King gates STAR OPEN 4000 Product manual

STAR OPEN
Made in Italy
IT Barriera automatica - Installazione elettronica
Istruzioni ed avvertenze per l’installazione e l’uso
EN Automatic boom gate - electronic installation
Installation and use instructions and warnings
FR Barrière automatique - Installation électronique
Instructions et avertissements pour l’installation et l’utilisation
ES Barrera automática - Instalación electrónica
Instrucciones y advertencias para la instalación y el uso


1
IT
GUIDA RAPIDA
ATTENZIONE! - Non installare la barriera senza aver
letto tutte le istruzioni!
Installare la barriera, gli elementi di comando (selettore a chiave o
pulsantiere) e di sicurezza (arresto di emergenza, fotocellule, bordi
sensibili e lampeggiante), poi eseguire i collegamenti elettrici se -
condo lo schema di .
01. -
ciata, eventualmente regolare la molla di bilanciamento.
02.
l’asta si possa muovere senza particolari sforzi per tutta la sua corsa.
03. 1-2 giungano
230 Vca e che sui morsetti 5-6 vi siano 24 Vcc; i LED posti sugli
ingressi attivi devono accendersi ed il led OK dovrà lampeggiare
alla frequenza di 1 al secondo.
04. Controllare la corrispondenza dei due led FCA e FCC , quando
l’asta è chiusa deve spegnersi solo FCC , quando è aperta deve
spegnersi solo FCA.
05. Per sfruttare la funzione di rallentamento è necessario che il
-
viene nel punto desiderato.
06.
“O ”, in questo modo il funzionamento è in modo manuale cioè a
tasto premuto. Bloccare la barriera con l’asta a 45° in modo che
possa muoversi liberamente nei due sensi di marcia, quindi dare
un breve impulso di comando sull’ingresso APRE, ora se l’asta non
si è mossa nel senso di apertura occorre procedere come segue:
a) Spegnere l’alimentazione elettrica alla barriera
b) MOTORE ” e reinserirlo ruotato di 180°
c) FINE CORSA ” e reinserirlo ruotato di 10°
07. Riprovare se il senso di rotazione è corretto ripetendo l’opera -
zione descritta sopra.
08. Regolare provvisoriamente i trimmer STOP_AMPERE e FOR -
ZA LAVORO al massimo della corsa, TEMPO PAUSA al minimo,
e FORZA RALLENTAMENTO a metà corsa. Provare ad eseguire
-
cessivo punto di arresto, provare poi la manovra contraria.
09. Impostare i dip-switch delle FUNZIONI nel modo desiderato:
Switch 1-2 :O O = Movimento “Manuale” (Uomo Presente)
On O = Movimento “Semiautomatico”
O On = Movimento “Automatico” (Chiusura Auto -
matica)
On On = Movimento “Automatico + Chiude Sem -
pre)
Switch 3 :On = Funzionamento Condominiale
Switch 4 :On = Annulla STOP nel ciclo Passo Passo
Switch 5 :On = Prelampeggio
Switch 6 :On = Lampeggiante anche in Pausa
Switch 7 :On = Richiudi subito dopo Foto (solo se in Au -
tomatico)
Switch 8 :On = Sicurezza (Foto) anche in apertura
Switch 9 :On =Spia C.A diventa semaforo in modalità “a
senso unico”
Switch 10 :On = Funzionamento in modo “Semaforo nei
due sensi”
10. Regolare i due trimmer di FORZA LAVORO e di FORZA RAL -
LENTAMENT0
rispettivamente durante le fasi di corsa e di rallentamento, solo ora
regolare il trimmer STOP_AMPERE
intervento desiderata.
Nel caso di funzionamento in modo automatico regolare a
piacere il trimmer TEMPO PAUSA.
24 Vcc
max 200 mA
- (0 v)
FCA
FINE
CORSA
FCC
1
2
3
4
+
-
MOTORE
OK
TEMPO
PAUSA
FUNZIONI
STOP
AMPER
14
ALT
FOTO
APRE
P. P.
FOTO2
8
6
5
+ (24v)
7
9
10
11
12
13
41
43
42
44
15
CHIUDE
FORZA
RALL.
FORZA
LAVORO
50-60 Hz
230 Vac
Lampeggiante
24 Vcc max 25 W
APRE (OROLOGIO)
ALT
FOTO
FOTO2
P. P.
COMUNE
SPIA C.A.
LUCE CORTESIA
ANTENNA
2¯ Ch
RADIO
CHIUDE
1

2
IT
Sommario
Avviso importante 3
1. Descrizione del prodotto 4
2. Installazione 4
3. Collegamenti elettrici 4
3.1 - Eseguire i collegamenti elettrici 4
3.2 - Prove di funzionamento 5
3.3 - Regolazione del tempo pausa 5
3.4 - Funzioni selezionabili 5
3.5 - Descrizione delle denizioni 6
3.6 - Semaforo nei due sensi 6
3.7 - Descrizione dei modi di funzionamento 7
3.8 - Scheda “carica” per alimentazione anche da batteria 7
4. Caratteristiche tecniche della centrale 8
5. Dichiarazioni CE di conformità 9
Avviso importante
È nostro dovere ricordare che state eseguendo delle operazioni su
impianti di macchine che sono classicati nella categoria dei:
“Cancelli e porte automatiche” e quindi considerati particolarmente
“Pericolosi”; è vostro compito renderli “Sicuri” per quanto sia ragio-
nevolmente possibile!
L’installazione ed eventuali interventi di manutenzione devono esse-
re effettuati solo da personale qualicato ed esperto, seguendo le
migliori indicazioni dettate dalla “Regola d’arte” ed in conformità a
quanto previsto dalle seguenti leggi, norme o direttive (norme, decreti
del Presidente della Repubblica, e decreti legislativi sono validi solo
per l’Italia; Direttive CEE sono invece valide in tutta Europa ):
- Norma UNI 8612 (Cancelli e portoni motorizzati: criteri costruttivi e
dispositivi di protezione contro gli infortuni)
- DPR N°46 del 5/03/1990 (Norme per la sicurezza degli impianti
elettrici, personale abilitato)
- Dlgs N°459/96 del 24/07/96 (Recepimento direttiva 89/392 CEE,
Direttiva Macchine)
- Dlgs N°615/96 del 12/11/96 (Recepimento direttiva 89/336 CEE,
Direttiva sulla Compatibilità Elettromagnetica)
- Dlgs N°626/96 del 26/11/96 (Recepimento direttiva 93/68 CEE,
Direttiva Bassa Tensione)
Nella progettazione e realizzazione dei propri prodotti, KING-GATES,
rispetta (per quanto compete alle apparecchiature) tutte queste nor-
mative, è fondamentale però che anche l’installatore (per quanto
compete agli impianti) prosegua nel rispetto scrupoloso delle mede-
sime norme.
Personale non qualicato o non a conoscenza delle normative appli-
cabili alla categoria dei “Cancelli e porte automatiche”: deve assolu-
tamente astenersi dall’eseguire installazioni ed impianti.
Chi esegue impianti senza rispettare tutte le normative applicabili: si
renderà responsabile di eventuali danni che l’impianto potrà
causare!
1. Descrizione del
prodotto
La scheda elettronica è adatta per comandare la barriera stradale
OPEN con motore in corrente continua a 24 V.
Si tratta di un progetto di nuova concezione infatti l’attuatore dispone
di necorsa con un sistema di controllo della velocità che permette il
raggiungimento dei limiti di corsa attraverso una fase di rallentamen-
to, inoltre viene sempre rilevato lo sforzo a cui è sottoposto il motore
durante il movimento e quindi ostacoli alla corsa vengono pronta-
mente rilevati con conseguente inversione del moto.
Per garantire la massima immunità nei confronti dei disturbi, la mag-
giore essibilità d’uso e la più vasta scelta di funzioni programmabili,
nel progetto sono state adottate avanzate tecniche e componenti fra
i più sosticati.
Sono possibili azionamenti in modo “manuale”, “semiautomatico” op-
pure “automatico”; vi sono sosticate funzioni come “Richiudi subito
dopo Foto ”o” Richiudi sempre”, ”Lampeggiante anche in pausa”e
due tipi di funzioni semaforiche; di particolari funzioni di tipo opera-
tivo “Partenza graduale” e “Rallentamento” inserite di serie, “Freno”
di tipo sensibile al contesto che interviene solo se richiesto l’arresto
istantaneo del movimento.
La scheda è predisposta per l’inserimento di tutta la gamma di rice-
vitori radio serie KING-GATES.
Vista la particolarità del prodotto, prima di iniziare con l’installazione
ed eseguire i collegamenti è opportuna una breve descrizione degli
elementi più importanti presenti sulla scheda di controllo.
(1) Serie di microinterruttori ”dip-switch” per la selezione delle FUNZIONI
(2) Led che lampeggia a cadenza regolare e segnala il corretto funzionamento
della centrale
(3) Trimmer ”STOP_AMPER” di regolazione della frizione basata su sistema di
misura amperometrica
(4) Trimmer ”TEMPO PAUSA” che regola il tempo di pausa nel modo automatico
(5) Trimmer ”FORZA LAVORO” per regolare la potenza al motore durante la fase
di movimento
(6) Trimmer ”FORZA RALLENTAMENTO” per regolare la potenza al motore nella
fase di rallentamento
(7) Serie di led che segnalano lo stato degli ingressi di comando
4
2
OK
1356
7
CHIUDE
APRE
P.P.
FOTO 2
FOTO
ALT
STOP
AMPER
FORZA
LAVORO FORZA
RALL.
TEMPO
PAUSA
2
Il led OK (2) ha il compito di segnalare il corretto funzionamento della
logica interna deve lampeggiare alla cadenza di 1 secondo ed indica
che il microprocessore interno è attivo ed è in attesa di comandi.
Quando c’è una variazione dello stato di un ingresso (sia ingresso di
comando che Switch delle funzioni) viene generato un doppio lam-
peggio veloce, questo anche se la variazione non provoca effetti im-
mediati. Un lampeggio veloce di 5 al secondo indica che la tensione
di alimentazione non è sufciente.
Quando la centrale è alimentata le spie luminose che sono poste
sugli ingressi (7) si accendono se quel particolare ingresso è attivo e

3
IT
quindi presente la tensione di comando a 24 Vcc. Normalmente i led
sugli ingressi delle sicurezze FOTO, FOTO 2 e ALT sono sempre ac-
cesi, mentre quelli sugli ingressi di comando PASSO PASSO, APRE-
OROLOGIO e CHIUDE sono normalmente spenti.
Visto che in un motore in corrente continua la corrente assorbita è
proporzionale allo sforzo cui è sottoposto, sviluppare un sistema di
rilevazione degli ostacoli è estremamente semplice. Durante il movi-
mento viene via via misurata la corrente assorbita dal motore, quan-
do questa supera un certo limite (regolabile dal trimmer) interviene il
sistema di sicurezza e viene eseguita una fermata con l’ausilio anche
del freno (che toglie la parte residua di energia cinetica accumula-
ta); poi se è attivo uno dei modi di funzionamento automatico viene
avviato un movimento in senso contrario. Per aumentare il livello di
sicurezza, se il sistema STOP_AMPERE interviene per tre volte con-
secutive senza mai raggiungere uno dei termini naturali del movimen-
to viene eseguito uno STOP denitivo.
2. Installazione
Eseguire l’installazione della barriera stradale seguendo scrupolosa-
mente tutte le indicazioni riportate nell’allegato manuale di istruzioni.
È necessario sottolineare che esistono delle normative, leggi e re-
golamenti che impongono limitazioni e modalità di esecuzione degli
impianti, rispettare scrupolosamente tutte le norme applicabili.
ATTENZIONE! - Non installare la barriera senza rispettare
tutte le norme per la categoria dei cancelli automatici!
Installare tutti gli elementi di comando (selettore a chiave o pulsantie-
re) e di sicurezza (arresto di emergenza, fotocellule, bordi sensibili e
lampeggianti) previsti. Poi eseguire i collegamenti elettrici secondo il
seguente schema.
24 Vcc
max 200 mA
- (0 v)
TRASFORM.
SECOND.
8 A
FUSE
FUSE
FCA
FINE
CORSA
FCC 1 A
FUSE
3,15 A
1
2
TRASF.
PRIM.
RELE'
COMUNE
RELE'
AP-CH
3
4
+
-
MOTORE
SCHEDA " RADIO "
SCHEDA " CARICA "
MICROPROCESSORE
COR.
LUCE
OK
TEMPO
PAUSA
FUNZIONI
STOP
AMPER
14
ALT
FOTO
APRE
P. P.
FOTO2
8
6
5
+ (24v)
7
9
10
11
12
13
41
43
42
44
15
CHIUDE
FORZA
RALL.
FORZA
LAVORO
50-60 Hz
230 Vac
LUCY 24 Vcc
max 25 W
APRE (OROLOGIO)
ALT
FOTO
FOTO2
P. P.
COMUNE
SPIA C.A.
LUCE CORTESIA
ANTENNA
2¯ Ch
RADIO
CHIUDE
3
Nota: L’installazione e i successivi interventi di manutenzione devono
essere effettuati solo da personale qualicato ed esperto, in confor-
mità a quanto previsto dal DPR N°46 del 5/3/1990, nel pieno rispetto
delle norme UNI 8612 e seguendo le migliori indicazioni dettate dalla
”Regola d’arte”. Chi esegue detti interventi si rende responsabile di
eventuali danni causati.
3. Collegamenti
elettrici
Di seguito, una breve descrizione dei possibili collegamenti della cen-
trale verso l’esterno:
1-2 230 Vac = Alimentazione elettrica 230 Vca 50/60 Hz
3-4 Lampeggiante = Uscita per collegamento al lampeg-
giante 24 Vcc, potenza massima della lampada 25 W
5-6 24 Vcc = Uscita 24 Vcc per alimentazione servizi (Foto,
Radio ecc) massimo 200 mA
7 Comune = Comune per tutti gli ingressi (come Comune
è utilizzabile anche il morsetto 6)
8Luce Cortesia = Uscita per luce di cortesia 24 Vcc, poten-
za massima dell’uscita 10 W
9Spia C.A. = Uscita per spia cancello aperto 24 Vcc, poten-
za massima della spia 10 W
10 Alt = Ingresso con funzione di ALT (Emergenza, blocco o
sicurezza estrema)
11 Foto = Ingresso per dispositivi di sicurezza (Fotocellule,
coste pneumatiche)
12 Foto 2 = Ingresso per sicurezze con intervento in apertu-
ra (Fotocellule, coste pneumatiche)
13 Passo Passo = Ingresso per funzionamento ciclico
(APRE STOP CHIUDE STOP)
14 Apre-Orologio = Ingresso per apertura (eventualmente
comandata da un orologio)
15 Chiude = Ingresso per chiusura
41-42 2° Ch Radio = Uscita dell’eventuale secondo canale del
ricevitore radio
43-44 Antenna = Ingresso per antenna del ricevitore radio
Le rimanenti connessioni vengono già eseguite in sede di produ-
zione, per completezza ne riportiamo l’elenco:
TRASF. PRIM. = Primario del trasformatore di alimentazione
TRASF. SECOND. = Secondario del trasformatore di alimenta-
zione
MOTORE = Uscita per collegamento motore 24 Vcc
Nella centrale sono presenti due altri innesti da usare per le se-
guenti schede opzionali:
RADIO = Innesto per ricevitori radio prodotti da Nice
CARICA = Innesto per scheda carica batteria
3.1 - Eseguire i collegamenti elettrici
ATTENZIONE! - Per garantire l’incolumità dell’operatore e per
prevenire danni ai componenti, mentre si effettuano i collegamenti,
sia di bassa tensione (230 V) che di bassissima tensione (24 V) o si
innestano le varie schede: la centrale non deve essere assoluta-
mente alimentata elettricamente.
È consigliabile attendere di aver completato l’installazione per inserire
le eventuali schede opzionali RADIO o CARICA e solo dopo aver
vericato la funzionalità dell’impianto. Le schede opzionali non sono
necessarie al funzionamento e se inserite rendono più difcile la ricer-
ca di eventuali guasti.
Ricordiamo inoltre che gli ingressi dei contatti di tipo NC (Normal-
mente Chiuso), se non usati, vanno ponticellati, se piú di uno vanno
posti in SERIE tra di loro; gli ingressi dei contatti di tipo NA (Normal-
mente Aperto) se non usati vanno lasciati liberi, se piú di uno vanno
posti in PARALLELO tra di loro. Per quanto riguarda i contatti questi

4
IT
devono essere assolutamente di tipo meccanico e svincolati da qual-
siasi potenziale, non sono ammessi collegamenti a stadi tipo quelli
deniti ”PNP”, ”NPN”, ”Open Collector” ecc. ecc.
01. Effettuare i collegamenti necessari seguendo lo schema di g. 3;
si ricorda che vi sono delle normative precise da rispettare in modo
rigoroso sia per quanto riguarda la sicurezza degli impianti elettrici
che per quanto riguarda i cancelli automatici.
02. Vericare che l’asta sia ben bilanciata, eventualmente regolare la
molla di bilanciamento.
03. Sbloccare la barriera agendo nell’apposita chiave e vericare che
l’asta si possa muovere senza particolari sforzi per tutta la sua corsa.
ATTENZIONE! - Non alimentare la barriera senza rispet-
tare tutte le norme per la categoria dei cancelli automatici!
04. Alimentare la centrale vericando immediatamente che sui mor-
setti 1-2 giunga una tensione di 230 Vca e che sui morsetti 5-6 sia
presente una tensione di 24 Vcc. Non appena la centrale è alimenta-
ta le spie luminose (LED) che sono poste sugli ingressi attivi devono
illuminarsi, inoltre dopo pochi istanti il led ”OK” dovrà iniziare a lam-
peggiare con cadenza regolare. Se tutto questo non avviene, togliere
immediatamente alimentazione e controllare con maggior attenzione
i collegamenti.
05. Controllare la corrispondenza dei due led FCA e FCC, quando
l’asta è chiusa deve spegnersi solo FCC, quando è aperta deve spe-
gnersi solo il led FCA. Per sfruttare la funzione di rallentamento è
necessario che il necorsa intervenga circa 20° prima dell’effettivo
punto di arresto; se necessario, regolare le due camme no a che il
necorsa interviene nel punto desiderato.
06. Ora vericare che i led relativi agli ingressi con contatti tipo NC si-
ano accesi (tutte le sicurezze attive) e che i led relativi ad ingressi tipo
NA siano spenti (nessun comando presente), se questo non avviene
controllare i collegamenti e l’efcienza dei vari dispositivi.
07. Vericare il corretto funzionamento di tutti i dispositivi di sicurezza
presenti nell’impianto (arresto di emergenza, fotocellule,coste pneu-
matiche ecc.), ogni volta che intervengono, il relativi led ALT, FOTO
o FOTO 2 devono spegnersi.
08. Vericare che tutti gli switch delle funzioni siano in posizione ”Off”
in questo modo il funzionamento è in modo manuale cioè a tasto
premuto, bloccare la barriera con l’asta a 45° in modo che possa
muoversi liberamente nei due sensi di marcia, quindi dare un breve
impulso di comando sull’ingresso APRE, ora se l’asta non si è mossa
nel senso di apertura occorre procedere come segue:
1) Spegnere l’alimentazione elettrica alla barriera
2) Slare il connettore “MOTORE” e reinserirlo ruotato di 180°
3) Slare il connettore “FINE CORSA” e reinserirlo ruotato di 180°
09. Eseguito quanto descritto conviene riprovare se il senso di rota-
zione ora è corretto ripetendo l’operazione del punto “G”.
Nota: quando si inverte il senso del movimento, occorre eseguire
tutte le tre operazioni descritte sopra. In particolare, se ad esempio,
si ruota il connettore ”MOTORE” e non si ruota il connettore ”FINE
CORSA” si provoca un errore nel sistema di rallentamento. In questo
caso, il motore è comandato, ad esempio in apertura, ma il necorsa
FCA non viene mai raggiunto e di conseguenza l’asta raggiunge il
punto di apertura con la massima forza, quindi interviene il sistema di
rilevazione amperometrica che inverte il moto in una nuova manovra
anche questa sbagliata.
10. Regolare provvisoriamente i trimmer STOP_AMPERE e FORZA
LAVORO al massimo della corsa, TEMPO PAUSA al minimo, rego-
lare poi FORZA RALLENTAMENTO a metà corsa.
11. Provare ad eseguire una intera manovra no a che l’asta rag-
giunge il punto di intervento del necorsa, ora deve entrare in gioco
il rallentamento che permette il proseguimento della corsa ad una
velocità ridotta per altri 3 secondi.
12. Regolare i Trimmer FORZA LAVORO e FORZA RALLENTA-
MENTO per ottenere che la manovra avvenga con la velocità e la
spinta desiderata e che la fase di rallentamento sia tale che l’asta
raggiunga i punti di arresto nel modo più ”dolce” possibile e senza
scossoni; naturalmente una perfetta regolazione della molla di bilan-
ciamento è fondamentale.
13. Alla ne, regolare il trimmer STOP_AMPERE in modo che il si-
stema di rilevazione degli ostacoli basato su frizione amperometrica
intervenga non appena all’asta viene applicata una appropriata azio-
ne contraria. Il sistema di frizione amperometrica interviene nei due
sensi del movimento.
3.2 - Prova di funzionamento
Vericati i collegamenti ed eseguita la fase di controllo (Cap. 3.1) è
possibile provare il movimento comandato elettricamente dell’asta, in
questo caso si consiglia di operare in modo manuale con tutte le
funzioni disattivate (tutti gli Switch Off); per ogni eventualità, in modo
manuale, rilasciando il tasto di comando si ottiene l’immediato arresto
del motore. Se si usa come comando l’ingresso Passo P. il primo mo-
vimento (dopo l’accensione) dovrà essere in apertura.
Agendo sugli ingressi di comando movimentare l’asta no al punto
di apertura, a circa 20° prima del punto di fermata deve scattare il
necorsa FCA che attiva la fase di”rallentamento”che permette di rag-
giungere il punto previsto con una velocità ridotta.
Eseguire poi un movimento in chiusura no al raggiungimento del
punto di chiusura anche in questo casi dovrà intervenire il necorsa
FCC che attiva la fase di rallentamento 20° prima dell’arresto del mo-
vimento. Passare ora a provare l’intervento dei dispositivi di sicurezza,
FOTO in apertura non ha alcun effetto, in chiusura provoca la fermata
dell’asta; FOTO 2 in chiusura non ha alcun effetto, in apertura pro-
voca la fermata dell’asta. I dispositivi collegati nell’ingresso ALT agi-
scono sia in apertura che in chiusura provocando sempre la fermata
dell’asta.
Le normative italiane UNI 8612 prescrivono che la spinta massima di
una automazione non superi i 150 N (~ 13,5 Kg) questo si ottiene me-
diante la regolazione della frizione amperometrica STOP_AMPERE.
Sulla scheda è presente un trimmer che permette di stabilire la soglia
di intervento della frizione; deve essere regolato in modo che interven-
ga non appena all’asta viene applicata una leggera forza in direzione
contraria al movimento in corso.
Per superare la fase di inizio del movimento che richiede sempre una
maggiore potenza dal motore Il sistema di frizione STOP_AMPERE
viene escluso nella fase di partenza del motore; per valutare l’effetto
della regolazione sul trimmer conviene quindi attendere che il movi-
mento sia avviato e che l’asta abbia raggiunto la velocità standard.
Attenzione anche al fatto che, sempre per questioni di sicurezza, se la
frizione interviene per tre volte consecutive il movimento viene fermato
senza eseguire l’inversione.
Se viene selezionato il modo di funzionamento in automatico al termi-
ne della manovra di apertura si esegue una “pausa” al termine della
quale viene attivata automaticamente una manovra di chiusura. Il tem-
po di pausa è regolabile attraverso l’apposito trimmer TEMPO PAU-
SA. La pausa viene attivata anche nel movimento in semiautomatico
quando, in chiusura, l’intervento di un dispositivo di sicurezza o della
frizione STOP_AMPERE provoca una inversione in apertura.
3.3 - Regolazione del tempo pausa
Quando viene selezionata attraverso l’apposito dip-switch la funzione
di chiusura automatica (Vedi Cap. 3.3), dopo una manovra di apertura
viene attivato un temporizzatore che controlla il cosiddetto ”Tempo
Pausa”, allo scadere del tempo si attiva automaticamente una ma-
novra di chiusura. Questo tempo può essere regolato con il trimmer
TEMPO PAUSA entro valori da 3 a 120 Secondi.
3.4 - Funzioni selezionabili
Il dip-switch FUNZIONI permette di selezionare i vari modi di funziona-
mento possibili e di inserire le funzioni desiderate.

5
IT
Switch 1-2 Off Off = Movimento “Manuale” (Uomo Presente)
On Off = Movimento “Semiautomatico”
Off On = Movimento “Automatico” (Chiusura Auto-
matica)
On On = Movimento “Automatico + Chiude Sem-
pre)
Switch 3 On = Funzionamento Condominiale
Switch 4 On = Annulla STOP nel ciclo Passo Passo
Switch 5 On = Prelampeggio
Switch 6 On = Lampeggiante anche in Pausa
Switch 7 On = Richiudi subito dopo Foto (solo se in Au-
tomatico)
Switch 8 On = Sicurezza (Foto) anche in apertura
Switch 9 On = Spia C.A diventa semaforo in modalità “a
senso unico”
Switch 10 On = Funzionamento in modo “Semaforo nei
due sensi”
ATTENZIONE! - Quando lo Switch è posto in “Off” non attiva
la funzione descritta.
3.5 - Descrizione delle denizioni
Diamo ora una breve descrizione delle funzioni selezionabili, tutte le
funzioni possono essere inserite o non inserite senza alcun limite an-
che se qualche combinazione potrebbe non avere senso e quindi non
essere eseguita (ad esempio la funzione N° 6, lampeggiante anche in
pausa, non viene eseguita se il movimento è modo manuale).
Switch 1-2 Off Off = Movimento “Manuale” (Uomo Presente)
On Off = Movimento “Semiautomatico”
Off On = Movimento “Automatico” (Chiusura Auto-
matica)
On On = Movimento “Automatico + Chiude Sem-
pre)
Nel funzionamento “Manuale” il movimento viene eseguito solo no
alla presenza del comando (tasto premuto).
In “Semiautomatico” basta un impulso di comando e viene eseguito
tutto il movimento no al raggiungimento dell’apertura o della chiusu-
ra. Nel modo di funzionamento “Automatico” con un solo impulso di
comando viene eseguita una apertura poi viene eseguita una pausa
e quindi automaticamente una chiusura.
La funzione “Chiude Sempre” interviene se, dopo una mancanza
momentanea di alimentazione, viene rilevata l’asta ancora aperta; in
questo caso si avvia automaticamente una manovra di chiusura pre-
ceduta da 5 secondi di prelampeggio.
Switch 3 On = Funzionamento Condominiale
Nel funzionamento condominiale, una volta avviato un movimento in
apertura, ad esempio con un impulso su Passo Passo, questo movi-
mento non puó piú essere interrotto da altri impulsi di comando no
alla ne del movimento in apertura.
Nel movimento in chiusura un nuovo comando provoca l’arresto e
l’immediata inversione del movimento in apertura.
Switch 4 On = Annulla STOP nel ciclo Passo Passo
Il ciclo del Passo Passo è normalmente: APRE - STOP - CHIUDE
- STOP, con questa funzione inserita il ciclo Passo Passo diventa:
APRE - CHIUDE - APRE quindi l’asta non potrà mai fermarsi a metà
ma solo tutta aperta o tutta chiusa.
Switch 5 On = Prelampeggio
Prima di ogni movimento viene attivato il lampeggiante poi dopo 5
secondi (2 sec. se in manuale) inizia il movimento.
Switch 6 On = Lampeggiante anche in Pausa
Normalmente il lampeggiante viene attivato solo durante il movimen-
to in apertura o chiusura, questa funzione prevede che il lampeggian-
te rimanga attivo anche durante la Pausa allo scopo di segnalare lo
stato di ”prossima chiusura”.
Switch 7 On = Richiudi subito dopo Foto (solo se in Au-
tomatico)
Questa funzione permette di tenere l’asta aperta solo per il tempo
necessario al transito, infatti la chiusura automatica avverrà sempre
5 secondi dopo il disimpegno della “Foto”, indipendentemente dal
Tempo Pausa programmato.
Switch 8 On = Sicurezza (Foto) anche in apertura
Normalmente la sicurezza “Foto” interviene solo nella manovra di
chiusura, se lo switch N° 8 viene posto ”On” l’intervento del dispo-
sitivo di sicurezza provoca una interruzione del movimento anche
in apertura, se in Semiautomatico od Automatico si avrà la ripresa
nuovamente del moto in apertura subito dopo il nuovo consenso dal
dispositivo di sicurezza.
Switch 9 On = Spia C.A diventa semaforo in modalità “a
senso unico”
In alternativa alla funzione spia C.A. l’uscita può essere riprogramma-
ta perchè esegua la funzione di semaforo “a senso unico”; così che
l’uscita è spenta quando l’asta è chiusa o in chiusura ed è accesa
nella manovra di apertura o quando l’asta è aperta.
In questo modo all’uscita può essere applicata una indicazione tipo:
Verde = Passaggio libero
Switch 10 On = Funzionamento in modo “Semaforo nei
due sensi”
Quando si attiva la funzione di “Semaforo nei due sensi” ponendo lo
switch 10 in “On” nella centrale avvengono svariati mutamenti, APRE
diventa PASSO-PASSO 2, mentre le due uscite Luce Cortesia e Spia
C.A. diventano Luce Verde per un senso e Luce Verde per l’altro
senso di marcia. Data la particolarità della funzione riportiamo una
descrizione separata.
3.6 - Semaforo nei due sensi
La funzione di semaforo nei due sensi è orientata principalmente al
controllo del usso dei veicoli in entrambe i sensi di marcia attraverso
il passaggio controllato dalla barriera stradale.
Per ogni senso di marcia viene posto un comando diverso per l’a-
pertura: P.P. per entrare e P.P 2 (Apre) per uscire; quindi vengono
installati due semafori con le segnalazioni Rosso e Verde collegate
alle uscite Spia C.A. e Luce Cortesia.
SEMAFORO
Lampade Max 5W
S.C.A.(9)
L. Cor.(8)
V
R
COMANDO
CON : P.P 2
ENTRA
ESCE
V
RCOMANDO
CON : P.P
4
Normalmente le due uscite sono spente e così pure le due luci dei
semafori, quando viene dato un comando con P.P. per entrare, si
avvia il movimento e si attiva l’uscita S.C.A e si avrà così luce verde
in entrata e luce rossa in uscita.
Se invece il comado per l’apertura viene dato con P.P 2 si attiva
l’uscita L. Cor. e si avrà quindi luce verde in uscite e luce rossa in
entrata.

6
IT
La luce rimarrà accesa per tutta la fase di apertura e per la successi-
va fase di pausa, nella fase di richiusura invece verranno attivate sia
le luci verdi che le rosse (il risultato è giallo) per indicare che non c’è
più priorità nel passaggio (vedi tabella 1).
Tabella 1
Rosso Verde Signicato
OFF OFF Asta chiusa, passaggio interrotto nei due sensi
OFF ON Asta aperta, passaggio libero
ON OFF Asta aperta, passaggio occupato
ON ON Asta in chiusura o passaggio non controllato
Le due uscite Spia C.A. e Luce Cor. possono comandare direttamen-
te piccole lampade a 24 Vcc per un totale massimo per uscita di 10
W. Nel caso sia necessario usare lampade con potenza maggiore
sarà opportuno usare dei relè pilotati dalle uscite della centrale che
comandano a loro volta le lampade del semaforo.
IMPORTANTE! - Si consiglia di inserire il ricevitore radio solo
ora, al termine di tutte le regolazioni e in assenza di alimenta-
zione elettrica.
3.7 - Descrizione dei modi di
funzionamento
Nel funzionamento in modo manuale, l’ingresso APRE consente il
movimento no al punto di apertura, l’ingresso CHIUDE consente il
movimento no al punto di chiusura, il PASSO P. consente il movi-
mento alternativamente in apertura e in chiusura; non appena cessa il
comando in ingresso il movimento si arresta. In apertura il movimento
si arresta quando viene raggiunto il punto massimo aperto oppure se
manca il consenso dalla FOTO 2; in chiusura invece il movimento si
arresta nel punto massimo chiuso o se manca il consenso da FOTO.
Un intervento su ALT provoca un immediato arresto del movimento
sia in apertura che in chiusura. Una volta che il movimento si è arresta-
to è necessario cessare il comando in ingresso prima di poter iniziare
un nuovo movimento.
Nel funzionamento in uno dei modi automatici (semiautomatico - au-
tomatico e chiude sempre) un comando sull’ingresso APRE provoca
il movimento in apertura, se il comando permane (OROLOGIO) una
volta raggiunta l’apertura l’asta rimane ”congelata” in una pausa in-
nita; solo quando cessa il comando l’asta potrà essere richiusa. Gli
impulsi di comando sull’ingresso CHIUDE provocano la chiusura, se il
comando permane l’asta rimarrà bloccata in chiusura no al cessare
del comando, solo dopo potrà essere riaperta. Un impulso su PASSO
P. provoca alternativamente apertura o chiusura.
Un secondo impulso sul PASSO P. o sullo stesso ingresso che ha
iniziato il movimento provoca uno Stop.
Sia in apertura che in chiusura un intervento su ALT provoca un imme-
diato arresto del movimento.
In apertura l’intervento della FOTO non ha effetto mentre la FOTO
2 provoca l’inversione del moto; in chiusura l’intervento dalla FOTO
provoca una inversione del moto quindi una nuova pausa, inne una
richiusura. Se all’inizio del movimento in apertura l’ingresso FOTO non
da il consenso la richiesta di apertura viene annullata.
Nel caso fosse inserito il modo di funzionamento automatico, dopo
una manovra di apertura, viene eseguita una pausa al termine vie-
ne eseguita una chiusura. Se durante la pausa vi fosse un intervento
di FOTO, il temporizzatore verrà ripristinato con un nuovo tempo; se
invece durante la pausa si interviene su ALT la funzione di richiusura
viene azzerata e si passa in uno stato di STOP.
3.8 - Scheda “carica” per
alimentazione anche da batteria
La barriera stradale dispone di un trasformatore di potenza adeguata
a supportare la richiesta di energia del motore e della scheda elettro-
nica tale da rendere il tutto alimentabile direttamente da rete.
Nel caso si desideri il funzionamento del sistema anche quando viene
a mancare l’energia elettrica da rete è necessario aggiungere una ido-
nea batteria e della relativa scheda caricabatteria.
La batteria va posta nell’apposito vano esternamente al box plastico
che protegge la scheda al motoriduttore e collegata sui due morsetti
della scheda caricabatteria, mentre quest’ultima va innestata nell’ap-
posito connettore sulla centrale.
4. Caratteristiche tecniche della centrale
Caratteristiche tecniche Open4000
Alimentazione da rete 230 Vac ±10%, 50 - 60 Hz
Alimentazione da batteria 21 ÷ 28 Vcc (capacità > 6Ah)
Corrente Max servizi 24 Vcc 200 mA
Potenza massima lampeggiante 25 W (24 Vcc)
Potenza massima luce cortesia 10 W (24 Vcc)
Potenza massima spia CA 10 W (24 Vcc)
Tempo pausa da 3 secondi a 120 secondi
Tempo luce di cortesia 60 secondi
Temperatura di esercizio -20 ÷ 70 °C

1
EN
QUICK GUIDE:
CAUTION! - Do not install the boom gate without ha-
ving read all the instructions!
Install the boom gate, the control (key selector switch or push but-
ton panel) and safety devices (emergency stop, photoelectric cells,
sensitive edges and ashing lights) after which do the wiring fol-
lowing the diagram g. 1.
01. Prior to turning power on check that the bar is well balanced,
adjusting the balancing spring if necessary.
02. Release the boom gate using the special spanner and check that
the bar can move without any effort for the whole length of travel.
03. Power the unit and check that on terminals 1-2 voltage is 230
V AC and on terminals 5-6 it is 24 V d.c.; the LEDs on the active
inputs must turn on and the OK LED must ash at a frequency of
1 ash/second.
04. Check correspondence of the two FCA and FCC LEDs: when
the bar is closed only the FCC LED should turn off and when it is
open only the FCA should turn off.
05. To exploit the slowing down function it is necessary that the
limit switch triggers about 20° before the actual stopping point is
reached; if necessary adjust the two cams until the limit switch
triggers at the point required.
06. Check that all the function switches are in the “OFF” position.
This means it is in the manual functioning mode, that is, with the
button pressed. Lock the boom gate with the bar at a 45° angle
so it can move freely in both directions. Now give a brief command
pulse on the OPEN input and if the bar does not move in the ope-
ning direction proceed as follows:
a) Turn the electricity off to the boom gate
b) Unplug the “MOTOR” connector and replug it after it has
been turned 180°
c) Unplug the “LIMIT SWITCH” connector and replug it after it
has been turned 180°
07. See if rotation direction is right, repeating the procedure de-
scribed above.
08. Temporarily adjust the STOP_AMPERE and WORKING
FORCE trimmer to the maximum of the travel, PAUSE TIME to
minimum and SLOWING DOWN FORCE to halfway travel. Now
try and carry out a complete manoeuvre until the limit switch is
reached and the subsequent stopping point and then try the ma-
noeuvre in the opposite order.
09. Set the FUNCTIONS dip-switches as required:
Switches 1-2:
Off Off = “Manual” movement (Man Present)
On Off = “Semiautomatic” movement
Off On =
“Automatic” movement (Automatic Closing)
On On = “Automatic + Always Closes” movement
Switches 3:On = Condominium function
Switches 4:On =Cancels STOP in the Step-by-Step cycle
Switches 5:On =Pre-ashing
Switches 6:On = Flashing also in Pause
Switches 7:On =Recloses straight after Photocell
(only if on Automatic)
Switches 8:On = Safety (Photocell) also in opening
Switches 9:On =Bar open indicator becomes trafc light in
the “one-way” mode
Switches 10:On =Functioning in the “Trafc light in both di-
rections” mode
10. Adjust the two trimmers WORKING FORCE and SLOWING
DOWN FORCE until obtaining the force and speed required du-
ring, respectively, the travelling and slowing down phases; only now
adjust the STOP_AMPERE trimmer until the triggering threshold
required is obtained.
If in the automatic functioning mode, adjust the PAUSE TIME
trimmer as wanted.
24 VDC
max 200 mA
- (0 v)
FCA
LIMIT
SWITCH
FCC
1
2
3
4
+
-
MOTOR
OK
PAUSE
TIME
SLOWING
DOWN
FORCE
WORKING
FORCE
FUNCTIONS
STOP
AMPERE
14
8
6
5
+ (24v)
7
9
10
11
12
13
41
43
42
44
15
CLOSE
OPEN
STEP BY STEP
PHOTO2
PHOTO
STOP
230 VAC
50-60 Hz
LUCY 24 VDC
max 25 W
OPEN (TIMER)
STOP
PHOTO
PHOTO2
STEPBYSTEP
COMMON
BAR OPEN INDICATOR
COURTESY LIGHT
AERIAL
2¯ Ch
RADIO
CLOSE
1

2
EN
Contents
Important notice 3
1. Description of the product 4
2. Installation 4
3. Electrical connections 4
3.1 - Electrical hookup 4
3.2 - Operational tests 5
3.3 - Adjusting the pause time 5
3.4 - Available functions 5
3.5 - Description of denitions 6
3.6 - Two-way trafc light 6
3.7 - Description of the functioning modes 7
3.8 - Charge card also battery powered 7
4. Technical features of the unit 8
5. CE declaration of conformity 9
Important notice
We are obliged to remind you that you are working on equipment
classied in the following category:
“Automatic gates and doors”, which are considered to be especially
“Dangerous”; you must make them as “Safe” as reasonably pos-
sible!
Only qualied, expert personnel must carry out the installation and
any servicing required, making the best possible job of it and in ac-
cordance with the following laws, standards and directives (norms,
decrees of the President of the Republic and law decrees are only
valid for Italy; EEC Directives are, on the other hand, applicable for
the whole of Europe):
- UNI 8612 (Motorised gates and doors: construction criteria and ac-
cident prevention equipment)
- DPR N° 46 of 5/03/1990 (Standards for the safety of electrical
installations, authorised personnel)
- Dlgs N° 459/96 of 24/07/96 (EEC directive 89/392, “Machinery
Directive”)
- Dlgs N° 615/96 of 12/11/96 (EEC directive 89/336, Directive on
Electromagnetic Compatibility)
- Dlgs N° 626/96 of 26/11/96 (EEC directive 93/68, Low Voltage
Directive)
When designing and producing its products, Nice observes (as re-
gards the equipment) all the above standards but it is of paramount
importance that the installer too (as regards the systems) strictly ob-
serves the same standards.
Unqualied personnel or those who do not know the standards appli-
cable to the “Automatic gates and doors” category: must not install
systems.
Whoever carries out systems without observing all the applicable
standards: Will be held responsible for any damages that the
system may cause!
1. Description of the
product
The electronic card is suitable for controlling OPEN model road boom
gates with 24 V DC motors.
This is an entirely new design where the actuator has a limit switch
with a speed control system that makes it possible to reach the travel
limits by means of a slowing down phase. In addition, the effort the
motor is subject to during movement is promptly detected as well as
any obstacles that may be in the path and in such an event direction
is reversed.
The most advanced techniques and sophisticated components
have been employed in the project to guarantee maximum immunity
against interference, greater exibility of use and the widest possible
range of programmable functions.
It can be controlled “manually”, “semiautomatically” or “automatical-
ly”. There are also certain highly sophisticated functions like “Reclose
immediately after Photocell” or “Reclose always”, “Flashing also in
pause” as well as other operating functions such as “Gradual Start-
up” and “Slowing down” (a standard feature) plus a sensitive “Brake”
that only comes into play if movement has to be stopped hastily.
The whole range of KING-GATES radio receivers can be inserted on
the card.
In view of the particularity of the product, before you start the instal-
lation and hookup, here is a brief description of the most important
elements on the control card:
(1) Set of micro dip-switches for selecting the FUNCTIONS
(2 LED that ashes at regular intervals and indicates that the unit is working correctly
(3)“STOP_AMPERE” trimmer to adjust friction and based on an ammetric
measurement system
(4) “PAUSE TIME” trimmer to adjust pause time in the automatic functioning mode
(5)“WORKING FORCE” trimmer to adjust power to motor during the movement
phase
(6)“SLOWING DOWN FORCE” trimmer to adjust power to motor during the slowing
down phase
(7) Set of LEDs to signal the state of the command inputs
4
2
OK
1356
7
CLOSE
OPEN
STEP BY STEP
PHOTO 2
PHOTO
STOP
STOP
AMPERE
WORKING
FORCE SLOWING
DOWN
FORCE
PAUSE
TIME
2
The OK LED (2) has the task of signalling the correct functioning of
the internal logic and must ash at 1 second intervals; it indicates
that the internal microprocessor is active and waiting for commands.
Whenever there is a change in the state of an input (whether it is a
command input or function switch) a fast double ashing is gener-
ated which happens even if the change does not have an immediate
effect. Fast ashing at 5 second intervals means that the power volt-
age is insufcient.
When the unit is powered, the indicator lights on the inputs (7) turn
on if that particular input is active and hence 24 V DC control voltage
is present. Normally, the LEDs on the safety inputs, PHOTOCELL,

3
EN
PHOTOCELL2 and STOP, are always on while those on the com-
mand inputs, STEP-BY-STEP, OPEN-TIMER and CLOSE, are usually
off.
Since the current absorbed by a DC motor is in proportion to the
force it is subject to, developing an obstacle detection system is very
easy. During movement, the current absorbed by the motor is meas-
ured; when it exceeds a certain limit (adjustable with the trimmer) the
safety system is activated which causes movement to stop with the
aid of the brake (removing the residual part of accumulated kinetic
energy); then, if one of the automatic functioning modes is active,
a movement in the opposite direction starts. To increase the level
of safety still further, if the STOP_AMPERE system comes into play
three consecutive times without ever reaching any of the natural ends
of the movement, a nal STOP is carried out.
2. Installation
When installing the road boom gate, all the instructions given in the
enclosed instruction manual must be followed.
It is necessary to underline that there are standards, laws and regula-
tions that establish limits and ways to make systems: please comply
strictly with all the applicable standards.
CAUTION! - Do not install the boom gate unless all the
standards regarding the automatic gate category have been
complied with!!
Install all the control (key selector switch or push button panel) and
safety devices (emergency stop, photoelectric cells, sensitive edges
and ashing lights) after which do the wiring following the diagram:
Then make the electrical connections per the following diagram.
24 VDC
max 200 mA
- (0 v)
FUSE
1 A
FUSE
8 A
FUSE
3.15 A
FCA
LIMIT
SWITCH
OPEN/CLOSE
RELAY
COMMON
RELAY
TRANSFORMER
SECONDARY
STOP
AMPERE
TRANSFORMER
PRIMARY
PAUSE
TIME WORKING
FORCE
SLOWING
DOWN
FORC
COURTESY
LIGHT
FCC
1
2
3
4
+
-
MOTOR
RADIO CARD
CHARGE CARD
MICROPROCESSOR
OK
FUNCTIONS
14
STOP
PHOTO
OPEN
STEPBYSTEP
PHOTO2
8
6
5
+ (24v)
7
9
10
11
12
13
41
43
42
44
15
CLOSE
50-60 Hz
230 VAC
LUCY 24 VDC
max 25 W
OPEN (TIMER)
STOP
PHOTO
PHOTO2
STEP BY STEP
COMMON
BAR OPEN INDICATOR
COURTESY LIGHT
AERIAL
2¯ Ch
RADIO
CLOSE
3
Note: Only qualied, expert personnel must carry out the installa-
tion and subsequent maintenance which must be in compliance with
the DPR N° 46 dated 5/3/1990 and in total observance of the UNI
8612 standards and following the best indications dictated by “ex-
pert workmanship”. Whoever carries out these jobs shall be held re-
sponsible for any damage caused.
3. Electrical
connections
Here is a brief description of the possible connections on the unit to
the outside:
1-2 230 V AC = 230 V AC 50/60 Hz power
3-4 Flashing light = Output for connection to the 24 V DC
ashing light, maximum lamp power: 25 W
5-6 24 V DC = 24 V DC output for supplying accessories
(Photocell, Radio, etc.) maximum 200 mA
7 Common = Common for all inputs (terminal 6 can also be
used as the Common)
8Courtesy light = 24 V DC output for the courtesy light,
maximum output power 10 W
9Bar open indicator = 24 V DC output for bar open
indicator light, maximum indicator power 10 W
10 STOP = Input with STOP function (Emergency, shutdown
or extreme safety)
11 Photocell = Input for safety devices (Photocells,
pneumatic edges)
12 Photocell 2 = Input for safety devices with triggering in
the opening phase (Photocells, pneumatic edges)
13 Step by step = Input for cyclic functioning (OPEN STOP
CLOSE STOP)
14 Open-Timer = Input for opening (which can be timer
controlled)
15 Close = Input for closing
41-42 2° Radio channel = Second radio receiver channel input
(as applicable)
43-44 Antenna = Input for the radio receiver antenna
The remaining connections are done in the factory but for the sake
of completeness here is the list:
TRANSFORMER PRIMARY = Primary of the power transformer
TRANSFORMER SECONDARY = Secondary of the power transformer
MOTOR = Output for 24 V DC motor connection
There are an additional two slots for optional cards:
RADIO = Slot for Nice radio receivers
CHARGE = Slot for battery charge card
3.1 - Electrical hookup
CAUTION! - To safeguard the operator and to prevent damag-
ing components when carrying out the connections, whether in low
voltage (230 V) or extra low voltage (24 V), or when plugging in the
cards: the unit must, under no circumstances, be electrically
powered
We recommend waiting until installation is complete to plug in the
optional cards RADIO or CHARGE and only after having checked
that the system is working properly. The optional cards are not nec-
essary for the working of the system and if they are used they make
troubleshooting more complex.
We would also like to remind you that if the inputs of the NC (Nor-
mally Closed) contacts are not used, they should be jumpered; if
there is more than one then they should be placed in SERIES with
one another; if the inputs of the NO (Normally Open) contacts are
not used they should be left free and if there is more than one then
they should be placed in PARALLEL with one another. As for the
contacts, they must only be the mechanical type and free from any

4
EN
potential; no connections are allowed like those dened as “PNP”,
“NPN”, “Open Collector”, etc., etc.
01. Carry out the necessary connections, following the diagram in
Fig. 3; remember that there are specic standards that must be
complied with both as regards the safety of the electrical systems
and as regards automatic gates.
02. Check that the bar is well balanced and adjust if necessary by
means of the balancing spring.
03. Release the boom gate with the spanner and make sure the bar
can move without any effort for the whole length of its travel.
CAUTION! - Do not install the boom gate unless all the
standards regarding the automatic gate category have been
complied with!
04. Supply power to the unit, checking immediately that a voltage of
230 V AC reaches terminals 1-2 and a voltage of 24 V DC reaches
terminals 5-6. As soon as the unit is switched on the indicator lights
(LEDs) on the active inputs should turn on and after a moment, the
“OK” LED should start ashing at a regular rhythm. If none of this
happens, switch off immediately and check the connections more
carefully.
05. Check correspondence of the two LEDs, FCA and FCC: when
the bar is closed only the FCC LED should turn off and when it is
open only the FCA should turn off. To exploit the slowing down func-
tion it is necessary that the limit switch triggers about 20° before the
actual stopping point is reached; if necessary adjust the two cams
until the limit switch triggers at the point required.
06. Now check that the LEDs corresponding to the inputs with NC
type contacts are on (all the safety devices are active) and that the
LEDs corresponding to inputs of the NO type are off (no command
present); if this does not happen check connections and effective-
ness of the various devices.
07. Check that all the safety devices of the system are in proper
working order (emergency stop, photocells, pneumatic edges, etc.);
each time they trigger the relative STOP, PHOTOCELL and PHO-
TOCELL 2 LEDS must turn off.
08. Check that all function switches are off; in this way the gate is in
manual mode (hold to run). Lock the boom gate with the bar at a 45°
angle so it can move freely in both directions. Now give a brief com-
mand pulse on the OPEN input and if the bar does not move in the
opening direction proceed as follows:
1) Switch off electrical power to the gate
2) Unplug the “MOTOR” connector and replug it after it has been
turned 180°
3) Unplug the “LIMIT SWITCH” connector and replug it after it has
been turned 180°
09. Repeat the procedure described above in point Gto see if rota-
tion direction is right.
N.B.: When direction is reversed then all the three procedures de-
scribed above have to be carried out. In particular, if, for example, you
turn the “MOTOR” connector but not the “LIMIT SWITCH” connector
it will cause an error in the slowing down system. In such a case, the
motor is controlled, for instance, in the opening phase but the FCA
limit switch is never reached and consequently the bar reaches the
opening point with maximum force; the ammetric detecting system
then comes into play reversing direction in a new manoeuvre which
is also wrong.
10. Temporarily adjust the STOP_AMPERE and WORKING FORCE
trimmer to the maximum of the travel, PAUSE TIME to minimum and
SLOWING DOWN FORCE to halfway travel.
11. Try and carry out a complete manoeuvre until the bar reaches
the point where the limit switch triggers; the braking system should
come into play at this point and travel ought to continue for a further
3 seconds at a slower speed.
12. Adjust trimmers WORKING FORCE and SLOWING DOWN
FORCE so that the manoeuvre is carried out at the speed and with
the force required and that the slowing down phase is such that the
bar reaches the stopping points as “gently” as possible without any
jerking; of course, a perfect adjustment of the balancing spring is
fundamental.
13. Lastly adjust the trimmer STOP_AMPERE so the obstacle de-
tecting system, based on an ammetric friction system, is activated
as soon as an appropriate opposite action is applied to the bar. The
ammetric friction system comes into play in both directions.
3.2 - Operational tests
After the connections have been checked and veried (Chapter 3.1)
the electrically controlled movement of the bar can be tested; in this
case we suggest you work in the manual mode with all the func-
tions deactivated (all switches OFF); in all cases, in the manual mode,
by releasing the command key the motor stops immediately. If you
use the Step-by-Step input command the rst movement (after turn-
ing on) should be an opening one.
By means of the command inputs, move the bar up to the opening
point; about 20° from the stopping point the FCA limit switch should
trigger, activating the “slowing down” phase which makes the bar
reach the set point at a slower speed.
Now carry out a closing phase until the closing point is reached; in
this case too, the FCC limit switch should trigger, activating the slow-
ing down phase 20° before movement stops. Now test triggering of
the safety devices: PHOTOCELL in opening has no effect while in the
closing phase it causes the bar to stop; PHOTOCELL 2 has no effect
in the closing phase while in the opening phase it causes the bar to
stop. The devices connected to the STOP input act both in the open-
ing and in the closing phases, causing the bar to stop.
The UNI 8612 standards state that the maximum thrust of an auto-
matic device must not exceed 150 N (~13.5 kg); this is achieved by
adjusting the ammetric friction STOP_AMPERE. There is a trimmer
on the card to establish the triggering threshold of this the friction;
is has to be adjusted so that it comes into action as soon as a light
pressure is applied to the bar in the direction opposite to the way it
is moving.
To overcome the initial movement phase that always needs greater
motor power, the STOP_AMPERE friction system is excluded from
the motor start up phase; to evaluate the effect of the adjustment on
the trimmer, you ought to wait until the movement has started and the
bar has reached standard speed.
Keep in mind that, always for a question of safety, if the friction comes
into play three consecutive times, movement is stopped without any
reversal.
If the automatic functioning mode is selected at the end of the open-
ing manoeuvre, there is a “pause time” after which a closing manoeu-
vre is automatically launched. Pause time is adjusted with the trim-
mer PAUSE TIME. Pause time is also activated in the semiautomatic
functioning mode when, in the closing phase, the triggering of a safety
device or the STOP_AMPERE friction, causes a reversal in the open-
ing manoeuvre.
3.3 - Adjusting the pause time
When the automatic closing function is enabled with its dip switch
(see Chapter 3.3), following an opening manoeuvre, a timer is acti-
vated that controls the so-called “Pause Time”; when this time has
elapsed a closing manoeuvre is automatically activated. This time can
be adjusted with the PAUSE TIME trimmer from 3 to 120 seconds.
3.4 - Available functions
The FUNCTIONS dip-switch lets you select the various possible func-
tioning modes and to enable the functions you want.

5
EN
Switches 1-2
Off Off = “Manual” movement (Man Present)
On Off = “Semiautomatic” movement
Off On
= “Automatic” movement (Automatic Closing)
On On = “Automatic + Always Closes” movement
Switches 3
On = Condominium function
Switches 4
On = Cancels STOP in the Step-by-Step cycle
Switches 5
On = Pre-ashing
Switches 6
On = Flashing also in Pause
Switches 7
On = Recloses straight after Photocell
(only if on Automatic)
Switches 8
On = Safety (Photocell) also in opening
Switches 9
On = Bar open indicator becomes trafc light in
the “one-way” mode
Switches 10
On = Functioning in the “Trafc light in both
directions” mode
CAUTION! - Of course, with each switch OFF the function
described will not be activated.
3.5 - Description of denitions
Below is a brief description of the functions that can be selected;
all the functions can be enabled or disabled without any limit even if
some combinations would have no sense and, therefore, not be car-
ried out (for instance, function 6, Flashing also in Pause, would not be
carried out if movement is in the manual mode).
Switches 1-2
Off Off = “Manual” movement (Man Present)
On Off = “Semiautomatic” movement
Off On
= “Automatic” movement (Automatic Closing)
On On = “Automatic + Always Closes” movement
When in the “Manual” functioning mode, movement will only be car-
ried out while the command is being given (button pressed).
In the “Semiautomatic” mode just one command pulse is needed
and the complete manoeuvre will be carried out until it is either fully
open or fully closed. In the “Automatic” functioning mode one com-
mand pulse will cause an opening manoeuvre to be carried out fol-
lowed by a pause and then a closing manoeuvre.
The “Always Closes” function works if, subsequent to a temporary
power cut, the bar is still open; in this case, a closing manoeuvre is
started automatically preceded by 5 seconds of preashing.
Switches 3
On = Condominium function
In the Condominium functioning mode, once an opening manoeuvre
has started, for instance with a Step-by-Step pulse, it cannot be in-
terrupted by any other command pulses until it has nished.
During a closing manoeuvre, a new command pulse will stop the bar
and immediately reverse the direction, opening the bar.
Switches 4
On = Cancels STOP in the Step-by-Step cycle
The Step-by-Step cycle is normally: OPEN-STOP-CLOSE-STOP;
in this functioning mode the Step-by-Step cycle becomes: OPEN-
CLOSE-OPEN so the bar can never stop midway, but only when
completely open or completely closed.
Switches 5
On = Pre-ashing
The ashing light starts prior to each movement; after 5 seconds (2
seconds if on manual) movement starts.
Switches 6
On = Flashing also in Pause
The ashing light is normally activated only during the opening and
closing manoeuvres; with this function the ashing light remains ac-
tive also during the Pause Time to signal the “closing soon” condition.
Switches 7
On = Recloses straight after Photocell (only if on
Automatic)
With this function the bar can be kept open only for the length of time
needed for transit; in fact, it will close automatically always 5 seconds
after the last object has passed by the “Photocell”, irrespective of the
programmed Pause Time.
Switches 8
On = Safety (Photocell) also in opening
As a rule the safety “Photocell” only works in the closing cycle; if
switch 8 is “ON” the triggering of the safety device will cause the bar
to stop even in the opening phase; if on Semiautomatic or Automatic,
movement will start again, in opening, immediately after the last ob-
ject has passed by the Photocell.
Switches 9
On = Bar open indicator becomes trafc light in
the “one-way” mode
As an alternative to the Bar Open indicator, the output can be repro-
grammed so that it performs the function of a “one-way” trafc light;
this means the output is off when the bar is closed or closing, and on
when the bar is opening or is opened.
In this way, the output can be used for an indication as follows: Green
= Transit free.
Switches 10
On = Functioning in the “Trafc light in both
directions” mode
Several changes occur in the control unit when the “Trafc light in
both directions” function is activated when Switch 10 is ON: OPEN
becomes STEP-BY-STEP 2, while the two outputs, Courtesy Light
and Bar Open Indicator become a Green Light in both directions.
Due to the specic nature of this function we are giving a separate
description.
3.6 - Two-way trafc light
The function of the trafc light in both directions is mainly to control
the ow of trafc in both directions as they go across the controlled
road barrier.
A different command is placed for opening in both directions: Step
by Step for entering and Step by Step 2 (Open) for leaving; two trafc
lights are installed with the indications Red and Green, connected to
the Bar Open Indicator and Courtesy Light outputs.
TRAFFIC LIGHT
Bulbs Max 5W
BAR OPEN
INDICATOR (9)
COUR
ESY LIGHT (8)
V
R
CONTROL WITH:
STEP BY STEP 2
ENTER
EXIT
V
RCONTROL WITH:
STEP BY STEP
4
The two outputs are usually off and so are the two trafc lights; when
a command is given with Step by Step to enter, movement is started
and the Bar Open Indicator output is activated: this means there will
be a green light to enter and a red light to leave.
But should the command be given with the Step by Step 2, the Cour-
tesy Light output will be activated and there will be a green light to
leave and a red light to enter.

6
EN
The light will stay on for the entire opening manoeuvre and for the
subsequent pause time; during the closing manoeuvre both the
green and red lights will be activated (the result being yellow) to indi-
cate there is no longer any transit priority (see table).
Table 1
Red Green Meaning
OFF OFF Bar closed, no passage in either direction
OFF ON Bar open, free transit
ON OFF Bar open, transit occupied
ON ON Bar closing and transit not controlled
The two Bar Open Indicator and Courtesy Light outputs can directly
control small 24 V DC lamps for a total of 10 W. If stronger lamps have
to be used, use the relays piloted by the unit outputs that control, in
turn, the trafc lights.
IMPORTANT! - It is best to t the radio receiver at this point,
once all adjustments have been completed and with the pow-
er switched off.
3.7 - Description of the functioning
modes
In the manual functioning mode the OPEN input allows movement
up to the opening point; the CLOSE input allows movement up to
the closing point; STEP-BY-STEP allows alternative opening and clos-
ing manoeuvres; as soon as the command in input stops, movement
stops. In the opening phase movement stops when the maximum
opening point is reached or if there is no consent from PHOTOCELL
2; to the contrary, in the closing phase movement will stop at the max-
imum closed point or if there is no consent from the PHOTOCELL. If
STOP is triggered it will cause movement to stop immediately both in
the opening and closing manoeuvres. Once movement has stopped
the command in input has to be stopped before any new movements
can be active)
In either of the automatic functioning modes (semiautomatic-auto-
matic and closes always) a command on the OPEN input will cause
an opening manoeuvre; if the command remains (TIMER) once the
bar is open, the bar remains “frozen” in an innite pause; only when
the command stops will the bar be able to close. Command pulses
on the CLOSE input will cause a closing manoeuvre; if the command
remains the bar will stay locked in the closed position until the com-
mand ceases and only then can it be reopened. A pulse on STEP-BY-
STEP causes alternative opening and closing.
A second pulse on the STEP-BY-STEP or on the same input that
started the movement, will cause a Stop.
Whether in the opening or closing phase, if STOP triggers it will cause
movement to stop immediately.
In an opening manoeuvre, triggering of the PHOTOCELL has no ef-
fect while PHOTOCELL 2 will cause reversal of movement; in a clos-
ing manoeuvre, triggering of the PHOTOCELL causes movement to
reverse followed by a new pause and lastly reclosing. If at the begin-
ning of an opening movement, the PHOTOCELL input does not give
consent, the request to open is cancelled.
If the automatic functioning mode is being used, there will be a pause
time subsequent to an opening manoeuvre and followed by a closing
manoeuvre. If, during the pause the PHOTOCELL triggers, the timer
will be reset with a new time; if, on the other hand, a STOP comes
into play during the pause, the reclosing function will be cancelled and
there will be a STOP condition.
3.8 - Charge card also battery
powered
The road boom gate is equipped with a power transformer that can
withstand the energy required by both the motor and electronic card
so it can all be powered directly by the mains.
If you want the system to work even when there is a power cut then
you have to add a suitable battery and relative battery charger card.
The battery must be installed in its own compartment outside the
plastic box that protects the gearmotor card and connected to two
terminals on the battery charger card; the latter must be connected to
the connector on the unit.
4. Technical featurs of the unit
Open4000 technical features
Mains power 230 V AC ± 10%, 50-60 Hz
Battery power 21-28 V DC (> 6Ah capacity)
Max. current accessories, 24 V DC 200 mA
Max. power ashing light 25 W [24 V DC]
Max. power Courtesy Light 10 W [24 V DC]
Max. power Open Bar indicator 10 W [24 V DC]
Pause time from 3 to 120 seconds
Courtesy light time 60 seconds
Operating temperature -20 to 70° C

1
FR
GUIDE RAPIDE
ATTENTION ! - Ne pas installer la barrière sans avoir lu
toutes les instructions !
Installer la barrière, les éléments de commande (sélecteur à clé ou
tableau de commande) et de sécurité (arrêt d’urgence, photocel-
lules, barres palpeuses et clignotant), puis exécuter les connexions
électriques selon le schéma g. 1.
01. Avant d’alimenter le dispositif, vérier que la barre est bien
équilibrée, régler éventuellement le ressort d’équilibrage.
02. Débloquer la barrière en actionnant la clé prévue à cet usage et
vérier que la barre peut être actionnée sans efforts particuliers sur
toute sa course.
03. Alimenter la centrale, vérier que les bornes 1-2 sont alimen-
tées à 230 Vca et que les bornes 5-6 sont alimentées à 24 Vcc ;
les LED situées sur les entrées actives doivent s’allumer et la LED
OK devra clignoter à la fréquence d’un clignotement par seconde.
04. Contrôler la correspondance des deux LED FCA et FCC,
quand la barre est fermée seule FCC doit s’éteindre, quand elle est
ouverte, seule FCA doit s’éteindre.
05.
Pour bénécier de la fonction de ralentissement, il faut que le
micro-interrupteur de n de course intervienne environ 20° avant le
point d’arrêt effectif ; si nécessaire, régler les deux cames jusqu’à ce
que le micro-interrupteur de n de course intervienne au point désiré.
06. Vérier que tous les dip-switchs des fonctions se trouvent sur
« Off », de cette manière, le fonctionnement est en mode manuel
c’est-à-dire avec la touche enfoncée. Bloquer la barrière avec la
barre à 45° de manière qu’elle puisse bouger librement dans les
deux sens de marche, puis donner une brève impulsion sur l’entrée
OUVERTURE. Si la barre n’a pas bougé dans le sens de l’ouver-
ture, il faut procéder de la façon suivante :
a) Éteindre l’alimentation électrique de la barrière
b) Extraire le connecteur « MOTEUR» et le remettre tourné de 180°
c) Extraire le connecteur « FIN DE COURSE » et le remettre
tourné de 180°
07. Contrôler de nouveau si le sens de rotation est correct en répé-
tant l’opération décrite plus haut.
08. Régler provisoirement les trimmers STOP AMPÈRE et FORCE
TRAVAIL au maximum de la course, TEMPS PAUSE au minimum
et FORCE RALENTISSEMENT à mi-course. Essayer d’effectuer
une manœuvre entière jusqu’à ce que le micro-interrupteur de n
de course et le point d’arrêt successif soient atteints, essayer en-
suite la manœuvre opposée.
09. Régler ensuite les dip-switchs des FONCTIONS de la façon
désirée :
Dip-switch 1-2:
Off Off =Mouvement « Manuel » (Homme Présent)
On Off = Mouvement « Semi-automatique »
Off On =Mouvement « Automatique »
(Fermeture Automatique)
On On = Mouvement
« Automatique + Ferme Toujours »
Dip-switch
3:On = Fonctionnement usage collectif
Dip-switch
4:On = Annule STOP dans le cycle Pas-à-Pas
Dip-switch
5:On = Pré-clignotement
Dip-switch
6:On = Clignotement également en Pause
Dip-switch
7:On =Referme juste après Photocellule
(seulement en mode Automatique)
Dip-switch
8:On =
Sécurité (PHOTO) également en ouverture
Dip-switch
9:On =Voyant portail ouvert devient feu en mode
« à sens unique »
Dip-switch
10:On =Fonctionnement en mode « Feu dans les
deux sens »
10. Régler les deux trimmers FORCE TRAVAIL et FORCE RA-
LENTISSEMENT jusqu’à l’obtention de la force et de la vitesse
désirée respectivement durant les phases de course et de ralen-
tissement puis régler seulement à ce point-là le trimmer STOP
AMPÈRE jusqu’à l’obtention du seuil d’intervention désiré.
En cas de fonctionnement en mode automatique, régler
selon les désirs le trimmer TEMPS PAUSE.
24 Vcc
max 200 mA
- (0 v)
FCA
FIN DE
COURSE
FCC
1
2
3
4
+
-
MOTEUR
OK
TEMPS
DE PAUSE
FORCE
RAL.
FORCE
TRAVAIL
FONCTIONS
STOP
AMPÈRE
14
HALTE
PHOTO
OUVERTURE
P. P.
PHOTO2
8
6
5
+ (24v)
7
9
10
11
12
13
41
43
42
44
15
FERMETURE
50-60 Hz
230 Vca
LUCY 24 Vcc
max 25 W
ANTENNE
2° Canal
RADIO
FERMETURE
OUVERTURE (TEMPORISATEUR)
P. P.
PHOTO2
PHOTO
HALTE
VOYANT PORTAIL OUVERT
ÉCLAIRAGE DE FONCTIONNEMENT
COMMUNE
1

2
FR
Sommaire
Recommandation importante 3
1. Description du produit 4
2. Installation 4
3. Connexions électriques 4
3.1 - Effectuer les connexions électriques 4
3.2 - Essais de fonctionnement 5
3.3 - Réglage du temps de pause 5
3.4 - Fonctions sélectionnables 5
3.5 - Description des dénitions 6
3.6 - Feu dans les deux sens 6
3.7 - Description des modes de fonctionnement 7
3.8 - Carte « charge » pour alimentation également par batterie 7
4.
Caractéristiques techniques de la logique de commande
8
5. Déclaration CE de conformité 9
Recommandation importante
Nous nous devons de rappeler que vous effectuez des opérations
sur des installations appartenant à la catégorie :
« Portails et portes automatiques » et donc considérées comme par-
ticulièrement « Dangereuses » ; vous avez donc pour tâche de les
rendre « sûres » dans la mesure où cela est raisonnablement pos-
sible !
L’installation et les éventuelles interventions de maintenance doivent
être effectuées exclusivement par du personnel qualié et expéri-
menté, suivant les meilleures indications dictées par les « règles de
l’art » et conformément aux lois, normes ou directives suivantes (les
normes, les décrets du Président de la République et les décrets
législatifs sont valables uniquement pour l’Italie ; les Directives CEE
sont valables quant à elles dans toute l’Europe) :
- Norme UNI 8612 (Portails et portes motorisés : critères de construc-
tion et dispositifs de protection contre les accidents)
- DPR N°46 du 5/03/1990 (Normes pour la sécurité des installations
électriques, personnel autorisé)
- Dlgs N°459/96 du 24/07/96 (Adoption directive 89/392 CEE, Direc-
tive Machines)
- Dlgs N°615/96 du 12/11/96 (Adoption directive 89/336 CEE, Direc-
tive sur la Compatibilité électromagnétique)
- Dlgs N°626/96 du 26/11/96 (Adoption directive 93/68 CEE, Direc-
tive Basse Tension)
Dans le projet et dans la fabrication de ses produits, KING-GATES
respecte toutes ces normes (en ce qui concerne ses appareils) ; il
est indispensable toutefois que l’installateur lui aussi continue à res-
pecter scrupuleusement ces mêmes normes (en ce qui concerne les
installations).
Le personnel non qualié ou n’étant pas informé des normes appli-
cables à la catégorie des « Portails et portes automatiques » : doit
absolument s’abstenir d’effectuer les installations et de réali-
ser les circuits.
Toute personne qui réalise des installations sans respecter toutes les
normes applicables : sera tenu pour responsable de tout dom-
mage que l’installation pourra provoquer !
1. Description du
produit
La carte électronique est prévue pour commander la barrière routière
OPEN avec moteur en courant continu à 24 V.
Il s’agit d’un projet de conception nouvelle car, en effet, l’actionneur
dispose de micro-interrupteurs de n de course avec un système de
contrôle de la vitesse qui permet d’atteindre des limites de course
à travers une phase de ralentissement ; de plus, l’effort auquel est
soumis le moteur durant la manœuvre est mesuré en permanence,
les éventuels obstacles à la course sont par conséquent détectés
immédiatement et le dispositif active l’inversion de la manœuvre.
On a adopté pour le projet les techniques et les composants les plus
pointus pour garantir le maximum de protection contre les parasites,
une grande exibilité d’utilisation et un vaste choix de fonctions pro-
grammables.
Les actionnements en mode « manuel », « semi-automatique » ou
« automatique » sont possibles. On a prévu des fonctions sophis-
tiquées telles que « Referme juste après photocellule », « Referme
toujours » et « Clignotement également en pause », deux types de
fonctions avec feux ainsi que des fonctions particulières pour les
manœuvres « Départ progressif » et « Ralentissement » montées de
série, « Frein » de type sensible qui intervient seulement si l’arrêt ins-
tantané du mouvement est demandé.
La carte est prévue pour le fonctionnement avec toute la gamme de
récepteurs radio série KING-GATES.
Étant donné la particularité du produit, avant de commencer l’ins-
tallation et d’effectuer les connexions, il est indispensable de décrire
brièvement les éléments les plus importants présents sur la carte de
contrôle.
(1) Série de micro-interrupteurs « dip-switchs » pour la sélection des FONCTIONS
(2) Led clignotant à un rythme régulier qui signale le fonctionnement correct de la
centrale
(3) Trimmer « STOP AMPERE » de réglage de l’embrayage basé sur système de
mesure ampèremétrique
(4) Trimmer « TEMPS PAUSE » pour régler le temps de pause dans le mode
automatique
(5) Trimmer « FORCE TRAVAIL » pour régler la puissance du moteur durant la phase
du mouvement
(6) Trimmer « FORCE RALENTISSEMENT » pour régler la puissance du moteur dans
la phase de ralentissement
(7) Série de LED qui signalent l’état des entrées de commande
4
2
OK
1356
7
FERMETURE
OUVERTURE
P.P.
PHOTO 2
PHOTO
HALTE
FORCE
TRAVAIL
STOP
AMPÈRE
TEMPS
DE PAUSE FORCE
RAL.
2
La led OK (2) a pour fonction de signaler le fonctionnement correct
de la logique interne et doit clignoter au rythme d’1 clignotement à
la seconde ; elle indique que le microprocesseur interne est actif et
en attente de commandes. La variation de l’état d’une entrée (qu’il
s’agisse d’une entrée de commande ou d’un Dip-Switch des fonctions)
provoque un double clignotement rapide, même si la variation ne pro-
voque pas d’effets immédiats. Un clignotement rapide au rythme de 5
par seconde indique que la tension d’alimentation n’est pas sufsante.

3
FR
Quand la centrale est alimentée, les voyants se trouvant sur les entrées
(7) s’allument si cette entrée particulière est active et onc que la ten-
sion de commande à 24 Vcc est présente. Normalement les led sur
les entrées des sécurités PHOTO, PHOTO 2 et HALTE sont toujours
allumées tandis que celles sur les entrées de commande PAS-A-PAS,
OUVERTURE-TEMPORISATEUR et FERMETURE sont normalement
éteintes.
Etant donné que dans un moteur en courant continu le courant ab-
sorbé est proportionnel à l’effort auquel il est soumis, développer un
système de détection des obstacles est extrêmement simple. Durant
la manœuvre, le courant absorbé par le moteur est mesuré au fur et à
mesure, quand une certaine limite (réglable avec le trimmer) est dépas-
sée, le système de sécurité intervient et un arrêt est effectué avec
l’aide également du frein (qui élimine la partie résiduelle de l’énergie
cinétique accumulée) ; si l’un des modes de fonctionnement automa-
tique est activé, on a ensuite une manœuvre dans le sens contraire.
Pour augmenter le niveau de sécurité, si le système STOP AMPERE
intervient trois fois de suite sans jamais atteindre l’une des conclusions
naturelles du mouvement, le dispositif exécute un STOP dénitif.
2. Installation
Effectuer l’installation de la barrière routière en suivant scrupuleuse-
ment toutes les indications reportées dans la notice d’instructions.
Il faut souligner qu’il existe des normes, des lois et des réglemen-
tations qui imposent des limites et des modalités d’exécution des
installations, respecter par conséquent scrupuleusement toutes les
normes applicables.
ATTENTION ! - Ne pas installer la barrière sans respecter
toutes les normes pour la catégorie des portails automatiques !
Installer tous les éléments de commande (sélecteur à clé ou tableaux
de commande) et de sécurité prévus (arrêt d’urgence, photocellules,
barres palpeuses et clignotants). Effectuer ensuite les connexions
électriques en suivant le schéma ci-après.
24 Vcc
max 200 mA
- (0 v)
FUSIBLE
1 A
FUSIBLE
8 A
FUSIBLE
3,15 A
FCA
FIN DE
COURSE
RALIS
AP-CH
RELAIS
COMMUN
TRANSFORM.
SECOND.
TRANSF.
PRIM.
STOP
AMPÈRE
TEMPS
DE PAUSE
FORCE
TRAVAIL
ÉCL. DE
FONCT.
FORCE
RAL.
FCC
1
2
3
4
+
-
MOTEUR
CARTE « RADIO »
CARTE « CHARGE »
MICROPROCESSEUR
OK
FONCTIONS
14
HALTE
PHOTO
OUVERTURE
P. P.
PHOTO2
8
6
5
+ (24v)
7
9
10
11
12
13
41
43
42
44
15
FERMETURE
50-60 Hz
230 Vca
LUCY 24 Vcc
max 25 W
OUVERTURE (TEMPORISATEUR)
HALTE
PHOTO
PHOTO2
P. P.
COMMUNE
VOYANT PORTAIL OUVERT
ÉCLAIRAGE DE FONCTIONNEMENT
ANTENNE
2° Canal
RADIO
FERMETURE
3
Remarque : L’installation et les interventions de maintenance suc-
cessives doivent être effectuées exclusivement par du personnel
qualié et expérimenté, conformément aux prescriptions du DPR
N°46 du 5/3/1990, dans le plein respect des normes UNI 8612 et
suivant les meilleures indications dictées par les « règles de l’art ». Qui
effectue ces interventions se rend responsable des éventuels dom-
mages qui en découlent.
3. Branchements
électriques
Ci-après une brève description des connexions possibles de la cen-
trale vers l’extérieur :
1-2 230 Vac = Alimentation électrique 230 Vca 50/60 Hz
3-4 Clignotant = Sortie pour connexion au clignotant 24
Vcc, puissance maximum de la lampe 25 W
5-6 24 Vcc = Sortie 24 Vcc pour alimentation services (pho-
tocellules, radio etc.) maximum 200 mA
7 Commune = Commune pour toutes les entrées (comme
Commune, on peut utiliser également la borne 6)
8
Éclairage de fonctionnement = Sortie pour éclairage de fon-
ctionnement 24 Vcc, puissance maximum de la sortie 10 W
9Voyant portail ouvert = Sortie pour voyant portail ouvert
24 Vcc, puissance maximum du voyant 10 W
10 Halte = Entrée avec fonction de HALTE (urgence, blocage
ou sécurité extrême)
11 Photocellule = Entrée pour dispositifs de sécurité
(photocellules, barres palpeuses)
12 Photocellule 2 = Entrée pour sécurités avec intervention
en ouverture (photocellules, barres palpeuses)
13 Pas à Pas = Entrée pour fonctionnement cyclique
(OUVRE STOP FERME STOP)
14 Ouverture-temporisateur = Entrée pour ouverture
(éventuellement commandée par un temporisateur)
15 Fermeture = Entrée pour fermeture
41-42 2° Canal Radio = Sortie de l’éventuel second canal du
récepteur radio
43-44 Antenne = Entrée pour antenne du récepteur radio
Les connexions restantes sont déjà effectuées en usine, pour une
information complète, nous en donnons la liste :
TRANSF. PRIM. = Primaire du transformateur d’alimentation
TRANSF. SECOND. = Secondaire du transformateur d’alimentation
MOTEUR = Sortie pour connexion moteur 24 Vcc
La centrale contient deux autres prises à utiliser pour les cartes
en option :
RADIO = Prise pour récepteurs radio produits par Nice
CHARGE = Prise pour carte chargement batterie
3.1 - Effectuer les connexions électriques
ATTENTION ! - Pour garantir la sécurité de l’opérateur et
pour prévenir les dommages aux composants, quand on effectue
les connexions, aussi bien en basse tension (230 V) qu’en très basse
tension (24 V) ou qu’on branche les différentes cartes : la centrale
ne doit absolument pas être alimentée électriquement.
Il est conseillé d’attendre d’avoir achevé l’installation pour brancher
les éventuelles cartes en option RADIO ou CHARGE et seulement
après avoir vérié le bon fonctionnement de l’installation. Les cartes
en option ne sont pas nécessaires au fonctionnement et quand elles
sont branchées, elles rendent plus difcile la recherche de pannes
éventuelles.
Nous rappelons en outre que les entrées des contacts de type NF
(Normalement fermé) doivent être shuntées si elles ne sont pas utili-
sées ; s’il y en a plus d’une, elles doivent être mises en SÉRIE. Les
entrées des contacts de type NO (Normalement Ouvert) doivent être
laissées libres si elles ne sont pas utilisées ; s’il y en a plus d’une, elles

4
FR
doivent être mises en PARALLÈLE. En ce qui concerne les contacts,
ceux-ci doivent être absolument de type mécanique et libres de toute
puissance ; toute connexion à conguration de type « PNP », « NPN »,
« Open Collector » etc. est exclue.
01.
Effectuer les connexions nécessaires suivant le schéma de la g. 3
; nous rappelons qu’il y a des normes précises à respecter de manière
rigoureuse tant en ce qui concerne la sécurité des installations élec-
triques qu’en ce qui concerne les portails automatiques.
02. Vérier que la barre est bien équilibrée, régler éventuellement le
ressort d’équilibrage.
03. Débloquer la barrière en actionnant la clé prévue à cet usage et
vérier que la barre peut être actionnée sans efforts particuliers sur
toute sa course.
ATTENTION ! - Ne pas alimenter la barrière sans respec-
ter toutes les normes pour la catégorie des portails automa-
tiques !
04.
Alimenter la centrale, vérier immédiatement que les bornes 1-2
sont alimentées à 230 Vca et que les bornes 5-6 sont alimentées
à 24 Vcc . dès que la centrale est alimentée, les led situées sur les
entrées actives doivent s’allumer et quelques instants plus tard, la
led « OK » devra commencer à clignoter à un rythme régulier. Si
tout cela ne se produit pas, couper immédiatement l’alimentation et
contrôler soigneusement les connexions.
05. Contrôler la correspondance des deux led FCA et FCC, quand
la barre est fermée seule FCC doit s’éteindre, quand elle est ouverte,
seule FCA doit s’éteindre. Pour bénécier de la fonction de ralentis-
sement, il faut que le micro-interrupteur de n de course intervienne
environ 20° avant le point d’arrêt effectif ; si nécessaire, régler les
deux cames jusqu’à ce que le micro-interrupteur de n de course
intervienne au point désiré.
06. Vérier maintenant que les led relatives aux entrées avec contacts
type NC sont allumées (toutes les sécurités sont actives) et que les
led relatives aux entrées type NA sont éteintes (aucune commande
présente), si cela ne se produit pas, contrôler les connexions et l’ef-
cacité des différents dispositifs.
07. Vérier le fonctionnement correct de tous les dispositifs de sécu-
rité présents dans l’installation (arrêt d’urgence, photocellules, barres
palpeuses etc...), chaque fois qu’ils interviennent, les led correspon-
dantes HALTE, PHOTO ou PHOTO 2 doivent s’éteindre.
08. Vérier que tous les dip-switchs des fonctions se trouvent sur
« Off » ; de cette manière, le fonctionnement est en mode manuel
c’est-à-dire avec la touche enfoncée. Bloquer la barrière avec la
barre à 45° de manière qu’elle puisse bouger librement dans les
deux sens de marche, puis donner une brève impulsion sur l’entrée
OUVERTURE. Si la barre n’a pas bougé dans le sens de l’ouverture,
il faut procéder de la façon suivante :
1) Couper l’alimentation électrique de la barrière
2) Extraire le connecteur « MOTEUR » et le remettre tourné de 180°
3) Extraire le connecteur « FIN DE COURSE » et le remettre tourné de 180°
09. Après avoir effectué ces opérations, il convient de contrôler de
nouveau si le sens de rotation est correct en répétant l’opération
décrite au point « G».
Remarque : quand on inverse le sens de manœuvre, il faut exécuter
les trois opérations décrites ci-dessus. En particulier, si par exemple
on tourne le connecteur « MOTEUR » sans tourner le connecteur
« FIN DE COURSE » on provoque une erreur dans le système de
ralentissement. Dans ce cas, le moteur est commandé, par exemple
en ouverture, mais le micro-interrupteur de n de course FCA n’est
jamais atteint et par conséquent, la barre atteint le point d’ouver-
ture avec la force maximum. On a donc l’intervention du système de
mesure ampèremétrique qui invertit le mouvement avec une nouvelle
manœuvre, elle aussi erronée.
10. Régler provisoirement les trimmers STOP AMPÈRE et FORCE
TRAVAIL au maximum de la course, TEMPS PAUSE au minimum et
régler ensuite FORCE RALENTISSEMENT à mi-course.
11. Essayer d’effectuer une manœuvre entière jusqu’à ce que la
barre atteigne le point d’intervention du micro-interrupteur de n de
course ; on doit avoir à ce point l’entrée en jeu du ralentissement
qui permet la poursuite de la course à une vitesse réduite pendant 3
secondes de plus.
12. Régler les Trimmers FORCE TRAVAIL et FORCE RALENTIS-
SEMENT pour obtenir que la manœuvre s’effectue avec la vitesse et
la poussée désirée et que la phase de ralentissement soit telle que la
barre atteigne les points d’arrêt de la manière la plus « douce» pos-
sible et sans secousses ; naturellement, un réglage parfait du ressort
d’équilibrage est fondamental.
13. A la n, régler le trimmer STOP_AMPERE de manière que le sys-
tème de mesure des obstacles basé sur embrayage ampèremétrique
intervienne dès qu’on applique à la barre une action contraire appro-
priée. Le système d’embrayage ampèremétrique intervient dans les
deux sens de manœuvre.
3.2 - Essais de fonctionnement
Une fois que les connexions ont été vériées et la phase de contrôle
exécutée (Chap. 3.1) on peut tester le mouvement de la barre com-
mandé électriquement, dans ce cas, il est conseillé d’opérer en
mode manuel avec toutes les fonctions désactivées (tous les dip-
switchs sur Off) ; dans tous les cas, en mode manuel, en relâchant
la touche de commande on obtient l’arrêt immédiat du moteur. Si on
utilise comme commande l’entrée Pas-à-Pas, le premier mouvement
(après l’allumage) devra être en ouverture.
En agissant sur les entrées de commande, manœuvrer la barre
jusqu’au point d’ouverture, environ 20° avant le point d’arrêt, le micro-
interrupteur de n de course FCA doit se déclencher, ce micro-inter-
rupteur active la phase de « ralentissement » permettant d’atteindre le
point prévu à une vitesse réduite.
Effectuer ensuite une manœuvre en fermeture de manière à atteindre
le point de fermeture. Dans ce cas également, le micro-interrupteur
de n de course FCC activant la phase de ralentissement 20° avant
l’arrêt du mouvement devra intervenir. Tester ensuite l’intervention
des dispositifs de sécurité : en ouverture PHOTOCELLULE n’a aucun
effet, tandis qu’en fermeture, ce dispositif provoque l’arrêt de la barre
; en fermeture PHOTOCELLULE 2 n’a aucun effet, tandis qu’en
ouverture, ce dispositif provoque l’arrêt de la barre. Les dispositifs
connectés à l’entrée HALTE agissent aussi bien en ouverture qu’en
fermeture en provoquant toujours l’arrêt de la barre.
Les normes italiennes UNI 8612 prescrivent que la poussée maxi-
mum d’un dispositif d’automatisation ne dépasse pas 150 N (~ 13,5
Kg) on obtient cette valeur en réglant l’embrayage ampèremétrique
STOP_AMPERE. La carte présente un trimmer qui permet d’établir
le seuil d’intervention de l’embrayage ; il doit être réglé de manière à
intervenir dès qu’on applique à la barre une légère force dans le sens
contraire au mouvement en cours.
Pour dépasser la phase de début de la manœuvre qui demande tou-
jours une plus grande puissance de la part du moteur, le système
d’embrayage STOP AMPERE est exclu dans la phase de mise en
marche du moteur ; pour évaluer l’effet du réglage sur le trimmer, il
faut donc attendre que le mouvement soit commencé et que la barre
ait atteint la vitesse standard.
Attention : toujours pour des raisons de sécurité, si l’embrayage intervient
trois fois de suite, le mouvement est arrêté sans effectuer l’inversion.
Quand le dispositif fonctionne en mode automatique, à la n de la
manœuvre d’ouverture, on a une « pause » à la n de laquelle une
manœuvre de fermeture est automatiquement activée. Le temps de
pause est réglable à l’aide du trimmer TEMPS DE PAUSE. La pause
est activée également dans le mouvement en semi-automatique
quand, en fermeture, l’intervention d’un dispositif de sécurité ou de
l’embrayage STOP_AMPERE provoque une inversion en ouverture.
3.3 - Réglage du temps de pause
Quand la fonction de fermeture automatique est sélectionnée à travers
le dip-switch prévu à cet effet (Voir Chap. 3.3), après une manœuvre
d’ouverture, on a l’activation d’un temporisateur qui contrôle le «
Temps de pause » ; quand le temps s’est écoulé, une manœuvre de
fermeture s’active automatiquement. Ce temps peut être réglé avec
le trimmer TEMPS DE PAUSE à un valeur allant de 3 à 120 secondes
3.4 - Fonctions sélectionnables
Les dip-switchs FONCTIONS permettent de sélectionner les différents
modes de fonctionnement possibles et d’activer les fonctions désirées.

5
FR
Dip-switch 1-2
Off Off = Mouvement « Manuel » (Homme Présent)
On Off = Mouvement « Semi-automatique »
Off On = Mouvement « Automatique »
(Fermeture Automatique)
On On = Mouvement
« Automatique + Ferme Toujours »
Dip-switch
3 On = Fonctionnement usage collectif
Dip-switch
4 On = Annule STOP dans le cycle Pas-à-Pas
Dip-switch
5 On = Pré-clignotement
Dip-switch
6 On = Clignotement également en Pause
Dip-switch
7 On = Referme juste après Photocellule
(seulement en mode Automatique)
Dip-switch
8 On
= Sécurité (PHOTO) également en ouverture
Dip-switch
9 On = Voyant Portail ouvert devient feu en mode
« à sens unique »
Dip-switch
10 On = Fonctionnement en mode
« Feu dans les deux sens »
ATTENTION ! - Quand le dip-switch est sur « Off », il n’active
pas la fonction décrite.
3.5 - Description des dénitions
Donnons maintenant une brève description des fonctions sélection-
nables. Toutes les fonctions peuvent être activées ou pas sans au-
cune limite, même si certaine combinaisons pourraient ne pas avoir
de sens et donc ne pas être effectuée (par exemple la fonction n°6,
clignotant même en pause, n’est pas effectuée si le mouvement est
en mode manuel).
Dip-switch 1-2
Off Off = Mouvement « Manuel » (Homme Présent)
On Off = Mouvement « Semi-automatique »
Off On = Mouvement « Automatique »
(Fermeture Automatique)
On On
= Mouvement « Automatique + Ferme Toujours »
Dans le fonctionnement « Manuel », le mouvement est exécuté seule-
ment jusqu’à la présence de la commande (touche enfoncée).
En « Semi-automatique », il suft d’une impulsion de commande et
tout le mouvement est exécuté jusqu’à ce que l’ouverture ou la fer-
meture soient effectuées. En mode de fonctionnement « Automa-
tique », avec une seule impulsion de commande, on a une ouverture
puis une pause et automatiquement une fermeture.
La fonction « Ferme Toujours » intervient si, après une coupure
momentanée de l’alimentation, le dispositif détecte la barre encore
ouverte ; dans ce cas, on a automatiquement une manœuvre de
fermeture précédée de 5 secondes de pré-clignotement.
Dip-switch
3 On = Fonctionnement usage collectif
Dans le fonctionnement usage collectif, une fois qu’une manœuvre
d’ouverture démarre, par exemple avec une impulsion sur Pas-à-
Pas, ce mouvement ne peut plus être interrompu par d’autres impul-
sions de commande jusqu’à la n du mouvement en ouverture.
Dans le mouvement en fermeture, une nouvelle impulsion de com-
mande provoque l’arrêt et l’inversion du mouvement en ouverture.
Dip-switch
4 On = Annule STOP dans le cycle Pas-à-Pas
Le cycle du Pas-à-Pas est normalement : OUVRE - STOP - FERME
- STOP, avec cette fonction activée, le cycle Pas-à-Pas devient :
OUVRE - FERME - OUVRE et donc la barre ne pourra jamais s’arrêter
à mi-course mais seulement quand elle est complètement ouverte ou
complètement fermée.
Dip-switch
5 On = Pré-clignotement
Avant chaque mouvement, l’impulsion de commande provoque l’ac-
tivation du clignotant puis après 5 secondes (2 s en mode manuel),
le mouvement commence.
Dip-switch
6 On = Clignotement également en Pause
Normalement, le clignotant est activé seulement durant le mouve-
ment en ouverture ou en fermeture, cette fonction prévoit que le cli-
gnotant reste actif même durant la Pause, an de signaler l’état de «
fermeture prochaine ».
Dip-switch
7 On = Referme juste après Photocellule
(seulement en mode Automatique)
Cette fonction permet de garder la barre ouverte seulement le temps
nécessaire au passage ; en effet, la fermeture automatique aura lieu
toujours 5 secondes après le dégagement de la photocellule, indé-
pendamment du Temps de Pause programmé.
Dip-switch
8 On
= Sécurité (PHOTO) également en ouverture
Normalement, la sécurité « Photo » intervient seulement dans la
manœuvre de fermeture, si le dip-switch N°8 est mis sur « On »,
l’intervention du dispositif de sécurité provoque une interruption du
mouvement également en ouverture ; en mode Semi-Automatique
ou Automatique, on aura la reprise du mouvement en ouverture juste
après le nouvel accord du dispositif de sécurité.
Dip-switch
9 On = Voyant Portail Ouvert devient feu en mode
« à sens unique »
En alternative à la fonction voyant C.A. (portail ouvert), la sortie peut
être reprogrammée pour exécuter la fonction de feu « à sens unique
» de sorte que la sortie soit éteinte quand la barre est fermée ou
en fermeture et allumée dans la manœuvre d’ouverture ou quand la
barre est ouverte.
De cette manière, on peut appliquer à la sortie une indication type :
Vert = Passage libre
Dip-switch
10 On = Fonctionnement en mode
« Feu dans les deux sens »
Quand on active la fonction de « Feu dans les deux sens » en plaçant
le dip-switch 10 sur « On » différents changements se produisent
dans la centrale, OUVERTURE devient PAS-A-PAS 2, tandis que
les deux sorties Éclairage de fonctionnement et Voyant C.A. (portail
ouvert) deviennent Feu Vert pour un sens et Feu Vert pour l’autre
sens de marche. Étant donné la particularité de la fonction, nous en
donnons ci-après une description séparée.
3.6 - Feu dans les deux sens
La fonction de feu dans les deux sens est orientée principalement au
contrôle du passage des véhicules dans les deux sens de marche à
travers le passage contrôlé par la barrière routière.
Pour chaque sens de marche, il y a une commande différente pour
l’ouverture : P.P. pour entrer et P.P.2 (Ouverture) pour sortir. On a
donc deux feux avec les signalisations Rouge et Vert reliées aux sor-
ties Voyant C.A. et Éclairage de fonctionnement.
FEU
Lampes Max 5W
V.P.O.(9)
ÉCL. FONCT.(8)
V
R
COMMANDE
AVEC : P.P 2
ENTRÉE
SORTIE
V
RCOMMANDE
AVEC : P.P.
4
Normalement les deux sorties sont éteintes de même que les deux
lumières des feux ; quand une commande est donnée avec P.P pour
entrer, la manœuvre commence et la sortie Voyant portail ouvert
s’active : on aura ainsi la lumière verte en entrée et la lumière rouge
en sortie.
Si, au contraire, la commande pour l’ouverture est donnée avec
P.P.2, la sortie Écl. de Fonct. s’active et on aura donc la lumière verte
en sortie et la lumière rouge en entrée.

6
FR
La lumière restera allumée pendant toute la phase d’ouverture et
pendant la phase de pause successive, dans la phase de referme-
ture au contraire, tant les lumières vertes que les rouges (le résultat
est jaune) seront activées pour indiquer qu’il n’y a plus de priorité
dans le passage (voir tableau 1).
Tableau 1
Rouge Vert Signication
OFF OFF
Barre fermée, passage interdit dans les deux sens
OFF ON Barre ouverte, passage libre
ON OFF Barre ouverte, passage occupé
ON ON Barre en fermeture ou passage non contrôlé
Les deux sorties Voyant Portail Ouvert et Eclairage de Fonctionne-
ment peuvent commander directement des petites ampoules à 24
Vcc un total maximum de 10 W par sortie. S’il se révèle nécessaire
d’utiliser des ampoules de puissance supérieure, il sera bon de pré-
voir des relais pilotés par les sorties de la centrale qui commandent à
leur tour les ampoules du feu.
IMPORTANT ! - Ce n’est qu’à présent, à la n de tous les
réglages et sans que la centrale soit alimentée, que nous
conseillons de brancher le récepteur radio.
3.7 - Description des modes de
fonctionnement
Dans le fonctionnement en mode manuel, l’entrée OUVERTURE per-
met le mouvement jusqu’au point d’ouverture, l’entrée FERMETURE
permet le mouvement jusqu’au point de fermeture, le PAS-A-PAS
permet le mouvement alternativement en ouverture et en fermeture
; dès que la commande en entrée cesse, le mouvement s’arrête. En
ouverture, le mouvement s’arrête quand le point maximum d’ouver-
ture est atteint ou en l’absence d’accord de la part de PHOTO 2 ;
en fermeture au contraire, le mouvement s’arrête au point maximum
de fermeture ou en l’absence d’accord de PHOTO. Une intervention
sur HALTE provoque un arrêt immédiat du mouvement aussi bien en
ouverture qu’en fermeture. Une fois que le mouvement s’est arrêté, il
faut arrêter la commande en entrée avant de pouvoir commencer un
nouveau mouvement.
Dans le fonctionnement dans l’un des modes automatiques (semi-
automatique - automatique et ferme toujours) une commande sur
l’entrée OUVERTURE provoque le mouvement en ouverture, si la
commande persiste (TEMPORISATEUR) une fois que l’ouverture est
atteinte, la barre reste « congelée » dans une pause innie ; seulement
quand la commande cesse, la barre pourra être refermée. Les impul-
sions de commande sur l’entrée FERMETURE provoquent la ferme-
ture, si la commande persiste, la barre restera bloquée en fermeture
jusqu’à la cessation de la commande, ce n’est qu’après qu’elle pour-
ra être de nouveau ouverte. Une impulsion sur PAS-A-PAS provoque
alternativement l’ouverture ou la fermeture.
Une seconde impulsion sur PAS-A-PAS ou sur l’entrée qui a com-
mencé le mouvement provoque un Stop.
Aussi bien en ouverture qu’en fermeture, une intervention sur HALTE
provoque un arrêt immédiat du mouvement.
En ouverture, l’intervention de PHOTO n’a pas d’effet tandis que
PHOTO 2 provoque l’inversion du mouvement ; en fermeture, l’inter-
vention de PHOTO provoque une inversion du mouvement puis une
nouvelle pause et enn une refermeture. Si au début du mouvement
en ouverture l’entrée PHOTO ne donne pas l’accord, la demande
d’ouverture est annulée.
Si le mode de fonctionnement automatique est activé, après une
manœuvre d’ouverture, on a une pause à la n de laquelle se produit
une fermeture. Si PHOTO intervient durant la pause, le temporisateur
sera réinitialisé avec un nouveau temps ; si au contraire on intervient
durant la pause sur HALTE, la fonction de refermeture est effacée et
on passe à un état de STOP.
3.8 - Carte « charge » pour alimentation
également par batterie
La barrière routière dispose d’un transformateur de puissance à
même de supporter la demande d’énergie du moteur et de la carte
électronique de manière à pouvoir alimenter tout le dispositif sur le
secteur.
Si l’on désire que le système fonctionne même en cas de coupure du
courant électrique, il faut ajouter une batterie appropriée et la carte
pour le chargement de la batterie.
La batterie doit être placée dans le logement à l’extérieur du coffret
plastique qui protège la carte et connectée aux deux bornes prévues
sur la carte pour le chargement de la batterie tandis que la carte pro-
prement dite doit être branchée dans le connecteur présent sur la
centrale.
4. Caractéristiques techniques de la centrale
Caractéristiques techniques Open4000
Alimentation secteur 230 Vca ± 10%, 50 - 60 Hz
Alimentation par batterie 21 ÷ 28 Vcc (capacité > 6 Ah)
Courant max. services 24 Vcc 200 mA
Puissance maximum clignotant 25 W (24 Vcc)
Puissance maximum Éclairage de fonct. 10 W (24 Vcc)
Puissance maximum voyant portail ouvert 10 W (24 Vcc)
Temps de pause de 3 secondes à 120 secondes
Temps d’éclairage de fonctionnement
60 secondes
Température de fonctionnement -20 ÷ 70 °C
Other manuals for STAR OPEN 4000
1
Table of contents
Languages:
Other King gates Automatic Barrier manuals