Table 2. Service parameters list.
Disp. Parameter Min Max Step Factory
default.
Π100 Blower work capacity or maximum capacity when
Πr 1. 1 100 1% 100
n 40 Blower minimum capacity. 1 100 1% 40
Πh 5 Ratio of blower speed change. 2 20 1 5
Πr 0 Automatic regulation of blower speed. -, 0 10 1 0
Πn 5 Induced draught duration. --, 5 60 1s 5
Πu 6 Draught interval duration. 1 99 1min 6
r 50 Blower maximum speed at ignition. 1 100 1% 50
rh 5 Hysteresis of ignition turn-off. 1 45 1°C 5
P 40 Temperature of central heating pump turn-on. --, 20 70 1°C 40
Ph 2 Hysteresis of central heating pump turn-on. 1 40 1°C 2
Pc 2 30 second interval while turning on central heating
pump . --, 1 99 1min 2
ur 0 Sensor and additional pump working mode. 0 4 1 0
u 50 Additional pump operating temperature. 30 60 1°C 50
uh 5 Hysteresis of additional pump work. 1 30 1°C 5
uP 5 Increase in boiler temperature while heating
domestic water. 1 20 1°C 5
L 45 Boiler minimum temperature. 30 65 1°C 45
H 85 Boiler maximum temperature. 80 95 1°C 85
h 2 Hysteresis of boiler temperature. 1 10 1°C 2
A 99 Hysteresis of boiler temperature. 90 99 1°C 99
Fd2h Fuel shortage testing time with burning. --, 1 99-4h 1min 2h
Fb2h Duration of fuel demand testing in working mode. --, 1 99-4h 1min 2h
Ar 0 Additional output: 0-FUEL, 1-ALARM. 0 1 1 0
c--- Temperature of exhaust gases/exhaust gases
sensor turn-off. ---, 50 250 1°C ---
ch10 Hysteresis of exhaust gases temperature. 1 99 1°C 5
ct 5 Time constant of exhaust gases temperature
stabilization. 1 99 1 min 5
cF10 Blower speed jump while stabilizing exhaust gases
temperature. 1 20 1% 10
c90 Temperature of exhaust gases while detecting fuel
demand. 30 150 1°C 90
Prod Restoring producer’s settings after pressing OK
button.
outΠ Testing blower output. outΠ out1
outP Testing central heating pump output. outP out2
outu Testing additional pump output. outu out3
outr Testing additional output. outr out4
End Exiting service mode after pressing OK button.
Examples of display indications are shown in the first column. The next columns
contain: description of a parameter, the minimum and maximum values that may be
programmed as well as the jump of a value while setting. The values
preprogrammed by the producer can be found in the last column – it is possible to
restore them by selecting the [Prod] option.