remove and discard the module cover (Figure 2).
3. Insert a support standoff as shown in Figure 5 (sup-
plied with panel) into the panel circuit board.
Figure 5. Support Standoff
4. Slide the module back-plate onto the two clips located
on the top-left corner or center of the cabinet
(Figure 6).
Note
The two mounting clips in the top-right corner of the
cabinet are designated for a receiver module, but if a
receiver module is not being used, the mounting clips
may be used for the 4-Relay Output Module.
5. Push the lower-right corner of the module onto the
support standoff (see detail in Figure 6).
6. Gently press the module up and onto the cabinet side
tab.
Figure 6. Mounting Module in Concord Cabinet
9710G02B.DSF
MOUNTING HOLES
REED SWITCH
HOLDER
12345678910 11 12 13 14 15 16 17 18
MAGNET
CLIP
9
712G11A.DSF
PANEL CABINET
(COVER NOT SHOWN)
MOUNTED MODULE
ROOM FOR 3RD
MODULE
MOUNT WITH
SELF TAPPING
SCREWS
SUPPORT STANDOFF
8573g64A.DSF
PANEL
END
MODULE
END
9712G08A.DSF
USABLE MOUNTING
CLIPS (6)
CARD ON
MODULE
BACK-PLATES
PANEL CABINET
(COVER NOT SHOWN)
DETAIL
SUPPORT STANDOFF
(Included with Concord
panel accessory package)
SIDE TAB

4SuperBus® 2000 4-Relay Output Module
Installation
Wiring
Note
A) Class 2, Class 3, and power-limited fire alarm cir-
cuits must be installed using FPL, FPLR, FPLP, or
substitute cable permitted by the National Electrical
Code ANSI/NFPA 70. Wire that extends beyond the
cable jacket must be separated from all other conduc-
tors by a minimum of 1/4-inch or by a nonconductive
barrier.
OR
(B) Class 2, Class 3, and power-limited fire alarm cir-
cuit conductors must be installed as Class 1 or higher
circuits.
Wiring the Module to a Panel
Important!
On Advent panels, the BUS 1 and BUS 2 headers
must be used only for fire or burglary applications. Do
not mix fire and burglary bus devices on either header.
Auxiliary power supplies must be power limited.
1. Turn off (or disconnect) the panel power and discon-
nect the panel backup battery(s).
2. Wire the module to the panel as shown in Figure 7 and
Table 4.
Note
For specific wiring details, see the panel
Installation
Instructions
.
3. Wire multiple modules in “daisy-chain” fashion (in
parallel) to the panel terminals or connector.
Figure 7. General Module Wiring
* Panel SuperBus device connector wiring harness.
(Connect to either panel connector.)
4. Wire the module outputs as shown in Figures 7 and 8.
For specific wiring details, see the device Installation
Instructions.
Table 4: Module SuperBus/Panel Wiring
Module
Terminals Advent* Ultra-
Gard Concord
13 (+12VDC) Red 12 4
14 (BUS A) Green 13 5
15 (BUS B) White 14 6
16 (GND) Black 15 3
9710G03A.DS
F
12 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
NO 1
NC 1
COM 1
+12 VDC*(RED)
BUS A (GRN)
BUS B (WHT)
GND**(BLK)
TO OUTPUT 4
DEVICE
TO OUTPUT 3
DEVICE
TO OUTPUT 2
DEVICE
TO OUTPUT 1
DEVICE
TO PANEL SUPERBUS
TERMINALS OR
CONNECTOR
(SEE TABLE)
*ALSO OUTPUT AND AUX. SUPPLY
**ALSO OUTPUT AND AUX. SUPPLY GND (COMMON
)
18
ZONE 1
NO 2
NC 2
COM 2
NO 3
NC 3
COM 3
NO 4
NC 4
COM 4
ZONE COM TO ZONE 1
INPUT DEVICE(S)
ID: XXXXXXXX

5
SuperBus® 2000 4-Relay Output Module
Installing a Cover Tamper Switch
Connecting Devices to Outputs
Note
All terminals are Class 2 power limited.
Figure 8. Module Typical Output Wiring
Connecting Devices to the Zone Input
Follow the maximum zone input wire length (run) guide-
lines in Table 5 based on the type of wire used.
Important!
For Advent UL-864 Listed Installations, all inputs must
be dedicated to either fire or burglary applications. Do
not mix fire and burglary on
any
module in
any
partition for these installations.
Figure 9 shows an example of how to connect normally
closed (N/C) or normally open (N/O) intrusion circuits to
the module zone input.
Figure 9. Module Zone Input Wiring
Installing a Cover Tamper Switch
If you are mounting the module in its own plastic or mount-
ing it inside a metal cabinet, you must add module tamper
detection for UL Listed systems.
To do this, install a UL listed ¼-inch press-fit reed switch
on the module back-plate and wire the switch to the module
zone input terminals or unused panel hardwire input termi-
nals. Once programmed, if someone opens the module
cover, the tamper switch opens and causes an alarm.
The tamper switch holder is located at the lower-right side
of the back-plate as shown in Figure 10. The plastic cover
holds the magnet.
Figure 10. Installing the Reed Switch
Table 5. Zone Input Wire Runs
Gauge Max. Wire Run*
18 750 Feet
22 300 Feet
*Wire run based on 10 ohms maximum wire and
device resistance including 2.0K ohm EOL resistor.
12 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
NO 1
NC 1
COM 1
+
12 VDC
GND
18
*
2K OHM
1/2 W
(TYPICAL)
LED
* DO NOT EXCEED RELAY CONTACT
VOLTAGE AND CURRENT RATINGS
**
DO NOT EXCEED PANEL +12V POWER CONSUMPTION
LIMITS (SEE PANEL INSTALLATION INSTRUCTIONS)
OUTPUT
DEVICE
(N.O. INPUT)
**
NO 2
NC 2
COM 2
NO 3
NC 3
COM 3
NO 4
NC 4
COM 4
9710G04A.DSF
12 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
ZONE 1
ZONE COM
NORMALLY
OPEN
(N/O)
CONTACTS
IN PARALLEL
2.0K Ohm EOL RESISTOR 46-467
(INSTALL AT LAST DEVICE)
NORMALLY
CLOSED
(N/C)
CONTACTS
IN SERIES
< OR >
9712G12A.DSF
MODULE
BACK-PLATE
MODULE
COVER
REED
SWITCH
MAGNET
CLIP
MAGNET
T
O ANY ZONE
INPUT
2.0K OHM EOL
RESISTOR (49-467)

6SuperBus® 2000 4-Relay Output Module
Setting the Module Unit Numbers
To install the tamper reed switch:
1. Slide the reed switch into the holder located on the
module back-plate.
2. Insert the reed switch magnet into the nibs on the
module cover (not shown). Press the magnet clip (sup-
plied) down over the magnet until it clicks into place.
3. On Advent and Concord (software versions 2.0 and
later) Systems:
Connect the normally closed reed switch (in series
with a 2.0K ohm [ITI part number 46-467] EOL resis-
tor) to the module ZONE 1 (17) and ZONE COM-
MON (18) terminals (Figure 9).
On UltraGard Systems:
Connect the reed switch in series with 4.7K ohm (ITI
part number 49-365) EOL resistor and to the panel
GND and unused panel hardwire zone input terminals.
On Concord (software versions 1.0–1.6) Systems:
Connect the reed switch in series with a 2.0K ohm (ITI
part number 46-467) EOL resistor to the panel ZONE
COMMON/GND and unused panel hardwire zone
input terminals.
Setting the Module Unit Numbers
On Concord (software version 2.0 or later) and Advent
Panels
Locate the DIP switches on the module circuit board and set
all switches to “A” (for automatic). The unit number will be
automatically set when powering up the system.
On Concord (software versions 1.0–1.6) and UltraGard
Panels
Note
Concord panels with software versions 1.0–1.6 will
only recognize 4-Relay Output modules with unit num-
bers set from 0 to 7.
Locate the DIP switches on the module circuit board. Set
switch 1 to “M” (on for manual). Set the remaining switches
for the desired unit number (Figure 11).
❑Unit Number 0-7 for UltraGard
❑Unit Number 0-7 for Concord (software versions 1.0–
1.6)
Figure 11. Module Unit Number DIP Switch Settings
(Non-SuperBus 2000 systems)
Power Up and Bus Communication
This section describes how to power up the panel and the
module for both new and existing installations.
Advent and Concord Panels
New Installations
1. Verify that all wiring between the panel, touchpad and
module is correct.
2. Connect the panel battery(s) and restore panel AC
power. Alphanumeric touchpad displays should come
on.
3. Both the green and red LEDs will turn on for one sec-
ond. The green POWER LED will remain on and the
red BUS status LED should flash to indicate success-
ful communication with the panel.
Note
If the green POWER LED is not on or the red BUS
status LED does not flash, remove AC panel power,
disconnect the battery(s), and see Table 6 “Trouble-
shooting.”
Existing Installations
Concord Panels- Same as new installation.
Advent Panels-
1. Verify that all wiring between the panel and module is
correct.
9712G09A.DSF
UNIT NUMBER 0
12345678
ON
UNIT NUMBER 1
12345678
ON
UNIT NUMBER 2
12345678
ON
UNIT NUMBER 3
12345678
ON
UNIT NUMBER 4
12345678
ON
UNIT NUMBER 5
12345678
ON
UNIT NUMBER 6
12345678
ON
UNIT NUMBER 7
12345678
ON
UNIT NUMBER 8
12345678
ON
UNIT NUMBER 9
12345678
ON
UNIT NUMBER 10
12345678
ON
UNIT NUMBER 11
12345678
ON
UNIT NUMBER 12
12345678
ON
UNIT NUMBER 13
12345678
ON
UNIT NUMBER 14
12345678
ON
12345678
ON
UNIT NUMBER 15--Do not use in Concord RF systems.
M
AM
AM
A
M
AM
AM
A
M
AM
AM
A
M
AM
AM
A
M
AM
AM
A
M
A

7
SuperBus® 2000 4-Relay Output Module
Programming and Testing
2. Connect the panel battery(s) and restore panel AC
power. Alphanumeric touchpad displays should come
on. Both the green and red LEDs turn on for one sec-
ond, then the green POWER LED will remain on.
3. Press 8for System Menu.
4. Press 0for Program Menu.
5. Enter your Install Code (default 0123).
6. Enter Item Number 48001 to add SuperBus 2000
devices. All installed devices are automatically added
(learned) into panel memory when Devices Added is
indicated.
7. Press * twice to return to the Main Menu.
8. The red BUS status LED should flash to indicate suc-
cessful communication with the panel.
Note
If the green POWER LED is not on or the red BUS
status LED does not flash, remove AC panel power,
disconnect the battery(s), and see Table 6 “Trouble-
shooting.”
UltraGard Panels
1. Verify that all wiring at the panel and the module is
correct.
2. Verify nonconflicting bus unit number settings.
3. Connect the panel battery and restore panel AC power.
4. Turn on the panel AC power.
5. Set the UltraGard panel RUN/PROGRAM switch to
PROGRAM.
If the alphanumeric touchpad displays 1-OFF and the 1is
flashing, you must enter the 4-digit installer access code to
get the panel into program mode.
Alphanumeric touchpads should display PROGRAM
MODE and the red BUS status LED on the module should
be flashing continuously, indicating successful communica-
tion to the panel.
Note
If the green POWER LED is not on or the red BUS
status LED does not flash, set the RUN/PROGRAM
switch (UltraGard) to RUN, remove AC panel power,
disconnect the backup battery, and see Table 6 “Trou-
bleshooting.”
Programming and Testing
Refer to the specific panel Installation Instructions for
configuring module outputs, adding (learning) hardwire
sensors, and testing.
Troubleshooting
Use the following table to determine possible solutions to
module problems.
Table 6: Troubleshooting
Problem Solution
The green POWER
LED stays off. 1. Check for incorrect wiring con-
nections.
2. Make sure panel AC power is
applied and the backup battery(s)
are connected.
3. If the LED still remains off,
replace the module.
The red BUS LED
doesn’t flash to
indicate
communication
with the panel.
1. Verify that the panel recognizes
the module by entering program
mode (see specific panel Installa-
tion Instructions).
2. Check for incorrect wiring con-
nections.
3. For Concord (software versions
1.0–1.6) and UltraGard panels
make sure that module DIP switch
1 is set to “M.” For Concord (soft-
ware versions 2.0 or later) and
Advent panels make sure that
module DIP switch 1 is set to “A.”
4. If the LED still doesn’t flash,
replace the module.
Output(s) activate
only momentarily,
activate randomly,
or module and/or
touchpads lock up.
1. For Concord (software versions
1.0–1.6) and UltraGard systems,
check for bus devices with the
same unit number setting.
2. Re-initialize the panel by discon-
necting and reconnecting panel
power.
3. Verify that the output/point is con-
figured correctly (see specific
panel Installation Instructions).
4. Make sure the zone has been
“learned” into panel memory.
5. Verify that the panel recognizes
the module by entering program
mode (see specific panel Installa-
tion Instructions).
6. Check module/panel wire routing
and length.
7. Replace the module.
Module Zone input
is inoperable.
(UltraGard &
Concord)
1. Some panels and panel versions
do not read the module built-in
zone input status. Use a panel zone
input instead.
One output stays
activated. 1. Check if the point is programmed
for a 3 minute “on” time and if the
triggering event for the point is
repeatedly “resetting” the 3
minute timer (see specific panel
Installation Instructions).
2. Output may have failed or been
overloaded. Reprogram using a
different (unused) module output
or replace the module.

8SuperBus® 2000 4-Relay Output Module
Specifications
Specifications
Compatibility: Advent, Concord, and UltraGard
Power Requirements: 12V nominal, 12 mA typical (idle), 180
mA maximum (all relays energized)
Inputs: One supervised, fire-rated, hardwire
zone
Outputs: Four, panel programmable outputs with
“Form-C” relay contacts (COMMON,
N/C, N/O). Relay contacts rated 4A @
24VDC, 4A @ 24VAC, 1A @
70VAC maximum.
Storage Temperature: -30° to 140° F (-34° to 60° C)
Operating Temperature: 32° to 140°F (0°to 60° C), up to 140°
F (60° C) under temporary
conditions
Maximum Humidity: 90% relative humidity, non-condensing
Dimensions: 5.25" x 4.125" x 1.0" (L x W x D)
Color: Belgian grey
Case Material: High-impact ABS plastic
Installation: On wall or in panel cabinet
mounting
Listings (for ancillary use only):
UL 365 Police Station Connected
Burglar Alarm Units and Systems
UL 609 Local Burglar Alarm Units and
Systems
UL 864 Control Units for Fire
Protective Signaling Devices
UL 985 Household Fire Warning
System Units
UL 1023 Household Burglar Alarm
System Units
UL 1610 Central Station Burglar Alarm
Units (Commercial Burglary)
UL 1637 Home Health Care Signaling
Equipment
CSFM California State Fire Marshall
(applied for)
FM Factory Mutual (applied for)
MEA New York City Material
Equipment Acceptance (applied for)
DOD Sensitive Compartment
Information Fac. (applied for)
ULC Canada Commercial
Fire/Burglary Warning (applied for)
Note
See specific panel
Installation Instructions
for
complete UL installation requirements for the system
you are installing.
Notices
FCC Part 15 Information to the User
Changes or modifications not expressly approved by Interactive Technologies,
Inc. can void the user’s authority to operate the equipment.
FCC Part 15 Class A
This equipment has been tested and found to comply with the limits for a class A
digital device, pursuant to part 15 of the FCC rules. These limits are designed to
provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a residential
area is likely to cause harmful interference in which case users will be required to
correct the interference at their own expense.
FCC Part 15 Class B
This equipment has been tested and found to comply with the limits for a Class B
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against interference in a residential installation.
This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful interfer-
ence to radio communications. However, there is no guarantee that interference
will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception,
which can be determined by turning the equipment off and on, the user is encour-
aged to try to correct the interference by one or more of the following measures:
❑Reorient or relocate the receiving antenna.
❑Increase the separation between the equipment and receiver.
❑Connect the affected equipment and the panel receiver to separate outlets,
on different branch circuits.
❑Consult the dealer or an experienced radio/TV technician for help.
©2000 Interlogix™Inc. Interlogix and Concord are trademarks of
Interlogix, Inc. ITI, Advent, UltraGard, and SuperBus are registered trade-
marks of Interlogix, Inc.
www.itii.com
T: 651/777-2690
F: 651/779-4890
2266 Second Street North
North Saint Paul, MN 55109-2900
1-800-777-1415
This manual suits for next models
1
Table of contents
Other ITI Switch manuals