Krampitz Tanksystem TTD Series User manual

Operation and Installation Instructions TTD
for Double Wall Tank System for Diesel Fuel
or Mineral Oil (Fresh or Spent Oil)
Any disclosure or duplication of this documents, commercial exploitation or communication of the contents is prohibited except
with the prior express approval of Krampitz Tanksystem GmbH. Any contravention can be prosecuted and compensation can be
claimed.
Issue 04/2011 www.krampitz.de
Tank No.:
Year of construction:
Type TTD:

2Krampitz Tanksystem GmbH - Operation and Installation Instructions TTD for Tank System - Issue 04/2011
TABLE OF CONTENTS ................................................................................................................................................................................................. 2
SETTINGS OF THE LIMIT SENSOR FOR DAY TANK TTD ................................................................................................................................................ 3
SETTINGS OF THE OVERFLOW GUARD OF DAY TANK TTD .......................................................................................................................................... 3
INSTALLATION AND TEST CERTIFICATE ...................................................................................................................................................................... 4
PRELIMINARY NOTE ................................................................................................................................................................................................................... 5
ABBREVIATIONS USED ............................................................................................................................................................................................................... 5
1. SAFETY INSTRUCTIONS AND REGULATIONS ........................................................................................................................................................................ 5
1.1 Safety instructions .............................................................................................................................................................................................................. 5
1.2 Operation procedures ......................................................................................................................................................................................................... 6
1.2.1 General operation procedures ..................................................................................................................................................................................... 6
1.2.2 Action to take .............................................................................................................................................................................................................. 6
1.2.3 Instruction of operators ............................................................................................................................................................................................... 6
1.2.4 Repairs and maintenance ............................................................................................................................................................................................ 6
1.2.5 Safety tests and inspections ......................................................................................................................................................................................... 6
1.2.6 Handling fuel oil, Diesel fuel and mineral oil ............................................................................................................................................................... 6
2. DESCRIPTION .......................................................................................................................................................................................................................... 7
2.1 Illustration of the TTD ......................................................................................................................................................................................................... 7
2.2 Intended use of the TTD ...................................................................................................................................................................................................... 7
2.3 Specifications of the TTD ..................................................................................................................................................................................................... 7
2.3.1 Dimensions and weights of the TTD ............................................................................................................................................................................. 7
2.3.2 Connections of the TTD ................................................................................................................................................................................................ 8
2.3.3 Filling and discharge rates of the TTD from tank trucks ............................................................................................................................................... 8
2.3.4 Plant layout scheme .................................................................................................................................................................................................... 8
2.4. Units of the TTD - standard equipment .............................................................................................................................................................................. 9
2.4.1 The tank vessel ............................................................................................................................................................................................................ 9
2.4.2 The static vacuum leakage indicator ............................................................................................................................................................................ 9
2.4.3 The rupture disk ......................................................................................................................................................................................................... 9
2.4.4 The transport plug ........................................................................................................................................................................................................ 9
2.4.5 The ball valve ............................................................................................................................................................................................................... 9
2.4.6 Corrosion protection for indoor installation ................................................................................................................................................................. 9
2.4.7 The nameplate ............................................................................................................................................................................................................. 10
2.5. Connection kit .................................................................................................................................................................................................................... 10
2.5.1 The level indicator ........................................................................................................................................................................................................ 10
2.5.2 The filling socket .......................................................................................................................................................................................................... 10
2.5.3 The suction pipe - machine flow pipe .......................................................................................................................................................................... 10
2.5.4 The adapter set ............................................................................................................................................................................................................ 10
2.5.5 The machine return pipe .............................................................................................................................................................................................. 11
2.5.6 The bleeding adapter with hood .................................................................................................................................................................................. 11
2.6. Units of the TTD - special design ........................................................................................................................................................................................ 11
2.6.1 The level sensor ........................................................................................................................................................................................................... 11
2.6.1.1 The level switch (miniature alarm) ..................................................................................................................................................................... 11
2.6.1.2 The electronic volume indicator ......................................................................................................................................................................... 12
2.6.1.3 Floating switch volume indicator and dipstick with dipstick pipe plug .............................................................................................................. 12
2.6.2 Bearing charts ............................................................................................................................................................................................................ 12
2.6.2.1 Bearing charts for TTD 250,TTD 500 ................................................................................................................................................................ 12
2.6.2.2 Bearing charts for TTD 750,TTD 990, TTD 1500 and TTD 1950 ......................................................................................................................... 13
2.6.3 The electronic leakage indicator .................................................................................................................................................................................. 14
2.6.4 The electronic vacuum leakage indicator ..................................................................................................................................................................... 14
2.6.5 The oil warning sensor with alarm and evaluation unit .............................................................................................................................................. 15
2.6.5.1 Function of the oil alarm .................................................................................................................................................................................... 15
2.6.5.2 Configuration of the oil alarm ........................................................................................................................................................................... 15
2.6.6 The overfill guards ....................................................................................................................................................................................................... 15
2.6.6.1 The limit sensor with PTC thermistor - only for fuel oil and Diesel fuel .............................................................................................................. 15
2.6.6.2 The overfill guard with evaluation logic ............................................................................................................................................................. 15
2.6.6.3 Overview: Possible switching points and control instructions ............................................................................................................................ 16
2.6.7 The pump combination ................................................................................................................................................................................................ 16
2.6.7.1 Other pumps from the delivery range of Krampitz Tanksystem GmbH ............................................................................................................... 16
2.6.8 The tank heater............................................................................................................................................................................................................. 16
2.6.9 The wall brackets ......................................................................................................................................................................................................... 16
2.6.10 The supporting column .............................................................................................................................................................................................. 17
2.6.11 The Krampitz special nut with captive washer ........................................................................................................................................................... 17
2.6.12 The feet ...................................................................................................................................................................................................................... 17
3. START-UP ................................................................................................................................................................................................................................. 17
3.1 Transport of the TTD ............................................................................................................................................................................................................ 17
3.2 Wall mounting of the TTD ................................................................................................................................................................................................... 17
3.3 Setting up the TTD on feet / supporting column .................................................................................................................................................................. 18
3.4 First start-up ....................................................................................................................................................................................................................... 18
3.5 Operation sequence ............................................................................................................................................................................................................ 18
4. DOCUMENTATION .................................................................................................................................................................................................................. 19
5. WARRANTY ............................................................................................................................................................................................................................. 19
TABLE OF CONTENTS

3
Specifications may change as design revisions take place!
Settings of the limit sensor for day tank TTD
Setting the overfill guard for Day tank TTD
HI - Inside height X-GWG – Settling dimension for limit sensor
Y - Control dimension
a - Height between tank roof and limit sensor setpoint
b - Roof thickness
c - Sleeve height (20 mm)
d - Reducing height (12 mm) HI - Inside height
Limit sensor detail
a - Height between tank roof and overfill guard
b - Roof thickness
c - Sleeve height (20 mm)
d - Reducing height (12 mm) HI - Inside height
Overfill guard detail
HI - Inside height X-ÜSI - Settling dimension for Overfill guard
Y - Control dimension
X-GWG = a + b + c + d
Y = 360 - 25 - X-GWG
a = HI - ( HI*0,95)
X-ÜSI = a + b + c + d
Y = 200 - X-ÜSI
a = HI - ( HI*0,95)
TTD – Day tank Detail
a
b
c
XY
Probes nominal dimensions 360 mm
d
Tank type HI b X-GWG Y
mm mm mm mm
TTD 250 481 3 59 276
TTD 500 481 3 59 276
TTD 750 731 3 71 264
TTD 990 731 3 71 264
TTD 1500 980 4 85 250
TTD 1950 980 4 85 250
Inside height
Detail
a
b
c
XY
Probes nominal dimensions 200 mm
d
Tanktyp HI b X-ÜSI Y
mm mm mm mm
TTD 250 481 3 59 141
TTD 500 481 3 59 141
TTD 750 731 3 71 129
TTD 990 731 3 71 129
TTD 1500 980 4 85 115
TTD 1950 980 4 85 115
Inside height
TTD – Day tank
Krampitz Tanksystem GmbH - Operation and Installation Instructions TTD for Tank System - Issue 04/2011

5
1. SAFETY INSTRUCTIONS AND REGULATIONS
The TTD is subject to recurrent testing and inspection after the initial start-up.
PRELIMINARY NOTE
ABBREVIATIONS USED
These technical operation and installation instructions describe the „TTD double wall day tank for Diesel fuel and mineral oil“. It contains de-•
scriptions and instructions required for the operator’s understanding and ensuring the correct operation, proper maintenance of all materials and
compliance with all safety and health instructions.
Designation of the tank system: For brevity sake, the TTD double wall day tank for Diesel fuel and mineral oil is referred to as TTD in this ma-•
nual.
The Table of Contents provides an overview of the organization of this manual and identifies the main and sub-chapters, plus page numbers.•
Important instructions relating to technical safety and health protection are emphasized by the following symbols.•
TTD - Double wall day tank
WHG - Water management act
TRbF - Technical rules for combustible liquids
BMA - Operation and installation instructions
VDE - Verband der Elektrotechnik (Electrical engineering association)
VAwS - Verordnung über Anlagen zum Umgang mit Wasser gefährdenden Stoffen and über Fachbetriebe (Ordinance regarding plants
for handing potentially water polluting substances and on specialist manufacturers)
VDS - Verband der Sachversicherer (property insurer association)
Refers to work and operation procedures which when ignored cause danger to persons.
Refers to work and operation procedures which when ignored cause risk of damage or destruction to assets.
Technical requirements which the user should observe.
WARNING
CAUTION
NOTE
Krampitz Tanksystem GmbH - Operation and Installation Instructions TTD for Tank System - Issue 04/2011
WARNING Maintenance and repair work to overfill guard and leakage warning equipment should only be performed by
authorized specialist personnel according to Article 19 l WHG.
WARNING After connecting the electrical components to a power source, the plant is live with dangerous voltage.
Electrically isolate the power supply cable before starting work on electrical components.
WARNING Enter the tank only by the openings provided for this purpose. The tank should be completely empty, cleaned
and degassed before entry is permitted. Anyone entering the tank is required to wear full personal protection
equipment as required by the rules of safety and health protection.
CAUTION No work such as drilling, welding, cutting or grinding should be performed on the tank body
(i.e., the sheet metal containing the medium).
CAUTION Wrong operation or con-compliance with the instructions in this manual or the requirements of safety
and health protection can be the cause of damage to equipment, persons and the environment
and can void any warranty or guarantee.
1.1 Safety instructions

6Krampitz Tanksystem GmbH - Operation and Installation Instructions TTD for Tank System - Issue 04/2011
1.2 Operation procedures
1.2.1 General operation procedures
Initial start-up
Inspect the TTD and the other equipment for visible damage before initial start-up. Check the leakage indicator for pressure loss.
Readiness for operation
The plant requires constant technical monitoring to ensure that disruptions of normal operation are identified and remedial action taken as quickly as
possible. Only trained and instructed personnel should monitor the equipment and perform necessary repairs.
Temporary shut-down
For temporary shut-down, switch off the TTD or disconnect it from the power supply.
Restart
Inspect the TTD to ensure that it is in proper and good technical condition before it is restarted. Inspect the following equipment:
- Leakage indicator,
- Electrical connections and components (outside),
- Vessels and connecting piping for leaks.
1.2.2 Action to take
1. The owner is obliged to maintain the TTD in a state suitable for storing fuels or mineral oil, perform necessary repairs without delay and take all
safety precautions required by circumstances.
2. If the owner cannot judge the state of the equipment or repair defects, he should obtain help from an expert or conclude a maintenance contract
with an accredited specialist firm.
3. The plant must not be operated when a defect exists that can be the cause of danger.
4. Action to avert or contain the dangerous state should be taken without delay.
5. Prescribed safety devices must be used.
6. All safety devices should be operated and maintained so that they are effective at any time.
7. In particular, safety devices must not be bypassed or rendered ineffective in part or whole.
8. Liquids potentially contaminating water should only be filled in tanks which are intended for such liquids.
9. Fill the TTD, but avoid overfilling. Find out the filling level in the tank before starting the filling procedure. You should know how much more liquid
the TTD can hold.
10. The truck or barrel filling procedure requires constant monitoring by the operator.
1.2.3 Instruction of operators
All operators should be familiar with the start-up and handling of the TTD and the content of these operation instructions. All operators should also
know the dangers that can arise in connection with storage and filling of potentially water contaminating liquids and action to avoid such dangers and
should be instructed accordingly before the first operation and then in regular intervals, but at least once a year, and the instruction should be put on
record.
1.2.4 Repairs and maintenance
No liquid should be filled in or withdrawn from the tank when maintenance work is under way. Electrically isolate the complete plant before starting
repair.
1.2.5 Safety tests and inspections
Test item
Designation Person(s) carrying out the test/inspection Time interval Proof of test/inspection
Visual inspection of the tank Owner weekly -
Visual inspection for leaks of connections to the tank Owner weekly -
Function control of the leakage indicator Specialist firm acc. to WHG* yearly Certification
Function control of the limit sensor** Specialist firm acc. to WHG* yearly Certification
Function control of the overfill guard** Specialist firm acc. to WHG* yearly Certification
Function control of the level sensor** Specialist electric firm or instructed personnel yearly Certification
* after instruction by manufacturer * * if installed - probes
1.2.6 Handling of fuel oil, Diesel fuel and mineral oil:
Observe all applicable general safety instructions.

7Krampitz Tanksystem GmbH - Operation and Installation Instructions TTD for Tank System - Issue 04/2011
2.2 Intended use of the TTD
The TTD is used as day tank to supply plants and equipment with fuel or lubricating oil. The TTD is also referred to as supply tank. It can be installed at
indoor sites or in an equipment container. The area on which the tank is installed should be level and have sufficient load bearing capacity. The tank
should only be installed in areas which are not exposed to additional hazards or requirements. If the tank is used under special conditions, all applicable
requirements should be observed.
The cube shape of the TTD ensures maximum utilization of available space. The tank is set up close by the equipment which it supplies so that the small
external pump or the pump integrated in the tank unit can pump the liquid. To facilitate this, the connected piping should not include any considerable
height differences or bends. The TTD is manufactured according to the general inspectorate approval No. Z-38.12-23.
CAUTION Move the TTD only when it is empty and clean.
CAUTION When installing the TTD under special conditions, e.g. in a potentially explosive zone, all applicable requirements should be
observed.
2.1 Illustration of the TTD
TTD without fittings TTD with fittings
Fittings
Mechanical
level indicator
Leakage
indicator KÜR 5
2. DESCRIPTION
Bleeding hood
with pipe socket
Filling socket Adapter
AG 2´´ x IG ¾´´
¾´´ 1“
2“
2“2“
Dummy plug
AG 2´´
Adapter
AG 2´´ x IG 1´´
Suction pipe
with foot
valve, flanged
2.3 Specifications of the TTD
2.3.1 Weights and dimensions of the TTD
The TTD is available in six different standard sizes. Tanks of non-standard length, width or height can be made without problem. The only point is that the
tank must be of a size than can be transported.
The volume capacities of the different tank types are listed in the table below. The digit in the designation is an indicator and designated the tank type.
Tank type Volume 100% Volume 95% Length Total length Width Height Total height Weight
Art.-Nr. Liter Liter mm mm mm mm mm kg
TTD 250 245 230 1.260 1.280 500 505 630 133
TTD 500 470 440 1.510 1.530 750 505 630 186
TTD 750 730 700 1.510 1.530 750 755 880 248
TTD 990 975 940 2.010 2.030 750 755 880 316
TTD 1500 1.800 1.730 2.010 2.030 1.000 1.005 1.130 524
TTD 1950 2.300 2.190 2.010 2.030 1.250 1.005 1.130 658

8Krampitz Tanksystem GmbH - Operation and Installation Instructions TTD for Tank System - Issue 04/2011
111111
3
44
2
Total length
Length Width
Height
Total height
2.3.2 Connections of the TTD
1Connecting sleeve
2Rupture disk
3Overflow
4Leakage indicator
connecting points
NOTE The general inspectorate approval No. Z-38.12-23
limits the maximum filling volume to 95 percent
of the tank height.
2.3.3 Filling and discharge rates of the TTD from tank trucks
TTD type Filling rate (max) Withdrawal rate
Up to TTD 990 150 liters/min - only with dispensing nozzle 600 liters/min
From TTD 990 600 liters/min - with tank truck hose set 600 liters/min
Storage tanks are filled at the tank truck connection. Tanks
up to 1,000 liters volume can also be filled by dispensing
nozzle which stops the liquid flow according to the dead
man’s principle
The following connections are provided on the TTD:
1. Roof side: Six connecting sleeves 2´´ for optional installation of level
sensor, overfill guard, machine return pipe, filling by pump, filling from tank
truck, and bleeding. Located at the center is an NBR rupture disk which
protects the tank from overpressure. If the rupture disk is removed, the
opening can be used as hand hole or for inspection.
2. Front side: A 2” overflow sleeve for connection of an overflow pipe
back to the storage tank is located on the right, centrally relative to the
top edge 2”. If no overflow pipe is installed, the connecting sleeve should
be closed by a dummy plug. The overfill tube is a reasonably priced alter-
native to the overfill guard, for which the storage tank should not be more
than five meters away from the day tank and not placed lower than the
outline of the day tank.
If the day tank is used without a storage tank, an approved safety device
protecting against overfilling is prescribed for capacities of 1,000 liters or
more. The same requirement also applies to smaller tanks which are not
filled from tank truck via dispensing nozzle.
Standard tank with tank fittings
containers with standard equip-
ment and optional accessories in
working order
2.3.4 Plant layout scheme
Legend - Symbols according to DIN 2481
Connection for filling from tank truck
Rupture disk (overpressure)
Foot valve
Filter / mud trap
Level meter
Bleeding to atmosphere
Indicates direction of liquid flow
Leakage indicator
Suction socket leakage indicator
Level meter, Switching contacts for
top and bottom limits
Double wall vessel
Legend - Designations acc. to DIN 19227
Vacuum leak alarm with design
approval (static, type KÜR 5)
Rupture disk overpressure guard
Local level indicator Mechanical level
indicator
Float switch
Overfill guard Limit monitor with
design approval
TTD - Day tank, Double wall

9Krampitz Tanksystem GmbH - Operation and Installation Instructions TTD for Tank System - Issue 04/2011
2.4. Units of the TTD - standard equipment
2.4.1 The tank vessel
The typical feature of the tank vessel is the double wall cube design. This
design ensures maximum utilization of the available space. The standard
tank vessel of the TTD is made of steel (S235 JRG2).
To protect it from corrosion, the tank vessel is provided with a 2-compo-
nent coat of paint on the outside (RAL 7032). The inside wall is blank and
oiled.
2.4.3 The rupture disk (installed)
The rupture disk is installed in the center of the tank roof. If a sudden over-
pressure occurs, it protects the tank by being ejected before it bursts. The
opening of the rupture disk can also be used as hand hole and inspection
opening.
Sealing
membrane
Outside sealing bead
Inside sealing bead
The static vacuum leakage indicator is suitable for tank systems without
permanent power supply. It consists of an impact resistant stainless steel
housing with capsule pressure gauge and a filling of glycerol.The alarm is
indicated visibly by pointer. The vacuum is produced by an external pump
in the space monitored for leakage and enclosed. If the vacuum drops, the
alarm is indicated by the pointer entering the red range.
The vacuum leakage indicator should be inspected visual
• regularly during operation and, in particular, after
• every transport
• every change of another location
• every initial start-up
• every restart
• every temporary shut-down
• in accordance with control procedures during operation.
Stop operation of the equipment if the pointer enters the red range of the
scale. The static vacuum leakage indicator is marketed general inspecto-
rate certificate No. Z-65.22-158.
2.4.2 The static vacuum leakage indicator (installed)
Working range I
(dark green)
Working range II
(dark green)
Working range III
(light green)
Alarm
(red range)
Atmospheric
range
Pointer
Connection socket
-1
-0,5 -0,4
-0,1
0
2.4.4 The transport plug (installed)
The plastic transport plugs are inserted in all sleeves of the tank vessel.
They provide protection from corrosion during transport. All transport
plugs should be removed before the fittings are installed or the TTD or fit-
tings of the TTD are put into operation. Sleeves not used should be closed
by dummy plug (see item 2.5.2).
2.4.6 Corrosion protection for indoor installation
Every TTD storage tank is provided with standard corrosion protection of
2-component textured paint. The standard finish of Krampitz Tanksystem
GmbH for this series is RAL 7032 (pebble grey). Other RAL finishes are
possible on request and against extra price.
The inside of the tank is not treated and provided with a thin coat of oil
as corrosion protection.
2.4.5 The ball valve (installed)
The ball valve 3/8´´ is installed in the tank roof. The manufacturer provides
the ball valve for generating the required vacuum. Once the vacuum is
established, the toggle of the ball valve is removed and the socket closed
by dummy plug and O-ring.
NOTE Work on or tampering with the ball valve is forbidden
and will void all warranty claims.
Inform the manufacturer if the vacuum drops.

10Krampitz Tanksystem GmbH - Operation and Installation Instructions TTD for Tank System - Issue 04/2011
2.5.1 The level indicator
2.4.7 The nameplate
Every TTD storage tank is provided with a nameplate according to general inspectorate certificate No. Z-38.12-
23. Placed on the right side of the nameplate is the logo of the manufacturer Krampitz Tanksystem GmbH.
All relevant data of the tank (manufacturer’s number, year of production, test pressure, tank capacity, material,
etc.) is placed in the center of the nameplate.
The label confirming compliance with the EC directives for vessels is attached on the left of the nameplate.The
name of the manufacturer, the number of the general inspectorate approval and the organization by which
the manufacturer is inspected are also put there. The nameplate is attached on the long side of the tank. The
tester’s code according to DIN 6600 is added to the nameplate after the successful test of the tank.
2.5 Connection kit
The floating switch volume indicator is a universal
mechanical level gauge with gear drive of brass and
nickel silver. It is held by double screw thread 2”
and 1 ½” and installed in tanks from 750 mm to
2,000 mm height. Shifting to other locations is only
permitted inside a building.
Setting screw G2’’
Indicator (scale)
Setting screw G1½’’
Float thread
Float
2.5.2 The filling socket
Every TTD should have sockets for a filling pipe and a filling socket, resp.
(also see TRbF 20).
The tank truck connection socket 2´´ x 2 ½´´ is installed in the tank roof by
a 45° angle A/A in a 2´´ sleeve. If the owner installs this connection outside
the equipment room, the socket can also be mounted on a wall.
Tank truck connection
with cap
45° angle 2´´ A/A
2.5.3 The suction pipe - machine flow pipe
The suction pipe is flange mounted to the roof. The machine flow pipe is
connected to it after installation of the suction pipe with foot valve.
Flange
Pipe 1“
Foot valve
2 reducers AG 2“ x IG ¾“
2 reducers AG 2“ x IG 1“
¾“
1“
2“
2“
2“
4 dummy plugs AG 2“
2.5.4 The adapter set
The 2“ dummy plug and the reducers are made of PE-HD. The plug is
sealed by O-ring in a sealing groove in the plug. The plug is installed tight
simply by screwing it hand-tight into the respective 2´´sleeve on the tank
roof. For ease of handling, the plug is knurled on the outer surface.
The adapter set ensures that fittings can be mounted. In addition to this,
the 2” sleeves in the tank roof facilitate the connection of the flow and
return pipes to the machine.
The adapter set consists of:

11Krampitz Tanksystem GmbH - Operation and Installation Instructions TTD for Tank System - Issue 04/2011
Level sensors sense the level of a liquid inside a tank. There are different
types of level sensors:
a) a switching system with level switches, and
b) an electronic measuring system with encoders.
The signals of level switches can be used directly for automatic control,
regulation or signaling.
In electronic measuring systems, the signal from the encoder is converted
in appropriate switching signals by the associated evaluation logic.
Flexible connecting cable
Cable glands
4-way adapter with AG 2“
Level switch max-max max/min
(no approved overfill guard)
Level switch max
Level switch min
Level switch min-min
2.6.1.1 The level switch (miniature alarm)
CAUTION Observe the specifications of the switch.
Specifications
Switching voltage max. 200 V DC / max. 120 V AC
Switching capacity max. 10 W
Contact resistance max. 0.5 mOhm
Switching current max. 0.5 A
Cable size 2 x 0.5 mm2 x 4,000 mm
Material Float, weight, shaft Stainless steel,
non-corrosive
Cable PVC
2.6 Units of the TTD - special design
2.6.1 The level sensor
2.5.5 The machine return pipe
The machine return pipe can be connected to one of the 2” sleeves in the tank roof installed without problem with a 2´´ x ¾´´ reducing adapter.
2.5.6 The bleeding adapter with hood
The 2´´bleeding tube is installed in a 2´´connecting sleeve in the tank roof.
If the tank is filled from a tank truck by the tank truck connection, the bleeding
line should at least be at the same height above the tank roof as the socket for
filling from tank truck.
Tanks installed below ground level (for example in the basement of a building)
should have the bleeding adapter installed at least up to 500 mm above the
connection for filling from tank trucks and 500 mm above ground level. The
bleeding pipe should not end inside an enclosed room.
Exception: Above-ground individual tank for Diesel fuel or fuel oil smaller than
1000 liters.
Hood
Pipe
(min. DN 50)
The electric level switch (miniature alarm) control and signals exactly de-
fined levels in the tank.When a 4-way cable gland is used, up to four level
switches can be installed in a tank.
The level switch does not need approval because it is only used as normal-
ly-open contact in tank systems, for example, for „pump on“ control (low
level contact) or „pump off“ (high level contact). Only approved overfill
guards are permitted for „overfilling alarm switching point (max-max).
The level switch can also be used for simple detection of leaks.
The level switch is made of stainless steel and is equipped with a flexible,
oil-resistant cable. The permitted temperature range of the cable is bet-
ween -5°C and +50°C. The 5-meter connecting cable is installed directly
at the control of the system.
Pull off turn 180° install
The level switch can be set to the required level by means of the cable
glands in the multiple-way adapter and fastened appropriately. The le-
vel switch can be converted from a normally open to a normally closed
contact simply by turning the float by 180° on the switch shaft.

12Krampitz Tanksystem GmbH - Operation and Installation Instructions TTD for Tank System - Issue 04/2011
2.6.1.2 The electronic volume indicator
The TTD can be equipped with an electronic volume indicator for com-
fortable recording filling data.
The Level Control V electronic volume indicator is a complete measuring
system for the continuous measurement of levels in tanks.
With this system, the tank height can be adapted and up to four limit
values defined.These relay contacts are galvanically separated from the
system. The system displays the level on the evaluation logic as a per-
centage value.
The electronic volume indicator is tested and precalibrated for the tar-
get tank before it is shipped.
Screw-in body with Mounting case
Adapter 2“-1 ¼“
Rod
Evaluation logic
Floating switch volume indicator
Universal mechanical level gauge with gear drive of brass and nickel
silver.
Description:
- Constant display
- Reading: in percent of the total height
- Set pointer as consumption indicator
- Mounting: Double screw thread 2” and 1 1/2”
- Vessel: Krampitz tanks height: 750 to 2,000 mm
- For tank systems inside buildings
- Housing of ABS and float of PE-HD
Display (scale)
Float threat
Float
2.6.1.3 Floating switch volume indicator (AM-001) and dipstick with dipstick pipe plug (AM-006)
Setting screw G2’’
Setting screw G1½’’
Dipstick with dipstick pipe plug
Only for outdoor plants because the dipstick cannot be pulled out unless
there is enough space.
Description:
- Dipsticks with centimeter graduation, easy to read
- Long brass chain
- Medium fuel oil and Diesel fuel dipsticks
made of plastic
- Carburetor fuel
as medium -
Dipsticks
of aluminium
Holes for liquid compensation
Dipstick tube 1” bottom closed
Dipstick pipe plug
Chain with ring
Reducer 2” AG to 1” IG
Holes for liquid compensation
Sleeve 2” IG
Roof panel
Dipstick with scale
2.6.2 Bearing charts
2.6.2.1 Bearing charts for TTD 250, TTD 500
Bearing charts - TTD 250
Level
mm
Content
Liter
Level
%
Level
mm
Content
Liter
Level
%
Level
mm
Content
Liter
Level
%
10 3,35 2,1% 170 83,94 35,3% 330 173,93 68,6%
20 6,95 4,2% 180 89,56 37,4% 340 179,55 70,7%
30 10,79 6,2% 190 95,19 39,5% 350 185,18 72,8%
40 14,88 8,3% 200 100,81 41,6% 360 190,80 74,8%
50 19,22 10,4% 210 106,44 43,7% 370 196,34 76,9%
60 23,80 12,5% 220 112,06 45,7% 380 201,63 79,0%
70 28,62 14,6% 230 117,68 47,8% 390 206,67 81,1%
80 33,70 16,6% 240 123,31 49,9% 400 211,48 83,2%
90 39,01 18,7% 250 128,93 52,0% 410 216,03 85,2%
100 44,57 20,8% 260 134,56 54,1% 420 220,34 87,3%
110 50,19 22,9% 270 140,18 56,1% 430 224,41 89,4%
120 55,82 24,9% 280 145,81 58,2% 440 228,23 91,5%
130 61,44 27,0% 290 151,43 60,3% 450 231,80 93,6%
140 67,07 29,1% 300 157,05 62,4% 460 235,29 95,6%
150 72,69 31,2% 310 162,68 64,4% 470 238,78 97,7%
160 78,31 33,3% 320 168,30 66,5% 480 242,26 99,8%
Bearing charts - TTD 500
Level
mm
Content
Liter
Level
%
Level
mm
Content
Liter
Level
%
Level
mm
Content
Liter
Level
%
10 7,73 3,2% 170 163,84 35,7% 330 331,27 69,3%
20 15,76 4,2% 180 174,31 37,8% 340 341,73 71,4%
30 24,08 6,3% 190 184,77 39,9% 350 352,20 73,5%
40 32,69 8,4% 200 195,23 42,0% 360 362,66 75,6%
50 41,61 10,5% 210 205,70 45,2% 370 373,02 77,7%
60 50,81 12,6% 220 216,16 46,2% 380 383,09 79,8%
70 60,32 14,7% 230 226,63 58,8% 390 392,86 81,9%
80 70,12 16,8% 240 237,09 50,4% 400 402,33 84,0%
90 80,21 18,9% 250 247,56 52,5% 410 411,51 87,2%
100 90,59 21,0% 260 258,02 54,6% 420 420,39 88,2%
110 101,06 24,2% 270 268,48 56,7% 430 428,98 90,3%
120 111,52 25,2% 280 278,95 58,8% 440 437,27 92,4%
130 121,99 27,3% 290 289,41 60,9% 450 445,27 94,5%
140 132,45 29,4% 300 299,88 63,0% 460 453,16 96,6%
150 142,91 31,5% 310 310,34 66,2% 470 461,05 98,7%
160 153,38 33,6% 320 320,81 67,2% 480 242,26 99,8%

13Krampitz Tanksystem GmbH - Operation and Installation Instructions TTD for Tank System - Issue 04/2011
2.6.2.2 Bearing charts for TTD 750, TTD 990, TTD 1500, TTD 1950
Bearing charts - TTD 750
Level
mm
Content
Liter
Level
%
Level
mm
Content
Liter
Level
%
Level
mm
Content
Liter
Level
%
10 7,73 1,4% 250 247,56 34,4% 490 498,70 67,5%
20 15,76 2,8% 260 258,02 35,8% 500 509,16 68,9%
30 24,08 4,1% 270 268,48 37,2% 510 519,63 70,2%
40 32,69 5,5% 280 278,95 38,6% 520 530,09 71,6%
50 41,61 6,9% 290 289,41 39,9% 530 540,55 73,0%
60 50,81 8,3% 300 299,88 41,3% 540 551,02 74,4%
70 60,32 9,6% 310 310,34 42,7% 550 561,48 75,8%
80 70,12 11,0% 320 320,81 44,1% 560 571,95 77,1%
90 80,21 12,4% 330 331,27 45,5% 570 582,41 78,5%
100 90,59 13,8% 340 341,73 46,8% 580 592,88 79,9%
110 101,06 15,2% 350 352,20 48,2% 590 603,34 81,3%
120 111,52 16,5% 360 362,66 49,6% 600 613,80 82,6%
130 121,99 17,9% 370 373,13 51,0% 610 624,27 84,0%
140 132,45 19,3% 380 383,59 52,3% 620 634,63 85,4%
150 142,91 20,7% 390 394,06 53,7% 630 644,69 86,8%
160 153,38 22,0% 400 404,52 55,1% 640 654,46 88,2%
170 163,84 23,4% 410 414,98 56,5% 650 663,94 89,5%
180 174,31 24,8% 420 425,45 57,9% 660 673,11 90,9%
190 184,77 26,2% 430 435,91 59,2% 670 682,00 92,3%
200 195,23 27,5% 440 446,38 60,6% 680 690,58 93,7%
210 205,70 28,9% 450 456,84 62,0% 690 698,88 95,0%
220 216,16 30,3% 460 467,31 63,4% 700 706,87 96,4%
230 226,63 31,7% 470 477,77 64,7% 710 714,77 97,8%
240 237,09 33,1% 480 488,23 66,1% 720 722,66 99,2%
Bearing charts - TTD 1500
Level
mm
Content
Liter
Level
%
Level
mm
Content
Liter
Level
%
Level
mm
Content
Liter
Level
%
10 15,29 1,0% 340 625,47 34,8% 670 1.250,80 68,6%
20 30,98 2,0% 350 644,42 35,9% 680 1.269,75 69,7%
30 47,06 3,1% 360 663,37 36,9% 690 1.288,69 70,7%
40 63,53 4,1% 370 682,32 37,9% 700 1.307,64 71,7%
50 80,41 5,1% 380 701,27 38,9% 710 1.326,59 72,7%
60 97,67 6,1% 390 720,22 40,0% 720 1.345,54 73,8%
70 115,34 7,2% 400 739,17 41,0% 730 1.364,49 74,8%
80 133,40 8,2% 410 758,12 42,0% 740 1.383,44 75,8%
90 151,85 9,2% 420 777,07 43,0% 750 1.402,39 76,8%
100 170,69 10,2% 430 796,01 44,1% 760 1.421,34 77,9%
110 189,64 11,3% 440 814,96 45,1% 770 1.440,29 78,9%
120 208,59 12,3% 450 833,91 46,1% 780 1.459,24 79,9%
130 227,54 13,3% 460 852,86 47,1% 790 1.478,19 80,9%
140 246,49 14,3% 470 871,81 48,2% 800 1.497,14 82,0%
150 265,44 15,4% 480 890,76 49,2% 810 1.516,09 83,0%
160 284,38 16,4% 490 909,71 50,2% 820 1.535,03 84,0%
170 303,33 17,4% 500 928,66 51,2% 830 1.553,98 85,0%
180 322,28 18,4% 510 947,61 52,3% 840 1.572,93 86,1%
190 341,23 19,5% 520 966,56 53,3% 850 1.591,88 87,1%
200 360,18 20,5% 530 985,51 54,3% 860 1.610,83 88,1%
210 379,13 21,5% 540 1.004,46 55,3% 870 1.629,64 89,1%
220 398,08 22,5% 550 1.023,41 56,4% 880 1.648,05 90,2%
230 417,03 23,6% 560 1.042,35 57,4% 890 1.666,07 91,2%
240 435,98 24,6% 570 1.061,30 58,4% 900 1.683,70 92,2%
250 454,93 25,6% 580 1.080,25 59,4% 910 1.700,93 93,2%
260 473,88 26,6% 590 1.099,20 60,5% 920 1.717,76 94,3%
270 492,83 27,7% 600 1.118,15 61,5% 930 1.734,20 95,3%
280 511,78 28,7% 610 1.137,10 62,5% 940 1.750,24 96,3%
290 530,73 29,7% 620 1.156,05 63,5% 950 1.765,89 97,3%
300 549,67 30,7% 630 1.175,00 64,5% 960 1.781,39 98,4%
310 568,62 31,8% 640 1.193,95 65,6% 970 1.796,90 99,4%
320 587,57 32,8% 650 1.212,90 66,6%
330 606,52 33,8% 660 1.231,85 67,6%
Bearing charts - TTD 990
Level
mm
Content
Liter
Level
%
Level
mm
Content
Liter
Level
%
Level
mm
Content
Liter
Level
%
10 10,34 1,4% 250 331,30 34,4% 490 667,40 67,5%
20 21,09 2,8% 260 345,31 35,8% 500 681,41 68,9%
30 32,22 4,1% 270 359,31 37,2% 510 695,41 70,2%
40 43,75 5,5% 280 373,32 38,6% 520 709,42 71,6%
50 55,68 6,9% 290 387,32 39,9% 530 723,42 73,0%
60 68,00 8,3% 300 401,32 41,3% 540 737,43 74,4%
70 80,72 9,6% 310 415,33 42,7% 550 751,43 75,8%
80 93,84 11,0% 320 429,33 44,1% 560 765,43 77,1%
90 107,35 12,4% 330 443,34 45,5% 570 779,44 78,5%
100 121,24 13,8% 340 457,34 46,8% 580 793,44 79,9%
110 135,24 15,2% 350 471,35 48,2% 590 807,45 81,3%
120 149,25 16,5% 360 485,35 49,6% 600 821,45 82,6%
130 163,25 17,9% 370 499,35 51,0% 610 835,46 84,0%
140 177,26 19,3% 380 513,36 52,3% 620 849,32 85,4%
150 191,26 20,7% 390 527,36 53,7% 630 862,79 86,8%
160 205,26 22,0% 400 541,37 55,1% 640 875,86 88,2%
170 219,27 23,4% 410 555,37 56,5% 650 888,54 89,5%
180 233,27 24,8% 420 569,38 57,9% 660 900,82 90,9%
190 247,28 26,2% 430 583,38 59,2% 670 912,71 92,3%
200 261,28 27,5% 440 597,38 60,6% 680 924,20 93,7%
210 275,29 28,9% 450 611,39 62,0% 690 935,30 95,0%
220 289,29 30,3% 460 625,39 63,4% 700 946,01 96,4%
230 303,29 31,7% 470 639,40 64,7% 710 956,57 97,8%
240 317,30 33,1% 480 653,40 66,1% 720 967,13 99,2%
Bearing charts - TTD 1950
Level
mm
Content
Liter
Level
%
Level
mm
Content
Liter
Level
%
Level
mm
Content
Liter
Level
%
10 20,23 1,0% 340 793,60 34,8% 670 1.582,11 68,6%
20 40,87 2,0% 350 817,50 35,9% 680 1.606,01 69,7%
30 61,89 3,1% 360 841,39 36,9% 690 1.629,90 70,7%
40 83,31 4,1% 370 865,28 37,9% 700 1.653,79 71,7%
50 105,13 5,1% 380 889,18 38,9% 710 1.677,69 72,7%
60 127,34 6,1% 390 913,07 40,0% 720 1.701,58 73,8%
70 149,95 7,2% 400 936,97 41,0% 730 1.725,48 74,8%
80 172,96 8,2% 410 960,86 42,0% 740 1.749,37 75,8%
90 196,36 9,2% 420 984,76 43,0% 750 1.773,27 76,8%
100 220,14 10,2% 430 1.008,65 44,1% 760 1.797,16 77,9%
110 244,03 11,3% 440 1.032,54 45,1% 770 1.821,05 78,9%
120 267,93 12,3% 450 1.056,44 46,1% 780 1.844,95 79,9%
130 291,82 13,3% 460 1.080,33 47,1% 790 1.868,84 80,9%
140 315,72 14,3% 470 1.104,23 48,2% 800 1.892,74 82,0%
150 339,61 15,4% 480 1.128,12 49,2% 810 1.916,63 83,0%
160 363,50 16,4% 490 1.152,01 50,2% 820 1.940,52 84,0%
170 387,40 17,4% 500 1.175,91 51,2% 830 1.964,42 85,0%
180 411,29 18,4% 510 1.199,80 52,3% 840 1.988,31 86,1%
190 435,19 19,5% 520 1.223,70 53,3% 850 2.012,21 87,1%
200 459,08 20,5% 530 1.247,59 54,3% 860 2.036,10 88,1%
210 482,98 21,5% 540 1.271,49 55,3% 870 2.059,85 89,1%
220 506,87 22,5% 550 1.295,38 56,4% 880 2.083,21 90,2%
230 530,76 23,6% 560 1.319,27 57,4% 890 2.106,18 91,2%
240 554,66 24,6% 570 1.343,17 58,4% 900 2.128,75 92,2%
250 578,55 25,6% 580 1.367,06 59,4% 910 2.150,92 93,2%
260 602,45 26,6% 590 1.390,96 60,5% 920 2.172,70 94,3%
270 626,34 27,7% 600 1.414,85 61,5% 930 2.194,08 95,3%
280 650,24 28,7% 610 1.438,75 62,5% 940 2.215,07 96,3%
290 674,13 29,7% 620 1.462,64 63,5% 950 2.235,66 97,3%
300 698,02 30,7% 630 1.486,53 64,5% 960 2.256,11 98,4%
310 721,92 31,8% 640 1.510,43 65,6% 970 2.276,57 99,4%
320 745,81 32,8% 650 1.534,32 66,6%
330 769,71 33,8% 660 1.558,22 67,6%

14Krampitz Tanksystem GmbH - Operation and Installation Instructions TTD for Tank System - Issue 04/2011
Specifications
Dimensions (L x W x H) in mm 215 x 165 x 100
Footprint (L x W x H) in mm 250 x 170 x 999
Weight in kg 1,7
Supply voltage 230 V AC +/-10% 50/60 Hz
Rated output 95 VA
Line fuse T 0,8 A
Output relay 1 changeover switch
Output relay switching capacity max. 250 V, 2 A, ohmic load
Relay contact fuse T 2 A
Switching point “Alarm on” in mbar -325 to -355
Switching point “Alarm off” in mbar -380 (value for information, exact le-
vel depends on switching hysteresis)
Switching point „Pump on“ in mbar -380 (value for information, exact le-
vel depends on switching hysteresis)
Switching point „Pump off“ in mbar -410 to -450
Hose connection, diameter in mm 5
Connecting hose PVC hose 4 x 2 mm, 6 x 2 mm
Permitted ambient temperature in °C -5 to +50
Protection class 11 EN 60730
Type of protection IP 30 EN 60529
Radio interference suppression according to EN 50081-1
Noise immunity according to EN 50082-2
If operating voltage (230 V, 50 Hz) is supplied and vacuum has built up,
the green lamp lights. The leakage indicator generates constant vacuum
(approximately -400 mbar) in the monitored space of the tank and sounds
an alarm if the vacuum drops (= pressure rises) (below about -340mbar).
The alarm is provided visually (red alarm lamp) and audibly and can be
sampled at a floating relay contact (1 switchover). The audible alarm can
be muted after breaking the seal under the „alarm sound“ toggle switch.
When the supply voltage fails, no alarm is triggered.The device is ready for
operation immediately after the power supply is restored.
A leak that may have developed in the meantime will be signaled.
A visual check of the leakage indicator is made
• every time the device is transported
• every time the device is moved to another site
• every initial start-up
• every restart
• every temporary shut-down.
Bitte beachten:
1. Gerät vor dem Öffnen spannungsfrei schalten.
2. Grüne Betriebslampe muß immer leuchten.
3. Im Alarmfall leuchtet rote Alarmlampe und Hupe
ertönt. Hupe am Kippschalter nach Lösen
der Plombe ausschalten Installationsfirma
benachrichtigen!
4. Wartung durch den Sachkundigen 1 x jährlich
durchführen lassen.
Hierzu Betriebsanleitung beachten.
Unterdruck-Leckanzeiger Eurovac Betrieb
LECK
aus
Alarmton
ein
Installationsfirma
2.6.3 The electronic leakage indicator (installed)
Green operating lamp
Red alarm lamp
„Alarm tone“
toggle switch
In an impact resistant housing, the leakage indicator contains the indica-
ting and control elements, a vacuum pump, a pressure switch, a printed
circuit board with the required electromagnetic components for proces-
sing the output signal, a filter and three hose connections for the pneu-
matic connection to the monitored space of the tank.
CAUTION
1 Green operating lamp
2 Red alarm lamp
3 Toggle switch
4 Seal mount
5 Check valve
6 Suction line connection
7 Exhaust line connection
8 Measuring line connection
6785
2
3
4
1
Leuchtmelder
BETRIEB
(grün)
Leuchtmelder
ALARM
(rot)
Typenschild
The pump cannot produce more vacuum. Vacuum remaining in the moni-
tored space and the measuring line is consumed by the entry of more
liquid.
When the alarm threshold is obtained, visual and audible alarms are trig-
gered. Vacuum remaining when alarm is triggered is sufficient to prevent
the entry of stored medium in the environment.
2.6.4 The electronic vacuum leakage indicator
Vacuum leakage indicator for monitoring double wall tanks. The leakage
indicator establishes and maintains vacuum in the monitored space of
the double wall tank. If a gas leak occurs, air or fumes is taken in the
monitored space and causes a vacuum drop.
Minor leaks are compensated by starting the pump. Major leaks cannot
be compensated by the pump because the pump capacity is insufficient
for this. In this case, vacuum will be reduced further. When the vacuum
alarm threshold is obtained, visual and audible alarms are triggered.
If a liquid leakage occurs, stored medium or ground water will be taken
in the monitored space. Vacuum drops and the pump starts working to
restore the operating vacuum level.
After some time, stored medium or ground water will be taken in the
monitored space. The liquid barrier closes and separates the pump from
the monitored space.
The leakage indicator operates on 230 V, 50Hz
mains voltage. This voltage can cause extreme-
ly severe burn injuries. Contact with this voltage
can be fatal. Disconnect the supply voltage before
you open the leakage indicator or starting main-
tenance or repair work (switch off the fuse!).

15Krampitz Tanksystem GmbH - Operation and Installation Instructions TTD for Tank System - Issue 04/2011
Any tank that is intended for storing Diesel fuel or fuel oil and which has with the tank truck connection, except above-ground tanks containing not more
than 1,000 liters, which are filled by manual nozzle without permanently installed piping, must have an overfill guard which stops the filling procedure in
time when the permitted level is obtained or triggers an audible alarm.Tanks containing more than 1,000 liters and intended for storing Diesel fuel or fuel
oil, which are filled from road tank trucks or top-mounted tanks, must be equipped with a limit sensor which functions as safety device on tank trucks or
top-mounted tanks (also refer to TRbF 20 Article 9.3). Tanks for storage of other potentially water-contaminating liquids and flammable substances, e.g.,
mineral oil, which are filled automatically, must be equipped with an approved overfill guard.The overfill guard should not be used as switching point for
actuating the replenishing device in normal operation.
NOTE The overfill guard must be approved for the storage medium.
NOTE Tanks must not be filled higher than the permitted maximum filling level.The permitted filling level depends on the medium
(coefficient of cubic expansion; also refer to TRbF 20) and is limited to 95 % of the tank height of the TTD.
The limit sensor is a device which in coo-
peration with the safety device (evaluation
logic) on tank trucks prevents overfilling of
permanently installed tanks. Permanently in-
stalled tanks for storage of Diesel fuel or fuel
oil which are filled from tank trucks must have a limit sensor. Exception:
Tanks smaller than 1,000 liters filled by manual nozzle without perma-
nently installed pipe. The limit sensor should be adapted to the highest
permitted filling level of the tank. (Also refer to limit sensor installation
instructions).
2.6.6.1 The limit sensor (GWG) with PTC thermistor -
only for Diesel fuel and fuel oil
Screw-in body with connec-
ting housing ¾“
Adapter 2“ - ¾“
PTC thermistor inside
2.6.6.2 The overfill guard with evaluation logic
The PTC termistor based level sensor of the approved overfill guard is in-
stalled in a 2” sleeve in the tank roof by means of a 2´´ x ¾´´ adapter (refer
to adapter). An approved overfill guard is required in any case if the tank
is filled by electric pump and permanently installed pipeline. The overfill
guard should be adapted to the highest permitted filling level of the tank.
(Refer to overfill guard installation instructions).
Electrical housing
screw-in body with
¾” locking screw
screw-in adapter 2´´ x ¾´´
PTC thermistor element, inside
Evaluation logic
2.6.5 The oil warning sensor with alarm
and evaluation unit
opto-electronic
sensor
Evaluation logic
green operating lamp
check button
red alarm lamp
reset button
yellow control lamp
no function
Ölmelder
Prüftaste
Betrieb
Alarm
Quittieren
Sonde 1-2-3-4-5
Olmelder OM5
für 5 Sonden
230V, 50Hz, 5VA
The oil alarm sensor detects the different optical behavior of air and liquids.
It is placed at the lowest point of the monitored space. The integrated signal module
provides constant monitoring of the electric output signal of the sensor. When the system
is ready, the green lamp lights. If the sensor is exposed to air, the signal module sends
a go ahead signal: The green operating lamp lights, the red alarm lamp is off, the relay
drops out. When the sensor is immersed in oil, the signal module signals a leak (alarm):
The red alarm lamp and the audible alarm are triggered, the relay picks up. The audible
alarm can be muted by pressing the “Rest” button. Pressing the button activates the
audible alarm again.
If several sensors are connected to one evaluation logic, the sensors can be closed by
the number of blinking pulses of the yellow indicator lamp. The frequency of the blinking
pulses is about three seconds. No alarm is triggered if mains power fails. The device is
ready when mains power is restored. Any leak occurring during power outage will be in-
dicated. The green operating lamp shines as soon as the oil alarm is supplied with mains
voltage. The function of the alarm function can be simulated with the check button.
The oil alarm is an approved leakage warning device. It is installed in the sump space
of the day tank. Up to 5 sensors can be connected to one evaluation logic. The oil alarm
quickly detects leaks of substances dangerous to water according to VAwS. If a sensor
is immersed in liquid, the signal module identifies the change of the sensor signal and
triggers a visible and an audible alarm and also operates the relay for the output unit.
The oil alarm consists of a signal module and up to five sensors.The signal module and the sensors are connected with each other by a 3-wire signal cable
of up to 10 meters length. The oil alarm sensor consists of an infrared transmitter and an infrared receiver attached at a certain distance to each other.
Both parts together form an optical barrier. If air is between the transmitter and the receiver, most of the infrared radiation emitted by the transmitter is
received. The system operates on the optical coupler principle. The signal module contains an impact resistant plastic housing indicators and controls as
well as the required electronic components for evaluating and converting the sensor signal into a digital output signal. The output signal is available as
floating relay contact (changeover contact).
2.6.5.2 Configuration of the oil alarm
2.6.6 The overfill guards
2.6.5.1 Function of the oil alarm

16Krampitz Tanksystem GmbH - Operation and Installation Instructions TTD for Tank System - Issue 04/2011
2.6.7.1 Further pumps from the product range of Krampitz Tanksystem GmbH
hand wing pump
from 20 litres/min
to 100 litres/min
Example: 20 litres/min
W2 U2 V2 U2 V2
V1 W1
U1 V1 W1
U1
PE
L3(T)L2(S)
L1(R)
W2
PE
L3(T)
L2(S)
L1(R)
CB
PE
L1 N
Connection schemes for electropumps
electrical centrifugal pump
from 45 litres/min
to 1,000 litres/min
Example: 80 litres/min
gear pump
from 6 litres/min
to 200 litres/min
Example: 200 litres/min
block pump unit
from 6 litres/min
to 26 litres/min
Example: 26 litres/min
Gerotor pump
from 6 litres/min
to 26 litres/min
Example: 26 litres/min
Connection scheme 400 V
Rotary current
(three-phase)
Star connection
Connection scheme 400 V
Rotary current
(three-phase)
Delta connection
Connection scheme 230 V/AC
Alternating current (single-phase)
CB operating capacitor
(internally connected to motor,
no internal bridge required!)
2.6.9 The wall brackets
The wall brackets will be installed at the two boreholes in the front wall
area.The tank with the wall brackets will then be positioned on the wall to
which it is to be fixed and installed with the relevant dowels.
NOTE Due to the static requirements
concerning the wall of the building, the
use of wall brackets will only make sense
for tanks up to the TTE 990 series.
tank type TTD 250 TTD 500 TTD 750 TTD 990
Wall brackets type WK 2 WK 3
weight/pair 12 kg 18 kg
Power Tank volume Voltage
220 W up to 2,000 litres 230 V, 50 Hz
NOTE Not permitted/approved
for liquids with a flash point
< 55°
2.6.8 Tank heater
The use of a tank heater with
integrated thermostat between
8°C bis 12°C
and thermal limiter reliably pre-
vents the separation of paraffin
fractions of
light heating oil and diesel at
low temperatures. In this man-
ner, the pump
and nozzle viscosity of the oil
and diesel in the suction area is
maintained.
Tank heater up to 1,500 W / up to 8,000 litres
Adaptor G2‘‘ with
cable gland
Cable
Housing containing
integrated regulator
Heating element
2.6.7 The Pump Combination
The pump combination uses the KTD storage tank to supply remote dai-
ly tanks. The pump combination contains an electrical pump and a hand
wing pump in one case. In the event of a failure or defect of the electrical
pump, the hand pump ensures that the system can be operated without
interruption. It also serves the ventilation of the suction pipe (for further
details see the operating instructions for the pump combination).
hand wing pump
electrical pump
pressure connection
suction connection
2.6.6.3. Overview: Possible switching points and control
instructions
Symbol Designa-
tion
Filling
level
in percent
Level sensor type Control
command
max-max 95
limiting-value
transmitter/
overfill protectio-
nin case of export
application:
mini detector
over-fill
alarm
pump off
max 70 mini detector operating contact:
pump off
min 40 mini detector
operating contact:
pump on and
signal indicating
the repeat order
of fuel
min-min 10 mini detector Mangel-Alarm:
Maschine aus

17
2.6.10 The supporting column
The vertical column is made up of two columns in double T-shape that are manufac-
tured from square tube dimensioned 100 x 100 x 3 mm. These columns will be
bolted with four nuts each to a cross-member at two head plates. The collecting pan
or the daily storage tank will then be lifted onto this vertical column, placed on
the relevant welding bolts and fi xed with four M10 nuts and non-detachable was-
hers. The openings of the square tubes will then be sealed with the lids that are
included in the delivery.
tank type TTD 250 TTD 500 TTD 750 TTD 990 TTD 1500 TTD 1950
height vertical
column vertical column type and weight
500 mm ST 2/5 ST 3/5 ST 3/5 ST 4/5 ST 5/5 ST 6/5
1000 mm ST 2/10 ST 3/10 ST 3/10 ST 4/10 ST 5/10 ST 6/10
1500 mm ST 2/15 ST 3/15 ST 3/15 ST 4/15 ST 5/15 ST 6/15
2.6.11 The Krampitz special nut with captive washer
For quick and safe installation, the Krampitz Tanksystems come with spe-
cial bolts. Unlike conventional fasteners is in the Krampitz special bolt
washer connected with the captive nut. So quickly and a permanent con-
nection can be established.
2.6.12 The feet
tank type TTE 250 TTE 500 TTE 750 TTE 990 TTE 1500 TTE 1950
foot type FS 1 FS 2 FS 3 FS 4
weight/pair 9 kg 14 kg 16 kg 18 kg
The feet consist of a pair of square steel tubes dimensioned 100 x 100 x 3
mm. They are equipped with M10 welding bolts and M10 nuts with non-
detachable washers. The daily storage tank or the collecting pan can be
put up on the ground in the most optimal way with their help.
3.1 Transport of the TTD
The KTD can be easily transported by fork lift or hand lift.
During transport, the relevant, currently valid safety regula-
tions must be observed and damages must be avoided.
In the event that the colour coat is damaged, corrosion
protection must be properly restored.
CAUTION
3. START-UP
The permit system for mounting the tank wall at a building site must be
obtained. The static strength of the wall (at least B15) must be proven
before installation. The day tank can be mounted by using two anchor
wall brackets with four corresponding types of fasteners. The wall bracket
(pos. 2) will be at the rear holes of the front walls (pos. 1) mounted with
the tank bolts M 10 (pos. 3).
After the day tank means including wall bracket with hoist on the wall is
positioned. Now it’s possible to drill holes in the wall, then can be the wall
anchor (corresponding to manual) fixed. Now, the day tank with the wall
brackets on the wall or be attached to the wall anchor.
3.2 Wall mounting of the TTD
2
31
2
13
Krampitz Tanksystem GmbH - Operation and Installation Instructions TTD for Tank System - Issue 04/2011

18Krampitz Tanksystem GmbH - Operation and Installation Instructions TTD for Tank System - Issue 04/2011
CAUTION The lifting of the tanks is to follow safety rules for appropriate and valid. There is danger of injury and damage to components.
CAUTION Rollover risk in cases of excessive movement by moving the construction.
3.4 First start-up
Before filling the TTD for the first time, check that::
1. the tank is properly fastened and placed
2. the pipe connections are leak-tight and properly connected
3. the sensors are properly connected, such as the
a. level sensor b. over-fill protection
c. oil warning probe (oil detector) d. limiting-value transmitter
4. the blind plugs are tightly connected
3.5 Operation sequence
• Check the position of the ball valves. The ball valves at the system flow connection must be closed.
• Apply voltage. The voltage puts the sensors into operation.
• Bei Betankung mit anlageneigener Pumpe Stellung der Pumpenkugelhähne überprüfen.
CAUTION The over-fill protection triggers an alarm during the first seconds because the PTC thermistor of the level sensor
must heat up first.
• Fillings by tank lorry:
1. When the filling level rises, the switching of the level switch points can be checked (if applicable, these are: MIN-MIN, MIN, MAX, MAX-MAX).
2. As soon as the limiting-value transmitter is wet, the filling is automatically interrupted. The filling via filling connection with a tank lorry is mandatory
for storage tanks with a capacity of more than 1,000 litres. Smaller daily tanks can be filled with the petrol pump nozzle with a dead man‘s switch
which automatically shuts off fuel delivery
• Fillings by system pump:
1. When the filling level rises, the switching of the level switch points can be checked (if applicable, these are: MIN-MIN, MIN, MAX, MAX-MAX).
2. As soon as the installed over-fill protection is wet, the pump must be automatically switched off
• check pipe connections for leak-tightness
• filling level per level indicator to check again
• if necessary, open the ball valves at the system flow connection
• The TTD is now ready to use
3.3 Setting up the TTD on feet / supporting
The KTD must only be placed on even and load-bearing floor space (minimum quality B 15 or equal). A stress analysis must be performed and presented.
Generally, storage tanks up to a maximum storage volume of 5,000 litres can be operated in a machine room.
The day tank can be positioned exactly over the injection pump of a motor with the stand column. For this will be the foots of the stand column connected
wit the head plate of the sub-carrier (bolts M 10).
TTD-500 double wall daily storage tank
with wall brackets
TTD-500 double wall daily storage tank
with vertical column
TTD-500 double wall daily storage tank
with feet

19
The TTD double wall daily storage tank are delivered with the documents below:
inspection sheet in German language (two copies)•
drawing (one copies)•
building authority permit Z-38.12-23 (one copies)•
operating instructions for the individual module components, such as level sensor, over-fill protection, pump combination•
The permit book contains with National Technical Approval Z-65.22-158 leak indicator with the indication “KÜR 5” without vacuum generator for•
the control room of double-wall tanks for the storage of liquids hazardous to water (two copies)
These documents are sent to the customer by mail. Only the delivery note is delivered together with the tank to avoid that important documents get lost
at the construction site
The permit book contains an inspection table for the respective tank. This inspection table holds the tank dimensions, the tank type, the date of the first
inspection as well as further inspection dates. The person conducting the further inspections can sign in the book to acknowledge the inspections.
4. DOCUMENTS
§1 Scope of warranty
(1) The warranty covers system defects throughout the warranty period which occur during proper operation and use of the system and circuitry and
which don‘t result from external causes of any kind, mechanical damages or non-compliance of regulations regarding the use of the system or circuitry.
(2) In addition, the warranty doesn‘t cover damages resulting from improper maintenance and repair work.
§2 Warranty Period
The warranty period begins when the system is taken into operation on-site. Any warranty claims made within the warranty period are reviewed.This
only applies to the tank system. The warranty period is 24 months.
For fittings and devices (mechanical, electromechanical, electrical and electronic), supplied by external manufacturers, the warranty period is 6 months.
§3 Handling
(1) In the event that defects occur during the warranty period, warranty claims must be made immediately, at the latest within two weeks, in writing.
(2) Only Krampitz Tanksystem GmbH is authorised to accept warranty claims.
§ 4 Warranty Exclusion
Warranty claims cannot be considered:
a. if the damage to – or destruction of – the installation, circuitry, or parts of such, has been caused by an act of nature or by the consequences of
operation of the installation in a manner not intended, in particular by external mechanical or chemical factors;
b. if damage has occurred as a result of improper handling, particularly non-compliance with the operating instructions provided.
c. if the circuitry, or parts of such, have not been repaired or serviced by legitimate representatives, employees or agents of Krampitz Tanksystem GmbH.
d. if the circuitry, or parts of such, exhibit mechanical damage of any kind.
§5 Supplementary regulations
(1) In the event of a warranty claim, the foregoing provisions regulate the legal relationship with respect to us in a fi nal and conclusive manner.
Any further claims, in particular those concerning damage or loss, of whatever nature, arising from the installation, circuitry, parts of the circuitry or
by operation of such, are excluded.
(2) The burden of proof for the proper installation and operation of the facility, circuitry or parts of such, in accordance with the operating instructions
provided, rests with the purchaser.
(3) Place of performance, applicable law, venue of jurisdiction
Place of performance for the delivery is the destination, for payment the place of the customer. Supplementary to the purchasing conditions, German
law is applicable. The applicability of the UN law on sale of goods, however, is excluded.
The sole venue of jurisdiction for all disputes arising directly or indirectly from the contractual relationship – provided that the contractor is a
registered trader – is Lüneburg.
If the contractor is not a registered trader, then Lüneburg is the venue of jurisdiction for claims for summary proceedings for collection procedure
(Mahnverfahren). Should any of the individual provisions of the contract be – or become – void, the validity of the
remaining parts of these conditions shall not be affected.
5. WARRANTY
Krampitz Tanksystem GmbH - Bedienungs- und Montageanleitung - TTD Tagestanksystem - Ausgabe 04/2011

Krampitz Tanksystem GmbH
Headquarters:
Dannenberger Str. 15
21368 Dahlenburg/Lbg.
Germany
Tel.: +49(0)5851/9443-0
Fax: +49(0)5851/9443-21
Office:
Siedlung des Friedens 40
29410 Hansestadt Salzwedel
Germany
Tel.: +49(0)3901/3088-100
Fax.:+49(0)3901/3088-131
Henningen plant:
Henningen 78
29410 Salzwedel/OT Henningen
Germany
Tel.: +49(0)39038/9078-0
Fax: +49(0)39038/9078-10
Internet: www.krampitz.de
Email: [email protected]
This manual suits for next models
6
Table of contents