LAPP ETHERLINE ACCESS U04TP01T Assembly instructions

ETHERLINE ACCESS U04TP01T
Hardware Installation Manual
Disclaimer: U.I. Lapp GmbH tries to keep the content of this manual as accurate and as
updated as possible. This document is not guaranteed to be error-free, and we reserve the
right to amend it without notice to users.
Copyright © U.I. Lapp GmbH 2019. All rights reserved.
No part of this documentation may be excerpted, reproduced, translated, annotated or
duplicated, in any form or by any means without the prior written permission of U.I. Lapp
GmbH.

Notice for Safety Operation
The product performs reliably as long as it is used according to the guidance. Artificial
damage or destruction of the device should be avoided. Before using the device, read this
notice carefully for personal and equipment safety. Please keep the manual for further
reference. If the equipment is used in a manner not specified in this manual, the protection
provided by the equipment may be impaired. LAPP is not liable to any personal or equipment
damage caused by violation of this notice.
Do not place the device near water sources or damp areas. Keep the ambient relative
humidity within the range from 5% to 95% (non-condensing).
Do not place the device in an environment with high magnetic field, strong shock, or high
temperature. Keep the working and storage temperatures within the allowed range.
Install and place the device securely and firmly.
Please keep the device clean; if necessary, wipe it with a soft cotton cloth.
Do not place any irrelevant materials on the device or cables. Ensure adequate heat
dissipation and tidy cable layout without knots.
Wear antistatic gloves or take other protective measures when operating the device.
Avoid any exposed metal wires because they may be oxidized or electrified.
Install the device in accordance with related national and local regulations.
Before power-on, make sure the power supply is within the allowed range of the device.
High voltage may damage the device.
Power connectors and other connectors should be firmly interconnected.
Do not plug in or out the power supply with wet hands. When the device is powered on,
do not touch the device or any parts with wet hands.
Before operating a device connected to a power cable, remove all jewelry (such as rings,
bracelets, watches, and necklaces) or any other metal objects, because they may cause
electric shock or burns.
Do not operate the device or connect or disconnect cables during an electrical storm.
Use compatible connectors and cables. If you are not sure, contact our sales or technical

support personnel for confirmation.
Do not disassemble the device by yourself. When an anomaly occurs, contact our sales
or technical support personnel.
If any part is lost, contact our sales or technical support personnel to purchase the
substitute. Do not purchase parts from other channels.
Dispose of the device in accordance with relevant national provisions, preventing
environmental pollution.
In the following cases, please immediately shut down your power supply and contact your
LAPP representative:
Water gets into the equipment.
Equipment damage or shell damage.
Equipment operation or performance has abnormally changed.
The equipment emits odor, smoke or abnormal noise.

Contents
1 Product Overview...............................................................................................................1
2 Structure and Interface.......................................................................................................2
2.1 Front Panel ..................................................................................................................2
2.2 Top Panel.....................................................................................................................3
3 Mounting.............................................................................................................................3
3.1 Dimension Drawing......................................................................................................3
3.2 Mounting......................................................................................................................4
3.2.1 DIN-Rail Mounting.................................................................................................4
3.2.2 DIN-Rail Dismounting............................................................................................5
4 Connection .........................................................................................................................6
4.1 10/100Base-T(X) Ethernet Port....................................................................................6
4.2 Grounding....................................................................................................................8
4.3 Power Terminal Block..................................................................................................8
4.4 DIP Switches................................................................................................................9
5 LEDs.................................................................................................................................10
6 Basic Features and Specifications....................................................................................11

1
1 Product Overview
The ETHERLINE ACCESS U04TP01T entry-level unmanaged POE industrial Ethernet
switch is equipped with one 10/100Base-T(X) Ethernet port and four 10/100Base-T(X) PoE
ports compliant with IEEE802.3at/af. While transmitting data over the cable, PoE port can
output up to 30 watts to PoE terminals directly, eliminating the need of additional wiring.
The ETHERLINE ACCESS U04TP01T supports wide operating temperature range of -40℃
to 75℃, IP30 rated metal housing and 24VDC dual power inputs, becoming an economical
and harsh-environment-resistant solution for the ITS, video surveillance and other automation
applications.
Note:
This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his
own expense.

2
2 Structure and Interface
2.1 Front Panel
Figure 1 Front Panel
(1) Power 1 LED
(2) Power 2 LED
(3) POE LED
(4) Link/ACT LED of 10/100Base-T(X) PoE Ethernet port (green)
(5) Speed LED of 10/100Base-T(X) PoE Ethernet port (yellow)
(6) Link/ACT LED of 10/100Base-T(X) Ethernet port (green)
(7) Speed LED of 10/100Base-T(X) Ethernet port (yellow)
(8) 10/100Base-T(X) PoE Ethernet port
(9) 10/100Base-T(X) Ethernet port

3
2.2 Top Panel
Figure 2 Top Panel
3 Mounting
3.1 Dimension Drawing
Figure 3 ETHERLINE ACCESS U04TP01T Dimensions (unit: mm)

4
Caution:
As part of the heat dissipation system, the housing of the switch becomes hot while working.
Please do not touch or cover the housing while the switch is working.
3.2 Mounting
The device supports DIN-rail mounting.
Mounting Environment:
1) The temperature, humidity and power supply is within the allowable range.
2) No direct sunlight, distant from heat source and areas without strong electromagnetic
interference.
3) The switches are open type equipment for indoor use.
4) The switches are intended for use in a Pollution Degree 2 industrial environment
5) The switches are recommended to be mounted in an enclosure that provides a minimum
protection rating of IP54.
Note:
Devices should be installed and accessed by service personnel or users who have been
instructed about the reasons for the restrictions applied to the location and about any precautions
that shall be taken.
3.2.1 DIN-Rail Mounting
Step 1: Select the mounting position for the device and guarantee adequate space and heat
dissipation.
Step 2: Insert the connecting seat onto the top of the DIN rail, and push the bottom of the
device inward and upward to ensure the DIN rail fits in the connecting seat. Make
sure the device is firmly installed on the DIN rail, as shown in the following figure.

5
Figure 4 DIN-Rail Mounting
3.2.2 DIN-Rail Dismounting
Step 1: As shown in the following figure, press the device downward and move the device in
direction 1 until the bottom of the device is detached from the DIN rail.
Step 2: Pull the device upward and move the device in direction 2 until the device is removed
from the DIN rail completely.
Figure 5 DIN Rail Dismounting
Caution:
Cut off the power and disconnect all cables before mounting, dismounting or moving the
equipment.

6
4 Connection
4.1 10/100Base-T(X) Ethernet Port
Data Transmission
10/100Base-T(X) Ethernet port is equipped with RJ45 connector. The port is self-adaptive. It
can automatically configure itself to work in 10M or 100M state, full or half duplex mode. The
port can also adapt to MDI or MDI-X connection automatically. You can connect the port to a
terminal or network device with a straight-through or cross-over cable.
Figure 6 RJ45 Port
Table 1 Pin Definitions of 10/100Base-T(X) RJ45 Port
Pin
MDI-X Signal
MDI Signal
1
Receive Data+ (RD+)
Transmit Data+ (TD+)
2
Receive Data- (RD-)
Transmit Data- (TD-)
3
Transmit Data+ (TD+)
Receive Data+ (RD+)
6
Transmit Data- (TD-)
Receive Data- (RD-)
4,5,7,8
Unused
Unused
Note:
+" and "-" indicate level polarities.
PoE Power Supply
The switch can serve as a Power Sourcing Equipment (PSE). While transmitting data over
the cable, the switch can provide power supply to PDs (Powered Device) through Ethernet
Port 2-5. Each POE port can output up to 30 watts, compliant with IEEE802.3af/at.

7
Table 2 Pin Definitions of POE Power Supply
Pin
Power
1
V+
2
V+
3
V-
6
V-
Wiring Sequence
Figure 7 Connection Using Straight-through/Cross-over Cable
Note:
The color of the cable for RJ45 connector meets the 568B standard: 1-orange and white, 2-
orange, 3-green and white, 4-blue, 5-blue and white, 6-green, 7-brown and white, and 8-brown.

8
4.2 Grounding
Grounding protects the device from lightning and interference. Therefore, you must ground
the device properly. You need to ground the switch before it is powered on and disconnect
the grounding cable after the device is powered off.
There is a grounding screw (see Figure 2) on the top panel for chassis grounding. After
crimping one end of the grounding cable to a cold pressed terminal, secure the end of the
grounding cable to the grounding screw and firmly connect the other end to ground.
Note:
Cross-sectional area of the chassis grounding cable>2.5mm2; Grounding resistance<5.
4.3 Power Terminal Block
There is a power terminal block on the top panel of the device. You need to connect the power
wires to the terminal block to provide power for the device. The switch supports redundant
power supply with a 4-pin 5.08mm-spacing plug-in terminal block. When one power input is
faulty, the switch can continue operating properly, thereby improving network reliability.
4-Pin 5.08mm-Spacing Plug-in Terminal Block
Figure 8 4-Pin 5.08mm-Spacing Plug-in Terminal Block (socket)
Table 3 Pin Definitions of 4-Pin 5.08mm-Spacing Plug-in Terminal Block
Pin Number
DC Wiring Definition
1
PWR1: -
2
PWR1: +
3
PWR2: -
4
PWR2: +

9
Wiring and Mounting
Step 1: Ground the device properly according to section 4.2.
Step 2: Remove the power terminal block from the device.
Step 3: Insert the power wires into the power terminal block according to Table 3 and tighten
the wires.
Step 4: Plug the terminal block with the connected wires into the terminal block socket on the
device.
Step 5: Connect the other end of the power cable to an external power supply system within
the allowed power range. If the corresponding power LED on the front panel of the
switch turns on, the power supply is connected properly.
Table 4 Wiring and Mounting Specifications
Terminal Type
Required Torque
Wire Range (AWG)
Terminal Block Plug
4.5-5.0 lb-in
12-24
Warning:
Use copper conductors only.
Do not touch any exposed conducting wire, terminal, or component with a voltage warning
sign, because it may cause personal injury.
Do not remove any part or plug in or out any connector when the device is powered on.
4.4 DIP Switches
There are two DIP switches on the top panel of the device, each switch has ON and OFF
states and the default state is OFF. The function of the DIP switches is shown in the following
table.
Figure 9 DIP Switches

10
Table 5 Description of the DIP Switches
DIP Switches
State
Description
Ⅰ
ON
Enable broadcast storm protection
OFF
Disable broadcast storm protection
Ⅱ
ON
Transmit Jumbo frame (up to 10KB)
OFF
Drop Jumbo frame
5 LEDs
Table 6 LEDs
LED
State
Description
P1 LED
On
Power 1 is connected and operates properly.
Off
Power 1 is not connected or operates abnormally.
P2 LED
On
Power 2 is connected and operates properly.
Off
Power 2 is not connected or operates abnormally.
POE LED
On
POE power output
Off
No POE power output
10/100Base-T(X)
Speed LED (yellow)
On
100M working state (100Base-TX)
Off
10M working state (10Base-T) or no connection
Link/ACT LED (green)
On
Effective port connection
Blinking
Ongoing network activities
Off
No effective port connection

11
6 Basic Features and Specifications
Power Supply
Voltage Range
24VDC (12-36VDC)
Terminal Block
4-Pin 5.08mm-Spacing Plug-in Terminal Block
Rated Power Consumption
and Input Current
Max 5.5W (No PD), Max 0.5A (No PD)
Max 60W PoE output@12VDC, Max 6A
Max 120W PoE output@24VDC, Max 6A
Data Port
Model
10/100Base-T(X) RJ45 Port
10/100Base-T(X) RJ45 POE Port
ETHERLINE ACCESS U04TP01T
1
4
Physical Characteristics
Housing
Metal, fanless
Protection Class
IP30
Installation
DIN-Rail Mounting
Dimensions (W×H×D)
30mm×134mm×106mm
(excluding the connector and DIN-Rail mounting kit)
Weight
0.5Kg
Environmental Limits
Ambient Temperature
-40℃~+75℃
Storage Temperature
-40℃~+85℃
Ambient Relative Humidity
5%~95% (no condensing)
Altitude
2000m
Table of contents