Kilsen KFP-CE4 Series User guide

P/N 501-415503-5-20 • REV 2.0 • ISS 08SEP11 1
KFP-CE4 Series Quick Operation Guide
If you hear the buzzer
Determine the cause of the buzzer
If the buzzer is sounding and the Fire Alarm LEDs are
flashing or steady, then it’s a fire alarm.
WARNING: Depending on your fire alarm system
configuration, the buzzer may be your first indication of a
fire alarm.
If the buzzer is sounding and the Fault LED is flashing,
then it’s a fault.
For a fire alarm
1. Determine the location of the fire
Check the location of the fire, indicated by the Zone
LEDs.
If Fire Alarm and Zone LEDs are flashing, the fire alarm
has been activated by a detector. If they are steady, the
fire alarm has been activated by a manual call point.
2. Verify the fire alarm
If necessary, investigate the location of the fire alarm to
confirm that the alarm is genuine.
Depending on the configuration of your fire and
evacuation alarm system, you may have up to ten
minutes to investigate the alarm before fire brigade
notification devices are activated.
3. Leave the building
Once the fire alarm has been confirmed, leave the
building and follow your company’s evacuation drill.
FAULT
FIRE ALARM
2 KFP-CE4 Series Quick Operation Guide
For a fault
WARNING: Never silence the buzzer without first
investigating the cause of the warning signal.
1. Silence the buzzer
To silence the buzzer, press Panel Silence.
The Panel Silence LED turns on and the buzzer stops.
New alarm or fault events will turn the buzzer back on.
2. Contact your maintenance contractor
Contact your maintenance contractor immediately to
investigate and repair the fault.
Activating an evacuation alarm
To activate an evacuation alarm in all evacuation areas,
press the All Sounders Start button and the Confirm
button.
To activate an evacuation alarm in a specific evacuation
area, press the corresponding Evacuation Area button
and the Confirm button.
The Evacuation Area LEDs are steady for evacuation
areas in alarm.
For more information
This document includes basic control panel operation
instructions to be followed in the event of a fire alarm or
fault indication. For detailed operation, refer to the
operation manual.
Maintenance information
Inspect and test the fire and evacuation alarm system in
accordance with all applicable requirements and
regulations.
For service contact
Name:
Address:
Telephone:
Copyright © 2011 UTC Fire & Security. All rights reserved.
ALL SOUNDERS
START
PANEL
SILENCE

Other manuals for KFP-CE4 Series

2

Popular Fire Alarm manuals by other brands

Hochiki HCA-2 Installation and operation manual

Hochiki

Hochiki HCA-2 Installation and operation manual

Honeywell Farenhyt Series manual

Honeywell

Honeywell Farenhyt Series manual

Eaton SQUASHNI MICRO Technical data

Eaton

Eaton SQUASHNI MICRO Technical data

Telguard TG-7 Series Quick installation guide

Telguard

Telguard TG-7 Series Quick installation guide

Johnson Controls IFC-1010 Technical manual

Johnson Controls

Johnson Controls IFC-1010 Technical manual

Tyco Fire Product TY-B Series quick start guide

Tyco Fire Product

Tyco Fire Product TY-B Series quick start guide

E2S BExCP3B-PB instruction manual

E2S

E2S BExCP3B-PB instruction manual

Simplex 4099-9032 installation instructions

Simplex

Simplex 4099-9032 installation instructions

Gamewell IDENTIFLEX 632 Installation & operation manual

Gamewell

Gamewell IDENTIFLEX 632 Installation & operation manual

ESP MAGPRO-WSBIP65 installation instructions

ESP

ESP MAGPRO-WSBIP65 installation instructions

Honeywell Notifier ID60 operating manual

Honeywell

Honeywell Notifier ID60 operating manual

Brooks FIRETRACKER FT128 Quick operation guide

Brooks

Brooks FIRETRACKER FT128 Quick operation guide

GST DI-9204Exd Installation and operation manual

GST

GST DI-9204Exd Installation and operation manual

Satel SPP-100 installation manual

Satel

Satel SPP-100 installation manual

Sierra Monitor Corporation 3100-xx instruction manual

Sierra Monitor Corporation

Sierra Monitor Corporation 3100-xx instruction manual

Evonicfires Newton 6 instruction manual

Evonicfires

Evonicfires Newton 6 instruction manual

Abus FU8310 operating instructions

Abus

Abus FU8310 operating instructions

Secutron MRM-800MP Series installation instructions

Secutron

Secutron MRM-800MP Series installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.