
INSTALLATION GUIDE
InstallingandOperating the ESUSA Repeater
INTRODUCTION
TheESUSARepeaterisanunintelligent
routerusedsolelyforpassinginformation
andaddinglengthtoanexistingLONWORKS
network. Itwillnotfilternetworkpackets.
ECHELON
FTT-10A
50051
G9441B
ECHELON
FTT-10A
50051
G9441B
5.00ECSD
JP2
BUS
FREE
JP1
BUS
FREE
Figure 1 - Repeater board shown in enclosure with
cover removed.
INSTALLATION
TherepeaterconnectstotheLONWORKS
networkviaasuitablenetworkcable.The
repeaterispoweredbyaseparatepower
supply. SeeWiringRecommendations.
Wiring
WARNING - TO PREVENT
ELECTRICAL SHOCK OR DAMAGE
TO THE EQUIPMENT, YOU MUST
DISCONNECT THE POWER
SUPPLY TO THE REPEATER BEFORE YOU
MAKE THE WIRING CONNECTIONS.
Allwiringislowvoltageandshouldbein
accordancewithlocalregulationsandthe
NationalElectricalCode.
Useshieldedcableonlywhenitisrequired.
Mostapplicationsdonotrequireshielding
andwillbenefitfromunshieldedcable.
NXE-REP-FTT Repeater
Electronic Systems USA 9410 Bunsen Parkway Louisville, KY 40220 (502) 495-6700
TEC DOC # LIT-TD-2034 11/00
Figure 2 - Wiring connections for the Repeater.
Whenusingtheoptionalshieldedcable,
groundonlyoneendoftheshield. Low
voltagecontrolwiringshouldnotberunin
thesameconduitaslinevoltagewiringor
otherconductorsthatsupplyhighly-
inductiveloads(suchascontactors,coils,
motors,generators,etc.).
CAUTION - MAKE ALL CONNEC-
TIONS AND CHECK ALL CON-
NECTIONS BEFORE APPLYING
POWER. IMPROPER WIRING
MAY CAUSE PERMANENT
DAMAGE TO THIS EQUIPMENT.
WIRING RECOMMENDA-
TIONS
Unshielded (Recommended)
22AWG, Stranded: Belden #8443 (3-wire),
8444 (4-wire), 8445 (5-wire)
18AWG, Stranded: Belden #8489(4-wire),
8465(5-wire)
Plenum-rated, 22AWG, Stranded: Belden
#82444(4-wire), 82743(6-wire)
Plenum-rated, 18AWG, Stranded: Belden
# 82489(4-wire)
Shielded (Optional)
Stranded: Belden #8761
Plenum-rated, Stranded: Belden
#88761
To Wire the Repeater:
The terminal block slides into the slot on the
right side of the board. Refer to Figure 2.
1. Orient the terminal block as if you will
mount it on the board.
2. Wire the two Net A wires in the top
two positions of the terminal block.
3. Connect the ground wire via the third
screw on the terminal block.
4. Connect the 24VAC hot wire to the
forth terminal screw.
5. Wire the two Net B wires into the
bottom two positions of the terminal
block.
NOTE: Network wiring is polarity inde-
pendent, but the drawing indicates
Net - and Net + to accommodate the
conventions of circuitry design.
Copyright ©2000. Electronic Systems USA All Rights Reserved.
NET A -
NET A +
24VAC NEU
24VAC HOT
NET B -
NET B +
Net A
Net B
Net B
Ground
24 VAC Hot
Net A
Note: Network wiring is pol rity independent.