Jets 121315143 User manual

VAC Controller CVS/VIP Tel. +47 70 03 91 00
www.jetsgroup.com
Product No. 121315143 Doc. Rev.: 5 (2020-11-30)
1
Technical Data
......................................
Outside Dimensions 190 x 80 x 60 mm (LxWxH)
................................................................................
Generic Material ABS
....................................................................................
Net Weight 0.67 kg
Operating Data
................................................................................
Voltage 100-240VAC
12-24VDC
Disclaimer
Note: Our products and services are offered and sold subject to Jets
Vacuum AS’ General Sales Conditions, copies of which will be
furnished upon request. Information provided herein is solely for
information purposes, does not constitute any warranty or
representation of any kind and is subject to change without notice.
We strive to reproduce product colors reasonably accurate. Without
prior written approval, this document or any part of may not be
reproduced in any form. Jets™, Vacuumarator™, Helivac™, VC™,
VOD™, CVS™ and Softsound™ are trademarks and/or registered
trademarks of Jets. © Jets AS. All rights reserved.
Components
1| Power Supply 12VDC, complete
.................................
121201627*
Additional Components
| US plug adapter
............................................................
121201621
| UK plug adapter
............................................................
121201622
| AUS plug adapter
.........................................................
121201623
* Component/s avaliable as replacement parts.

VAC Controller CVS/VIP Tel. +47 70 03 91 00
www.jetsgroup.com
Product No. 121315143 Doc. Rev.: 5 (2020-11-30)
2
Function and Principle
The VAC Controller is programmed to control the following:
● Automatic start and stop of a Vacuumarator™ pump.
● Manual start and stop of a Vacuumarator™ pump.
● Vacuum level monitoring.
● Auto stop after delayed run time (default 10 min).
● Tank level monitoring from a level switch in a tank.
● Activation of an alarm signal.
● Ready signal from a presence sensor (optional). Starts the Vacuumarator™ pump and produces vacuum to a set vacuum level.
Alarm
The VAC Controller is programmed with the following alarm settings:
● Power ON - Engages closed contact at alarm output F.
● Low Vacuum - Engages and activates alarm output G.
● Full Tank - Alarm is based on a level indication from a tank. Requires a level switch (not included).
● Long Running Time - Engages and activates alarm output I.
● Vacuum Transmitter Fault - Alarm is based on vacuum transmitter not connected, connected wrong, not working.
● Full Tank Warning - If the time setting in "runtime after full tank" has been set over 00, a pre-warning alarm will sound. This means that the
pump will run in xx-minutes before the full tank alarm sounds. Start planning to have the tank emptied.
Operation
● AUTO Mode 1.1
When the system is intended to be used as a constant vacuum system (CVS), and the motion/presence sensors are not connected to the
VAC Controller.
● VIP Mode 1.2
When the system is used with motion/presence sensors that are connected to the VAC Controller. Vacuum is produced when activating the
zone of the motion sensor.
● Manual Mode 1.3
Starts and stops the Vacuumarator™ pump via the VAC Controller, regardless of the vacuum transmitter (vacuum level).
WARNING: This can cause the vacuum to reach a very high level in the system and the pump will not stop.
● OFF Mode 1.4
System OFF, the VAC Controller will not start in this mode.

VAC Controller CVS/VIP Tel. +47 70 03 91 00
www.jetsgroup.com
Product No. 121315143 Doc. Rev.: 5 (2020-11-30)
3
Important Health and Safety Information
Installation, operation and maintenance must be carried out in strict accordance with this guide and with all applicable regulations. For your own
protection and the protection of others, it is necessary to familiarize yourself with, and always follow, the contained safety and environmental
precautions for our products.
This manual is an integral part of the product/delivery. Always keep it in a safe place for future reference. It is entirely the owner’s responsibility to
ensure that all safety and environmental measures, in accordance with local, state and federal laws are followed. Jets Vacuum AS assumes no
responsibility for equipment damage, personal injury or death and/or delays that result from a lack of respect for the instructions for installation
and/or use as stated in this documentation. Disregarding these instructions may invalidate all warranties.
Safety information references are in accordance with Jets Vacuum AS documentation system. If you do not understand the warnings, stop work
immediately and contact Jets Vacuum AS (citing the safety reference number) for further clarification.
For further information about the included warnings or any other safety concerns please contact Jets Vacuum AS.
Important Health and Safety Warnings
3.1 Warning
All wiring should be performed by a licensed or certified electrician.
3.2 Warning
Never work on the equipment when mains power is applied.
For equipment fitted with a frequency converter: After disconnecting the
input power, always wait for 5 min to let the intermediate circuit
capacitors discharge before you start working on the equipment.
1.2 Warning
Be thoroughly familiar with the controls and the proper use of the equipment
prior to installing, starting or using the equipment. Know the equipment
application, limitations and potential hazards.
3.3 Warning
Avoid kinking and protect electrical cord/s from sharp objects, hot
surfaces, oil and chemicals. Replace or repair damaged or worn cords
immediately. In case of cable damage contact a qualified technician for
replacement.
3.4 Warning
Shoreside applications only: For maximum safety, the equipment should be
connected to a grounded circuit equipped with a ground fault interrupter
device. Before installing the equipment, have the electrical outlet checked by
a licensed or certified electrician to make sure the outlet is properly grounded.
Make sure that grounding conductors are adequately sized as required by
safety regulations.
3.5 Warning
Ensure that the line voltage and frequency of electrical current supply
agrees with the equipment specifications
3.21 Warning
Do not use plugs or connectors that are damaged.
3.24 Warning
Avoid touching the connector with wet hands. Do not disconnect the
plug by pulling the electrical cord
2.14 Warning
The equipment safety is guaranteed only if used in compliance with the
instructions provided. Do not exceed the limits provided.
6.11 Notice
Immediately upon receipt check the equipment for external damage.
Any damage detected after dispatch should be reported immediately to
Jets Vacuum AS and commissioning must be postponed until equipment
has been inspected. Do not dispose of damaged items. Your direct
supplier will advise you of the procedure to follow.
6.3 Notice
Check total quantities of each item against shipping records. Ensure that all
items have been received as per Jets™ order confirmation. Any
discrepancies must be reported to the carrier and to your direct supplier or
Jets Vacuum AS immediately.
6.4 Notice
After unpacking the equipment carefully inspect and tighten any parts,
nuts, bolts or screws that may have become loose in transit.
6.6 Notice
Goods to be protected against shock, falls, dust, foreign matter, grinding,
welding, humidity and moisture.
3.6 Warning
Risk of electric shock. Never connect the green (or green and yellow)
wire to a live terminal.
3.31 Caution
Jets Vacuum AS electrical supply includes cables outfitted with a Shuko 2
pole plugs + PE dependent on equipment specifications. Do not alter this
configuration without authorization from a specialized technician.
Delivery, Receipt of Goods and Transportation
Goods to be protected against shock, dust, humidity and frost. Suitable adequately dimensioned transporting equipment is to be used. Note that
the equipment may contain components that are easily damaged as a result of inappropriate handling. Jets Vacuum AS is not responsible for or
liable for delivery delays resulting from occurrences outside of Jets Vacuum AS' immediate control. On receipt of goods, check for visual damage.
Any damage detected after dispatch should be reported immediately to Jets Vacuum AS. Damages and/or discrepancies must be reported in
writing no later than eight (8) days after receipt of goods. Commissioning must be postponed until the equipment has been inspected. Do not
dispose of damaged items. Your direct supplier will advise you of the procedure to follow.
Storage
Unless otherwise specified, goods are to be stored in a dry environment between 0°C and +40°C prior to installation. The storage location must be
dust free, low humidity (≤95%) and be free from moisture. Keep clear of foreign objects.
Installation to End Use
Site to be a dry environment between +0°C and +45°C. The site is to be dust free and protected from grinding and welding. During installation, the
site is to be protected from water, frost and moisture. Goods are to be stored as per the instructions for delivery, storage and transport. A visual
inspection is to be carried out on receipt of goods as well as at the time of installation to ensure that storage and transport conditions after receipt
have not compromised the quality of the product/s.

VAC Controller CVS/VIP Tel. +47 70 03 91 00
www.jetsgroup.com
Product No. 121315143 Doc. Rev.: 5 (2020-11-30)
4
Installation
Prior to Installation
Before starting any work on the VAC Controller, ensure that the power has been disconnected.
3.2 Warning
Never work on the equipment when mains power is applied.
For equipment fitted with a frequency converter: After disconnecting the input power, always wait for 5 min to let the intermediate circuit capacitors discharge before you start
working on the equipment.
3.1 Warning
All wiring should be performed by a licensed or certified electrician.
Prior to installing the VAC Controller, read all technical information in this document. The document contains important information related to the
installation and settings for your installation.
Electrical Connections Diagram
A - Pre-wired
B - Signal cable to the Vacuumarator™ pump
C - Vacuum transmitter
D - VIP signal (optional)
E - Tank level (optional)
F - Alarm - Power on (normally open contact)
G - Alarm - Low vacuum
H - Alarm - Full tank
I - Alarm - Long running time
J - Optional power supply
K - Power supply
L - Presence detectors (max 10 sensors)
M - Grey water tank level switch connections (max 5 grey water
tanks)
Power Supply
● J - Optional 12/24VDC Power Supply
Optional power output or VIP sensor power supply, if needed.
● K - Power Supply
The power supply includes an EU plug adapter. If needed, US, UK and AUS plug adapters are also available.
If connecting to a 12/24V battery supply, a 12VDC power cable (pn 121201625) is required.

VAC Controller CVS/VIP Tel. +47 70 03 91 00
www.jetsgroup.com
Product No. 121315143 Doc. Rev.: 5 (2020-11-30)
5
Electrical Connections Diagram if VIP Presence Detectors are Installed
Installation Steps
1.
Insert a screwdriver into both of the
slots on the front cover to open the
controller.
2.
Lift the display out of the housing.
3.
Using the four screw holes in the
corners of the housing, secure the
controller to the wall (screws not
provided).
4.
Return the display back into
position on the housing.
5.
Close both side covers. Ensure both
sides are locked in place.

VAC Controller CVS/VIP Tel. +47 70 03 91 00
www.jetsgroup.com
Product No. 121315143 Doc. Rev.: 5 (2020-11-30)
6
Operation
Start-up Procedures
First Start-up / Power-up the VAC Controller
At first start-up, CVS (Auto Mode) and English language is set as default. All vacuum and alarm settings are pre-set.
The VAC Controller is not a touch screen. Use the arrow keys to navigate through the system (refer to Navigation Principles below for more
information).
To change the mode for the VAC Controller, go to Operations menu 1:
1.1 - CVS (Auto Mode)
1.2 - Auto VIP Mode
1.3 - Manual Mode
1.4 - System Off
To change the date and time, go to Menu 2.6:
2.6.1 - Date
2.6.2 - Time
To change the language, go to menu 2.7.
Navigation Principle
● A dark frame around a setting or an arrow (►) insde the selection indicates which setting you are currently on.
● Arrow up/down indicates that there are several choices in the menu you are currently on.
● Activating and changing values occurs by having a blue frame around a current setting, then OK is pressed and the value begins to blink. Use
the arrow keys to adjust, then press OK or Done to save. The blinking will stop and the value will be saved.
● Each time a keystroke activates a button, a small beep will be heard, if the alarm sound is turned on/off in menu 2.6.8.
● Press and hold the return button for 5 seconds to restart the VAC Controller. The controller's long running time and warning tank level values
will reset.
● Press the return button to go back to the main menu.
Factory Settings
CVS (Auto Mode) and English language is set as default. All vacuum and alarm settings are pre-set.
The default setting is based on:
● The Vacuumarator™ is set to start at 30% vacuum, and stop at 50% vacuum.
● Maximum run time for the Vacuumarator™ is set to 10 minutes.
● Low vacuum alarm is set at 20%.
● Maximum run time after full tank alarm is 00 minutes.
● Vacuum if present setting is set at 5 minute delay run time.
If the default setting can be used, the system is ready for immediate use.
Manual Mode
Manual mode may be required in troubleshooting, i.e. to provide an extra powerful flush or when emptying a tank.
To run the Vacuumarator™ pump MANUALLY:
Go to Manual Mode in the Operations 1 menu. Press On to run the pump manually and Off to stop the pump. The pump will automatically
stop after the long running time is reached.
WARNING: The pump will not stop at high vacuum when in manual mode.

VAC Controller CVS/VIP Tel. +47 70 03 91 00
www.jetsgroup.com
Product No. 121315143 Doc. Rev.: 5 (2020-11-30)
7
Turning the VAC Controller OFF
From the main menu, press Auto and scroll down to System OFF. Press OK.
Service and Maintenance
Turn the VAC Controller Off and unplug the power supply.
This must always be done before installation, maintenance or repair.
Note: If the Vacuumarator™ pump's power is disconnected, the VAC Controller's power must also be disconnected.
3.28 Warning
Never work on the equipment when power is applied.
Setting Selections
1. Menu screen
2. Return/Reset button
3. Scroll down button
4. Scroll right button
5. Scroll left button
6. Scroll up button
7. OK/Save selection button
8. Power light
Main Menu
● Vacuum Level - Shows the current vacuum level.
● Menu - To enter Main Menu 2 screen.
● Auto - To enter Operation 1 screen.
___________________________________________________________________________________________________________________

VAC Controller CVS/VIP Tel. +47 70 03 91 00
www.jetsgroup.com
Product No. 121315143 Doc. Rev.: 5 (2020-11-30)
8
Selecting Auto from the main menu screen will take you to the the Operations 1 menu.
1.1 - Auto Mode (CVS)
Constant Vacuum System Controlled
- Shows the current vacuum level.
1.2 - Auto VIP Mode
Vacuum if Present System Controlled
- Shows the current vacuum level.
1.3 - Manual Mode
- Manual start and stop of the Vacuumarator™
pump
1.4 - System OFF
___________________________________________________________________________________________________________________
Main Menu
Selecting Menu from the main menu screen will take you to Main Menu 2.
Alarm
Alarm history
Alarm setting
Vacuum setting
VIP setting
Operation data
Language
Factory setting
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
___________________________________________________________________________________________________________________

VAC Controller CVS/VIP Tel. +47 70 03 91 00
www.jetsgroup.com
Product No. 121315143 Doc. Rev.: 5 (2020-11-30)
9
Main Menu Settings
● Active Alarm 2.1 Displays the 'current" date and time and will list any active alarms in the system.
___________________________________________________________________________________________________________________
● Alarm history 2.2 Use the up and down arrow keys to view a history log, including dates and times, of the last 100 alarms.
The newest alarm will show in the display when the history log opens.
___________________________________________________________________________________________________________________
● Alarm setting 2.3 2.3.1 - Long running time
Default: 10 minutes
Maximum constant pump running time: 1-60
minutes
2.3.2 - Low vacuum alarm
Default: 20%
Low vacuum alarm: 0-30%
2.3.3 - Runtime after full tank
Default: 0 minutes
Maximum time it is possible to run the pump after
the high level tank alarm has been activated.
When this runtime expires, the pump will stop.
Empty the tank.
___________________________________________________________________________________________________________________

VAC Controller CVS/VIP Tel. +47 70 03 91 00
www.jetsgroup.com
Product No. 121315143 Doc. Rev.: 5 (2020-11-30)
10
● Vacuum setting 2.4 2.4.1 - Start vacuum level
Default: 30%
Pump start level: 30-50% vacuum
2.4.2 - Stop vacuum level
Default: 50%
Stop pump level: 40-70% vacuum
___________________________________________________________________________________________________________________
● VIP setting 2.5 Runtime after VIP signal (minutes)
Default: 5 minute delay active operation time (the
pump will hold the vacuum betwen set point in xx-
minutes) after activated sensor or level switch:
1-60 minutes.
___________________________________________________________________________________________________________________
● Operation data 2.6 2.6.1 - Date
Press OK and the value will
blink. Arrow up and down and
press OK to set the day,
month and year.
2.6.2 - Time
Press OK and the value will
blink. Arrow up and down and
press OK to set the hour and
minutes, using the 24-hour
clock.
2.6.3 - Running hours
Total count of pump running
time in hours.
This is a read out only and
cannot be reset.
2.6.4 - Total PowerUp count
A counter for the total time the
controller has been connected
to power.
This is a read out only and
cannot be reset.

VAC Controller CVS/VIP Tel. +47 70 03 91 00
www.jetsgroup.com
Product No. 121315143 Doc. Rev.: 5 (2020-11-30)
11
2.6.5 - Pump start-up count
The total number of times the
pump has started.
This is a read out only and
cannot be reset.
2.6.6 - Full tank count
A counter for the number of
times the full tank alarm has
been activated.
This is a read out only and
cannot be reset.
2.6.7 - Reset counters
To reset the number of times
the pump has started and the
number of operating minutes.
Will reset this counter only.
2.6.8 - System Status
Firmware - Shows the current
software version on the
controller.
Alarm sound - ON (default) /
OFF function will deactivate all
the sound from the controller
(alarm and key stroke
sounds).
Alarm outputs - NC (default)
(normally closed) / NO
(normally open) alarm output.
Choose if alarm output "long
running time", "full tank" and
"low vacuum" should be
normally open or normally
closed. Alarm output "Power
ON" should always be pre-set
at NO and is not included in
this selection. This setting will
not reset after power failure or
factory setting.
___________________________________________________________________________________________________________________
● Language 2.7 2.7.1 - English (Default)
2.7.2 - Norwegian
2.7.3 - German
2.7.4 - Spanish
___________________________________________________________________________________________________________________

VAC Controller CVS/VIP Tel. +47 70 03 91 00
www.jetsgroup.com
Product No. 121315143 Doc. Rev.: 5 (2020-11-30)
12
● Factory setting 2.8 To restore the controller back to the factory
settings.
___________________________________________________________________________________________________________________
Troubleshooting
Jets Vacuum AS provides the following troubleshooting information to assist in resolving issues that may arise with your installation. For more
detailed information or assistance, please contact Jets Vacuum AS.
Problem Cause Action
Long Running Time If the pump is constantly running, more
than the set maximum running time,
an alarm will activate and the pump
will stop. There is also a limitation on
how long it is possible to run the pump
in manual mode.
The pump will stop when the alarm is activated. The pump/
unit must be restarted. The alarm output long running time
is activated.
Press and hold the return/reset button for 5 seconds to
reset the controller.
Full Tank Warning The full tank warning alarm will
activate when the high level tank
signal/input is active (closed signal).
The pump does not stop immediately,
but a running time count starts
(runtime after full tank alarm). The
runtime time is adjustable in the
settings menu 2.3.3. The counter will
be reset by a power failure.
The full tank alarm is activated. The runtime after full tank
time in alarm setting 2.3.3. can be adjusted.
Start planning to have the tank emptied.
Full Tank Alarm A full tank alarm will show on the
display. The pump will stop
immediately when the runtime after full
tank alarm counts down completely to
0.
The full tank alarm is activated and the pump stops
immediately. Empty the tank.
Low Vacuum Alarm The alarm is only activated in
automode, not in auto VIP or manual
mode. When vacuum in the system is
less than the set value in 2.3.2 for
longer than 1 continuous minute, a low
vacuum alarm will show in the display.
When the vacuum level goes back above the set value in
2.3.2, the alarm will disappear. Adjust the low vacuum
alarm level in 2.3.2
Vacuum Transmitter Fault The vacuum transmitter is not
connected, which will show the level
as 125 on the display. The vacuum
transmitter is connected wrong or is
broken.
Check the vacuum transmitter connections. Replace the
transmitter, if necessary.
Table of contents
Popular Controllers manuals by other brands

Kelly
Kelly KLS2418ND user manual

Mitsubishi Electric
Mitsubishi Electric MELSEC iQ-F Series Quick connection guide

Lennox
Lennox V0STAT54P-2 Installation & operation instructions

USA Technologies
USA Technologies VendingMiser VM150 installation instructions

Lumisys
Lumisys LRP user guide

Zamel
Zamel exta life ROB-21 instructions