Kidde Fire Systems DS Series User guide

w
K-73-200 Rev AB July 2015
w
DS Series Addressable Detector
Application Guide
K-76-1000


July 2016 -1- K-76-1000
FOREWORD

K-76-1000 -2- July 2016
PURPOSE OF THIS GUIDE
This guide, K-76-1000, is to be used by qualified and factory-trained personnel, knowledgeable of NFPA standards and
any other applicable standards in effect. This guide is intended to provide guidance to qualified technical professionals
for the installation and maintenance of the DS Series Addressable Detectors.
Any questions concerning the information presented in this guide should be addressed to:
Kidde-Fenwal, Inc.
400 Main Street
Ashland, MA 01721, USA
Phone: (508) 881-2000
Toll Free: (800) 872-6527
Technical Support: (866) 287-2531
Fax: (508) 881-8920
www.kiddefiresystems.com
LIMITATION OF LIABILITY
Only qualified persons experienced and trained in the installation of this type of equipment should install and configure
DS Series Addressable Detectors. Installation in accordance with this guide, applicable codes, and the instructions of
the Authority Having Jurisdiction is mandatory.
The technical data contained herein is provided for informational purposes only, and should not be used as a substitute
for professional judgment. The content of this manual is proprietary in nature and is intended solely for distribution to
authorized persons, companies, distributors or others for the sole purpose of conducting business associated with
Kidde-Fenwal, Inc. Although, Kidde-Fenwal, Inc. believes this information to be true and correct, it is published and
presented without any guarantee or warranty whatsoever. Kidde-Fenwal, Inc. disclaims any liability for any use of the
data other than as set out in this manual, foreword included.
The DS Series Addressable Detectors have been designed to meet the requirements of the following standards:
• CAN/ULC-S529-09
•ICES-003
• NFPA 72
• NFPA 720
• UL 268
• UL 268A•
• UL 521
• UL 864
FCC WARNING
This equipment can generate and radiate radio frequency energy. If this equipment is not installed in accordance with
this guide, it may cause interference to radio communications. This equipment was tested and found to comply within
the limits for Class A computing devices pursuant to Subpart B of Part 15 of the FCC Rules. These rules provide
reasonable protection against such interference when this equipment is operated in a commercial environment. If the
operation of this equipment causes interference, the user must correct the interference and incur the expense.

July 2016 -3- K-76-1000
RELATED DOCUMENTATION
National Fire Protection Association (NFPA)
1 Batterymarch Park
Quincy, MA 02169-7471
• NFPA 70 National Electric Code
• NFPA 72 National Fire Alarm and Signaling Code
Underwriters Laboratories, Inc. (UL)
333 Pfingsten Road
Northbrook, IL 60062-2096
• UL 268 Smoke Detectors for Fire Protective Signaling Systems
• UL 268A Smoke Detectors for Duct Applications
• UL 521 Heat Detectors for Fire Protective Signaling Systems
• UL 864 Control Units and Accessories for Fire Alarm Systems
Underwriters Laboratories of Canada (ULC)
7 Underwriters Rd
Toronto Canada M1R 3A9
• CAN/ULC S-529-09 Smoke Detectors for Fire Alarm Systems
• CAN/ULC-S530-M91 Heat Actuated Fire Detectors for Fire Alarm Systems

K-76-1000 -4- July 2016
NOTES:

July 2016 -5- K-76-1000
OVERVIEW

K-76-1000 -6- July 2016
OVERVIEW OF DS SERIES ADDRESSABLE SMOKE AND HEAT DETECTORS
DS Series smoke and heat detectors are intelligent analog addressable devices which make alarm
decisions based on the information collected by their sensors. The detectors are constructed of a high-
impact polymer. Each detector features an optional base-locking tab The following detectors and bases
are available:
1. Model DS-PS Photoelectric Smoke Detector
• addressable and intelligent
• built-in two-color LED
• conformal coated PCB
2. Model DS-HFS Programmable Fixed Temperature Heat Detector
• addressable and intelligent
• built-in two-color LED
• conformal coated PCB
3. Model DS-SB Detector Base
• 4-in. diameter
• for 2-wire or 4-wire terminal connection to Signaling Line Circuit (SLC)
• 6-in. trim ring included
4. Model DS-RB Detector Base
• 4-in. diameter
• for 2-wire or 4-wire terminal connection to Signaling Line Circuit (SLC)
• terminal connections available for Normally Open and Normally Closed Relays
• 6-in. trim ring included
ORDERING INFORMATION
Part Number Description
DS-PS Intelligent Photoelectric Smoke Detector, head only
DS-HFS Intelligent 135°F (57°C) Fixed-Temperature Heat Detector, head only
DS-SB Detector Mounting Base, 4 in. diameter, with 6 in. trim ring and 2-wire
or 4-wire terminal connection to SLC
DS-RB Detector Mounting Base, 4 in. diameter, with 6 in. trim ring and 2-wire
or 4-wire terminal connection to SLC and relay option
SIGA-DMP Duct Mounting Plate for DS-PS Photoelectric Smoke Detector
2-SPRC1 Replacement Smoke Chamber for DS-PS Photoelectric Smoke
Detector
SM200-12PKG Canned smoke for functional testing of smoke detectors

July 2016 -7- K-76-1000
FEATURES
•Addressing: DS Series detectors feature electronic addressing. No addressing switches are
used.
•LEDs: DS Series detectors use an LED to indicate the detector’s condition. In normal con-
dition, a flashing green LED indicates that the control panel is performing back-
ground supervision and a flashing red LED indicates an alarm condition.
•Sensitivity:The alarm sensitivity is the minimum obscuration level at which the detector initiates
an alarm condition and can be specified via the control unit menus or the remote
configuration software. The control unit to which these detectors are connected is
capable of interrogating each detector to determine its sensitivity.The table below
lists the acceptable smoke and heat ranges of sensitivity for the DS-PS and DS-
HFS detectors:
•Protocol: DS Series detectors operate on a Kidde Fire Systems fire alarm-suppression
control unit (Kidde, Fenwal and Chemetron brands) employing SmartOne®
communications protocol and can be mixed in any order with SmartOne legacy
detectors.
SPACING AND LOCATION
This section discusses the parameters for the spacing and location of DS Series smoke and heat
detectors. To better understand the requirements, use the following definitions:
Beams — are solid structures that project down from the ceiling surface more than 4 in. (100 mm) and are
spaced at intervals of more than 36 in. (910 mm), center-to-center.
Ceiling — is the upper surface of a space, regardless of the height. Consider a ceiling:
• Smooth, if it is uninterrupted by continuous projections, such as solid joists, beams, or ducts that ex-
tend more than 4 in. (100 mm) below the ceiling surface.
• Level, if it has a slope of less than or equal to 1 in 8.
• Sloping, if it has a slope of more than 1 in 8.
• Sloping peaked-type, if the ceiling slopes in two directions from the highest point. Consider curved or
domed ceilings as a peaked ceiling, with the slope figured as the slope of the chord from highest to
lowest point. .
• Sloping shed-type, if the high point is at one side with the slope extending toward the opposite side..
Ceiling Height — is the height from the floor to the ceiling of a room or space.
Design spacing — the spacing required for a particular installation.
Listed spacing — the spacing for which a heat detector is rated.
Partitions — walls extending from the floor toward the ceiling. If they are within 15% of the ceiling,
consider the space separated by the partitions as separate rooms.
Solid joists — are solid structures that project down from the ceiling surface more than 4 in. (100 mm)
and are spaced at intervals of 36 in. (910 mm) or less, center-to-center. Consider solid joists equivalent to
beams for smoke detector spacing guidelines.
Table 1. Acceptable Sensitivity Ranges for DS Series Detectors as Reported by Control Unit
Model Detection elements Factory-assigned
sensitivity
Adjustable alarm point
setting (%obsc./ft.)
DS-PS Photoelectric (open air) 2.0% obsc./ft. 0.9 to 3.5% obsc./ft.
DS-PS Photoelectric (in-duct) 2.0% obsc./ft. 0.9 to 2.0% obsc./ft.
DS-HFS Fixed-temperature 135°F (57°C) fixed 135°F (57°C)

K-76-1000 -8- July 2016
NOTES:

July 2016 -9- K-76-1000
HEAT DETECTOR SPACING

K-76-1000 -10- July 2016
HEAT DETECTOR SPACING
Do not install heat detectors in areas with an ambient temperature above 100.4° F (38°C). When
determining detector placement, consider ceiling height, construction, and ventilation as these affect a
detector’s performance.
A heat detector’s listed spacing rating is based on detector installation on a flat smooth ceiling that is 10
ft. (3 m) high. The spot-type listed spacing equates detector operation with the opening of a standard
sprinkler head within 2 minutes (±10 seconds) located 10 ft. (3 m) from the same fire.
Detector spacing is shown in Figure 1 below.
Figure 1. Listed Spacing for DS-HFS Heat Detector
Detector coverage is typically represented as a square because most structures have flat sidewalls. Actual
detector coverage is a circle whose radius is 0.7 times the listed spacing.
The listed spacing for DS-HFS heat detectors is S = 50 ft. (15.2 m).
1. Heat detector Listed spacing between detectors (S) = 50 ft. (15.2 m)
Note: Spacing is dependent on the ceiling height
S
S/2
S/2 S/2
S/2 S/2
.7S .7S
S
S
S
SS
1

July 2016 -11- K-76-1000
Figure 2 below shows that the square areas of coverage, A, B, and C, are all within the detector's circle of
coverage.
Figure 2. Heat Detector’s Circle of Coverage
Since all of the area within the detector’s circle of coverage is suitable for detecting a fire, the shape and
dimensions of the detector coverage “square” in Figure 3 may be modified. Note that, although the
coverage “square” is now a “rectangle,” the coverage area remains within the overall detector circle of
coverage.
Figure 3. Heat Detector Spacing, Rectangular Areas
1. Based on 50 ft. listed
spacing
Note: Smoke detectors are not listed for spacing
A
B
C
25 ft. x 34 ft. = 850
ft.²
(7.6 m x 10.4 m = 79 m²)
20 ft. x 37 ft. = 740
ft.²
(6.1 m x 11.3 m = 69 m²)
15 ft. x 39 ft. = 585
ft.²
(4.6 m x 11.9 m = 54 m²)
10 ft. x 41 ft. = 410
ft.² (3.1 m x 12.5 m = 38 m²)
30 ft. x 30 ft. = 900 ft.² (9.1 m x 9.1 m = 84 m
²)
1

K-76-1000 -12- July 2016
When installed on the ceiling, locate the heat detectors a minimum of 4 in. (100 mm) from the wall. When
installed on walls, locate the detector between 4 in. (100 mm) and 12 in. (300 mm) from the ceiling, as
shown in Figure 4.
Figure 4. Heat Detector Placement Near Ceiling/Wall Joints
1. Smooth ceiling, place detector 4 in. (100 mm) from wall
2. Never in this area: 4 in. (100 mm) from top of wall or corner
3. Top of detector is acceptable in shaded area: 4 to 12 in. (100 to 300 mm)
from ceiling
4. Wall
5. Floor
2
3
4
5
4 in. (0.1 m) min.
12 in. (0.3 m) max.
4 in. (0.1 m) min.
4 in.
1

July 2016 -13- K-76-1000
Ceiling Height and Construction
Make spacing adjustments when installing DS-HFS heat detectors on other than flat smooth ceilings or at
ceiling heights 10 ft. (3 m) to 30 ft. (9.1 m) high. The table below shows the reduction in spacing required
when mounting the DS-HFS detector on ceilings higher than 10 ft. (3 m). This reduced spacing yields the
equivalent response of detectors located on a 10 ft. (3 m) ceiling. Evaluate ceilings above 30 feet carefully
with consideration to the best placement and spacing.
Sloping Peaked-Typed Ceilings
In rooms with sloping peaked-typed ceilings (refer to Figure 5), place the first row of DS-HFS detectors
within 36 in. (910 mm) horizontally of the peak, but not closer than 4 in. (100 mm) vertically to the peak.
Space additional DS-HFS detectors, if required, based upon the horizontal projection of the ceiling and
ceiling construction. For a ceiling slope of:
• Less than 30 degrees, space the detectors using the height at the peak.
• Greater than 30 degrees, space the detectors, other than those located in the peak, based on the av-
erage slope height or the height of the peak.
Figure 5. Heat or Smoke Detector Spacing for Sloping Peaked-Type Ceilings
Ceiling height
Percent of
listed
spacing
Spacing Between DS-HFS Detectors
0 to 10 ft. (0 to 3.0 m) 100 20.0 ft. (6.0 m) 50.0 ft. (15.3 m)
10 to 12 ft. (3 to 3.7 m) 91 18.2 ft. (5.5 m) 45.5 ft. (13.9 m)
12 to 14 ft. (3.7 to 4.3 m) 84 16.8 ft. (5.1 m) 42.0 ft. (12.8 m)
14 to 16 ft. (4.3 to 4.9 m) 77 15.4 ft. (4.7 m) 38.5 ft. (11.7 m)
16 to 18 ft. (4.9 to 5.5 m) 71 14.2 ft. (4.3 m) 35.5 ft. (10.8 m)
18 to 20 ft. (5.5 to 6.0 m) 64 12.8 ft. (3.9 m) 32.0 ft. (9.8 m)
20 to 22 ft. (6.0 to 6.7 m) 58 11.6 ft. (3.5 m) 29.0 ft. (8.8 m)
22 to 24 ft. (6.7 to 7.3 m) 52 10.4 ft. (3.2 m) 26.0 ft. (7.9 m)
24 to 26 ft. (7.3 to 7.9 m) 46 9.2 ft. (2.8 m) 23.0 ft. (7.0 m)
26 to 28 ft. (7.9 to 8.5 m) 40 8.0 ft. (2.4 m) 20.0 ft. (6.0 m)
28 to 30 ft. (8.5 to 9.1 m) 34 6.8 ft. (2.1 m) 17.0 ft. (5.2 m)
Note: Ceiling heights higher than 30 ft. (9.1 m) exceed the limits of the
testing for the requirement of the code.
1. Do not mount detector in this area
2. Mount detector anywhere in this area
3. Heat or smoke detector
S = Listed spacing between DS-HFS detectors
= 50 ft. (15.2 m)
3
36 in. (910 m)
4 in.
(100 m)
36 in. (910 m)
1/2 S ½ S
S
1
2

K-76-1000 -14- July 2016
Sloping Shed-Typed Ceilings
In rooms with sloped ceilings having a slope greater than 1 ft. in 8 ft. (1 m in 8 m), place the first row of
detectors within 36 in. (910 mm) of the high end of the ceiling, but not closer than 4 in. (100 mm) from the
adjoining wall or ceiling. (Refer to Figure 6 below.) Space additional detectors, if required, based upon the
horizontal projection of the ceiling and ceiling construction.
If the slope is:
• Less than 7.2° (1 in 8), treat the ceiling as a level ceiling
• Less than 30°, adjust the horizontal spacing according to the height of the peak
Greater than 30°, adjust the horizontal spacing according to the average sloped ceiling height or to the
height of the peak. This spacing modification for sloped shed-typed ceilings is identical for spot-type heat
detectors and smoke detectors.
Figure 6. Heat or Smoke Detector Spacing for Sloping Shed-Typed Ceilings
1. Heat or smoke detector
2. Do not mount detector in this area
3. Mount detector anywhere in this area
S = Listed spacing between DS-HFS detectors
= 50 ft. (15.2 m)

July 2016 -15- K-76-1000
Solid Joists
When spacing heat detectors at right angles to the solid joists, do not exceed 50-percent of the listed
spacing and mount the detectors at the bottom of the joists.
Figure 7. Heat Detector Spacing for Solid Joists
Figure 8. Reduced Heat Detector Spacing for Solid Joists Construction
Exposed Beams
Exposed beams may impede the flow of fixed temperature heat detectors. Beams are defined as solid
structures extending 4 in. (100 mm) or more down from the ceiling. Beam spacing depends on the depth
of projection from the ceiling and the center-to-center spacing between the beams.
D. Depth
W. Spacing between joist
1. Ceiling
2. Detector
3. Joist
1. Heat detector
2. Joist
S = Listed spacing between DS-HFS detectors
= 50 ft. (15.2 m)
W
D
1
2
3
> 4 in.
(100 mm)
1/2 S
1/2 S
1/2 S
1/2 S
1/4 S
1/4 S
S
1
2

K-76-1000 -16- July 2016
If the beams project:
• Less than or equal to 4 in. (100 mm) below the ceiling, mount the detector on the ceiling with normal
ceiling spacing. See Figure 9, item 1.
• More than 4 in. (100 mm) below the ceiling, mount the detector on the ceiling. Do not exceed 66% of
the listed spacing at right angles to the beam direction. Treat the spacing in the direction parallel to
the beams separately. See Figure 9, item 2.
• Less than 12 in. (300 mm) in depth and are spaced less than 96 in. (2.44 m) on center, mount the
detectors on the bottom of the beams. See Figure 9, item 3.
• Greater than 18 in. (460 mm) below the ceiling and are more than 96 in. (2.44m) on center, treat each
bay created by the beams as a separate area. See Figure 9, item 4.
• For additional details, see NFPA 72.
Figure 9. Heat Detector Spacing for Beam Construction
D = Depth of beam
W = Beam spacing
1. D = ≤4 in. (100 mm)
2. D = > 4 in. (100 mm)
3. D = > 12 in (300 mm,
W = < 96 in. (2.4 m)
4. D = > 18 in. (460 mm),
W = > 96 in. (2.4 m)
5. Ceiling Section
6. Heat detector
7. Solid beam
8. Side view
W
W
W
D
D
D
D
5
5
5
5
1
6
6
6
6
6
2
3
4
7
7
7
7
8
8
8
8
> 4 in.
(100 mm)
> 12 in.
(300 mm)
> 18 in.
(460 mm)
4 in.
(100 mm)
≤
< 96 in. (2.44 m)
> 96 in. (2.44 m)

July 2016 -17- K-76-1000
SMOKE DETECTOR SPACING

K-76-1000 -18- July 2016
SMOKE DETECTOR SPACING
The DS-PS spot-type smoke detector spacing recommendation of 30 ft. (9.1 m) ±5% or 18 in. (460 mm)
is based upon the detector installation on a smooth ceiling that is 10 ft. (3 m) high. Detector coverage is
typically represented as a square, because most structures have flat sidewalls. Like spot-type heat
detectors, smoke detector coverage is a circle whose radius is 0.7 times the listed spacing. Since all of
the area within the detector’s circle of coverage is suitable for detecting smoke from fire, the shape and
dimensions of the detector coverage “square” may be modified. Note that, although the coverage “square”
is a “rectangle,” the coverage area is within the overall detector circle coverage. (Refer to Figure 3.)
Note: Unlike heat detectors, smoke detectors are not given a listed spacing. It is recommended that
smoke detectors be installed on S = 30 ft. (9.1 m) ±5% or 18 in. (460 mm) installed on “x” centers,
on smooth ceilings. NFPA 72, National Fire Alarm and Signaling Code contains additional infor-
mation regarding spacing adjustments.
Ceilings and Walls
Locate smoke detectors on the ceiling or, if on a sidewall, between the ceiling and 12 in. (300 mm) down
from the ceiling to the top of the detector.
Figure 10. DS-PS Smoke Detector Placement Near Ceiling/Wall Joints
For a smooth ceiling, for every point on the ceiling, locate the detector within a horizontal measurement
no greater than 0.7 times the selected spacing.
1. Smooth ceiling
2. Top of detector is acceptable in this area
3. Wall
4. Floor
2
3
4
12 in. (300 mm) max.
1
This manual suits for next models
4
Table of contents