VariTrans® P 27000-S009
Universal Isolators
Read these instructions before using the product and retain for future information.
TA-251.102-KNE01 20111128

2
1. Safety Information
Caution!
The VariTrans® P 27000 universal isolators must be installed only by qualified
and specially trained personnel authorized by the operating company.
Do not connect the device to power supply before it is professionally installed.
Do not change the measuring range during operation. Observe the national
codes and regulations during installation and selection of cables and lines.
Equipment shall be provided with a means for disconnecting it from each
operating energy supply source. The disconnecting means shall disconnect all
current-carrying conductors. (It must be easily accessible and clearly identifiable
by the operator.)
Mains supply must be protected by a fuse of 20 A max.
Caution!
Be sure to take protective measures against electrostatic discharge
(ESD) when handling the devices!
The warning symbol on the device (exclamation point in triangle)
means: Observe instructions!
Warning! Protection against electric shock
For applications with high working voltages, take measures to prevent
accidental contact and make sure that there is sufficient distance or
insulation between adjacent devices!

3
Warning! EXPLOSION HAZARD
Do not connect/disconnect equipment unless power has been
removed or the area is known to be non-hazardous.
Warning! EXPLOSION HAZARD
Substitution of components may impair suitability for Class I,
Division 2.
For the use in hazardous locations, this equipment is to be installed
into suitable enclosure, providing a degree of protection not less
than IP 54.
Devices containing user accessible switches and/or potentiometers:
the device must be installed into an end-use enclosure with tool
removable cover.
Conditions for safe use (Haz. Loc.)

4
2. Intended Use
The special models P 27000-S009 universal isolators are used for galvanic
isolation and conversion of input signals from 0 ... ± 10 V to output signals from
±0 ... 10 V or ± 0 ... 20 mA. The calibrated output signal range is selected via
DIP switches. Signal transmission is linear. By means of the broad-range mains
adapter, the units can be powered by voltages from 20 to 253 V AC/DC.
Connection is made using pluggable screw clamp terminals.
Warning against misuse
Do not operate the device outside the conditions specified by
the manufacturer, as this might result in hazards to operators or
malfunction of the equipment.
3. Configuration
3.1 Tools
A screwdriver with a width of 2.5 mm is required to open and adjust the unit
and to connect the wires to the screw clamp terminals.

5
3.2 Opening the unit
Disengage the top part of the housing on
both sides using the screwdriver.
Pull out the top part of the housing and
the electronics section until they lock.
3.3 Settings
Adjust the output range using DIP switches
S1, S2 and S3 as shown in the tables or on
the rating plate.
Input Output S1 S2 S3
1 X 1 2 3 4 5 1 2 3
0 ... ± 10 V 0 ... ± 10 V OFF OFF OFF ON OFF ON ON ON ON OFF
0 ... ± 10 V 0 ... ± 20 mA ON OFF OFF ON OFF ON ON OFF OFF OFF

6
Terminal assignments
1 Do not connect
2 Do not connect
3 Input +
4 Input -
5 Output +
6 Output -
7 Power supply
8 Power supply
Wire cross-section max. 2,5 mm2
Multi-wire connection max. 1 mm2
(two wires with same cross-section)
AWG 30-12, tightening torque 0.7 Nm
Wiring has to be suitable for a
temperature of min. 75 °C
4. Mounting
The universal isolators are mounted on standard TS 35 rails.
5. Electrical Connection
Warning!
For applications with high working voltages, take measures to prevent
accidental contact and make sure that there is sufficient distance or insulation
between adjacent devices!
5.1 Power supply
22 to 230 V AC/DC ± 10 %, 0.9 W, AC 48 to 62 Hz, 2.5 VA,
(overvoltage category II)

7
6. Dimensions
Metal lock for fastening
on top-hat rail
Fixed screw clamp
terminals
111
99

8
7. Declarations, Certificates and Approvals
Open-type Process Control Equipment also listed
Proc. Contr. Eq. for Use in Haz. Loc.
File: E340287, E308146, E340288
CE marking
The EU Declaration of Conformity is included in the documentation.
The Statement of Conformity for ATEX Zone 2 apparatus is included
in the documentation.
GL
Certificate No. 42 843 - 02 HH
Environmental Category: D
Test Standard: Regulations of the Performance of Type Tests, Part 1
EN 61010-1
8. Order Information
Adjustable Device Order No.
Pluggable screw
clamp terminals
P 27000-S009 Universal Isolator P 27000 H1-S009

9
9. Technical Data
Input data
Voltage input ± 0 ... 10 V
Overload
Voltage input
limited by 36 V suppressor diode,
max. permissible continuous current ≤ 20 mA
Output data
Output 0 ... ± 10 V, 0 ... ± 20 mA
calibrated selection
Load
for output current
for output voltage
≤12 V1) (600 Ω at 20 mA)
≤10 mA (1 kΩ at 10 V)
Offset error 20 µA / 10 mV
Residual ripple approx. 20 mVrms
General data
Gain error < 0.08 % meas. value
typical additional error for AC (45 ... 65 Hz sinus)
0.05 % meas. value
Temperature
coefficient2)
< 50 ppm/K of final value
Cutoff frequency approx. 20 kHz
Test voltage 5 kV~ input against output
4 kV~ output against power supply
Working voltage3)
(basic insulation)
1 kV~for overvoltage category II and
pollution degree 2 to EN 61010-1
For applications with high working voltages, take precautions
to prevent accidental contact and make sure that there is
sufficient distance to adjacent devices or sufficient insulation
between them.

10
Protection against
electric shock3)
Protective separation to EN 61140 by reinforced insulation
according to EN61010-1 up to 600 V AC/DC across input
and output for overvoltage category II and pollution
degree2, up to 300 V AC/DC across output and ower
supply for overvoltage category II and pollution degree 2.
For applications with high working voltages, take measures
to prevent accidental contact and make sure that there
is sufficient distance to adjacent devices or sufficient
insulation between them.
EMC4) 2004/108/EC
EN 61326
EN 61326/A1
Surge withstand 5 kV, 1.2/50 μs, to IEC 255-4
Ambient temperature Operation
Transport and storage
-10 to +70 °C
-40 to +85 °C
Ambient conditions Stationary application, weather-protected
Relative air humidity 5 ... 95 %, no condensation
Barometric pressure: 70 ... 106 kPa, altitude up to 2000 m
Water or wind-driven precipitation (rain, snow, hail)
excluded
Power supply 22 to 230 V AC/DC ± 10 %, 0.9 W, AC 48 to 62 Hz; 2.5 VA,
(overvoltage category II)
Construction Modular housing with pluggable screw clamp terminals,
see dimension drawing
Protection IP 20
Weight approx. 150 g

11
Explosion protection Europe: II 3G Ex nA IIC T4 Gc X
USA: Class I Div.2 GRP A,B,C,D T4
Class I Zone 2 AEx nA IIC T4
Canada: Class I Zone 2 Ex nA IIC T4 X
Class I Div.2 GRP A,B,C,D T4
1) Higher output load on request
2) Average TC in specified operating temperature range -10 ˚C ... +70 ˚C.
3) cULus certification: Working voltage (basic insulation) up to 600 V,
working voltage (reinforced insulation) up to 300 V across input and output,
each for overvoltage category II and pollution degree 2
4) Slight deviations are possible while there is interference

12
Knick Elektronische Messgeräte
GmbH & Co. KG
Beuckestraße 22
D-14163 Berlin
Phone: +49 (0)30 - 801 91 - 0
Fax: +49 (0)30 - 801 91 - 200
Internet: http://www.knick.de
Email: [email protected]
Table of contents
Popular Network Hardware manuals by other brands

Omron
Omron CS1W-SLK11-21 - 06-2004 manual

HP Enterprise
HP Enterprise AFS3 Installation

INSIGHT
INSIGHT DLP SENSOR 600 Hardware installation guide

FieldServer
FieldServer ControlNet FS-8700-24 Driver manual

Rittal
Rittal CMC-TC ISDN Unit 7320.830 operating manual

Interlogix
Interlogix TruVision NVR 20 user manual