KLIK OSFM User manual

Presence Mode with Photocell:
On movement the light will be turned ON when ambient light level
is below Setpoint On lux level. If no presence is detected, light will
be turned off after Time Out Period. If a presence is detected, light
will continue ON.
In this mode the detector can be overridden on (off) by use of the
remote control, it will remain on (off) for that period of occupancy.
A new programming command will cancel the override.
During programming the sensor will switch the lights ON or OFF
(depending on current state) for 2 seconds to acknowledge a
successful programming operation.
Set the dil switches to the following positions to achieve the desired
modes, point at the OSFM/P or OSSM/P and press the button.
Introduction
Occupancy Sensor - OSFM/P, OSSM/P
Hand Held Controller - OSRC, OSRCP
Congratulations on purchasing your new Klik Occupancy sensor
and/or hand held controller.
This product must be installed by a competent person in accordance
with the current editions of the IEE Wiring Regulations (BS7671) and
Building Regulations.
The Klik occupancy sensor responds automatically to presence and
ambient light conditions to provide a quick and efficient means of
lighting control.
The OSFM/P and OSSM/P use passive infrared technology and
combine an integral photocell to provide automatic control of light-
ing. Programming is achieved using the hand held remote control
(OSRCP), which enables easy commissioning when you have
multiple sensors, saving time during installation.
The time delay and lux levels can be adjusted using the hand held
programmer, without the need to even touch the sensor.
Positioning Considerations
The OSFM/P and OSSM/P should be mounted in the centre of the
group of luminaires to be controlled and the optimum all round cov-
erage is achieved with the unit mounted at a height of 2.5m. The
coverage for these sensors at this height is 6m diameter.
For Technical Support regarding this product please phone:
0870 607 6677
Installation and Mounting: OSSM/P Surface Mounted Version
OSSM/P is suitable for surface mounting. The product can be
directly mounted onto a BESA box or to any solid surface using the
fixing positions.
1. Decide upon the position for mounting the occupancy sensor.
2. Remove the top cover of the sensor by twisting the top cover
anti-clockwise.
3. Fix the ceiling-mounting bracket using the two screws provided.
4. Connect the cables to the corresponding terminals on the base
cover assembly. (see page 2 for connection diagrams)
5. Position the base cover assembly over the ceiling-mounting
bracket and rotate.
Note: Thi product can be in talled without the need for the ceiling
mounting bracket if there i no BESA box.
Modes of Operation
Installation and Mounting: OSFM/P Flush Mounted Version
Minimum
125 mm
Maximum
35mm
Secure with locking ring
before terminating the
cable into the KLDS,
junction Box or Luminaire.
Cut 50mm
circular hole
Ensure there is sufficient
cable length to reach from
the chosen location to the
LDS box, unction box or
Luminaire tray.
Close
Presence Detection Mode:
On movement the light will turn ON and remain on whilst presence is
detected. If no presence is detected, light will be turned off after
Time Out Period. This mode is independent of the photocell and
lighting levels.
In this mode the detector can be overridden on (off) by use of the
remote control, it will remain on (off) for that period of occupancy.
A new programming command will cancel the override.
alk Test Mode:
On movement the light will turn on, and off after 5 seconds if no
movement has been detected. This mode should be selected during
commissioning stage to verify the operation of the sensor.
Factory Reset:
This will reset the sensors settings to the default factory settings.
- Timeout = 24 min
- Normal Mode
Hager Ltd. Hortonwood 50, Telford, Shropshire, TF1 7FT
Sales Hotline: 0870 240 2400
Technical Support Helpline: 0870 607 6677
Modify Parameters:
Setting Time Out Period:
Set the switch positions according to the time delay period
required.
i.e. 36 minutes = 24 + 12
9 minutes = 6 + 3
After this time period if no presence is detected the lights will go
off.
14
Ceiling mounting
bracket
Base cover assembly
Top cover
For normal operation For presence detection only
For commissioning and testing
Open
Possible Modes of Operation:
Normal Mode
Presence Detection Only
Walk Test Mode
Default to Factory Settings
www.hager.co.uk
4696016 v5
Setting Set Point On:
Wait for, or simulate a lux level at which the lighting should switch
on. (Note: the lights should be switched off before programming
this setting) Aim programmer at sensor and push button.
NB: After modifying any parameters return the dil switches to the
desired mode of operation.

Connection Diagrams OSFM/P directly connected to a Klik Lighting Distribution Box (KLDS)
Ensure that the supply is isolated before removing any covers of the
KLDS.
1. Remove the end cap terminal cover from the KLDS distribution
box.
2. Remove 20mm knockout from a suitable position for cable entry
on the KLDS box.
3. Fit the 20mm cord grip bush provided into this exposed opening.
4. Thread the connection cable of the OSFM/P through this bush,
tighten cord grip bar to hold cable securely.
5. Connect the three core Sensor cable as shown.
• Blue Neutral conductor to Neutral terminal.
• Brown Live conductor to LOOP In terminal.
• Black Switch Return conductor to Switch ‘A’ or
Switch ‘B’ to control sockets ‘A’ or ‘B as required.
6. Remove the Line coupler if circuit A & B are switched
independantly.
7. Replace the end cap terminal cover and secure with fixing screws
to make safe.
Note: If the en or i delivered with 4 core , the yellow/green
conductor hould be terminated in the earth terminal.
Connection Diagrams OSFM/P directly connected
to a luminaire tray or junction box.
Connection diagram for OSSM/P directly connected
to a Klik Lighting Distribution Box (KLDS)
Connection diagram for OSSM/P
2
Using a suitable terminal block or junction box make the following
connection
1. Using a suitable terminal block or junction box make the following
connections:
• Earth conductor to a free terminal point, and then onto the
luminaire tray.
• Neutral conductor to a free terminal point, and then onto the
luminaire tray.
• Live conductor to a free terminal point, DO NOT CONNECT to
the luminaire tray.
• Live connection of the luminaire tray to a free terminal point.
2. Run the Occupancy Sensor connection cable to this terminal
bank/junction box, and secure in position using the 20mm cord
grip bush provided, or another suitable means. Ensure that there
is sufficient free cable length for connections to be made.
3. Connect the three core Sensor cable as follows:
• Blue Neutral conductor to Neutral termination.
• Brown Live conductor to Live termination.
• Black Switch Return conductor to luminaire tray Live
termination.
4. Seat terminal bank/junction box to make installation electrically
safe.
Technical Data:
OSFM/P & OSSM/P
Recommended Mounting Height 2.5m
Detection Angle & Range Angle = 360°
Range in diameter approximately 6 meter @2.5m ceiling height
Photocell Lux adjustment 5 - 1000 Lux adjustable
Time Out Period adjustment 10 sec to 45 min
Factory-set time out 24 minutes
Warm up time 35 - 45 seconds
Power supply AC 230V+/- 10% @ 50Hz
Current consumption 39mA (for OSSM/P and OSFM/P)
(Capacity/loading)
Incandescent lamp load Maximum 6A
Resistive load Maximum 10A
Fluorescent load Maximum 6A
Compact fluorescent Maximum 3A
Operating Temperatures -5ºc to 40ºc
IP Rating IP20
Weight OSFM/P: 388g with cable, 108g without cable
OSSM/P: 100g
Battery CR2032
Cable OSFM/P Low Smoke Zero Halogen (LSOH) 3m, 1.00mm2
Infrared user override for Klik Occupancy Sensor
OSRC - Remote Controller for User Overriding
The remote controller enables the occupancy sensors to be manually
overridden on or off.
1. Aim the OSRC at the occupancy sensor and press the button
once.
2. When the detector has been overridden on (off) by use of the
remote control, it will remain on (off) for that period of occupancy.
N.B Before use remove clear plastic tab which protects the battery.
3
OSRCP - Remote Controller for Programming and User
Overriding
Overview
This product is a programming tool used in conjunction with OSFM/P
and OSSM/P products. It can also be used to manually override the
Occupancy Sensor.
The programming tool OSRCP is almost identical to the user override
OSRC, the only difference being the six dil switches that may be set
to give the desired programme parameters. Operation is simple: set
the dil switches, point at the OSFM/P/OSSM/P and press the button
once.
The following settings and configurations are possible using the hand
held programmer:
Infrared programming tool for Klik Occupancy Sensor
Time Out Period Set the time period after the last observed movement for which the lights will switch off -10 sec to 45 min.
Lux Level Set the lux level at which the occupancy sensor should switch the lights on or off automatically. There are two set points:
Setpoint On: Light will be turned ON when the ambient light level is below Setpoint On. If no presence is detected the
light will be turned off after time out period elapses.
N.B Before use remove clear plastic tab which protects the battery
N.B The OSFM/P is Double Insulated
Earth conductor
(if 4 wire cable)

Connection Diagrams OSFM/P directly connected to a Klik Lighting Distribution Box (KLDS)
Ensure that the supply is isolated before removing any covers of the
KLDS.
1. Remove the end cap terminal cover from the KLDS distribution
box.
2. Remove 20mm knockout from a suitable position for cable entry
on the KLDS box.
3. Fit the 20mm cord grip bush provided into this exposed opening.
4. Thread the connection cable of the OSFM/P through this bush,
tighten cord grip bar to hold cable securely.
5. Connect the three core Sensor cable as shown.
• Blue Neutral conductor to Neutral terminal.
• Brown Live conductor to LOOP In terminal.
• Black Switch Return conductor to Switch ‘A’ or
Switch ‘B’ to control sockets ‘A’ or ‘B as required.
6. Remove the Line coupler if circuit A & B are switched
independantly.
7. Replace the end cap terminal cover and secure with fixing screws
to make safe.
Note: If the en or i delivered with 4 core , the yellow/green
conductor hould be terminated in the earth terminal.
Connection Diagrams OSFM/P directly connected
to a luminaire tray or junction box.
Connection diagram for OSSM/P directly connected
to a Klik Lighting Distribution Box (KLDS)
Connection diagram for OSSM/P
2
Using a suitable terminal block or junction box make the following
connection
1. Using a suitable terminal block or junction box make the following
connections:
• Earth conductor to a free terminal point, and then onto the
luminaire tray.
• Neutral conductor to a free terminal point, and then onto the
luminaire tray.
• Live conductor to a free terminal point, DO NOT CONNECT to
the luminaire tray.
• Live connection of the luminaire tray to a free terminal point.
2. Run the Occupancy Sensor connection cable to this terminal
bank/junction box, and secure in position using the 20mm cord
grip bush provided, or another suitable means. Ensure that there
is sufficient free cable length for connections to be made.
3. Connect the three core Sensor cable as follows:
• Blue Neutral conductor to Neutral termination.
• Brown Live conductor to Live termination.
• Black Switch Return conductor to luminaire tray Live
termination.
4. Seat terminal bank/junction box to make installation electrically
safe.
Technical Data:
OSFM/P & OSSM/P
Recommended Mounting Height 2.5m
Detection Angle & Range Angle = 360°
Range in diameter approximately 6 meter @2.5m ceiling height
Photocell Lux adjustment 5 - 1000 Lux adjustable
Time Out Period adjustment 10 sec to 45 min
Factory-set time out 24 minutes
Warm up time 35 - 45 seconds
Power supply AC 230V+/- 10% @ 50Hz
Current consumption 39mA (for OSSM/P and OSFM/P)
(Capacity/loading)
Incandescent lamp load Maximum 6A
Resistive load Maximum 10A
Fluorescent load Maximum 6A
Compact fluorescent Maximum 3A
Operating Temperatures -5ºc to 40ºc
IP Rating IP20
Weight OSFM/P: 388g with cable, 108g without cable
OSSM/P: 100g
Battery CR2032
Cable OSFM/P Low Smoke Zero Halogen (LSOH) 3m, 1.00mm2
Infrared user override for Klik Occupancy Sensor
OSRC - Remote Controller for User Overriding
The remote controller enables the occupancy sensors to be manually
overridden on or off.
1. Aim the OSRC at the occupancy sensor and press the button
once.
2. When the detector has been overridden on (off) by use of the
remote control, it will remain on (off) for that period of occupancy.
N.B Before use remove clear plastic tab which protects the battery.
3
OSRCP - Remote Controller for Programming and User
Overriding
Overview
This product is a programming tool used in conjunction with OSFM/P
and OSSM/P products. It can also be used to manually override the
Occupancy Sensor.
The programming tool OSRCP is almost identical to the user override
OSRC, the only difference being the six dil switches that may be set
to give the desired programme parameters. Operation is simple: set
the dil switches, point at the OSFM/P/OSSM/P and press the button
once.
The following settings and configurations are possible using the hand
held programmer:
Infrared programming tool for Klik Occupancy Sensor
Time Out Period Set the time period after the last observed movement for which the lights will switch off -10 sec to 45 min.
Lux Level Set the lux level at which the occupancy sensor should switch the lights on or off automatically. There are two set points:
Setpoint On: Light will be turned ON when the ambient light level is below Setpoint On. If no presence is detected the
light will be turned off after time out period elapses.
N.B Before use remove clear plastic tab which protects the battery
N.B The OSFM/P is Double Insulated
Earth conductor
(if 4 wire cable)

Presence Mode with Photocell:
On movement the light will be turned ON when ambient light level
is below Setpoint On lux level. If no presence is detected, light will
be turned off after Time Out Period. If a presence is detected, light
will continue ON.
In this mode the detector can be overridden on (off) by use of the
remote control, it will remain on (off) for that period of occupancy.
A new programming command will cancel the override.
During programming the sensor will switch the lights ON or OFF
(depending on current state) for 2 seconds to acknowledge a
successful programming operation.
Set the dil switches to the following positions to achieve the desired
modes, point at the OSFM/P or OSSM/P and press the button.
Introduction
Occupancy Sensor - OSFM/P, OSSM/P
Hand Held Controller - OSRC, OSRCP
Congratulations on purchasing your new Klik Occupancy sensor
and/or hand held controller.
This product must be installed by a competent person in accordance
with the current editions of the IEE Wiring Regulations (BS7671) and
Building Regulations.
The Klik occupancy sensor responds automatically to presence and
ambient light conditions to provide a quick and efficient means of
lighting control.
The OSFM/P and OSSM/P use passive infrared technology and
combine an integral photocell to provide automatic control of light-
ing. Programming is achieved using the hand held remote control
(OSRCP), which enables easy commissioning when you have
multiple sensors, saving time during installation.
The time delay and lux levels can be adjusted using the hand held
programmer, without the need to even touch the sensor.
Positioning Considerations
The OSFM/P and OSSM/P should be mounted in the centre of the
group of luminaires to be controlled and the optimum all round cov-
erage is achieved with the unit mounted at a height of 2.5m. The
coverage for these sensors at this height is 6m diameter.
For Technical Support regarding this product please phone:
0870 607 6677
Installation and Mounting: OSSM/P Surface Mounted Version
OSSM/P is suitable for surface mounting. The product can be
directly mounted onto a BESA box or to any solid surface using the
fixing positions.
1. Decide upon the position for mounting the occupancy sensor.
2. Remove the top cover of the sensor by twisting the top cover
anti-clockwise.
3. Fix the ceiling-mounting bracket using the two screws provided.
4. Connect the cables to the corresponding terminals on the base
cover assembly. (see page 2 for connection diagrams)
5. Position the base cover assembly over the ceiling-mounting
bracket and rotate.
Note: Thi product can be in talled without the need for the ceiling
mounting bracket if there i no BESA box.
Modes of Operation
Installation and Mounting: OSFM/P Flush Mounted Version
Minimum
125 mm
Maximum
35mm
Secure with locking ring
before terminating the
cable into the KLDS,
junction Box or Luminaire.
Cut 50mm
circular hole
Ensure there is sufficient
cable length to reach from
the chosen location to the
LDS box, unction box or
Luminaire tray.
Close
Presence Detection Mode:
On movement the light will turn ON and remain on whilst presence is
detected. If no presence is detected, light will be turned off after
Time Out Period. This mode is independent of the photocell and
lighting levels.
In this mode the detector can be overridden on (off) by use of the
remote control, it will remain on (off) for that period of occupancy.
A new programming command will cancel the override.
alk Test Mode:
On movement the light will turn on, and off after 5 seconds if no
movement has been detected. This mode should be selected during
commissioning stage to verify the operation of the sensor.
Factory Reset:
This will reset the sensors settings to the default factory settings.
- Timeout = 24 min
- Normal Mode
Hager Ltd. Hortonwood 50, Telford, Shropshire, TF1 7FT
Sales Hotline: 0870 240 2400
Technical Support Helpline: 0870 607 6677
Modify Parameters:
Setting Time Out Period:
Set the switch positions according to the time delay period
required.
i.e. 36 minutes = 24 + 12
9 minutes = 6 + 3
After this time period if no presence is detected the lights will go
off.
14
Ceiling mounting
bracket
Base cover assembly
Top cover
For normal operation For presence detection only
For commissioning and testing
Open
Possible Modes of Operation:
Normal Mode
Presence Detection Only
Walk Test Mode
Default to Factory Settings
www.hager.co.uk
4696016 v5
Setting Set Point On:
Wait for, or simulate a lux level at which the lighting should switch
on. (Note: the lights should be switched off before programming
this setting) Aim programmer at sensor and push button.
NB: After modifying any parameters return the dil switches to the
desired mode of operation.
This manual suits for next models
5
Other KLIK Accessories manuals