LEAK DEFENSE LDS-3-API User manual

API-Alarm
API-Alarm Panel Interface
The All-Purpose Interface (API) is a device that can wirelessly interface to
various accessories to complement the performance of the LDS system,
reduce nuisance alarms, and improve the customer's experience and
satisfaction with the system. It should be placed within 100' of the
control panel to maximize signal strength. A few of the common
adaptations and applications are described below.
POLD+ if you were to wire up a POLD sensor to the API (and it is
polarized) the Sensor would have its black wire going to GND and its red
wire going to POLD+. When the POLD+ goes to GND level, it trips.
To reset the alarm: First make sure that the sensor is completely dry. Then press
and hold the TEST button on the API for 3 seconds. The LED will go dark until
the button is released and will stay lit until the alarm condition is cleared at the
control panel.
The opto isolators used for HOME/AWAY and STANDBY have non-committed inputs for maximum exibility.
The input voltage is not to exceed 12 volts.
The IN+ would need to go to the positive input potential through a switch or wire.
The IN- would need to go to the negative or GND potential through a switch or wire.
Each opto-isolator has its own IN+ and IN- and they can be wired for high going signals, or GND (low) going signals.
The +REF and -REF signals are used as the voltage references for the optos. +REF usually reads 12VDC, while
-REF is GND.
If (for example) you want the STANDBY to activate when its signal is grounded, then you would wire up the IN+ of
STANDBY to the +REF and the IN- goes through a switch or relay to GND. If connecting to an alarm panel, make sure
that the GND’s are the same potential by connecting its GND to the API GND or -REF pins.
If (for example) you wanted to hook up an Alarm Panel that goes to 12 volts when in AWAY mode. Then wire the Alarm
Panel GND and HOME/AWAY IN- to the API GND or -REF and wire the HOME/AWAY IN+ to the 12 volt AWAY trigger
signal. (HOME mode is when the AWAY mode is not activated.)
Here are the valid MODE SEL combinations:
0 - H/A DIS STBY DIS POLD DIS
1 - H/A ENA STBY DIS POLD DIS
2 - H/A DIS STBY ENA POLD DIS
3 - H/A ENA STBY ENA POLD DIS
4 - H/A DIS STBY DIS POLD ENA
5 - H/A ENA STBY DIS POLD ENA
6 - H/A DIS STBY ENA POLD ENA
7 - H/A ENA STBY ENA POLD ENA
8 - F is presently unused
API-Alarm
API-Alarm Panel Interface (continued)
These settings will selectively create events that the API can generate and transmit to the control panel. DIS means that
function is disabled and the system will ignore any activity on those input lines. ENA means that function will transmit and the
panel will respond to input activity on those lines.
The LED will ash briey during data transmissions and glow solid when the ALARM is active.
The RELAYS both operate together (as of rev 1.00) when an ALARM condition is transmitted. When the panel releases the
ALARM, the RELAYS will deactivate.
ATTENTION: Putting the leak defense system in standby means water owing into the home is NOT monitored.
A leak will go undetected in standby mode.
DIAL POSITIONS:
F: Triggers on Water Off command (alarm or user requested).
Ideal for connecting to circ pump switches and solid state relays
7: Triggers on Alarm Only
Ideal for connecting to alarm panels
API Installations
FOR TECHNICAL SUPPORT: Please call our ofce at 1.866.410.1134 – 9:00am to 5:00pm Pacic Time
SEE FIGURE 2 DIAGRAM
Connecting a Four-Hour Timer to the LDS API
This accessory is typically installed outdoors for a gardener or landscaper to remotely and manually put the LDS in
standby (ignore water ow) mode for the length of time the timer is rotated to.
• Connect the red wire from the timer to IN- (below STANDBY) on the API.
• Connect the black wire from the timer to –REF on the API.
• Place a jumper from IN+ (below STANDBY) to +REF.
• The yellow arrow dial on the API should face 2.
• When the timer is activated you should see the Leak Defense control panel switch from Home or Away to
Standby. When the timer runs out, the Leak Defense should go back to the original state of Home or Away.
NOTE: This applies a 12-volt signal across the terminals IN- and IN+ (below standby), when the timer is active.
API Installations
FOR TECHNICAL SUPPORT: Please call our ofce at 1.866.410.1134 – 9:00am to 5:00pm Pacic Time
LDS-3 Connecting POL and SS relays to API
This application is typical for when a 240VAC (up to 50amp) well pump or pressure pump is wanting to be disconnected
when a leak is detected with a POL or when the LDS valve closes upon suspected water leak.
For terminals 1 and 2 of solid-state relay #1, break a hot leg of the well pump wire and connect one side of the broken wire
to terminal 1 and the other to terminal 2. For terminals 1 and 2 of solid-state relay #2, break the other hot leg of the well
pump wire and connect one side of the split wire to terminal 1 and the other to terminal 2.
On the API place a jumper between +REF and NO on either of the API relays.
Wire the solid-state relay input terminals in series as follows.
Take COM of the same API relay and run a wire to terminal 3 of solid-state relay #1. Then take terminal 4 of solid-state relay
#1 and connect it to 3 of solid-state relay #2, with a jumper wire. Then take terminal 4 of solid-state relay #2 and run a wire
back to –REF on the API.
The POLD and GND terminals of the API get connected to the two wires of the POL sensor. No connection necessary for
wireless POLD sensor.
NOTE 1: The yellow arrow dial, located toward the center of the API circuit board, needs to be
facing 4 to enable the POL sensor.
NOTE 2: To test the POL sensor, take a moist paper towel and touch the 2 metal screws. The
Leak Defense System will go into alarm and the solid-state relays should turn off the well pump.
Push the reset button on the API before pressing reset on the Leak Defense control panel.
NOTE 3: When alarm is active, a 6-volt signal is being applied across each of the solid-state
relay’s terminal 3 and 4, from the API. Which causes the normally-closed solid-state relay to
open and shut off the pump.
SEE FIGURE 3 DIAGRAM
API Installations
FOR TECHNICAL SUPPORT: Please call our ofce at 1.866.410.1134 – 9:00am to 5:00pm Pacic Time
Recirculation Pump Switch to API
This wiring application is typical when a customer desires their hot-water recirculation pump to shut off during a leak, so the
pump doesn't continue to push water making the leak worse, or alternatively to save the pump from burn out due to
pumping with no water in the system.
On the API, place the provided jumper wire between +REF and the NO terminal of one of the relays on the API. Connect the
red wire from the recirculation pump switch to COM of the same API relay. Finally, connect the black wire from the
recirculation pump switch to -REF or GND on the API.
NOTE 1: This applies a 12-volt signal to the switch inside the recirculation pump switch, to open
a normally-closed switch, shutting off power to the recirculation pump.
SEE FIGURE 5 DIAGRAM
API Installations
Wiring Instructions for a PAM-1 Relay
(Irrigation Control Interface Wiring)
• Connect the blue wire from the PAM-1 to IN- (below STANDBY)
on the API.
• Connect the orange wire from the PAM-1 to –REF on the API.
• Place a jumper wire from IN+ (below STANDBY) to +REF on the API.
• Connect the red wire from the PAM-1 to the MV/P (master valve/
pump) terminal on the irrigation controller.
• Connect the white wire from the PAM-1 to COM on the irrigation
controller.
• The yellow arrow dial on the API should face 2.
• When irrigation starts, you should see the Leak Defense System
control panel switch from Home or Away to Standby. When irrigation
stops, the Leak Defense System should go back to Home or Away.
NOTE: This applies a 12-volt signal across the IN- and IN+ (below STANDBY) terminals on the
API, while the irrigation system is running. You may be able to start irrigation manually to test
that this connection is functioning properly.
FOR TECHNICAL SUPPORT: Please call our ofce at 1.866.410.1134 – 9:00am to 5:00pm Pacic Time
SEE FIGURE 6 DIAGRAM
FOR TECHNICAL SUPPORT: Please call our ofce at 1.866.410.1134 – 8:00am to 5:00pm Pacic Time
Figure 2
Connecting a
Four-Hour Timer
to the LDS API
FOR TECHNICAL SUPPORT: Please call our ofce at 1.866.410.1134 – 8:00am to 5:00pm Pacic Time
Figure 3
Connecting
SS Relays to API
Figure 4
Connecting
External Sensors
to API
FOR TECHNICAL SUPPORT: Please call our ofce at 1.866.410.1134 – 8:00am to 5:00pm Pacic Time
Figure 5
Connecting a
Recirculation Pump
Switch to API
FOR TECHNICAL SUPPORT: Please call our ofce at 1.866.410.1134 – 8:00am to 5:00pm Pacic Time
Figure 6
Wiring Instructions for
a PAM-1 Relay
FOR TECHNICAL SUPPORT: Please call our ofce at 1.866.410.1134 – 8:00am to 5:00pm Pacic Time
Figure 7
Zone Loops from
Security System to API
S E C U R I T Y PA N E L I / O
P O W E R S TA N D B Y H O M E / A W AY
POLD GND V+ I N - IN+ -REF IN- I N + + R E F N CC O MN O N O C O M N C
A L A R M A L A R M
R E L AY
#2
R E L AY
#1
9-12VDC
5.5 x 2.1mm
L E D
T E S T P B
Here a r e the v a l i d M OD E SEL combinatio n s :
0 - H / A D I S , S T B Y D I S , P O L D D I S
1 - H / A E N A , S T B Y D I S , P O L D D I S
2 - H / A D I S , S T B Y E N A , P O L D D I S
3 - H / A E N A , S T B Y E N A , P O L D D I S
4 - H / A D I S , S T B Y D I S , P O L D E N A
5 - H / A E N A , S T B Y D I S , P O L D E N A
6 - H / A D I S , S T B Y E N A , P O L D E N A
7 - H / A E N A , S T B Y E N A , P O L D E N A
M O D E S E L
N O R M A L LY
O P E N Z O N E
L O O P
N O R M A L LY
C L O S E D
Z O N E L O O P
( D R Y C O N T A C T I N P U T S )
N E G AT I V E
1 2 V D C
T R I G G E R
-12V G N D
P O S I T I V E
1 2 V D C
T R I G G E R
G N D +12V
N C - R E L AY I N
H O M E M O D E
N C N OC O M
FOR TECHNICAL SUPPORT: Please call our ofce at 1.866.410.1134 – 8:00am to 5:00pm Pacic Time
Figure 8
Relay trigger from
Security System to API
SECURITY PANEL I/O
POWER STANDBY HOME/AWAY
POLD GND V+ IN- IN+ -REF IN- IN+ +REF NCCOMNO NO COM NC
ALARM ALARM
RELAY
#2
RELAY
#1
9-12VDC
5.5 x2.1mm
LED
TEST PB
Here are the valid MODE SEL combinations:
0 - H/A DIS, STBY DIS, POLD DIS
1 - H/A ENA, STBY DIS, POLD DIS
2 - H/A DIS, STBY ENA, POLD DIS
3 - H/A ENA, STBY ENA, POLD DIS
4 - H/A DIS, STBY DIS, POLD ENA
5 - H/A ENA, STBY DIS, POLD ENA
6 - H/A DIS, STBY ENA, POLD ENA
7 - H/A ENA, STBY ENA, POLD ENA
MODE SEL
NORMALLY
OPENZONE
LOOP
NORMALLY
CLOSED
ZONE LOOP
(DRY CONTACT INPUTS)
NEGATIVE
12VDC
TRIGGER
-12V GND
POSITIVE
12VDC
TRIGGER
GND +12V
NC-RELAY IN
HOME MODE
NC COM NO
JUMPER
FOR TECHNICAL SUPPORT: Please call our ofce at 1.866.410.1134 – 8:00am to 5:00pm Pacic Time
Figure 9
Positive trigger from
Security System to API
SECURITY PANEL I/O
POWER STANDBY HOME/AWAY
POLD GND V+ IN- IN+ -REF IN- IN+ +REF NCCOMNO NO COM NC
ALARM ALARM
RELAY
#2
RELAY
#1
9-12VDC
5.5 x2.1mm
LED
TEST PB
Here are the valid MODE SEL combinations:
0 - H/A DIS, STBY DIS, POLD DIS
1 - H/A ENA, STBY DIS, POLD DIS
2 - H/A DIS, STBY ENA, POLD DIS
3 - H/A ENA, STBY ENA, POLD DIS
4 - H/A DIS, STBY DIS, POLD ENA
5 - H/A ENA, STBY DIS, POLD ENA
6 - H/A DIS, STBY ENA, POLD ENA
7 - H/A ENA, STBY ENA, POLD ENA
MODE SEL
NORMALLY
OPENZONE
LOOP
NORMALLY
CLOSED
ZONE LOOP
(DRY CONTACT INPUTS)
NEGATIVE
12VDC
TRIGGER
-12V GND
POSITIVE
12VDC
TRIGGER
GND +12V
B R
JUMPER
NC-RELAY IN
HOME MODE
NC COM NO
RB
FOR TECHNICAL SUPPORT: Please call our ofce at 1.866.410.1134 – 8:00am to 5:00pm Pacic Time
Figure 10
Negative Trigger from
Security System to API
SECURITY PANEL I/O
POWER STANDBY HOME/AWAY
POLD GND V+ IN- IN+ -REF IN- IN+ +REF NCCOMNO NO COM NC
ALARM ALARM
RELAY
#2
RELAY
#1
9-12VDC
5.5 x2.1mm
LED
TEST PB
Here are the valid MODE SEL combinations:
0 - H/A DIS, STBY DIS, POLD DIS
1 - H/A ENA, STBY DIS, POLD DIS
2 - H/A DIS, STBY ENA, POLD DIS
3 - H/A ENA, STBY ENA, POLD DIS
4 - H/A DIS, STBY DIS, POLD ENA
5 - H/A ENA, STBY DIS, POLD ENA
6 - H/A DIS, STBY ENA, POLD ENA
7 - H/A ENA, STBY ENA, POLD ENA
MODE SEL
NORMALLY
OPENZONE
LOOP
NORMALLY
CLOSED
ZONE LOOP
(DRY CONTACT INPUTS)
NEGATIVE
12VDC
TRIGGER
-12V GND
POSITIVE
12VDC
TRIGGER
GND +12V
B
R
R
B
JUMPER
NC-RELAY IN
HOME MODE
NC COM NO

Popular Security System manuals by other brands

WatchOvers WG13 user manual

WatchOvers

WatchOvers WG13 user manual

ELT GsmAlarm-420 manual

ELT

ELT GsmAlarm-420 manual

GJD mini Opal Installation and setup guide

GJD

GJD mini Opal Installation and setup guide

Honeywell MAXPRO MPIP2000U Series Installation and setup guide

Honeywell

Honeywell MAXPRO MPIP2000U Series Installation and setup guide

Ingics iBS08 user guide

Ingics

Ingics iBS08 user guide

Federal Signal Corporation G-LED Series manual

Federal Signal Corporation

Federal Signal Corporation G-LED Series manual

Z Microsystems Surveillance Video System brochure

Z Microsystems

Z Microsystems Surveillance Video System brochure

logika WL-ZSPCNPW-AL-02 product manual

logika

logika WL-ZSPCNPW-AL-02 product manual

Honeywell Home TUXEDOW Quick installation guide

Honeywell Home

Honeywell Home TUXEDOW Quick installation guide

Directed Electronics Automate AM5 owner's guide

Directed Electronics

Directed Electronics Automate AM5 owner's guide

DSC neo HS2016 user manual

DSC

DSC neo HS2016 user manual

Westar WSS55010 installation manual

Westar

Westar WSS55010 installation manual

EVERSPRING EVR_SE812 quick start

EVERSPRING

EVERSPRING EVR_SE812 quick start

Johnson Controls Qolsys IQ Remote PowerG user guide

Johnson Controls

Johnson Controls Qolsys IQ Remote PowerG user guide

DSC Power832 Program Update Procedure

DSC

DSC Power832 Program Update Procedure

Swann PLATINUM HD instruction manual

Swann

Swann PLATINUM HD instruction manual

Uniden Guardian UDRC57 user manual

Uniden

Uniden Guardian UDRC57 user manual

Satel SILVER quick start guide

Satel

Satel SILVER quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.