Kospel HPSW-2/250 User manual

Installation and operating instructions
Heat Pump
HPSW-2/250
9:37 WT 2.01.2018
17
°
41
°
12.7°
Tzad
50°

This appliance may be used by children at the min.
age of 8 years and by persons with reduced physical,
sensory or mental capabilities or lack of experience
and knowledge about the product, provided that they
have been given supervision or instruction concerning
safe usage of the appliance and that they are aware of
potential dangers that might result from usage of the
appliance. Children should not play with the device.
Children without supervision should not complete any
cleaning nor maintenance procedures.
Used product can’t be treated as general communal waste.
Disassembled appliance has to be delivered to the collection
point of electrical and electronic equipment for recycling.
Appropriate utilisation of used product prevents potential
negative environmental inuences that may occur as a result
of inappropriate handling of waste. In order to get more detailed
information about recycling this product you should contact the
local government unit, waste management service or the shop
where this product has been purchased.

GB-097B_f 3
Safety instructions
1. Read and strictly follow the installation and operating instructions to ensure a long
life and reliable operation of this appliance.
2. Installation and use of heat pump inconsistent with this instruction is not permitted
- may cause malfunction and will void the warranty.
3. Room for installation should have cubature of minimum 20 m3and provide adequate
air exchange.
4. Device must not be installed in rooms where the ambient temperature may drop
below 0°C.
5. Mounting and commissioning of heat pump and accompanying installation should
be entrusted to a specialist service company.
6. Heat pump should be installed only in horizontal position on a at surface with
appropriate lifting capacity.
7. Device must be installed in such a place and in a such a way that the emergency
leakage from connectors would not cause ooding of the room.
8. Room must have a possibility to drain condensate to the sewer.
9. After installation device must be connected to water supply system and optionally
to heating system as described in the manual. Inconsistence with the description
of the connection invalidates the warranty and may cause malfunction.
10. Connection to the water supply system must be made in accordance with the binding
norms.
11. Heat pump is designed to connect to installation with pressure not exceeding
0,6MPa. If the water pressure exceeds 0,6MPa, install a pressure reducing valve
in front of the machine.
12. Water dripping from the discharge pipe of the safety valve is normal and should not
be prevented because blocking the valve can be the cause of failure.
13. Do not use the device if there is a possibility that the valve security is broken.
14. The tank is equipped with a magnesium anode - an additional protection against
corrosion. The anode is an operating part, therefore, it is exposed to wear.
The condition of the magnesium anode should be controlled every 12 months,
however, it is due to be replaced with a new one every 18 months.
15. The heating medium temperature must not exceed 80°C !.

4
Description
The HPSW-2 heat pump is device used to heat and store domestic hot water using
stored energy in the ambient air. Device is equipped with a 250l, an electric heater and
a coil to connect external heat source (e.g. central heating boiler).
[1] - control panel
[2] - controller
[3] - magnesium anode
[4] - upper temperature sensor
[5] - coil
[6] - electric heater
[7] - condensate pipe DN16
9:37 WT 2.01.2018
17
°
41
°
12.7°
Tzad
50°
8
ZW
PG
ZG
C
a
c
d
e
f
g
1
2
5
6
7
b
3
4
CW
[8] - bottom temperature sensor
ZW - cold water inlet
CW - cold water outlet
C - circulation connector
ZG - heating medium supply
PG - heating medium return

GB-097B_f 5
- install T-connector with safety valve of opening pressure 6 bar and drain valve to
cold water inlet connection between and safety valve; at its outlet cannot be placed
any cut-off valve or any throttling element; safety valve must be installed so that
water leak is visible,
- connect heat pump with mounted safety valve to water supply system,
- install cut-off valve at cold water inlet. Domestic hot water outlet must be connected
to CW connector which is located at the upper part of device.
- each device is equipped with a C connector designed to connect circulation.
Connection to the heating and water supply system
Connection to the water supply system must be
done in accordance with the binding norms. Heating
pump HPSW 2 is a pressure device adapted for
connection to water supply system not exceeding
pressure 0,6MPa. If the water pressure exceeds 0,6
MPa, install a pressure reducing valve in front of the
machine.
Connection to the water supply system should be
made as follows:
9:37 WT 2.01.2018
17
°
41
°
12.7°
Tzad
50°
CW
C
ZG
PG
ZW
ZB
NW
Tcrk

6
Air can be extracted from room in which the device is mounted, another room or
from outside of the building. Air can be extracted from room in which the device is
mounted, another room or from outside of the building. Install air lter of ltration
class G3 at the inlet channel.
In order to achieve optimal device parameters, provide air ow of 300m3/h. To minimize
losses associated with air resistance, cables must be performed in a straight line.
For DN200 the total length of the air inlet and outlet should not exceed 10m.
air outlet
air inlet
Air cables connection

GB-097B_f 7
4
1
2
3
6
5
[1] - front cover
[2] - side cover - back (with holes for connectors)
[3] - angular connections G1 with hose connector
[4] - upper cover
[5] - back bracket
[6] - side cover - back
Assemble of case and angular connectors
The device case has been designed to allow connector to be directed into right or left side.
To direct connectors to required angle rotate them in the socket of hose connector with
an angle of 180 degrees.

8
90˚
HPSW pump allows to change the position of the connectors. Connectors may be
directed to the back or side of device (right or left side).

GB-097B_f 9
During normal operation, moisture in the air condenses on the walls of evaporator.
Condensates ow into the drip tray where are led to the tube nozzle on the outside of
the device. Siphon should be hermetically connected to the condensate pipe and then
led to sewerage. The pipe should be led without any bends to allow free drainage.
Device is equipped with a power cord that must be permanently connected to electrical
installation.
The electrical system should be equipped with a residual current protective devices and
means providing that device can be disconnected from power source where distance
between joints of all poles is not less than 3 mm.
Before starting the unit, visually check the connection of the device and proper installation
in accordance with the diagrams.
Cylinder must be lled with water:
- open the valve on the cold water inlet,
- open the valve on the hot water outlet installation (full ow of water stream, without
air bubbles indicates that the tank is full)
- close the taps.
Open the valves connecting the heating system with the coil. Check for leaks on the
sanitary hot water and heating medium side. Check the operation of the safety valve
(in accordance with the valve’s manufacturer instruction).
Connection of the condensate hose
Connection to the electric installation
9:37 WT 2.01.2018
17
°
41
°
12.7°
Tzad
50°
Start-up

10
Operation of control panel
Use the lower knob to select operating mode
[3]:
- stand-by > heating pump is off, only
frost protection is active,
- compressor > according to congured
work schedule heat pump maintains
set hot water temperature if the air
temperature intake does not allow to
activate compressor, occasionally the
conditions of starting heat pump will be
veried,
- compressor + additional heat source>
according to congured work schedule heat
pump maintains set hot water temperature,
if the air temperature intake will not allow to
activate compressor additional heat source
is activated and occasionally the conditions
of starting heat pump will be veried,
- compressor + additional heat source
+ heater > according to congured work
schedule heat pump and external heat
source maintain set hot water temperature,
if the air temperature intake will not allow to
activate compressor heater is activated and
occasionally the conditions of starting heat
pump will be veried,
- additional heat source > according
to congured work schedule additional
heat source maintains set hot water
temperature,
-
A
turbo > selecting this mode enables
heating water with all available
heat sources until reaching the set
temperature,and returns to the previous
work mode except stand-by mode. In
[1] - display
[2] - preview and settings navigation
dial
[3] - mode dial
2
3
1
9:37 TUE 2.01.2018
9:37 TUE 2.01.2018
17
17
°
°
41
41
°
°
12.7°
12.7°
Tzad
Tzad
50°
50°
order to activate the mode enter required hot water temperature, then default
temperature of 50°C will be displayed. The temperature level can be corrected
using upper dial and then conrmed by pressing the upper dial. After around 10
seconds of inactivity the level of temperature will be automatically saved.

GB-097B_f 11
[1] - ventilator
[2] - signalling of program implementation
[3] - signalling of compressor work
[4] - electric heater
[5] - external heat source /coil
[6] - temperature of upper cylinder
[7] - temperature of bottom cylinder
[8] - temperature of inlet air (displayed only while
ventilator is working)
[9] - set hot water temperature
MAIN SCREEN
9:37 TUE 2.01.2018
9:37 TUE 2.01.2018
17
17
°
°
41
41
°
°
12.7°
12.7°
Tzad
Tzad
50°
50°
8
46
21 9
3 5 7
Signalling of set work program:
Maintaining efciency according to set daily/weekly schedule
Disinfection
Heat pump blocked by an external signal
FN FN function work indication
Device’s warning indication
Device’s error indication
Indication of switching on fan
gear 1
gear 2
Indication of switching on compressor
Indication of switching on heater
Indication of switching on additional heat source
The navigation dial switches function screens:
- MAIN SCREEN: informs about main heat pump parameters (→ MAIN SCREEN),
- SETTINGS: allows to adjust parameters to user’s preferences,
- SERVICE / CONFIGURATION: allows to set the hot water heating system (available
to specialized services) and preview of input and output signals of the device.
Access to individual functions is enabled after selecting suitable function screen and
pressing navigation dial.
The appearance of an error (s) or warnings of the device is signaled on the main ( /
) function screen, after pressing the knob, a list of errors and warnings is available.

12
Note that connection of the sensor is optional. When it is not mounted,
circulation pump works continuously according to circulation schedule.
If the sensor is mounted, circulation pump also works according to circulation
schedule but only until the temperature in the circulation stabilizes.
At certain time intervals circulation temperature is veried. If water temperature
needs to be raised, the pump is activated.
When the sensor is not mounted, the pump works continuously. When the sensor is
mounted, the pump works when temperature in circulation declines. Control system
automatically detects the presence of the sensor and adjusts accordingly circulation
pump control algorithm.
Master appliance (entry NA)
In order to limit the electricity used, it is possible to make the work of devices conditional
from other external controllers. In this case, the break contact needs to be connected
to NA entry so that switching on electricity master appliance will result in opening the
contact, which will block the heating.
Function entry (entry FN)
Entry of switching on heating regardless of the schedule. In order to use this function
the break contact needs to be connected to NA entry. Contraction of FN entry will result
in turning on heating with all available sources (heat pump, coil heater, external heat
source) to setting 60°C.
Exit ZC
It is a relay output for controlling an external heat source. It is active only if option
“Additional heat source” was switched on in setup.
Connection of external control appliances
Circulation temperature
sensor (Tcrk) (additional
component - WE sensor 019/01)
Location of mounting the sensor
is shown in the hydraulic system
diagram. Cable connection of
the sensor should be as short as
possible, shouldn’t be led close to
power cords or wrapped around
other wires.
FNNA Tcrk
ZC
SG
NO COMNC NO COMNC
Tcrk
FN
FN
Under no circumstances should any voltage be connected to these terminals
(SG, ZC, NA, FN, TCRK), as this will result in the damage of boiler’s controller.
!

GB-097B_f 13
8:38 THU 14.04.2020
8:38 THU 14.04.2020
SETTINGS
SETTINGS
SETTINGS:
DHW PROGRAMME NO1
DHW PROGRAMME NO1
SAVE AND EXIT
SAVE AND EXIT
1 6:20 - 8:00 42°
2 18:30 - 23:00
2 18:30 - 23:00
50°
50°
1234
1 - no. of time frame according to schedule
(max 5)
2 - time of starting the selected temperature
3 - time of nishing the selected temperature
4 - temperature setting
● DHW PROGRAMME:
- No1…No8 > setting 8 daily programs, in each daily program there are 5 editable time
frames, for which hot water temperature can be set between 30..60°C, in the remaining
time frost protection will be active. Setting up daily programs procedure is described
in Daily schedule paragraph.
- Weekly: assigning for each day of the week one of the previously set daily programs.
● CIRCULATION PROGRAMME (available only with the active circulation within hot
water system):
- No. 1...No. 8 > setting 8 daily programs, in each daily program there are 5 editable
time frames, in which circulation pump will be active. Setting up daily programs
procedure is described in Daily schedule paragraph.
- Weekly: assigning for each day of the week one of the previously set daily programs.
● DISINFECTION:
- TEMPERATURE: temperature of the storage tank during disinfection,
- WEEK DAY: day of the week of automatic disinfection,
- START UP TIME: time of starting automatic disinfection,
- OPERATION TIME: disinfection duration,
- AUTOMATIC OPERATION: start disinfection automatically at a given time (Hour,
Day of the week),
- CIRCULATION (available only with the active circulation): a possibility to select
disinfection of either the whole installation or just the cylinder,
- START UP NOW: start disinfection manually (irrespective of a day and time set
previously).

14
● DATE/ TIME:
- Setting current system time (year, month, day, hour, minute).
- AUTO TIME CHANGE: yes > automatic time switch from summer to winter mode
and reverse.
*Saving settings to the controller’s memory occurs after leaving menu, after pressing “Save
and leave” command.
● INTERFACE:
- BRIGHTNESS MIN: setting the brightness of the display in stand-by mode
- BRIGHTNESS MAX: setting the brightness of the display in working mode
- SOUND: yes - turn on/ no - turn off of acoustic sound of the dial
- DIAL’S SENSITIVITY: 1- high / 4- low
● SYSTEM:
- MSPC PROGRAMME: shows program version of the heat pump’s controller.
- PW PROGRAMME : shows panel’s software version,
- RESET: restarts the heat pump,
- FACTORY SETTINGS: return to factory settings.

GB-097B_f 15
8:38 THU 14.04.2020
8:38 THU 14.04.2020
SERVICE/CONFIGURATION
SERVICE/CONFIGURATION
SERVICE / CONFIGURATION
PARAMETERS PREVIEW:
Preview of input and output signals of the heat
pump.
First start-up
With the start-up of the heat pump or after the restoration of the factory settings, select
MENU’s language. Heat pump is ready to work properly
only after selection of this parameter.
CONFIGURATION
* Changes in the conguration menu are possible after entering an access code. When prompted
for an access code, set recquired code by turn the navigation dial to the left and conrm the code
by pressing the dial. If you want to retract from the code request screen, hold the navigation dial
or wait until automatic return to main function screen.
Code : 987
● CYLINDER: Change of hysteresis setting DHW.
● CIRCULATION: turn on or off the circuit.
● FAN: change of the minimum ventilator operating temperature.
● FROST PROTECTION (only when the circulation is active in the system): yes >
turn on the protection of hot water installation from frost.
● ADDITIONAL HEAT SOURCE: yes > providing an additional heat source.
● DEVICE’S NO: device’s number on the mains.
Exit any menu item by pressing ′End′ or by pressing and holding the navigation dial.
When not operated by the user, main function screen will appear after about 3 min.
SERVICE
Diagnostic options available only for authorised service

16
In daily schedule hot water circuit has dened starting time (3) and nishing time (4) of
maintaining selected temperature (5) (from range of 30..60°C). Except set time frames
only frost protection of the storage cylinder will be possible. For circulation circuit within
the schedule there is an adjustment of starting time and nishing time of circulation
pump’s operation. To change the parameters for the daily schedule, select chosen
program number and press navigation dial. Editing eld ashes, use the navigation dial
to set the new time frame value (hour and minutes separately) and conrm by pressing
the dial, then move to next eld edition that starts ashing. Last editable position is a
command. To save changes select command ‘save’ and press the dial to nish editing.
To delete selected time frame, edit chosen time frame and by pressing the dial go to
command position, select command ‘delete and press the dial.
To add new time frame, select last dened time frame and by pressing the dial go to
command position, select command ‘add’ and press the dial to add new time frame
which by editing can be adjusted to personal preferences (described above). If all ve
time frames were used or there is no time break for new period, the command will
not be visible. If there are no dened time frames within daily schedule, after selecting
“new”, 40 C will be set as daily temperature. The daily program will be saved to the heat
pump settings after leaving daily program and pressing the command “SAVE AND EXIT”.
Daily schedule:
DHW PROGRAMME NO1
DHW PROGRAMME NO1
SAVE AND EXIT
SAVE AND EXIT
1 6:20 - 8:00 42°
2 18:30 - 23:00
2 18:30 - 23:00
50°
50°
23456
1[1] - selected time period
[2] - no. of time frame according to schedule
(max 5)
[3] - time of starting set temperature
[4] - time of nishing set temperature
[5] - setting DHW temperature
[6] - command (active when editing):
accept
delete
add

GB-097B_f 17
Failures
If fault occurs there will be Err message on display. In case of error contact authorized
service of Kospel.
Anode’s state control
When device is in use, the anode wears naturally. That is why, periodic control and
replacement is necessary. In heat pump HPSW an insulated anode was used which
allows for preliminary control of its consumption with no need to disassemble. System
for measuring the state of anode is built into the device’s controller. The measurement
is carried out automatically once a day. In case when insufcient protection is detected,
a message about the need to replace the anode will appear on the panel. It is also
possible to verify the state of anode using universal meter.
To verify the state of anode:
- disconnect the power supply (leave device lled with water),
- remove the casing cover,
- disconnect the anode wire from connector joint,
- use universal meter to measure protective current between an anode and
a cylinder’s jacket (pic.).
If the value of measured current exceeds 0,3 mA, anode provides sufcient protection.
In other case, unscrew the anode, evaluate its state of use, and if needed exchange it.
0,3mA

18
Technical data
Model HPSW-2/250
Heating power W 2000 / 4000*
Electric power consumption W 600/2600**
Rated current A 2,6/11,3
COP (by PN EN 16147)
efciency factor
A20/W15-45 3,86
A20/W10-55 3,24
A15/W15-45 3,47
A15/W10-55 2,91
Power supply V/Hz 230/50
Electric heater W 2000
Maximum water temperature °C 60/70***
Capacity of hot water cylinder l 250
Rated water pressure (cylinder) MPa 0,6
Coil capacity l 8
Coil surface m21,2
Rated water pressure (coil) MPa 1,0
Maximum temperature of heating medium °C 80
Insulated magnesium anode M8 Ø33 mm 450
*Heat pump / Heat pump + heater
**Active electric heater
***Disinfection

GB-097B_f 19
Refrigerant type R134A
Volume g 460
GWP 1430
Equivalent of CO2t 0,658
Maximum pressure MPa 2,6
Amount of compressors szt. 1
Air ow m3/h 300
Ambient temperature °C 5 - 40
Dimensions
a
mm
125,8
b 229,3
c 332,5
d 831,5
e 932,5
f 1160
dimensions (HxWxD) 1669x627x670
Nett weight kg 152
Noise level
dB(A)
50
Table of contents
Other Kospel Heat Pump manuals
Popular Heat Pump manuals by other brands

CTC Union
CTC Union GS 6-8 Installation and maintenance manual

Rinnai
Rinnai Pro Series Operation guide

Nordic
Nordic PASRW150S-BP-PS-D Installation and instruction manual

Carrier
Carrier AQUAZONE 50PSH Installation and service instructions

Enertech
Enertech ERC Series Installation operation & maintenance

Dimplex
Dimplex SI 30TE Installation and operating instructions

Luxaire
Luxaire THGD18 Technical guide

Mitsubishi Electric
Mitsubishi Electric CAHV-R450YA-HPB Installation & operation manual

REVELL
REVELL LWRc-8kW Operational manual

Nibe
Nibe F470 Installer manual

Carrier
Carrier 25HBA3 Series Wiring diagrams

Viessmann
Viessmann VITOCAL 060-A Operating Instructions for the System User