Kanmor 360e User manual

- Data Brochure
Mixing Control 360e
D 360e
06/03
1 of 20 © 2003 D 360e - 06/03
The Mixing Control 360e is designed to control the supply water temperature to a hydronic system in order to provide outdoor
reset or setpoint operation. The control uses a floating action mixing valve to regulate the supply water temperature, while
protecting the boiler against flue gas condensation. The control has a Liquid Crystal Display (LCD) to view system status and
operating information.
Additional Functions Include:
• Quick Setup for easy installation and programming of
control
• User comfort adjustment to increase or decrease build-
ing space temperature
• Advanced settings to fine-tune building requirements
• Boiler Control for improved energy savings
• Powered mixing system pump output
• Optional indoor sensor for room air temperature control
• Test sequence to ensure proper component operation
• Setback input for energy savings
• 230 V (ac) power supply
• CE Approved
Input
Mixing
Demand
Signal
Output
Mixing System
Pump
Input
Indoor
Sensor
Optional
Input
Universal Sensor
Included
Input
Universal Sensor
Included
Input
Outdoor
Sensor
Include
d
Output
Boiler
Input
230 V (ac)
Power
Supply
Input
kanmor Timer
Optional
Output
Mixing Valve &
Actuating Motor
Do not apply power
Signal wiring must be
rated at least 300 V.
LNPmpN Sw
Sys UnO Com Boil
Mix
Pwr Opn Cls Mix Com Out Indr
13 52
4
6
91078 11 12
13 14
15
16 17
18
Mix Power Boiler
Demand
Advanced
Installer
Boiler Sensor
Supply
30% Enable
10% Enable
Return
Item Test
Terminal
Unit
Mixing
Demand
INSTALLATION CATEGORY II
Made in Canada
Power: 230 V ±10% 50 Hz 2300 VA
Relays: 230 V (ac) 10 A 1/3 hp, pilot duty 240 VA
Demand: 20 to 260 V (ac) 2 VA
H1211B
To increase or decrease the
building temperature:
• Press the Item,▲,▼buttons
simultaneously for 1 sec. to
enter the ADJUST menu
• Use the ▲,▼buttons to adjust
the ROOM setting
Display defaults back to VIEW
menu after 20 seconds.
ROOM
-
Set to desired room temperature.
OUTDR DSGN
-
Set to coldest (design)
outdoor temperature.
Terminal Unit Set to
High Mass Radiant 1
Low Mass Radiant 2
Fan Coil 3
Convector 4
Radiator 5
Baseboard 6
Refer to brochure for more information.
Installer Instructions
Mixing Control 360e
Floating Action
Open
Motor
Speed
Close
M

© 2003 D 360e - 06/03 2 of 20
How To Use The Data Brochure
User Interface
The 360e uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to set up and
monitor the operation of your system. The 360e has three push buttons (Item, ▲, ▼) for selecting, viewing, and adjusting settings.
As you program your control, record your settings in the ADJUST menu table which is found in the second half of this brochure.
Item
The abbreviated name of the selected item will be displayed in the item field of the
display. To view the next available item, press and release the Item button. Once
you have reached the last available item, pressing and releasing the Item button will
return the display to the first item.
Adjust
To make an adjustment to a setting in the control, press and hold simultaneously for
1 second the Item, ▲ and ▼ buttons. The display will then show the word ADJUST
in the top right corner. Then select the desired item using the Item button. Finally
use the ▲ and/or ▼ button to make the adjustment.
To exit the ADJUST menu, either select the ESC item and press the
▲or ▼button
, or leave the adjustment buttons alone for 20 seconds.
When the Item button is pressed and held in the VIEW menu, the display scrolls through all the adjust items in both access levels.
Additional information can be gained by observing the status field and pointers of the LCD. The status field will indicate which
of the control’s outputs are currently active. Most symbols in the status field are only visible when the VIEW menu is selected.
User Interface..................................................Pg 2
Description of Display Elements ..................Pg 3
Sequence of Operation..................................Pg 4
Section A: General Operation..............Pg 4
Section B: Mixing ..................................Pg 5
Section C: Boiler Operation .................Pg 8
Installation.......................................................Pg 10
Electrical Connections..........................Pg 10
Testing The Wiring.................................Pg 12
Cleaning...........................................................Pg 13
DIP Switch Settings........................................Pg 13
Quick Setup.....................................................Pg 14
Control Settings..............................................Pg 15
View Menu ..............................................Pg 15
Adjust Menu ...........................................Pg 16
Testing and Troubleshooting ........................Pg 17
Error Messages......................................Pg 19
Technical Data ................................................Pg 20
Limited Warranty ............................................Pg 20
This brochure is organized into four main sections. They are: 1) Sequence of Operation, 2) Installation, 3) Control Settings, and
4) Troubleshooting. The Sequence of Operation section has three sub-sections. We recommend reading Section A: General
Operation of the Sequence of Operation, as this contains important information on the overall operation of the control. Then
read the sub-sections that apply to your installation. For quick installation and setup of the control, refer to the Installation sec-
tion, DIP Switch Settings section, followed by the Quick Setup section.
The Control Settings section (starting at DIP Switch Settings) of this brochure describes the various items that are adjusted and
displayed by the control. The control functions of each adjustable item are described in the Sequence of Operation.
Table of Contents
Item
Item

3 of 20 © 2003 D 360e - 06/03
Symbol Description
Display
Definitions
The following defined terms and symbols are used throughout this manual to bring attention to the presence of hazards of various
risk levels, or to important information concerning the life of the product.
- Warning Symbol: Indicates presence of hazards which can cause severe personal injury, death or
substantial property damage if ignored.
- Double insulated
- Local level, appliances
INSTALLATION
CATEGORY II
OCC
UNOCC
°F, °C
Pump
Displays when the mixing system pump is in
operation.
Burner
Displays when the boiler relay is turned on.
Occupied Schedule
Displays when the control is in occupied (Day)
mode.
Unoccupied Schedule
Displays when the control is in unoccupied
(Night) mode.
°F, °C
Displays the unit of measure that all of the tem-
peratures are to be displayed in the control.
Pointer
Displays the control operation as indicated by
the text.
OpenMotor
Speed Close

© 2003 D 360e - 06/03 4 of 20
Sequence of Operation
Section A
General
Operation
Page 4 - 5
Section B
Mixing
Reset
Page 5 - 8
Section C
Boiler
Operation
Page 8 - 9
Section A —General Operation
POWERING UP THE CONTROL
When the Mixing Control 360e is powered up, the control displays the control type number in the LCD for 2 seconds. Next, the
software version is displayed for 2 seconds. Finally, the control enters into the normal operating mode.
OPERATION
The 360e uses a floating action mixing valve to vary the supply water temperature to a hydronic system. The supply water
temperature is based on either the current outdoor temperature, or a fixed setpoint.
Outdoor Reset
When the outdoor design (OUTDR DSGN) setting is not set to OFF, the 360e cal-
culates a mixing supply water temperature based on the outdoor air temperature.
The 360e uses a Characterized Heating Curve and optionally indoor temperature
feedback from an indoor sensor in this calculation.
Setpoint Control
When the outdoor design (OUTDR DSGN) setting is set to OFF, the 360e supplies
a fixed mixing supply temperature equal to the MIX TARGET setting. An outdoor
sensor is not required during this mode of operation.
FLOATING ACTION
A floating action actuator motor is connected to the 360e on the Pwr Mix, Opn, and Cls terminals (9,10 and 11). The 360e
pulses the actuator motor open or close to maintain the correct mixed supply water temperature at the mix sensor when there
is a mixing demand. The mixing valve that the actuator is connected to can be either a 2-way, 3-way, or 4-way valve. A visual
indication as to whether the control is currently opening or closing the mixing valve is displayed in the LCD.
BOILER PROTECTION (BOIL MIN)
The 360e is capable of providing boiler protection from cold mixing
system return water temperatures. If the boiler sensor temperature
is cooler than the BOIL MIN setting while the boiler is firing, the
360e reduces the output to the mixing valve. This limits the amount
of cool return water to the boiler and allows the boiler temperature to
recover. This feature can only be used if a boiler sensor is installed.
EXERCISING
The 360e has a built-in exercising function. If the system pump or valve has not been operated at least once every 3 days, the
control turns on the output for a minimum of 10 seconds. This minimizes the possibility of a pump or valve seizing during a long
period of inactivity. The 360e ensures that the mixing valve operates over its entire range at least once each exercising period.
While the control is exercising the Test LED flashes.
Note: The exercising function does not work if power to the control, pump, or valve is disconnected.
SETBACK (UNOCCUPIED)
To provide greater energy savings, the 360e has a setback capability. With set-
back, the supply water temperature in the system is reduced when the building is
unoccupied. By reducing the supply water temperature, air temperature in the space
may be reduced even when thermostat(s)are not turned down. Any time the UnO
Sw (12)and the Com (13) terminals are shorted together, the control operates in the
unoccupied (Night) mode. When in the unoccupied (Night) mode, the UNOCC seg-
ment is displayed in the LCD. The 360e adjusts the supply water temperature based on
the UNOCC settings made in the control. This feature has no effect when the control
is used as a setpoint control.
Decreasing Outdoor Temperature
Increasing Water Temperature
Terminal UnitTerminal Unit
Indoor DesignIndoor Design Outdoor DesignOutdoor Design
Design SupplyDesign Supply
Boiler Supply
Sensor
Mix Supply
Sensor
Boiler Return
Sensor
12
UnO
Sw
13
Com
Timer Switch

5 of 20 © 2003 D 360e - 06/03
FACTORY DEFAULTS
The control comes preset with several factory defaults. These defaults are based on the terminal unit selection (see section
B2). To fine-tune building requirements, these defaults may be changed. If a factory default value for a terminal unit is changed,
the terminal unit number will flash when selected in the ADJUST menu.
To reload the fac tory defaults listed in section B2, power down the control and wait for 10 seconds. Power up the control while
simultaneously holding the Item and ▼buttons. The terminal unit number should now be displayed constantly in the LCD rather
than flashing.
MIXING DEMAND
A mixing demand is required in order for the 360e to provide heat. A mixing demand
is generated by applying a voltage between 24 and 230 V (ac)across the Mixing
Demand terminals (1 and 2).Once voltage is applied, the Mixing Demand pointer is
displayed in the LCD. If the 360e is not in WWSD, the 360e closes the Sys Pmp con-
tact. The 360e calculates a MIX TARGET supply temperature based on the outdoor air
temperature and settings. If required, the 360e operates the boiler in order to provide
heat to the mixing valve.
SYSTEM PUMP OPERATION (SYS PMP)
The system pump contact (Sys Pmp, terminal 5) closes whenever there is a mixing demand and the 360e is not in WWSD.
The system pump segment is displayed in the LCD. After the mixing demand has been satisfied, the 360e continues to operate
the system pump for 20 seconds. This allows some residual heat to be purged out to the heating system. During WWSD, the
system pump is operated based on the exercise function.
INDOOR SENSOR
An indoor sensor may be used in order to provide indoor temperature feedback. The indoor sensor is connected to the Com
and Indr terminals (16 and 18). In addition, power must be applied to the Mixing Demand terminals (1 and 2) as described in the
MIXING DEMAND section. With the indoor sensor connected, the 360e is able to sense the actual room temperature. Indoor
temperature feedback fine-tunes the supply water temperature in the mixing system to maintain room temperature. To adjust
the room temperature, use the ROOM OCC or ROOM UNOCC setting in the ADJUST menu at the control.
If a multiple zone system is used with an indoor sensor, proper placement of the indoor sensor is essential. The indoor sensor
should be located in an area which best represents the average air temperature of the zones.
CHARACTERIZED HEATING CURVE
When used as a mixing reset control, the 360e varies the supply water temperature based on the outdoor air temperature. The
control takes into account the type of terminal unit that the system is using. Since different types of terminal units transfer heat
to a space using different proportions of radiation, convection and conduction, the supply water temperature must be controlled
differently. Once the control is told what type of terminal unit is used, the control varies the supply water temperature according
to the type of terminal unit. This improves the control of the air temperature in the building.
MIXING TARGET TEMPERATURE (MIX TARGET)
When used as a mixing reset control, the MIX TARGET temperature is calculated from the Characterized Heating Curve set-
tings, outdoor air temperature and optionally, indoor air temperature. When used as a setpoint control, the installer sets the
MIX TARGET temperature. The control displays the temperature that it is currently trying to maintain as the mixing supply
temperature. If the control does not have a mixing demand,”- - -” is displayed as the MIX TARGET.
Section B: Mixing
Section B1
General
Section B2
Installer
Section B3
Advanced
Section B1: General
12
Mix
Demand
24 to 230 V (ac)

© 2003 D 360e - 06/03 6 of 20
Section B2: Installer
OUTDOOR DESIGN (OUTDR DSGN)
The OUTDR DSGN is the outdoor air temperature that is the typical coldest tempera-
ture of the year where the building is located. This temperature is used when doing the
heat loss calculations for the building. If a cold outdoor design temperature is selected,
the mixing supply temperature rises gradually as the outdoor temperature drops. If a
warm outdoor design temperature is selected, the mixing supply temperature rises
rapidly as the outdoor temperature drops.
SETPOINT OPERATION (MIX TARGET)
For setpoint control, set the OUTDR DSGN to OFF. The MIX TARGET becomes the
setpoint supply temperature that the control is to maintain. The MIX TARGET tem-
perature is set by the installer in the ADJUST menu. An outdoor sensor is not required
during this mode of operation.
ROOM OCC & UNOCC (ROOM)
The ROOM is the desired room temperature for the mixing zones, and it provides a
parallel shift of the Characterized Heating Curve. The room temperature desired by
the occupants is often different from the design indoor temperature (MIX INDR). If the
room temperature is not correct, adjusting the ROOM setting increases or decreases
the amount of heat available to the building. A ROOM setting is available for both the
occupied (Day) and unoccupied (Night) modes.
TERMINAL UNITS
When using a Characterized Heating Curve, the control requires the selection of a terminal unit. The terminal unit determines
the shape of the Characterized Heating Curve according to how the terminal unit delivers heat into the building space. The 360e
provides for selection between six different terminal unit types: two types of radiant floor heat, fancoil, fin-tuben convector,
radiator, and baseboard. When a terminal unit is selected, the control automatically loads the design supply temperature (MIX
DSGN), maximum supply temperature (MIX MAX) and minimum supply temperature (MIX MIN). The factory defaults are listed
below. To change defaults, refer to section B3. If a default has been changed, refer to Section A to reload the factory defaults.
High Mass Radiant (1)
This type of a hydronic radiant floor is embedded in either a thick concrete or
gypsum pour. This heating system has a large thermal mass and is slow acting.
Default values: MIX DSGN = 120°F (49°C), MIX MAX = 140°F (60°C),MIX MIN = OFF
Low Mass Radiant (2)
This type of radiant heating system is either attached to the bottom of a wood sub-
floor, suspended in the joist space, or sandwiched between the sub-floor and the
surface. This type of radiant system has a relatively low thermal mass and responds
faster than a high mass system.
Default values:
MIX DSGN = 140°F (60°C), MIX MAX = 160°F (71°C), MIX MIN = OFF
Fancoil (3)
A fancoil terminal unit or air handling unit (AHU) consists of a hydronic heating coil
and either a fan or blower. Air is forced across the coil at a constant velocity by the
fan or blower, and is then delivered into the building space.
Default values: MIX DSGN = 190°F (88°C) MIX MAX = 210°F (99°C),
MIX MIN =100°F (38°C)
Decreasing Outdoor Temperature
Increasing Water Temperature
MIX DSGNMIX DSGN
Mix INDRMix INDR
OUTDR
DSGN
OUTDR
DSGN
ColdCold
WarmWarm
Decreasing Outdoor Temperature
Increasing Water Temperature
ROOMROOM
MIX INDRMIX INDR
A
c
t
u
a
l
T
e
m
p
e
r
a
t
u
r
e
N
o
r
m
a
l
D
e
s
i
g
n
TERMINAL
UNIT
HIGH MASS RADIANT
(1)
LOW MASS RADIANT
(2)
FANCOIL
(3)
FIN-TUBE CONVECTOR
(4)
RADIATOR
(5)
BASEBOARD
(6)
MIX DSGN
MIX MAX
MIX MIN
120°F (49°C)
140°F (60°C)
OFF
140°F (60°C)
160°F (71°C)
OFF
190°F (88°C)
210°F (99°C)
100°F (38°C)
180°F (82°C)
200°F (93°C)
OFF
160°F (71°C)
180°F (82°C)
OFF
150°F (66°C)
170°F (77°C)
OFF

7 of 20 © 2003 D 360e - 06/03
Fin-tube Convector (4)
A convector terminal unit is made up of a heating element with fins on it. This type
of terminal unit relies on the natural convection of air across the heating element to
deliver heated air into the space. The amount of natural convection to the space is
dependant on the supply water temperature to the heating element and the room
air temperature.
Default values:
MIX DSGN = 180°F (82°C) MIX MAX = 200°F (93°C), MIX MIN = OFF
Radiator (5)
A radiator terminal unit has a large heated surface that is exposed to the room. A radi-
ator provides heat to the room through radiant heat transfer and natural convection.
Default values: MIX DSGN = 160°F (71°C), MIX MAX = 180°F (82°C), MIX MIN = OFF
Baseboard (6)
A baseboard terminal unit is similar to a radiator, but has a low profile and is installed
at the base of the wall. The proportion of heat transferred by radiation from a base-
board is greater than that from a fin-tube convector.
Default values:
MIX DSGN = 150°F (66°C), MIX MAX = 170°F (77°C), MIX MIN = OFF
MIXING INDOOR (MIX INDR)
The MIX INDR is the room temperature used in the original heat loss calculations for the building. This setting establishes the
beginning of the Characterized Heating Curve for the mixing zones.
MIXING DESIGN (MIX DSGN)
The MIX DSGN temperature is the supply water temperature required to heat the mixing zones when the outdoor air is as cold
as the OUTDR DSGN temperature.
MIXING MAXIMUM (MIX MAX)
The MIX MAX sets the highest water temperature that the control is allowed to calculate as the MIX TARGET temperature. If the
control does target the MIX MAX setting, and the MIX temperature is near the MIX MAX, the MAX segment will be displayed in
the LCD while either the MIX TARGET temperature or the MIX temperature is being viewed.
MIXING MINIMUM (MIX MIN)
The MIX MIN is the lowest temperature that the control is allowed
to use as a MIX TARGET temperature. During mild conditions, if
the 360e calculates a MIX TARGET temperature that is below the
MIX MIN setting, the MIX TARGET temperature is adjusted to match
the MIX MIN setting. During this condition, the MIN segment will be
displayed in the LCD when either the MIX TARGET or MIX tempera-
ture is being viewed. If an indoor sensor is used, and the 360e is
operating at the MIX MIN temperature, the system pump is cycled
using Pulse Width Modulation (PWM) with a 15 minute cycle length.
By cycling the system pump and controlling the flow of supply
water, the control provides an average supply water temperature to
the system. This average temperature is equal to the original MIX
TARGET. This minimizes overheating of the zone while the control
is operating at the MIX MIN temperature.
WARM WEATHER SHUT DOWN (WWSD) OCC & UNOCC
When the outdoor air temperature rises above the WWSD setting,
the 360e turns on the WWSD segment in the display. When the
control is in Warm Weather Shut Down, the Mixing Demand pointer
is displayed if there is a demand. However the control does not
operate the heating system to satisfy this demand. If the control is
in setpoint mode, the WWSD feature is not functional.
Section B3: Advanced
MIX MAX
MIX DSGN
OUT DSGN
WWSD Occ
ROOM Occ
ROOM UnOcc
WWSD UnOcc
210
(99)
190
(88)
170
(77)
150
(66)
130
(54)
110
(43)
90
(32)
70
(21)
(50°F)
(10°C)
-20
(-29)
0
(-18)
20
(-7)
40
(5)
60
(16)
80
(27)
Outdoor Air Temperature
Supply Water Temperature
Mixing Characterized
Heating Curve
Mixing Characterized
Heating Curve
MIX MIN
MIX INDR

© 2003 D 360e - 06/03 8 of 20
BOILER OPERATION
When the 360e determines that boiler operation is required, the Boiler contact terminals (7 and 8) close. While the Boiler con-
tact is closed, the burner segment in the LCD is displayed.
BOILER MINIMUM (BOIL MIN)
Most boilers require a minimum water temperature in order to prevent flue gas condensation. The BOIL MIN adjustment is set
to the boiler manufacturer’s minimum recommended operating temperature. Only when the boiler temperature is measured by
a boiler sensor can the 360e provide boiler protection. In this case when the boiler is firing and the boiler temperature is below
the BOIL MIN Setting the 360e turns on the MIN segment and reduces the heating load on the boiler by limiting the output of
the mixing valve. If the installed boiler is designed for low temperature operation, set the BOIL MIN adjustment to OFF.
BOILER PROTECTION
Refer to section A for a description of boiler protection.
BOILER SENSOR ON THE SUPPLY (Boiler Sensor DIP switch = Supply)
The boiler sensor can be located on the boiler supply if the 360e is the only control that
is operating the boiler. When in the supply mode, the 360e determines the required
operating temperature of the boiler using Boiler Load Reset. With Boiler Load Reset,
the 360e operates the boiler at the lowest possible supply temperature that is sufficient
to satisfy the requirements of the mixing valve. If this mode of operation is selected,
the boiler pump should either operate continuously, or be operated in parallel with the
system pump contact (Sys Pmp).
Note:T h e b o i l e r p u m p s h o u l d n o t b e o p e r a t e d b y t h e b o i l e r ’s a q u a s t a t , a s t h i s m a y l e a d t o
improper cycling of the boiler because of inconsistent flow past the boiler supply sensor.
BOILER DIFFERENTIAL (BOIL DIFF)
An on / off heat source such as a boiler must be operated with a
differential in order to prevent short cycling. When the boiler supply
temperature drops below the bottom rail of the differential, the 360e
closes the Boiler contact to fire the boiler. When the boiler supply
temperature rises above the top rail of the differential, the 360e
opens the Boiler contact to turn off the boiler. With the 360e, either
a fixed or automatic differential setting is selected. If automatic dif-
ferential (Ad) is selected, the 360e automatically adjusts the boiler
differential under the current load conditions to avoid short cycling.
BOILER SENSOR ON THE RETURN (Boiler Sensor DIP switch = Return)
The boiler sensor should be located on the boiler return if the 360e is one of many
controls that can call for boiler operation. When in the return mode, the 360e provides
a boiler enable as described in the BOILER ENABLE section. The 360e no longer tries
to control the boiler supply water temperature directly but allows the boiler to operate
at its operating aquastat setting when required. If this mode of operation is selected,
the boiler pump should either operate continuously or be operated in parallel with the
system pump contact (Sys Pmp).
Note:T h e b o i l e r p u m p s h o u l d n o t b e o p e r a t e d b y t h e b o i l e r ’ s a q u a s t a t , a s t h i s m a y l e a d t o
improper cycling of the boiler because of inconsistent flow past the boiler return sensor.
NO BOILER SENSOR
The 360e is capable of operating without a boiler sensor if desired. Without a boiler
sensor, the 360e provides a boiler enable as described in the BOILER ENABLE section,
but is unable to provide boiler protection. This type of application is typical if the 360e is
drawing heat from a heat source t h a t a l re a d y i n c o r p o r a t e s s o m e f o r m o f b o i l e r p r o t e c t i o n .
Section C: Boiler Operation
Section C1: General Operation
Section C1
General
Operation
Section C2
Boiler Sensor
Placement
Section C2: Boiler Sensor Placement
Boiler Supply
Sensor
B
o
i
l
e
r
O
n
B
o
i
l
e
r
O
n
Time
Supply Water Temperature
Differential = 10˚F (6˚C)
165˚F (74˚C)
160˚F (71˚C)
155˚F (68˚C)
Boiler Return
Sensor
No Boiler
Sensor

9 of 20 © 2003 D 360e - 06/03
BOILER ENABLE (30% Enable / 10% Enable)
The 360e has a DIP switch that allows for the selection between a 30% boiler enable and a 10% boiler enable. This switch is
only functional when the Boiler Sensor DIP switch is set to Return.
In the 30% position, the 360e closes the Boiler contact when the position of the mixing valve exceeds 30%. The Boiler contact
remains closed until the position of the mixing valve reduces below 15%. This setting would normally be chosen for low mass
boilers (copper fin-tube, etc.) or systems with low thermal mass in the loop between the boiler and the mixing valve.
In the 10% position, the 360e closes the Boiler contact when the position of the mixing valve exceeds 10%. The Boiler contact
remains closed until the position of the mixing valve reduces below 5%. This setting is normally chosen for high mass boilers
(cast iron, steel, fire-tube, etc.) or systems with large thermal mass in the loop between the boiler and the mixing valve.
In order to prevent short cycling, the Boiler contact has a minimum on time, and a minimum off time.
CAUTION
Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury.
It is your responsibility to ensure that this control is safely installed to all applicable codes and standards. This electronic
control is not intended for use as a primary limit control. Other controls that are intended and certified as safety limits must
be placed into the control circuit. Do not open the control. Refer to qualifed personnel for servicing. Opening voids warranty
and can result in damage to the equipment and possibly even personal injury.
STEP ONE GETTING READY
Check the contents of this package. If any of the contents listed are missing or damaged, please contact your wholesaler or
kanmor sales representative for assistance.
Type 360e includes: One Mixing Control 360e, One Outdoor Sensor 070e, Two Universal Sensors 071e, Data
Brochures D 360e, D 070e, Essay E 021e.
Note:CarefullyreadthedetailsoftheSequenceofOperationt o e n s u r e t h a t y o u h a v e c h o s e n t h e propercontrolforyourapplication.
STEP TWO MOUNTING THE BASE
Installation
Press down at the fingertip
grips on top of the front cover
and pull out and down.
Lift the front cover up and
away from the control.
Loosen the screws at the
front of the wiring cover.
The wiring cover pulls
straight out from the
wiring chamber.
Remove the safety dividers
from the wiring chamber by
pulling them straight out of
their grooves.
Press the control release
clip on the base inside the
wiring chamber and slide
the control upwards.
The control lifts up and away
from the base.
The base is ready for
mounting. There are
10 conduit knock-
outs at the back and
bottom of the wiring
chamber.
Release Clip
13 mounting holes

© 2003 D 360e - 06/03 10 of 20
STEP THREE ROUGH-IN WIRING
All electrical wiring terminates in the control base wiring chamber. The base has standard 7/8” (22 mm) knockouts which accept
common wiring hardware and conduit fittings. Before removing the knockouts, check the wiring diagram and select those sec-
tions of the chamber with common voltages. Do not allow the wiring to cross between sections, as the wires will interfere with
safety dividers, which should be installed at a later time.
Power must not be applied to any of the wires during the rough-in wiring stage.
• All wires are to be stripped to a length of 3/8” (9 mm) to ensure proper connection to the control.
• Install the Outdoor Sensor 070e according to the installation instructions in the Data Brochure D 070e and run the
wiring back to the control.
• Install the Mixing Sensor 071e according to the installation instructions in the Data Brochure D 070e and run the wiring
back to the control.
• If a Boiler Sensor 071e is used, install the sensor according to the installation instructions in the Data Brochure D 070e
and run the wiring back to the control.
• If an Indoor Sensor 076e is used, install the sensor according to the installation instructions in the Data Brochure D
070e and run the wiring back to the control.
• Run wire from other system components (pumps, boilers, etc.) to the control.
• Run wires from the 230 V (ac) power to the control. Use a clean power source with a 15 A circuit to ensure proper
operation. Multi-strand 16 AWG wire is recommended for all 230 V (ac) wiring due to its superior flexibility and ease of
installation into the terminals.
STEP FOUR ELECTRICAL CONNECTIONS TO THE CONTROL
The installer should test to confirm that no voltage is present at any of the wires. Push the control into the base and slide it down
until it snaps firmly into place.
Powered Input Connections
230 V (ac) Power
Connect the 230 V (ac) power supply to the Power L and Power N terminals (3
and 4). This connection provides power to the microprocessor and display of the
control. As well, this connection provides power to the Sys Pmp terminal (5) from
the Power L terminal (3).
Mixing Demand
To generate a mixing demand, a voltage between 24 V (ac) and 230 V (ac) must
be applied across the Mixing Demand terminals (1 and 2).
The control can be mounted
on a standard DIN rail. This
will be a popular option for
those who prefer to mount
the control inside a larger
electrical panel.
The wiring can enter the bottom
or the back of the enclosure.
Knock-outs provided in the base
allow the wiring to be run in con-
duit up to the enclosure. The
base also has holes that line up
with the mounting holes of most
common electrical boxes.
Power
4
230 V (ac)
LN
3
12
Mix
Demand
24 to 230 V (ac)

11 of 2 0 © 2003 D 360e - 06/03
Output Connections
System Pump Contact (Sys Pmp)
The Sys Pmp output terminal (5) on the 360e is a powered output. When the
relay in the 360e closes, 120 V (ac) is provided to the Sys Pmp terminal (5) from
the Power L terminal (3). To operate the system pump, connect one side of the
system pump circuit to terminal (5), and the second side of the pump circuit to the
neutral (N) terminal 6.
Mixing Valve Actuator
Terminals 9, 10 and 11 are isolated outputs from the control.
Connect one side of the actuator power to the Pwr Mix terminal
(9) on the control. The output relay Opn (10) is then connected
to the open terminal of the actuator and the output relay Cls (11)
is connected to the close terminal of the actuator. Connect the
second side of the actuator power to the common terminal of
the actuator.
Boiler Contact
The Boiler terminals (7 and 8) are an isolated output in the 360e. There is no
power available on these terminals from the control. These terminals are to
be used as a switch to either make or break the boiler circuit. When the 360e
requires the boiler to fire, it closes the contact between terminals 7 and 8.
Sensor and Unpowered Input Connections
Do not apply power to these terminals as this will damage the control.
Outdoor Sensor
Connect the two wires from the Outdoor Sensor 070e to the Com and Out termi-
nals (16 and 17). The outdoor sensor is used by the 360e to measure the outdoor
air temperature
Boiler Sensor
Connect the two wires from the Boiler Sensor 071e to the Com
and Boil terminals (13 and 14). The boiler sensor is used by the
360e to measure boiler temperature.
Mixing Sensor
Connect the two wires from the Mixing Sensor 071e to the Com
and Mix terminals (13 and 15). The mixing sensor is used by
the 360e to measure the supply water temperateure after the
mixing valve. Normally the sensor is attached to the pipe down-
stream of the system pump.
46
Power Sys
N
LPmp N
230 V (ac)
N
L
35
9
Pwr
Mix
10
Opn
11
Cls
1
Com
C
Opn Cls
23
N
L
Boiler
8
7
16 17
Com Out
Boiler Supply
Sensor
or
Boiler Return
Sensor
13 14
Com Boil
13
Com
14
Boil
15
Mix
Mix Supply
Sensor
System
Pump

© 2003 D 360e - 06/03 12 of 20
Indoor Sensor
If an indoor sensor is used, connect the two wires from the
sensor to the Com and Indr terminals (16 and 18). The indoor
sensor is used by the 360e to measure the room air temperature.
Unoccupied Switch
If an external timer (kanmor Timer 032e) or switch is used, connect the two wires
from the external switch to the UnO Sw and Com terminals (12 and 13). When these
two terminals are shorted together, the control registers an unoccupied signal.
STEP FIVE TESTING THE WIRING
Each terminal block must be unplugged from its header on the control before power is applied for testing. To remove a termi-
nal block, pull it straight down from the control.
The following tests are to be performed using standard testing practices and procedures, and should only be carried out by
properly trained and experienced persons.
A good quality electrical test meter, capable of reading from at least 0 -300 V (ac) and at least 0 -2,000,000 Ohms, is essential
to properly test the wiring and sensors.
Test The Sensors
In order to test the sensors, the actual temperature at each sensor
location must be measured. A good quality digital thermometer
with a surface temperature probe is recommended for ease of
use and accuracy. Where a digital thermometer is not available, a
spare sensor can be strapped alongside the one to be tested, and
the readings compared. Test the sensors according to the instruc-
tions in the Data Brochure D 070e.
Test The Power Supply
Make sure exposed wires and bare terminals are not in contact
with other wires or grounded surfaces. Turn on the power and
measure the voltage between the Power L and PowerNterminals
(3 and 4) using an AC voltmeter. The reading should be between
207 and 253 V (ac).
Test The Powered Inputs
Mixing Demand
Measure the voltage between the Mixing Demand terminals
(1 and 2). When the mixing demand device calls for heat, you
should measure between 20 and 260 V (ac) at the terminals.
When the mixing demand device is off, you should measure
less than 5 V (ac).
16
Com
17
Out
18
Indr
12
UnO
Sw
13
Com
Timer Switch
13
Com
14
Boil
15
Mix
L
N
4
Power
V
207 to 253 V (ac)
3
1
2
Mixing
Demand
V
20 to 260 V (ac)

13 of 20 © 2003 D 360e - 06/03
Test The Outputs
System Pump (Sys Pmp)
If a system pump is connected to the Sys Pmp terminal (5)
and N terminal (6), make sure that power to the terminal block
is off, and install a jumper between the PowerLand the Sys
Pmp terminals (3 and 5). Install a second jumper between the
PowerNand Nterminals (4 and 6). When power is applied to
the PowerLand PowerNterminals (3 and 4), the system pump
should start. If the pump does not turn on, check the wiring
between the terminal block and pump, and refer to any instal-
lation or troubleshooting information supplied with the pump. If
the pump operates properly, disconnect the power and remove
the jumpers.
Boiler
If the boiler circuit is connected to the Boiler terminals (7 and 8), make sure power to the boiler circuit is off, and install a
jumper between the terminals. When the boiler circuit is powered up, the boiler should fire. If the boiler does not turn on, refer
to any installation or troubleshooting information supplied with the boiler (The boiler may have a flow switch that prevents
firing until the boiler loop pump is running). If the boiler operates properly, disconnect the power and remove the jumper.
Mixing Valve Actuator
Make sure power to the actuator circuit is off and install a jumper between the Pwr Mix (9) and the Opn (10) terminals.
When the circuit is powered up, the actuator should move in the open direction. If it does not, check the wiring between the
terminals and the actuator. Refer to any installation or troubleshooting information supplied with the actuator. If the motor
closes instead of opening, the wiring of the actuator must be reversed. If the valve opens correctly, turn off the power to
the circuit and remove the jumper. Install a jumper between the Pwr Mix (9) and the Cls (11) terminals. When the circuit is
powered up, the valve should move in the closing direction. If it does not, check the wiring between the terminals and the
actuator. Refer to any installation or troubleshooting information supplied with the motor. If the motor closes correctly, turn
off the power to the circuit and remove the jumper.
Connecting The Control
Make sure all power to the devices and terminal blocks is off, and remove any
remaining jumpers from the terminals.
Reconnect the terminal blocks to the control by carefully aligning them with their
respective headers on the control, and then pushing the terminal blocks into the
headers. The terminal blocks should snap firmly into place.
Install the supplied safety dividers between the unpowered sensor inputs and the
powered 230 V (ac) or 24 V (ac) wiring chambers.
Apply power to the control. The operation of the control on power up is described in
the Sequence of Operation section of this brochure.
The control’s exterior can be cleaned using a damp cloth. Moisten cloth with water and wring out prior to wiping control. Do not
use solvents or cleaning solutions.
The DIP Switch settings on the control are very important and should be set to the
appropriate settings prior to making any adjustments to the control through the user
interface. The DIP switch settings change the items that are available to be viewed
and / or adjusted in the user interface.
ADVANCED / INSTALLER
The Advanced / Installer DIP swi tch i s used to sel ect which items are available to be viewed and / or adjusted in the user interface.
30% ENABLE / 10% ENABLE
The position of the 30 %Enable / 10 %Enable DIP switch determines at which valve position the control will close the Boiler con-
tact under normal conditions. This switch is only operational if the Boiler Sensor DIP switch is set to Return. Refer to section C2.
Cleaning
DIP Switch Settings
46
Power Sys
N
LPmp N
230 V (ac)
System
Pump
N
L
35
12
Boil
UnO
Sw
Com
Mix
Com
13 14 15 16
30% Enable
10% Enable
Advanced
Installer
Return
Supply
Boiler Sensor

© 2003 D 360e - 06/03 14 of 20
BOILER SENSOR (RETURN / SUPPLY)
The Boiler Sensor DIP switch selects the installation location for the boiler sensor. When the boiler sensor is installed on the
supply side of the boiler loop, the DIP switch must be set to Supply. The boiler aquastat should be set at least 20 °F (11 °C)
higher than the required design boiler water temperature. The boiler is controlled as described in section C.
For systems where the 360e provides a heat demand to an external boiler control, the boiler sensor should be installed on the
return side of the boiler loop. When the boiler sensor is installed on the return side of the boiler loop, the DIP switch must be
set to Return. The 360e enables the boiler when the position of the mixing valve exceeds the boiler enable DIP switch setting.
The Boiler contact is controlled as described in section C. The boiler’s operating temperature is controlled by its aquastat, or
an external boiler reset control.
The quick setup can be used for both outdoor reset and setpoint operation. To enter the installer programming mode, set the
Advanced / Installer DIP switch to Installer.
OUTDOOR RESET
Access the ADJUST menu by pressing and holding simultaneously for 1 second, the Item, ▲and ▼buttons. The display will
now show the word ADJUST in the top right corner.
TheROOMOCCadjustmentisthefirstitemdisplayed.Usethe▲or▼buttontosettheROOMtemperature.
The ROOM OCC setting is set to the desired room air temperature during the occupied (Day) mode.
Note: To increase or decrease space temperature during the occupied (Day) mode, only adjust the
ROOM OCC setting.
Press and release the Item button to advance to the ROOM UNOCC adjustment. Use the ▲or ▼
button to set the desired temperature. The ROOM UNOCC setting is set to the desired room air
temperature during the unoccupied (Night) mode.
Note: To increase or decrease space temperature during the unoccupied (Night) mode, only adjust
the ROOM UNOCC setting.
Press and release the Item button to advance to the OUTDR DSGN adjustment. Use the ▲or ▼
button to set the outdoor design temperature. The OUTDR DSGN setting is set to the typical coldest
temperature of the year.
Press and release the Item button to advance to the Terminal Unit adjustment. Use the ▲or ▼
button to select the desired terminal unit. The terminal unit number corresponds to the type of termi-
nal that is being used. The table below lists the terminal units and their default values.
Press and release the Item button to advance to the units adjustment. Use the ▲or ▼button to set
the scale to °F or °C.
To exit the ADJUST menu, press and release the Item button to advance to the ESC item. Then
either press the ▲or ▼button, or leave the buttons alone for 20 seconds.
Quick Setup
Terminal
TERMINAL
UNIT
HIGH MASS RADIANT
(1)
LOW MASS RADIANT
(2)
FANCOIL
(3)
FIN-TUBE CONVECTOR
(4)
RADIATOR
(5)
BASEBOARD
(6)
MIX DSGN
MIX MAX
MIX MIN
120°F (49°C)
140°F (60°C)
OFF
140°F (60°C)
160°F (71°C)
OFF
190°F (88°C)
210°F (99°C)
100°F (38°C)
180°F (82°C)
200°F (93°C)
OFF
160°F (71°C)
180°F (82°C)
OFF
150°F (66°C)
170°F (77°C)
OFF

15 of 20 © 2003 D 360e - 06/03
View Menu (1 of 1)
SETPOINT CONTROL
Access the ADJUST menu by pressing and holding simultaneously for 1 second, the Item, ▲and ▼buttons. The display will
now show the word ADJUST in the top right corner.
Press and release the Item button to advance to the OUTDR DSGN adjustment. Press and hold the
▲ button until OFF is displayed.
Press and release the Item button to advance to the MIX TARGET adjustment. Use the ▲or ▼button to
selectthedesiredtemperature.TheMIXTARGETsettingissettothedesiredsetpointsupplytemperature.
Press and release the Item button to advance to the units adjustment. Use the ▲or ▼button to set
the scale to °F or °C.
To exit the ADJUST menu, press and release the Item button to advance to the ESC item. Then
either press the ▲or ▼button, or leave the buttons alone for 20 seconds.
Section
Installer
Advanced
RangeDescriptionDisplay
Current outdoor air temperature as measured by the outdoor
sensor. This is also the default display for the control.
(OUTDR DSGN ≠OFF)
Current room air temperature as measured by the indoor sensor.
(Indoor Sensor is present)
Current mixed supply water temperature as measured by the
mixing sensor
Target mixed supply is the temperature the control is currently
trying to maintain at the mixing sensor.
Current boiler temperature as measured by the boiler sensor.
(Boiler sensor is present)
-67 to 149°F
(-55 to 65°C)
23 to 113°F
(-5 to 45°C)
---, 14 to 266˚F
(---, -10 to 130˚C)
14 to 266°F
(-10 to 130°C)
14 to 266°F
(-10 to 130°C)
B1
B3
B2
B1
B3

© 2003 D 360e - 06/03 16 of 20
Adjust Menu (1 of 2)
Section
Installer
Advanced
Range Actual
Setting
DescriptionDisplay
B2
The desired room air temperature during an
occupied (Day) period.
(OUTDR DSGN ≠OFF)
35 to 100°F
(2 to 38°C)
The desired room air temperature during an
unoccupied (Night) period.
(OUTDR DSGN ≠OFF)
35 to 100°F
(2 to 38°C)
B2
Mixing setpoint temperature.
(OUTDR DSGN = OFF)
60 to 200°F
(16 to 93°C)
B2
The design outdoor air temperature used in the
heat loss calculation for the heating system. For
setpoint operation, set the OUTDR DSGN to OFF
-60 to 32°, OFF
(-51 to 0°C, OFF)
B2
The design indoor air temperature used in the
heat loss calculation for the heating system.
(OUTDR DSGN ≠OFF)
35 to 100°F
(2 to 38°C)
B3
The design supply water temperature used in
the heat loss calculation for the heating system.
(OUTDR DSGN ≠OFF)
70 to 220°F
(21 to 104°C)
B3
The maximum supply water temperature for the
mixing system
(OUTDR DSGN ≠OFF)
80 to 210°F
(27 to 99°C)
B3
The minimum supply temperature for the
mixing system.
(OUTDR DSGN ≠OFF)
OFF, 35 to 150°F
(OFF, 2 to 65°C)
B3
The minimum temperature allowed for the boiler
target temperature.
(Boiler sensor is present)
OFF, 80 to 180°F
(OFF, 27 to 82°C)
C1
The type of terminal units that are being used
in the heating system.
(OUTDR DSGN ≠OFF)
1 (High Ma
ss
Radiant
2 (Low Mass Radiant
3 (Fancoil)
4 (Fin-tube Convector
5 (Radiator)
6 (Baseboard)
B2
Terminal Unit
The time that the actuating motor requires to
operate from fully closed to fully open.
30 to 230 seconds
(1 sec. increments)
A
Motor Speed

17 of 20 © 2003 D 360e - 06/03
Section
Installer
Advanced
Range Actual
Setting
DescriptionDisplay
C2
The differential that the control is to use when
it is operating the boiler.
(Boiler Sensor DIP switch = Supply AND
Boiler sensor is present)
Ad, 2 to 42°F
(Ad, -17 to 6°C)
The system's warm weather shut down during
the occupied (Day) period.
35 to 100°F, OFF
(2 to 38°C, OFF)
B3
The system's warm weather shut down during
the unoccupied (Night) period.
35 to 100°F, OFF
(2 to 38°C, OFF)
B3
The units of measure that all of the temperatures
are to be displayed in the control. °F, °C
This item exits the ADJUST menu by pressing
either the ▲ or ▼ button.
Adjust Menu (2 of 2)
Testing the Control
The Mixing Control 360e has a built-in test routine which is used to test the main control
functions. The 360e continually monitors the sensors, and displays an error message
whenever a fault is found. See the following pages for a list of the 360e’s error mes-
sages and possible causes. When the Test button is pressed, the test light is turned
on. The individual outputs and relays are tested in the following test sequence.
TEST SEQUENCE
Each step in the test sequence lasts 10 seconds.
During the test routine, the test sequence may be paused by pressing the Test button. Only if there is a mixing demand can the
control be paused in a step. If the Test button is not pressed again for 5 minutes while the test sequence is paused, the control
exits the entire test routine. If the test sequence is paused, the Test button can be pressed again to advance to the next step.
This can also be used to rapidly advance through the test sequence. To reach the desired step, repeatedly press and release
the Test button until the appropriate device and segment in the display turn on.
Step 1 - The mixing valve is run fully open.
Step 2 - The mixing valve is run fully closed, and then the system pump (Sys Pmp) is turned on.
Step 3 - The Boiler contact is turned on for 10 seconds. After 10 seconds, the Boiler and Sys Pmp contacts are shut off.
Step 4 - After the test sequence is completed, the control resumes its normal operation.
Test

© 2003 D 360e - 06/03 18 of 20
Troubleshooting
Establish the
Problem
Understanding
the Sequence of
Operation
Use the Test
Routine
Sketch the
Piping in the
System
Document the
Control
Isolate the
Problem
Test the Con-
tacts, Voltages
and Sensors
When troubleshooting any heating system, it is always a good idea to establish a set routine to follow. By following a consistent
routine, many hours of potential headaches can be avoided. Below is an example of a sequence that can be used when diag-
nosing or troubleshooting problems in a hydronic heating system.
Establish the problem. Get as much information from the customer as possible about the problem.
Is there too much heat, not enough heat, or no heat? Is the problem only in one particular zone
or area of the building, or does the problem affect the entire system? Is this a consistent problem
or only intermittent? How long has the problem existed for? This information is critical in correctly
diagnosing the problem.
Understand the sequence of operation of the system. If a particular zone is not receiving enough
heat, which pumps or valves in the system must operate in order to deliver heat to the affected
zone? If the zone is receiving too much heat, which pumps, valves, or check valves must operate in
order to stop the delivery of heat?
Press the Test button on the control and follow the control through the test sequence as described
in the Testing section. Pause the control as necessary to ensure that the correct device is operating
as it should.
Sketch the piping of the system. This is a relatively simple step that tends to be overlooked, how-
ever, it can often save hours of time in troubleshooting a system. Note flow directions in the system
paying close attention to the location of pumps, check valves, pressure bypass valves, and mixing
valves. Ensure correct flow direction on all pumps. This is also a very useful step if additional assis-
tance is required.
Document the control for future reference. Before making any adjustments to the control, note down
all of the items that the control is currently displaying. This includes items such as error messages,
current temperatures and settings, and which devices should be operating as indicated by the LCD.
This information is an essential step if additional assistance is required to diagnose the problem.
Isolate the problem between the control and the system. Now that the sequence of operation is
known and the system is sketched, is the control operating the proper pumps and valves at the cor-
rect times? Is the control receiving the correct signals from the system as to when it should be oper-
ating? Are the proper items selected in the menus of the control for the device that is to be operated?
Test the contacts, voltages and sensors. Using a multimeter, ensure that the control is receiving ade-
quate voltage to the power terminals and the demand terminals as noted in the technical data. Use
the multimeter to determine if the internal contacts on the control are opening and closing correctly.
Follow the instructions in the Testing the Wiring section to simulate closed contacts on the terminal
blocks as required. Test the sensors and their wiring as described in the sensor Data Brochures.

19 of 20 © 2003 D 360e - 06/03
Error Messages
The control was unable to read a piece of information from its EEPROM. This error can be caused
by a noisy power source. The control will load the factory defaults and stop operation until all the
settings are verified.
The control is no longer able to read the outdoor sensor due to a short circuit. In this case the con-
trol assumes an outdoor temperature of 32°F (0°C) and continues operation. Locate and repair the
problem as described in the Data Brochure D 070e. To clear the error message from the control after
the sensor has been repaired, press the Item button.
The control is no longer able to read the outdoor sensor due to an open circuit. In this case the
control assumes an outdoor temperature of 32°F (0°C) and continues operation. Locate and repair
the problem as described in the Data Brochure D 070e. To clear the error message from the control
after the sensor has been repaired, press the Item button.
The control is no longer able to read the mixing supply sensor due to a short circuit. In this case the
control will operate the mixing valve at a fixed output as long as there is a mixing demand. Locate
and repair the problem as described in the Data Brochure D 070e. To clear the error message from
the control after the sensor has been repaired, press the Item button.
The control is no longer able to read the mixing supply sensor due to a short circuit. In this case the
control will operate the mixing valve at a fixed output as long as there is a mixing demand. Locate
and repair the problem as described in the Data Brochure D 070e. To clear the error message from
the control after the sensor has been repaired, press the Item button.
The control is no longer able to read the boiler sensor due to a short circuit. If the BOIL MIN adjust-
ment is higher than 100°F (38°C), the control closes the Boiler contact when the mixing valve starts
to operate. The boiler temperature is then limited by the operating aquastat. If the BOIL MIN adjust-
ment is lower than 100°F (38°C), the control does not operate the Boiler contact. Locate and repair
the problem as described in the Data Brochure D 070e. To clear the error message from the control
after the sensor has been repaired, press the Item button.
The control is no longer able to read the boiler sensor due to an open circuit. If the BOIL MIN adjust-
ment is higher than 100°F (38°C), the control closes the Boiler contact when the mixing valve starts
to operate. The boiler temperature is then limited by the operating aquastat. If the BOIL MIN adjust-
ment is lower than 100°F (38°C), the control does not operate the Boiler contact. Locate and repair
the problem as described in the Data Brochure D 070e. If the boiler sensor is deliberately removed,
the control must be powered down, and then powered back up. To clear the error message from the
control after the sensor has been repaired, press the Item button.
The control is no longer able to read the indoor sensor due to a short circuit. The control will con-
tinue to operate as if there was nothing connected to the indoor sensor input. Locate and repair the
problem as described in the Data Brochure D 070e. To clear the error message from the control after
the sensor has been repaired, press the Item button.
The control is no longer able to read the indoor sensor due to an open circuit. The control will con-
tinue to operate as if there was nothing connected to the indoor sensor input. Locate and repair the
problem as described in the Data Brochure D 070e. If the indoor sensor is deliberately removed,
the control must be powered down, and then powered back up. To clear the error message from the
control after the sensor has been repaired, press the Item button.

Technical Data
20 of 20
© 2003. All rights reserved.
Used under license by kanmor Control Systems Ltd.
All specifications are subject to change without notice.
Printed in Canada. D 360e - 06/03.
kanmor Control Systems Ltd.
5100 Silver Star Road
Vernon, B.C. CANADA V1B 3K4
250-545-2693 Fax. 250-549-4349
Web Site: www.kanmor.com
Limited Warranty and Product Return Procedure
Limited Warranty The liability of kanmor Control Systems Ltd.
(“kanmor”) under this warranty is limited. The Purchaser, by taking
receipt of any kanmor product (“Product”), acknowledges the terms
of the Limited Warranty in effect at the time of such Product sale and
acknowledges that it has read and understands same.
The kanmor Limited Warranty to the Purchaser on the Products sold
hereunder is a manufacturer’s pass-through warranty which the Purchaser
is authorized to pass through to its customers. Under the Limited Warranty,
each kanmor Product is warranted against defects in workmanship and
materials if the Product is installed and used in compliance with kanmor’s
instructions, ordinary wear and tear excepted. The pass-through warranty
period is for a period of twenty-four (24) months from the production date
if the Product is not installed during that period, or twelve (12) months from
the documented date of installation if installed within twenty-four (24) months
from the production date.
The liability of kanmor under the Limited Warranty shall be limited to, at
kanmor’s sole discretion: the cost of parts and labor provided by kanmor to
repair defects in materials and/or workmanship of the defective product; or
to the exchange of the defective product for a warranty replacement product;
or to the granting of credit limited to the original cost of the defective product,
and such repair, exchange or credit shall be the sole remedy available
from kanmor, and, without limiting the foregoing in any way, kanmor is not
responsible, in contract, tort or strict product liability, for any other losses,
costs, expenses, inconveniences, or damages, whether direct, indirect,
special, secondary, incidental or consequential, arising from ownership or
use of the product, or from defects in workmanship or materials, including
any liability for fundamental breach of contract.
The pass-through Limited Warranty applies only to those defective Products
returned to kanmor during the warranty period. This Limited Warranty does not
cover the cost of the parts or labor to remove or transport the defective Product,
or to reinstall the repaired or replacement Product, all such costs and expenses
being subject to Purchaser’s agreement and warranty with its customers.
Any representations or warranties about the Products made by Purchaser
to its customers which are different from or in excess of the kanmor Limited
Warranty are the Purchaser’s sole responsibility and obligation. Purchaser
shall indemnify and hold kanmor harmless from and against any and all
claims, liabilities and damages of any kind or nature which arise out of or
are related to any such representations or warranties by Purchaser to its
customers.
The pass-through Limited Warranty does not apply if the returned Product
has been damaged by negligence by persons other than kanmor, accident,
fi re, Act of God, abuse or misuse; or has been damaged by modifications,
alterations or attachments made subsequent to purchase which have not
been authorized by kanmor; or if the Product was not installed in compliance
with kanmor’s instructions and/or the local codes and ordinances; or if due
to defective installation of the Product; or if the Product was not used in
compliance with kanmor’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS
OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO
CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION,
IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR
A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE
PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS
OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLATION
OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY
LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY
CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL
NOT EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE
PRODUCTION DATE, TO THE EXTENT THAT SUCH LIMITATION IS
ALLOWED BY THE GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to have
defects in workmanship or materials must be returned, together with a written
description of the defect, to kanmor through its Representative. If kanmor
receives an inquiry from someone other than a kanmor Representative,
including an inquiry from Purchaser (if not a kanmor Representative) or
Purchaser’s customers, regarding a potential warranty claim, kanmor’s sole
obligation shall be to provide the address and other contact information
regarding the appropriate Representative.
Caution The nonmetallic enclosure does not provide grounding between conduit connections. Use grounding type bushings and
jumper wires.
Mixing Control 360e Floating Action
Literature — D 360e, D 070e, E 021e.
Control — Microprocessor PID control; This is not a safety (limit) control.
Packaged weight — 2.8 lb. (1250 g), Enclosure A, blue PVC plastic
Dimensions — 6-5/8” H x 7-9/16” W x 2-13/16” D (170 x 193 x 72 mm)
Approvals — CE approved, meets ICES & FCC regulations for EMI/RFI.
Ambient conditions — Indoor use only, 32 to 102°F (0 to 39°C), < 90% RH non-
condensing. Altitude <2000 m, Installation Category II,
Pollution Category II.
Power supply — 230 V ±10% 50 Hz 2300 VA
System Pump Relay — 230 V (ac) 10 A 1/3 hp, pilot duty 240 VA
Boiler Relay — 230 V (ac) 10 A 1/3 hp, pilot duty 240 VA
Open Relay — 230 V (ac) 10 A 1/3 hp, pilot duty 240 VA
Close Relay — 230 V (ac) 10 A 1/3 hp, pilot duty 240 VA
Mix Demand — 20 to 260 V (ac) 2 VA
Sensors included — NTC thermistor, 10 kΩ@ 77°F (25°C ±0.2°C) fl=3892
Outdoor Sensor 070e and 2 of Universal Sensor 071e.
Optional devices — kanmor type #: 032e, 070e, 071e, 076e, 079e.
Do not apply power
Signal wiring must be
rated at least 300 V.
LNPmpN Sw
Sys UnO Com Boil
Mix
Pwr Opn Cls Mix Com Out Indr
13 52
4
6
91078 11 12
13 14
15
16 17
18
Mix Power Boiler
Demand
Advanced
Installer
Boiler Sensor
Supply
30% Enable
10% Enable
Return
Item Test
Terminal
Unit
Mixing
Demand
INSTALLATION CATEGORY II
Made in Canada
Power: 230 V ±10% 50 Hz 2300 VA
Relays: 230 V (ac) 10 A 1/3 hp, pilot duty 240 VA
Demand: 20 to 260 V (ac) 2 VA
H1211B
To increase or decrease the
building temperature:
• Press the Item,▲,▼buttons
simultaneously for 1 sec. to
enter the ADJUST menu
• Use the ▲,▼buttons to adjust
the ROOM setting
Display defaults back to VIEW
menu after 20 seconds.
ROOM - Set to desired room temperature.
OUTDR DSGN - Set to coldest (design)
outdoor temperature.
Terminal Unit Set to
High Mass Radiant 1
Low Mass Radiant 2
Fan Coil 3
Convector 4
Radiator 5
Baseboard 6
Refer to brochure for more information.
Installer Instructions
Mixing Control 360e
Floating Action
Open
Motor
Speed
Close
Table of contents