Installation Guide
Pressure Monitoring
Installation Guide
Pressure Monitoring
Installation Guide
Pressure Monitoring
Installation Guide
Pressure Monitoring
®
®
®
®
Product Identication
Dimensions
Product Overview
The KDP2M transducer can measure either air pressure or velocity with the ip of a
switch. The KDP2M is available in three installation congurations: duct, panel or
universal. Duct and panel models have two pressure and velocity options: 0-1 in. WC /
0-3,000 ft/min or 1-10 in. WC / 3,000-6,000 ft/min with four eld-selectable sub-ranges.
The universal model comes in one pressure/velocity range: 0-10 in. WC / 0-6,000 ft/
min with seven eld-selectable sub-ranges. All variants are available with and without
display. The KDP2M has an IP65/NEMA 4 environmental rating and a 5-year limited
warranty.
KDP2M Series
Differential Pressure / Air Velocity Transducer
KDP2M
Enclosure Local Display
D = Duct
P = Panel
Range
1 = Pressure: 0 to 1 in. WC / 0 to 250 Pa
Velocity: 0 to 3,000 ft/min / 0 to 15 m/s
10 = Pressure: 1 to 10 in. WC/250 to 2,500 Pa
Velocity: 0 to 6,000 ft/min / 0 to 30 m/s
Local DisplayRange
010 = Pressure: 0 to 10 in. WC / 0 to 2,500 Pa
Velocity: 0 to 7,000 ft/min / 0 to 35 m/s
in. (mm)
KDP2M
Patent Pending
Specications
Installation, Wiring
& Conguration
FILTER
LOW HIGH
AIR FLOW
AIR FLOW
AIR FLOW
AIR FLOW
Static Pressure
Panel Installations
Duct Installations
Dierential Pressure
1. Plan the installation. Panel or duct mount?
2. For duct mount applications, thread the probe into the back of the device housing, as
shown in the dimensional drawing.
3. Congure the internal tubing for the selected installation method as described below.
Duct mount tubing conguration:
a. Connect the right-side tube to the rear brass barb marked as “-” on the
underside of the device housing.
b. Connect the left-side tube to the probe in the back of the device housing.
Panel mount tubing conguration:
a. Connect the right-side tube to the rear brass barb marked as “-” on the
underside of the device housing.
b. Connect the left-side tube to the front brass barb marked as “+” on the
underside of the device housing.
Installation, Wiring
& Conguration (cont.)
4. Mount the transducer (see the screw hole diagram below).
5. For applications using conduit, remove the cable gland nut on the bottom of the unit.
Thread a standard 1/2-inch NPT female threaded coupler onto the body of the cable
gland. Connect the opposite end of the coupler to the conduit.
Tubing for Duct Mount Tubing for Panel Mount
Tubing for Duct Mount Tubing for Panel Mount
2.3
(59)
CTR-CTR
3.3
(83)
R
2.5
(62)
To Pickup
Tube
1.4
(35)
0.5
(13)
3.2
NOTICE
•
This product is not intended for life or
safety applications.
• Do not install this product in hazardous
or classied locations.
•
Read and understand the instructions
before installing this product.
• Turn o all power supplying equipment
before working on it.
•
The installer is responsible for
conformance to all applicable codes.
If this product is used in a manner not specied
by the manufacturer, the protection provided
by the product may be impaired. No
responsibility is assumed by the manufacturer
for any consequences arising out of the use of
this material.
Z207542-0B Page 2 of 8 ©2018 Kele / USA 888-397-5363 / info@kele.com 0818
Z207542-0B Page 4 of 8 ©2018 Kele / USA 888-397-5363 / info@kele.com 0818
Z207542-0B Page 1 of 8 ©2018 Kele / USA 888-397-5363 / info@kele.com 0818
Z207542-0B Page 3 of 8 ©2018 Kele / USA 888-397-5363 / info@kele.com 0818
KDP2MU - --
- -
-
LCD = LCD Display
X = No Display
N = NIST
X = None
N = NIST
X = None
LCD = LCD Display
X = No Display
For velocity applications, use the FXP Series air velocity/measurement probe or AA18,
AA19 or AA20 velocity pitot tubes. For use with the PX3P (panel) and PX3U (universal)
models in Velocity mode only. Sold separately.
AIR FLOW
Velocity with FXP Probe Velocity with AA18/AA19/AA20 Pitot Tube
AIR FLOW
1.6
(42)
1.6
(42)
3.5
(88)
3.5
(88)
4.4
(112)
7.4
(188)
0.
(7
3.1
(78)
Media Compatibility Dry air or inert gas
Input Power Three-wire Volt mode: 24 Vac or 12-30 Vdc*
Two-wire mA mode: 12-30 Vdc*
Output Power Field-selectable: 2-wire, loop-powered 4-20 mA
Minimum input voltage for 4 to 20 mA operation: 250 Ω loop = 12 Vdc; 500 Ω loop = 19 Vdc
(DC only, clipped and capped), 24 Vac/dc or 3-wire 0-5V/0-10V
Minimum load resistance for Volt operation: 5 kΩ
Pressure
Range 1
Pressure
Mode
Unidirectional: 0.1/0.25/0.5/1 in. WC FS, switch selectable
Bidirectional: ±0.1/±0.25/±0.5/±1 in. WC FS, switch selectable
Unidirectional: 25/50/100/250 Pa FS, switch selectable
Bidirectional: ±25/±50/±100/±250 Pa FS, switch selectable
Velocity
Mode
500/1,000/2,000/3,000 ft/min
2.5/5/10/15 m/s
Pressure
Range 10
Pressure
Mode
Unidirectional: 1.0/2.5/5/10 in. WC FS, switch selectable
Bidirectional: ±1.0/±2.5/±5/±10 in. WC FS, switch selectable
Unidirectional: 250/500/1,000/2500 Pa FS, switch selectable
Bidirectional: ±250/±500/±1,000/±2500 Pa FS, switch selectable
Velocity
Mode
3,000/4,000/5,000/6,000 ft/min
15/20/25/30 m/s
Pressure
Range 010
Pressure
Mode
Unidirectional: 0.1/0.25/0.5/1/2.5/5/10 in. WC FS, switch selectable
Bidirectional: ±0.1/±0.25/±0.5/±1/±2.5/±5/±10 in. WC FS, switch selectable
Unidirectional: 25/50/100/250/500/1,000/2500 Pa FS, switch selectable
Bidirectional: ±25/±50/±100/±250/±500/±1,000/±2500 Pa FS, switch selectable
Velocity
Mode
500/1,000/2,000/3,000/4,000/5,000/6,000/7,000 ft/min
2.5/5/10/15/20/25/30/35 m/s
Response Time Standard: T95 in 20 sec, Fast: T95 in 2 sec, DIP switch selectable
Mode Unidirectional or bidirectional, DIP switch selectable
Display (Option) Pressure mode: Signed 3-1/2 digit LCD, indicates pressure, overrange indicator
Velocity mode: Signed 4-1/2 digit LCD, indicates velocity, overrange indicator
Proof Pressure 3 psid (20, 600 Pa)
Burst Pressure 5 psid (34, 500 Pa)
Pressure Mode Accuracy ±1% FS (combined linearity and hysteresis)
Velocity Mode Accuracy ±90 ft/min (±0.45 m/s) plus 5% of measured value**
Temperature Eect 1” (250 Pa) models: 0.05%/°C; 10” (2,500 Pa) models: 0.01%/°C
(Relative to 25 °C) 0 to 50 °C (32 to 122 °F)
Zero Drift (1-year) 1” (250 Pa) models: 2.0% max.; 10” (2,500 Pa) models: 0.5% max.
Zero Adjust Pushbutton auto-zero and digital input (2-position terminal block)
Operating Environment 0 to 60 °C (32 to 140 °F)
Altitude of Operation 0 to 3,000 m
Pollution Degree 2
Humidity Range 100% RH, non-condensing
Mounting Location For indoor use only.
Fittings Brass barb; 0.24” (6.1 mm) o.d.
Suggested Cable Shielded:
Belden #9939 (22 AWG) 3-wire multi-conductor (or similar)
Belden #9940 (22 AWG) 4-wire multi-conductor (or similar)
Belden #9939 (22 AWG) 5-wire multi-conductor (or similar)
Unshielded:
Belden #8443 (22 AWG) 3-wire multi-conductor (or similar)
Belden #8444 (22 AWG) 4-wire multi-conductor (or similar)
Belden #8445 (22 AWG) 5-wire multi-conductor (or similar)
Environmental Rating IP65, NEMA 4
Flammability Rating UL 94 5VA re retardant ABS, plenum rated
Limited Warranty 5 years
EMC Conformance: EN 61000-6-3 and A1 Class B, EN 61000-6-1. * Class 2/II power source. ** For measured values between 200 and 7000 ft/min (1 and 35 m/s).
1/2-inch NPT female threaded coupler