KNX AQS/TH-UP Touch Guide

KNX AQS/TH-UP Touch
Combined indoor sensor
Item numbers 70619 (black), 70620 (pure white)
EN
Installation and Ad justment


1 Content
Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany
Sensor KNX AQS/TH-UP Touch • from ETS programme version 1.0
Status: 23.10.2018 • Technical changes and errors excepted.
1. Description ........................................................................................... 4
1.0.1. Scope of delivery .......................................................................................... 5
1.1. Technical specifications ........................................................................................... 5
1.1.1. Accuracy of the measurement ..................................................................... 6
2. Installation and commissioning ........................................................... 6
2.1. Installation notes ...................................................................................................... 6
2.2. Installation position .................................................................................................. 7
2.3. Composition ............................................................................................................. 8
2.3.1. Housing .......................................................................................................... 8
2.4. Assembly of the sensor ........................................................................................... 8
2.5. Notes on mounting and commissioning ................................................................ 8
3. Display and operation at the device .................................................... 9
3.1. Mode display and manual temperature controller ................................................ 9
3.2. Change ambient temperature with the buttons .................................................. 10
4. Transfer protocol ............................................................................... 12
4.1. List of all communications objects ....................................................................... 12
5. Parameter setting .............................................................................. 23
5.1. Behaviour on power failure/ restoration of power .............................................. 23
5.2. General settings ..................................................................................................... 23
5.3. Temperature value ................................................................................................. 23
5.4. Temperature threshold values .............................................................................. 24
5.4.1. Threshold value 1, 2, 3 ............................................................................... 24
5.4.1.1. Threshold value ............................................................................ 24
5.4.1.2. Switching output .......................................................................... 25
5.4.1.3. Block .............................................................................................. 26
5.5. Temperature PI control .......................................................................................... 26
5.5.0.1. General control ............................................................................. 26
5.5.1. General set point values ............................................................................. 28
5.5.1.1. Set point Comfort ......................................................................... 29
5.5.1.2. Standby setpoint ........................................................................... 30
5.5.1.3. Eco setpoint ................................................................................... 30
5.5.1.4. Setpoint values for frost/heat protection (building protection) 31
5.5.1.5. General control variables ............................................................. 31
5.5.2. Heating control level 1/2 ............................................................................. 32
5.5.3. Cooling control level 1/2 ............................................................................. 34
5.6. Humidity measurement ......................................................................................... 36
5.7. Humidity threshold values .................................................................................... 36
5.7.1. Threshold value 1, 2 ................................................................................... 37
5.7.1.1. Threshold value ............................................................................ 37
5.7.1.2. Switching output .......................................................................... 38
5.7.1.3. Block .............................................................................................. 38
5.8. Humidity PI control ................................................................................................ 39

2 Content
Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany
Sensor KNX AQS/TH-UP Touch • from ETS programme version 1.0
Status: 23.10.2018 • Technical changes and errors excepted.
5.8.0.1. General control ............................................................................. 39
5.8.0.2. Controller setpoint ........................................................................ 40
5.8.0.3. Dehumidification and/or humidification ..................................... 41
5.9. Dewpoint measurement ........................................................................................ 42
5.9.1. Cooling medium temp. monitoring ........................................................... 42
5.9.1.1. Threshold value ............................................................................ 42
5.9.1.2. Switching output .......................................................................... 43
5.9.1.3. Blocking ......................................................................................... 43
5.10.Absolute humidity ................................................................................................. 44
5.11.Comfort field .......................................................................................................... 45
5.12.CO2parameter settings ......................................................................................... 45
5.13.CO2 threshold values ............................................................................................ 46
5.13.1. Threshold value 1, 2, 3, 4 ........................................................................... 46
5.13.1.1.Threshold value ............................................................................ 46
5.13.1.2.Switching output .......................................................................... 47
5.13.1.3.Block .............................................................................................. 48
5.14.CO2 PI-control ........................................................................................................ 49
5.14.0.1.General control ............................................................................. 49
5.14.0.2.Controller setpoint ........................................................................ 49
5.14.0.3.Ventilation control ........................................................................ 50
5.15.Variable comparator .............................................................................................. 51
5.15.1. Control variable comparator 1/2 ................................................................ 51
5.16.Logic ........................................................................................................................ 52
5.16.0.1.AND logic ....................................................................................... 52
5.16.0.2.OR logic ......................................................................................... 52
5.16.1. AND logic 1-4 and OR logic outputs 1-4 ................................................... 52
5.16.1.1.Block .............................................................................................. 54
5.16.2. Connection inputs of the AND logic .......................................................... 54
5.16.3. Connection inputs of the OR logic ............................................................. 56
5.17.Display .................................................................................................................... 56
5.18.Pushbutton ............................................................................................................. 58
5.18.1. Pushbutton for temperature control ......................................................... 59
5.18.2. Pushbutton interface .................................................................................. 59

3 Clarification of signs
This manual is amended periodically and will be brought into line with new software
releases. The change status (software version and date) can be found in the contents footer.
If you have a device with a later software version, please check
www.elsner-elektronik.de in the menu area "Service" to find out whether a more up-to-
date version of the manual is available.
Clarification of signs used in this manual
Installation, inspection, commissioning and troubleshooting of the device
must only be carried out by a competent electrician.
Safety advice.
Safety advice for working on electrical connections, components,
etc.
DANGER! ... indicates an immediately hazardous situation which will lead to
death or severe injuries if it is not avoided.
WARNING! ... indicates a potentially hazardous situation which may lead to
death or severe injuries if it is not avoided.
CAUTION! ... indicates a potentially hazardous situation which may lead to
trivial or minor injuries if it is not avoided.
ATTENTION! ... indicates a situation which may lead to damage to property if it is
not avoided.
ETS In the ETS tables, the parameter default settings are marked by
underlining.

4 Description
Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
1. Description
The Sensor KNX AQS/TH-UP Touch measures CO2concentration, temperature and
humidity and calculates the dew point. The sensor can receive external measured
values via the bus and process them with the own data to overall values (mixed values,
e. g. room average). The KNX AQS/TH-UP Touch offers two push buttons that may
be used for changing the ambient temperature (target value), for switching between
operating modes or as free programmable bus push buttons.
The KNX AQS/TH-UP Touch provides switching outputs with adjustable threshold
values. The switching outputs and further communication objects can be linked by
AND and OR logic gates. Additionally, an integrated actuating variable comparator can
compare and output values that are received via communication objects.
Integrated PI controllers allows for control of a ventilation (depending on CO2
concentration and air humidity) and a heating/cooling system (depending on
temperature). The KNX AQS/TH-UP Touch can emit a warning to the bus as soon as
the area of optimum comfort (according to DIN 1946) is left.
The integrated display shows the own values and data received from the bus (e.g. date,
time). The device is completed with a frame of the switching series installed in the
building and thus merges with the interior.
Functions:
• Measurement of CO2concentration of the air, of temperature and air
humidity (absolute and relative), calculation of the dew point
•Mixed values from own measured values and external values (proportions
can be set in percentage)
•Display 1-3 rows (own values or values received from the bus) or display of
temperature control (see Mode display and manual temperature controller)
•2 push buttons. Configuration as bus push button or for changing ambient
temperature and switching between operating modes (see Change ambient
temperature with the buttons)
•PI controller for heating (one or two step) and cooling (one or two step)
depending on temperature. Control according to separate target values or
basic target temperature
•PI controller for ventilation depending on humidity and CO2concentration:
dehumidification/humidification (one step) or dehumidification (one or two
step)
•Threshold values can be adjusted per parameter or via communication
objects: 3 × temperature, 2 × humidity, 4 × CO2
•4 AND and 4 OR logic gates with each 4 inputs. Every switching incident as
well as 16 logic inputs in the form of communication objects, may be used as
inputs for the logic gates. The output of each gate may optionally be configured
as 1 bit or 2 x 8 bits
•2 actuating variable comparators for output of minimum, maximum or
average values. Each with 5 inputs (for values received via communication
objects)

5 Description
Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
Configuration is made using the KNX software ETS 5. The product file can be
downloaded from the ETS online catalogue and the Elsner Elektronik website on
www.elsner-elektronik.de in the “Service” menu.
1.0.1. Scope of delivery
• Housing with display
• Base plate
You will need in addition (not supplied):
• Socket Ø 60 mm, 42 mm deep
• Frame (for element 55 x 55 mm), suitable for the switching programme used in
the building
1.1. Technical specifications
Housing ABS plastic material
Colours • similar to RAL 9005 jet black
• similar to RAL 9010 pure white
Mounting In-wall (wall mounting in socket Ø60 mm, 42 mm
deep, resp. cavity wall socket for hole Ø68 mm)
Protection category IP 20
Dimensions Housing approx. 55 x 55 (W x H, mm), mounting depth
approx. 8 mm, base plate approx. 71 x 71 (W x H, mm)
Total weight approx. 55 g
Ambient temperature Operation 0…+50°C, storage -10…+60°C
Ambient air humidity max. 95% RH, avoid bedewing
Operating voltage KNX bus voltage
Bus current max. 20 mA
Data output KNX +/- bus terminal plug
BCU type Own micro controller
PEI type 0
Group addresses max. 254
Allocations max. 254
Communication objects 224
CO2 measurement range 300...5000 ppm
CO2resolution 1 ppm
CO2accuracy ± 50 ppm plus ± 3% of the measured value (Mind the
notes on Accuracy of the measurement)
Temperature measurement
range
0…+50°C
Temperature resolution 0.1°C
Temperature accuracy ± 0,5°C at 0…+50°C (Mind the notes on Accuracy of the
measurement)

6 Installation and commissioning
Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
The product conforms with the provisions of EU guidelines.
1.1.1. Accuracy of the measurement
Measurement variations from permanent sources of interference (see chapter
Installation position) can be corrected in the ETS in order to ensure the specified
accuracy of the sensor (offset).
To ensure a correct CO2measurement, the device must be installed in a windproof
socket.
When measuring temperature, the self-heating of the device is considered by the
electronics. The heating is compensated by the software.
2. Installation and commissioning
2.1. Installation notes
Installation, testing, operational start-up and troubleshooting should
only be performed by an electrician.
CAUTION!
Live voltage!
There are unprotected live components inside the device.
• National legal regulations are to be followed.
• Ensure that all lines to be assembled are free of voltage and take
precautions against accidental switching on.
• Do not use the device if it is damaged.
• Take the device or system out of service and secure it against
unintentional use, if it can be assumed, that risk-free operation is no
longer guaranteed.
The device is only to be used for its intended purpose. Any improper modification or
failure to follow the operating instructions voids any and all warranty and guarantee
claims.
After unpacking the device, check it immediately for possible mechanical damage. If it
has been damaged in transport, inform the supplier immediately.
Humidity measurement
range
0% RH …95% RH
Humidity resolution 0.1%
Humidity accuracy ±7,5% RH at 0...10% RH
±4,5% RH at 10...90% RH
±7,5% RH at 90...95% RH
Humidity drift ± 0.5% R.H. per year in normal air

7 Installation and commissioning
Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
The device may only be used as a fixed-site installation; that means only when
assembled and after conclusion of all installation and operational start-up tasks and
only in the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may occur
after publication of these operating instructions.
2.2. Installation position
The Sensor KNX AQS/TH-UP Touch is made for wall mounting in a socket
(Ø 60 mm, 42 mm deep).
May be installed and operated in dry interior rooms only.
Avoid condensation.
When selecting an installation location, please ensure that the measurement results
are affected as little as possible by external influences. Possible sources of interference
include:
• Direct sunlight
• Drafts from windows and doors
• Draft from ducts which lead from other rooms or from the outside to the
junction box in which the sensor is mounted
• Warming or cooling of the building structure on which the sensor is mounted,
e.g. due to sunlight, heating or cold water pipes
• Connection lines and ducts which lead from warmer or colder areas to the
sensor
Measurement variations from permanent sources of interference can be corrected in
the ETS in order to ensure the specified accuracy of the sensor (offset).
To ensure a correct CO2measurement, the device must be installed in a windproof
socket.
Fig. 1: Sectional drawing.
The Sensor KNX AQS/TH-UP Touch fits into a standard
socket (Ø 60 mm, depth 42 mm).
The frame is not included!

8 Installation and commissioning
Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
2.3. Composition
2.3.1. Housing
2.4. Assembly of the sensor
First of all fit the windproof socket with connection. Also seal inlet pipes to avoid
infiltration.
Screw the base plate onto the socket and position the frame of the switching
programme. Connect the bus line +/- to the black-red plug.
Pin the housing with the notches on to the metal frame, so that device and frame are
fixed.
2.5. Notes on mounting and commissioning
Never expose the device to water (e.g. rain) or dust. This can damage the electronics.
You must not exceed a relative humidity of 95%. Avoid condensation.
After the bus voltage has been applied, the device will enter an initialisation phase
lasting a few seconds. During this phase no information can be received or sent via the
bus.
1
2
6
3
4
5
Fig. 2
1 Base plate
2 Openings for air circulation
3 Touch sensitive buttons
4 Catches
5 Programming LED (recessed)
6 Programming button (recessed) for teaching device
7 KNX terminal BUS +/-
7

9 Display and operation at the device
Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
3. Display and operation at the device
Detailed specifications for the display and the use of the push buttons are set in the
ETS.
Basically the display can show a two-row or three-row text (e. g. for measured values)
or a temperature controller. You can switch between the two types by pressing one of
the buttons, if this has not been disabled in the ETS.
3.1. Mode display and manual temperature
controller
Depending on the ETS setting selected, the mode display will only display show the
current target value, or the base target value setting with scale display. The manually
adjustable range can be set in the ETS.
The following display options are available:
Fig. 3
Mode display with current target value and/or base
target value
Fig. 4
Mode display with scale display for adjusting the base
target value.
The control position in the image reads "Base target
value reduced".
Fig. 5
Mode display with scale display and number.
Shows the set target value change.
The control position in the image reads "Base target
value reduced to 1.0°".
Fig. 6
Mode display with scale display and range.
Shows the possible adjustment range (as set in the ETS).
The control position in the image reads "Base target
value reduced".

10 Display and operation at the device
Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
Symbols
Priority (points)
One point: Priority 1/priority control. It is not possible to adjust the temperature
automation system manually. Neither the target temperature nor the operating modes
can be changed using the buttons on the unit.
Two points: Priority 2. The target temperature and operating mode can be changed
using the buttons.
3.2. Change ambient temperature with the
buttons
If the mode display is active, the target ambient temperature and the operating mode
can be changed manually using the buttons. The button functions can be blocked in
the ETS or be suppressed for Priority 1 operating modes. The individual operating
modes can also be locked for manual selection in the ETS.
Comfort mode.
Comfort (present) target
temperature will be used.
Standby mode.
Standby (absent during day)
target temperature will be used.
Eco mode.
Night target temperature will be
used.
Building protection mode.
Building protection target
temperature will be used. The
symbol will blink when the mode
has been activated but the
activation delay has not yet
expired.
Heating mode.
Heating will be provided.
Cooling mode
Cooling will be provided.
Fig. 7
Mode display with scale display, range and number.
Displays the possible adjustment range (as set in the
ETS) and the set target value change.
The control position in the image reads "Base target
value reduced to 1.0°".
Fig. 8
In "HVAC mode with 2x 8 bits" control mode, points are
shown under the symbol, to indicate the running priority
of the current mode.

11 Display and operation at the device
Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
Decrease target
temperature (-)
briefly press
left button
Ambient temperature in the current
mode is decreased.
The sep-size is defined in the ETS
(0.1°C to 5°C).
Increase target
temperature (+)
briefly press
right button
Ambient temperature in the current
mode is increased.
The sep-size is defined in the ETS
(0.1°C to 5°C).
Change mode press
left or right button
longer than 2 secs.
Changes between the operating
modes Comfort, Standby, Eco and
Building Protection (if deblocked in
the ETS).
Extend Comfort
mode
in Eco mode:
press both buttons
at the same time
longer than 2 secs.
Switches from Eco to Comfort mode
again for a certain time (e. g. if the
rooms are used longer in the
evening).
The period is defined in the ETS (up
to 10 hours). The time remaining in
Comfort mode is displayed.

12 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
4. Transfer protocol
Units:
Temperatures in degrees Celsius
Air humidity in %
Absolute air humidity in g/kg and/or g/m3
CO2content in ppm
Variables in %
4.1. List of all communications objects
Abbreviation flags:
C Communication
R Read
WWrite
T Transfer
UUpdate
No Name Function Flags Data Point Type Size
0 Software version readable R-CT [217.1]
DPT_Version
2 Bytes
1 Temperature/humidity malfunction
sensor
Output R-CT [1.1]
DPT_Switch
1 Bit
2 CO2 sensor malfunction Output R-CT [1.1]
DPT_Switch
1 Bit
3 Outside temperature reading Input -WC- [9.1]
DPT_Value_Temp
2 Bytes
4 Inside temperature reading Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
5 Overall temperature reading Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
6 Min./max. temperature value
request
Input -WC- [1.17]
DPT_Trigger
1 Bit
7 Minimum temperature reading Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
8 Maximum temperature reading Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
9 Reset min./max. temperature value Input -WC- [1.17]
DPT_Trigger
1 Bit
10 Temp. threshold value 1: Absolute
value
Input/
Output
RWC
T
[9.1]
DPT_Value_Temp
2 Bytes
11 Temp. threshold value 1: (1:+ | 0:-) Input -WC- [1.2]
DPT_Bool
1 Bit
12 Temp. threshold value 1:
Switching delay from 0 to 1
Input -WC- [9.010]
DPT_Value_Time
2 Bytes

13 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
13 Temp. threshold value 1:
Switching delay from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
14 Temp. threshold value 1: Switching
output
Output R-CT [1.1]
DPT_Switch
1 Bit
15 Temp. threshold value 1:
Switching output block
Input -WC- [1.2]
DPT_Bool
1 Bit
16 Temp. threshold value 2: Absolute
value
Input/
Output
RWC
T
[9.1]
DPT_Value_Temp
2 Bytes
17 Temp. threshold value 2: (1:+ | 0:-) Input -WC- [1.2]
DPT_Bool
1 Bit
18 Temp. threshold value 2:
Switching delay from 0 to 1
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
19 Temp. threshold value 2:
Switching delay from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
20 Temp. threshold value 2: Switching
output
Output R-CT [1.1]
DPT_Switch
1 Bit
21 Temp. threshold value 2:
Switching output block
Input -WC- [1.2]
DPT_Bool
1 Bit
22 Temp. threshold value 3: Absolute
value
Input/
Output
RWC
T
[9.1]
DPT_Value_Temp
2 Bytes
23 Temp. threshold value 3: (1:+ | 0:-) Input -WC- [1.2]
DPT_Bool
1 Bit
24 Temp. threshold value 3:
Switching delay from 0 to 1
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
25 Temp. threshold value 3:
Switching delay from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
26 Temp. threshold value 3: Switching
output
Output R-CT [1.1]
DPT_Switch
1 Bit
27 Temp. threshold value 3:
Switching output block
Input -WC- [1.2]
DPT_Bool
1 Bit
29 TR_1_ Eco-Standby HVAC 1 Input -WC- [20.102]
DPT_HVACMode
1 Byte
30 TR_1_ Comfort Activation HVAC 2 Input RWC
T
[20.102]
DPT_HVACMode
1 Byte
31 TR_1_ Frost/Heat activation Input RWC
T
[1.1]
DPT_Switch
1 Bit
32 TR_1_ Blocking object (active at
value = 1)
Input -WC- [1.1]
DPT_Switch
1 Bit
33 TR_1_ Target value, current Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
34 TR_1_ Switching object (0:Heat |
1:Cool)
Input -WC- [1.1]
DPT_Switch
1 Bit
35 TR_1_ Target value, comfort heat-
ing
Input/
Output
RWC
T
[9.1]
DPT_Value_Temp
2 Bytes
No Name Function Flags Data Point Type Size

14 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
36 TR_1_ Target value, comfort heat-
ing (1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
37 TR_1_ Target value, comfort cool-
ing
Input/
Output
RWC
T
[9.1]
DPT_Value_Temp
2 Bytes
38 TR_1_ Target value, comfort cool-
ing (1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
39 TR_1_ Target value_Basic offset
16 Bit
Input/
Output
RWC
T
[9.1]
DPT_Value_Temp
2 Bytes
40 TR_1_ Target value, Standby heat-
ing
Input/
Output
RWC
T
[9.1]
DPT_Value_Temp
2 Bytes
41 TR_1_ Target value, Standby heat-
ing (1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
42 TR_1_ Target value, Standby cool-
ing
Input/
Output
RWC
T
[9.1]
DPT_Value_Temp
2 Bytes
43 TR_1_ Target value, Standby cool-
ing (1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
44 TR_1_ Target value, Eco heating Input/
Output
RWC
T
[9.1]
DPT_Value_Temp
2 Bytes
45 TR_1_ Target value, Eco heating
(1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
46 TR_1_ Target value, Eco cooling Input/
Output
RWC
T
[9.1]
DPT_Value_Temp
2 Bytes
47 TR_1_ Target value, Eco cooling
(1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
48 TR_1_ Control variable heating
(stage 1)
Output R-CT [5.1]
DPT_Scaling
1 Byte
49 TR_1_ Control variable heating
stage 2
Output R-CT [5.1]
DPT_Scaling
1 Byte
50 TR_1_ Control variable cooling
(stage 1)
Output R-CT [5.1]
DPT_Scaling
1 Byte
51 TR_1_ Control variable cooling
stage 2
Output R-CT [5.1]
DPT_Scaling
1 Byte
52 TR_1_ Status heating 1 (1=ON |
0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
53 TR_1_ Status heating 2 (1=ON |
0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
54 TR_1_ Cooling status 1 (1=ON |
0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
55 TR_1_ Cooling status 2 (1=ON |
0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
56 TR_1_ Comfort Delay Status Input/
Output
RWC
T
[1.1]
DPT_Switch
1 Bit
57 TR_1_Comfort extension time (in
sec)
Input/
Output
RWC
T
[7.5]
DPT_TimePeriodSec
2 Bytes
No Name Function Flags Data Point Type Size

15 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
58 TR_1_Belimo_Control variable Output R-CT [5.1]
DPT_Scaling
1 Byte
59 Outside humidity reading Input -WC- [9.7]
DPT_Value_Humidity
2 Bytes
60 Inside humidity reading Output R-CT [9.7]
DPT_Value_Humidity
2 Bytes
61 Overall humidity reading Output R-CT [9.7]
DPT_Value_Humidity
2 Bytes
62 Min./max. humidity value request Input -WC- [1.17]
DPT_Trigger
1 Bit
63 Minimum humidity reading Output R-CT [9.7]
DPT_Value_Humidity
2 Bytes
64 Maximum humidity reading Output R-CT [9.7]
DPT_Value_Humidity
2 Bytes
65 Reset min./max. humidity value Input -WC- [1.17]
DPT_Trigger
1 Bit
66 Humidity threshold value 1: Abso-
lute value
Input/
Output
RWC
T
[9.7]
DPT_Value_Humidity
2 Bytes
67 Humidity threshold value 1: (1:+ |
0:-)
Input -WC- [1.2]
DPT_Bool
1 Bit
68 Humidity threshold value 1: Switch-
ing delay from 0 to 1
Input -WC- [[9.010]
DPT_Value_Time
2 Bytes
69 Humidity threshold value 1: Switch-
ing delay from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
70 Humidity threshold value 1: Switch-
ing output
Output R-CT [1.1]
DPT_Switch
1 Bit
71 Humidity threshold value 1: Switch-
ing output block
Input -WC- [1.2]
DPT_Bool
1 Bit
72 Humidity threshold value 2: Abso-
lute value
Input/
Output
RWC
T
[9.7]
DPT_Value_Humidity
2 Bytes
73 Humidity threshold value 2: (1:+ |
0:-)
Input -WC- [1.2]
DPT_Bool
1 Bit
74 Humidity threshold value 2: Switch-
ing delay from 0 to 1
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
75 Humidity threshold value 2: Switch-
ing delay from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
76 Humidity threshold value 2: Switch-
ing output
Output R-CT [1.1]
DPT_Switch
1 Bit
77 Humidity threshold value 2: Switch-
ing output block
Input -WC- [1.2]
DPT_Bool
1 Bit
78 Humidity controller: Blocking object Input -WC- [1.2]
DPT_Bool
1 Bit
79 Humidity controller: Target value Input/
Output
RWC
T
[9.7]
DPT_Value_Humidity
2 Bytes
No Name Function Flags Data Point Type Size

16 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
80 Humidity controller: Target value
(1:+ | 0:-)
Input -WC- [1.2]
DPT_Bool
1 Bit
81 Humidity controller: Control varia-
ble dehumidification (stage 1)
Output R-CT [5.1]
DPT_Scaling
1 Byte
82 Humidity controller: Control varia-
ble dehumidification stage 2
Output R-CT [5.1]
DPT_Scaling
1 Byte
83 Humidity controller: Control varia-
ble humidification
Output R-CT [5.1]
DPT_Scaling
1 Byte
84 Humidity controller: Dehumidifica-
tion 1 status (1=ON | 0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
85 Humidity controller: Dehumidifica-
tion 2 status (1=ON | 0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
86 Humidity controller: Humidification
status (1=ON | 0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
87 Dewpoint temperature Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
88 Coolant temp.: Threshold value Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
89 Coolant temp.: Actual value Input -WC- [9.1]
DPT_Value_Temp
2 Bytes
90 Coolant temp.: Offset change (1:+ |
0:-)
Input -WC- [1.2]
DPT_Bool
1 Bit
91 Coolant temp.: Switching delay
from 0 to 1
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
92 Coolant temp.: Switching delay
from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
93 Coolant temp.: Switching output Output R-CT [1.1]
DPT_Switch
1 Bit
94 Coolant temp.: Switching output
block
Input -WC- [1.2]
DPT_Bool
1 Bit
95 Absolute humidity [g/kg] Output R-CT [14.5]
DPT_Value_Ampli-
tude
4 Bytes
96 Absolute humidity [g/m³] Output R-CT [14.17]
DPT_Value_Density
4 Bytes
97 Ambient climate status: 1 = com-
fortable | 0 = uncomfortable
Output R-CT [1.2]
DPT_Bool
1 Bit
98 Outside CO2 reading Input -WC- [9.8]
DPT_Value_AirQua-
lity
2 Bytes
99 Inside CO2 Internal reading Output R-CT [9.8]
DPT_Value_AirQua-
lity
2 Bytes
No Name Function Flags Data Point Type Size

17 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
100 Total CO2 reading Output R-CT [9.8]
DPT_Value_AirQua-
lity
2 Bytes
101 CO2 maximum value request Input -WC- [1.17]
DPT_Trigger
1 Bit
102 Maximum CO2 reading Output R-CT [9.8]
DPT_Value_AirQua-
lity
2 Bytes
103 Reset CO2 maximum value Input -WC- [1.17]
DPT_Trigger
1 Bit
104 CO2 threshold value 1: Absolute
value
Input/
Output
RWC
T
[9.8]
DPT_Value_AirQua-
lity
2 Bytes
105 CO2 threshold value 1: (1:+ | 0:-) Input -WC- [1.2]
DPT_Bool
1 Bit
106 CO2 threshold value 1: Switching
delay from 0 to 1
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
107 CO2 threshold value 1: Switching
delay from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
108 CO2 threshold value 1: Switching
output
Output R-CT [1.1]
DPT_Switch
1 Bit
109 CO2 threshold value 1: Switching
output block
Input -WC- [1.2]
DPT_Bool
1 Bit
110 CO2 threshold value 2: Absolute
value
Input/
Output
RWC
T
[9.8]
DPT_Value_AirQua-
lity
2 Bytes
111 CO2 threshold value 2: (1:+ | 0:-) Input -WC- [1.2]
DPT_Bool
1 Bit
112 CO2 threshold value 2: Switching
delay from 0 to 1
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
113 CO2 threshold value 2: Switching
delay from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
114 CO2 threshold value 2: Switching
output
Output R-CT [1.1]
DPT_Switch
1 Bit
115 CO2 threshold value 2: Switching
output block
Input -WC- [1.2]
DPT_Bool
1 Bit
116 CO2 threshold value 3: Absolute
value
Input/
Output
RWC
T
[9.8]
DPT_Value_AirQua-
lity
2 Bytes
117 CO2 threshold value 3: (1:+ | 0:-) Input -WC- [1.2]
DPT_Bool
1 Bit
118 CO2 threshold value 3: Switching
delay from 0 to 1
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
119 CO2 threshold value 3: Switching
delay from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
No Name Function Flags Data Point Type Size

18 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
120 CO2 threshold value 3: Switching
output
Output R-CT [1.1]
DPT_Switch
1 Bit
121 CO2 threshold value 3: Switching
output block
Input -WC- [1.2]
DPT_Bool
1 Bit
122 CO2 threshold value 4: Absolute
value
Input/
Output
RWC
T
[9.8]
DPT_Value_AirQua-
lity
2 Bytes
123 CO2 threshold value 4: (1:+ | 0:-) Input -WC- [1.2]
DPT_Bool
1 Bit
124 CO2 threshold value 4: Switching
delay from 0 to 1
Input -WC- [7.5]
DPT_TimePeriodSec
2 Bytes
125 CO2 threshold value 4: Switching
delay from 1 to 0
Input -WC- [7.5]
DPT_TimePeriodSec
2 Bytes
126 CO2 threshold value 4: Switching
output
Output R-CT [1.1]
DPT_Switch
1 Bit
127 CO2 threshold value 4: Switching
output block
Input -WC- [1.2]
DPT_Bool
1 Bit
128 CO2 controller: Blocking object Input -WC- [1.2]
DPT_Bool
1 Bit
129 CO2 controller: Target value Input/
Output
RWC
T
[9.8]
DPT_Value_AirQua-
lity
2 Bytes
130 CO2 controller: Target value (1:+ |
0:-)
Input -WC- [1.2]
DPT_Bool
1 Bit
131 CO2 controller: Control variable
ventilation (stage 1)
Output R-CT [5.1]
DPT_Scaling
1 Byte
132 CO2 controller: Control variable
ventilation (stage 2)
Output R-CT [5.1]
DPT_Scaling
1 Byte
133 CO2 controller: Ventilation 1 status
(1=ON | 0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
134 CO2 controller: Ventilation 2 status
(1=ON | 0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
135 Comparator 1 actuating variable:
Input 1
Input -WC- [5.1]
DPT_Scaling
1 Byte
136 Comparator 1 actuating variable:
Input 2
Input -WC- [5.1]
DPT_Scaling
1 Byte
137 Comparator 1 actuating variable:
Input 3
Input -WC- [5.1]
DPT_Scaling
1 Byte
138 Comparator 1 actuating variable:
Input 4
Input -WC- [5.1]
DPT_Scaling
1 Byte
139 Comparator 1 actuating variable:
Input 5
Input -WC- [5.1]
DPT_Scaling
1 Byte
140 Comparator 1 actuating variable:
Output
Output R-CT [5.1]
DPT_Scaling
1 Byte
No Name Function Flags Data Point Type Size
Table of contents
Other KNX Accessories manuals
Popular Accessories manuals by other brands

GE
GE Learn Mode Shock Sensor installation instructions

Benewake
Benewake TF02-Pro product manual

Extron electronics
Extron electronics Universal Video Interface with Audio RGB 201... user guide

Drop
Drop massdrop x MEE audio Welcome guide

Krüger & Matz
Krüger & Matz KM2200 extended manual

Wenglor
Wenglor P1KH001 operating instructions

Philips
Philips Sonicare AirFloss Faq

pass & seymour
pass & seymour RWU600B installation instructions

XS Power Batteries
XS Power Batteries PB-13.0 user guide

Middle Atlantic Products
Middle Atlantic Products Display Station Series installation instructions

DSC
DSC WLS914 Installation instructions manual

Tektronix
Tektronix CT-6 instruction manual