Lebow Products Inc. 7558 User manual

1
GENERAL DESCRIPTION
The Model 7558 (Strain Gage Input Meter) offers many features and
performance capabilities to suit a wide range of industrial applications. The 4½
digit meter employs advanced technology for stable, drift free readout, while
incorporating features that provide flexibility now and in the future with Plug-
in option cards. The plug-in card options allow the opportunity to configure the
meter for present applications, while providing easy upgrades for future needs.
The Strain Gage meter has two bipolar mV input ranges: 24 mV DC or
240 mV DC. The internal bridge excitation is selectable for 5 VDC or 10 VDC.
The excitation output is based on a reference, ensuring accurate and drift-free
readouts. A 16 point scaling feature compensates for square-law devices and
other non-linear process characteristics.
The meter provides a Max and Min reading memory with programmable
capture time. The capture time is used to prevent detection of false max and min
readings which may occur during burst testing or unusual process events.
The signal totalizer (integrator) can be used to compute a time-input product.
This can be used to provide a readout of totalized flow, calculate service
intervals of motors and pumps, etc. The totalizer can also accumulate batch
weighing operations (batch weight).
The meter has four setpoint outputs, implemented on Plug-in cards. The
Plug-in cards provide dual FORM-C relays (5 A), quad FORM-A relays (3 A)
or either sinking or sourcing quad open collector logic outputs. The setpoint
alarms can be configured in modes to suit a variety of control and alarm
requirements.
- High and low absolute, high and low deviation and band acting
- Balanced or unbalanced hysteresis
- On and off delay timers
- Auto reset or latching modes
- Reverse phase output and/or panel indicator
- Selection of alternate list of setpoint values
Plug-in cards also facilitate bus communications. These include RS232,
RS485 and MODBUS (Consult factory for other bus formats). Readout values
and setpoint alarm values can be controlled via bus commands. Additionally, the
meter has features that allow a remote computer to directly control the outputs
of the meter. This is useful during commissioning phases and diagnostic use.
With a communication card installed, set-up software allows configuration from
a PC. The configuration data can be saved to a file for later recall.
A linear DC output signal is available as a Plug-in card. The card provides
either 20 mA or 10 V signals. The output can be scaled independent of the input
range.
The features of the linear output card are:
- Output tracks either input, totalizer, max or min readings
- Programmable output update times
Once the meter has been initially configured, the parameter list may be
locked out from further modification in its entirety, or only the setpoint values
can be made accessible.
The meter has been specifically designed for harsh industrial environments.
With NEMA 4X/IP65 sealed bezel and extensive testing of noise effects to CE
requirements, the meter provides a tough yet reliable application solution.
LOAD CELL, PRESSURE AND TORQUE BRIDGE INPUTS
DUAL RANGE INPUT 24 mV OR
240 mV
SELECTABLE 5 VDC OR 10 VDC BRIDGE EXCITATION
OPTIONAL CUSTOM UNITS OVERLAY W/ BACKLIGHT
PROGRAMMABLE AUTO-ZERO TRACKING
16 POINT SCALING FOR NON-LINEAR CORRECTION
9 DIGIT TOTALIZER (INTEGRATOR) WITH BATCHING
PROGRAMMABLE FUNCTION KEYS/USER INPUTS
FOUR SETPOINT ALARM OUTPUTS (W/Plug-in card)
COMMUNICATION AND BUS CAPABILITIES (W/Plug-in card)
ANALOG OUTPUT SIGNAL (W/Plug-in card)
PC SOFTWARE AVAILABLE FOR METER CONFIGURATION
NEMA 4X/IP65 SEALED FRONT BEZEL
MODEL 7558 - 1/8 DIN STRAIN GAGE INPUT PANEL METER
1
1
1
l
l:
l
l
l
l
l
l
l
l
l
l
l
DIMENSIONS “In inches (mm)” Note: Recommended minimum clearance (behind the panel) for
mounting clip installation is 2.1" (53.4) H x 5" (127) W. PANEL CUT-OUT
...
Lebow®Products Inc.
Tel (800) 803-1164
Fax (248) 643-8142
www.lebow.com
CAUTION: Risk of electric shock.
CAUTION: Read complete
instructions prior to installation
and operation of the unit.

2
Safety Summary
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use this unit to directly command motors, valves, or other actuators
not equipped with safeguards. To do so can be potentially harmful to persons or
equipment in the event of a fault to the unit.
SPECIFICATIONS
1. DISPLAY: 5 digit, 0.56" (14.2 mm) red LED, (-19999 to 99999)
2. POWER:
AC Versions
AC Power: 85 to 250 VAC, 50/60 Hz, 15 VA
Isolation: 2300 Vrms for 1 min. to all inputs and outputs.
DC Versions
DC Power: 11 to 36 VDC, 11 W
(Derate operating temperature to 40C if operating <15 VDC and three
plug-in cards are installed)
AC Power: 24 VAC, 10%, 50/60 Hz, 15 VA
Isolation: 500 Vrms for 1 min. to all inputs and outputs (50 V working).
3. ANNUNCIATORS:
MAX - max readout selected
MIN - min. readout selected
TOT - totalizer readout selected, flashes when total overflows
SP1 - setpoint alarm 1 is active
SP2 - setpoint alarm 2 is active
SP3 - setpoint alarm 3 is active
SP4 - setpoint alarm 4 is active
Units Label - software controlled units label backlight
4. KEYPAD: 3 programmable multi-function keys, 5 keys total
5. A/D CONVERTER: 16 bit resolution
6. UPDATE RATES:
A/D conversion rate: 20/readings sec
Step response: 200 msec. max. to within 99% of final readout value
(digital filter and internal zero correction disabled)**
700 msec. max. (digital filter disabled, internal zero correction enabled)**
Display update rate: 1 to 20 updates/sec
Setpoint output on/off delay time: 0.0 to 3275.0 sec
Analog output update rate: 0.0 to 10.0 sec
Max./Min. capture delay time: 0.0 to 3275.0 sec
7. DISPLAY MESSAGES:
“OLOL” - Appears when measurement exceeds + signal range.
“ULUL” - Appears when measurement exceeds - signal range
“. . . .” - Appears when display values exceed + display range.
“- . . .” - Appears when display values exceed - display range.
8. CONNECTION TYPE: 4-wire bridge (differential)
2-wire (single-ended)
9. COMMON MODE RANGE (w.r.t. input common): 0 to +5 VDC
Rejection: 80 db (DC to 120 Hz)
10. SENSOR INPUTS:
* After 20 minute warm-up. Accuracy is specified in two ways: Accuracy over
an 18 to 28C and 10 to 75% RH environment; and accuracy over a 0 to 50C
and 0 to 85%RH (non-condensing environment). Accuracy over the 0 to
50C range includes the temperature coefficient effect of the meter.
** The meter periodically (every 12 seconds) imposes a 500 msec delay to
compensate for internal zero drift. If the delay affects applications where step
response is critical, it can be defeated. Set the display update to 20/sec to
disable. In this case, add a zero error of 0.2% FS to the 24 mV input range
over the 0 to 50C span.
*** Nominal resolution. The internal resolution is the input divided by 65535.
11. BRIDGE EXCITATION :
Jumper Selectable: 5 VDC @ 65 mA max., 2%
10 VDC @ 125 mA max., 2%
Temperature coefficient (ratio metric): 20 ppm/C max.
12. LOW FREQUENCY NOISE REJECTION:
Normal Mode: > 60 dB @ 50 or 60 Hz ±1%, digital filter off
Common Mode: >100 dB, DC to 120 Hz (w.r.t. earth)
13. USER INPUTS (Logic Level): Three software defined user inputs, jumper
selectable for sink/source logic
Max. Continuous Input: 30 VDC
Isolation To Sensor Input Common: Not isolated
Response Time: 50 msec. max.
Logic State: Jumper selectable for sink/source logic.
14. TOTALIZER:
Time Base: second, minute, hour, or day
Time Accuracy: 0.01% typical
Decimal Point: 0 to 0.0000
Scale Factor: 0.001 to 65.000
Low Signal Cut-out: -19,999 to 99,999
Total: 9 digits, display alternates between high order and low order readouts
15. CUSTOM LINEARIZATION:
Data Point Pairs: Selectable from 2 to 16
Display Range: -19,999 to 99,999
Decimal Point: 0 to 0.0000
16. SERIAL COMMUNICATIONS: Field installable option card
(RS232 or RS485)
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Working Voltage: 50 V
Not Isolated from all other commons.
Data: 7/8 bits
Baud: 300 to 19200
Parity: no, odd or even
Bus Address: selectable 0 to 99, Max. 32 meters per line (RS485)
Transmit Delay: Selectable for 2 to 50 msec or 50 to 100 msec (RS485)
17. MODBUS CARD :
Type: RS485; RTU and ASCII MODBUS modes.
Isolation to Sensor & User Input Commons: 500 Vrms for 1 min.
Not isolated from all other commons.
Baud Rates: 300, 600, 1200, 2400, 4800, 9600, 19200, and 38400.
Addresses: 1-247.
Format: 7/8 bits, odd, even and no parity.
Transmit Delay: Programmable
18. ANALOG OUTPUT : Field installable option card
Types: 0 to 20 mA, 4 to 20 mA or 0 to 10 VDC
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Working Voltage: 50 V
Not Isolated from all other commons.
Accuracy: 0.17% of FS (18 to 28°C); 0.4% of FS (0 to 50°C)
Resolution: 1/3500
Compliance: 10 VDC: 10 Kload min.
20 mA: 500 load max.
19. SETPOINT OUTPUT: Four types of field installable option cards
Dual Relay Card:
Type: Two FORM-C relays
Isolation To Sensor & User Input Commons: 2000 Vrms for 1 min.
Working Voltage: 240 Vrms
Contact Rating:
One Relay Energized: 5 amps @ 120/240 VAC or 28 VDC (resistive
load), 1/8 HP @120 VAC, inductive load
Total current with both relays energized not to exceed 5 amps
Life expectancy: 100K cycles min. at full load rating. External RC snubber
extends relay life for operation with inductive loads
Quad Relay Card:
Type: Four FORM-A relays
Isolation To Sensor & User Input Commons: 2300 Vrms for 1 min.
Working Voltage: 250 Vrms
Contact Rating:
One Relay Energized: 3 amps @ 250 VAC or 30 VDC (resistive load),
1/10 HP @120 VAC, inductive load
Total current with all four relays energized not to exceed 4 amps
Life Expectancy: 100K cycles min. at full load rating. External RC
snubber extends relay life for operation with inductive loads
VIN > 2.5 VDC VIN < 0.7 VDC
Inactive
VIN < 0.7 VDC VIN > 2.5 VDC
Active
SINKING INPUTS
22 Kpull-up to +5 V
SOURCING INPUTS
22 Kpull-down
INPUT STATE
Input Range Accuracy*
(18 to 28C)
Accuracy*
(0 to 50C) Impedance
Max
Continuous
Overload
Resolution
24 mVDC 0.02% of
reading +3 V
0.07% of
reading +4 V100 Mohm 30 V 1V
240 mVDC 0.02% of
reading +30 V
0.07% of
reading +40 V100 Mohm 30 V 10 V
:
:
7. :
.
:
.
A
12. :
.r
:
ime Accuracy: 0.01% typical
rms for 1 min.
.
Isolation T
VIN > 2.5 VDC VIN < 0.7 VDC
Inactive
VIN < 0.7 VDC VIN > 2.5 VDC
Active
SINKING INPUTS
22 Kpull-up to +5 V
SOURCING INPUTS
22 Kpull-down
INPUT STATE
Input Range Accuracy*
(18 to 28C)
Accuracy*
(0 to 50C) Impedance
Max
Continuous
Overload
Resolution
24 mVDC 0.02% of
reading +3 V
0.07% of
reading +4 V100 Mohm 30 V 1V
240 mVDC 0.02% of
reading +30 V
0.07% of
reading +40 V100 Mohm 30 V 10 V
:
:
:
:
.
A
:
:
.
VIN > 2.5 VDC VIN < 0.7 VDC
Inactive
VIN < 0.7 VDC VIN > 2.5 VDC
Active
SINKING INPUTS
22 Kpull-up to +5 V
SOURCING INPUTS
22 Kpull-down
INPUT STATE
Input Range Accuracy*
(18 to 28C)
Accuracy*
(0 to 50C) Impedance
Max
Continuous
Overload
Resolution
24 mVDC 0.02% of
reading +3 V
0.07% of
reading +4 V100 Mohm 30 V 1V
240 mVDC 0.02% of
reading +30 V
0.07% of
reading +40 V100 Mohm 30 V 10 V
:
:
:
:
.
A
:
:
.
VIN > 2.5 VDC VIN < 0.7 VDC
Inactive
VIN < 0.7 VDC VIN > 2.5 VDC
Active
SINKING INPUTS
22 Kpull-up to +5 V
SOURCING INPUTS
22 Kpull-down
INPUT STATE
Input Range Accuracy*
(18 to 28C)
Accuracy*
(0 to 50C) Impedance
Max
Continuous
Overload
Resolution
24 mVDC 0.02% of
reading +3 V
0.07% of
reading +4 V100 Mohm 30 V 1V
240 mVDC 0.02% of
reading +30 V
0.07% of
reading +40 V100 Mohm 30 V 10 V

3
Quad Sinking Open Collector:
Type: Four isolated sinking NPN transistors.
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Working Voltage: 50 V
Not Isolated from all other commons.
Rating: 100 mA max @ VSAT = 0.7 V max. VMAX = 30 V
Quad Sourcing Open Collector:
Type: Four isolated sourcing PNP transistors.
Isolation To Sensor & User Input Commons: 500 Vrms for 1 min.
Working Voltage: 50 V
Not Isolated from all other commons.
Rating: Internal supply: 24 VDC ± 10%, 30 mA max. total all four outputs
External supply: 30 VDC max., 100 mA max. each output
20. MEMORY: Nonvolatile E2PROM retains all programmable parameters
and display values.
21. CERTIFICATIONS AND COMPLIANCES:
UL Recognized Component, File #E179259
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.
SAFETY
EN 61010-1, IEC 1010-1
Safety requirements for electrical equipment for measurement, control,
and laboratory use, Part I.
ELECTROMAGNETIC COMPATIBILITY
Notes:
1. Self-recoverable loss of performance during EMI disturbance at 10 V/m:
Measurement error exceeds unit specifications
For operation without loss of performance:
Mount unit in a metal enclosure (Buckeye SM7013-0 or equivalent)
Route power and I/O cables in metal conduit connected to earth
ground.
22. ENVIRONMENTAL CONDITIONS:
Operating Temperature Range: 0 to 50°C (0 to 45°C with all three plug-in
cards installed)
Storage Temperature Range: -40 to 60°C
Operating and Storage Humidity: 0 to 85% max. non-condensing
Altitude: Up to 2000 meters
23. CONNECTIONS: High compression cage-clamp terminal block
Wire Strip Length: 0.35" (9 mm)
Wire Gauge Capacity: One 14 AWG solid or Two 18 AWG
24. CONSTRUCTION:This unit is rated for NEMA 4X/IP65 indoor use. IP20
Touch safe. Installation Category II, Pollution Degree 2. One piece
bezel/case. Flame resistant. Synthetic rubber keypad. Panel gasket and
mounting clip included.
25. WEIGHT: 10.4 oz. (295 g)
Immunity to EN 50082-2
Electrostatic discharge EN 61000-4-2 Level 3; 8 Kv air
Electromagnetic RF fields EN 61000-4-3 Level 3; 10 V/m 1
80 MHz - 1 GHz
Fast transients (burst) EN 61000-4-4 Level 4; 2 Kv I/O
Level 3; 2 Kv power
RF conducted interference EN 61000-4-6 Level 3; 10 V/rms
ENV 50204 Level 3; 10 V/m
900 MHz ± 5 MHz
150 KHz - 80 MHz
Emissions to EN 50081-2
RF interference EN 55011 Enclosure class A
Power mains class A
200 Hz, 50% duty cycle
Simulation of cordless telephones
ype: Four isolated sinking NPN transistors.
:
A
: 10.4 oz. (295 g)
Immunity to EN 50082-2
Electrostatic discharge EN 61000-4-2 Level 3; 8 Kv air
Electromagnetic RF fields EN 61000-4-3 Level 3; 10 V/m 1
80 MHz - 1 GHz
Fast transients (burst) EN 61000-4-4 Level 4; 2 Kv I/O
Level 3; 2 Kv power
RF conducted interference EN 61000-4-6 Level 3; 10 V/rms
ENV 50204 Level 3; 10 V/m
900 MHz ± 5 MHz
150 KHz - 80 MHz
Emissions to EN 50081-2
RF interference EN 55011 Enclosure class A
Power mains class A
200 Hz, 50% duty cycle
Simulation of cordless telephones
:
A
Immunity to EN 50082-2
Electrostatic discharge EN 61000-4-2 Level 3; 8 Kv air
Electromagnetic RF fields EN 61000-4-3 Level 3; 10 V/m 1
80 MHz - 1 GHz
Fast transients (burst) EN 61000-4-4 Level 4; 2 Kv I/O
Level 3; 2 Kv power
RF conducted interference EN 61000-4-6 Level 3; 10 V/rms
ENV 50204 Level 3; 10 V/m
900 MHz ± 5 MHz
150 KHz - 80 MHz
Emissions to EN 50081-2
RF interference EN 55011 Enclosure class A
Power mains class A
200 Hz, 50% duty cycle
Simulation of cordless telephones
:
A
Immunity to EN 50082-2
Electrostatic discharge EN 61000-4-2 Level 3; 8 Kv air
Electromagnetic RF fields EN 61000-4-3 Level 3; 10 V/m 1
80 MHz - 1 GHz
Fast transients (burst) EN 61000-4-4 Level 4; 2 Kv I/O
Level 3; 2 Kv power
RF conducted interference EN 61000-4-6 Level 3; 10 V/rms
ENV 50204 Level 3; 10 V/m
900 MHz ± 5 MHz
150 KHz - 80 MHz
Emissions to EN 50081-2
RF interference EN 55011 Enclosure class A
Power mains class A
200 Hz, 50% duty cycle
ORDERING INFORMATION
Simulation of cordless telephones
7558 - X X X Basic Meter with Analog Output
Communications
0 = None
1 = RS232 / Software
2 = RS485 / Software
3 = DeviceNet / Software
4 = ModBus
Relays
0 = None
1 = Dual Relays
Operating Power
0 = DC Power
1 = AC Power

4
The 7558 series meters can be fitted with up to three optional plug-in cards.
However, only one card from each function type can be installed at a time. The
function types include Setpoint Alarms, Communications, and Analog
Output. The cards can be installed initially or at a later date. Each optional
plug-in card is shipped with installation and programming instructions.
SETPOINT ALARMS PLUG-IN CARDS
The 7558 series has four setpoint alarm output plug-in cards. Only one of
these cards can be installed at a time. (Logic state of the outputs can be reversed
in the programming.) These plug-in cards include
Dual relay, FORM-C, Normally open & closed
Quad relay, FORM-A, Normally open only
Isolated quad sinking NPN open collector
Isolated quad sourcing PNP open collector
SERIAL RS485 PLUG-IN CARD
An RS485 communication port can be installed with the serial RS485 plug-
in card. The RS485 option allows the connection of up to 32 meters or other
devices (such as a printer, PLC, HMI, or a host computer) on a single pair of
wires not longer than 4,000 feet. The address number of each meter on the line
can be programmed from 0-99. Data from the meter(s) can be interrogated or
changed and alarm outputs can be reset by sending the proper command string.
The function keys and user inputs can be programmed to send data to a printer
or other device via serial communications.
SERIAL RS232 PLUG-IN CARD
An RS232 communication port can be installed with the serial RS232 plug-
in card. The RS232 is intended to allow only 2 devices, not more than 50 feet
apart, to communicate to each other (such as a printer, PLC, HMI, or host
computer). Data from the meter(s) can be interrogated or changed and alarm
outputs can be reset by sending the proper command string. The function keys
and user inputs can be programmed to send data to a printer or device via serial
communication.
MODBUS PLUG-IN CARD
A MODBUS communication port can be installed with the MODBUS plug-
in card. The MODBUS card uses standard MODBUS protocol, which allows
the integration of devices of different types and manufacturers within a common
communication framework.
ANALOG OUTPUT PLUG-IN CARD
Either a 0(4)-20 mA or 0-10 V retransmitted linear DC output is available
from the analog output plug-in card. The programmable output low and high
scaling can be based on the input max, min, or total display value. Reverse
acting output is possible by reversing the scaling point positions.
UNITS LABEL KIT
Each meter has a units indicator with backlighting that can be customized
using the Units Label Kit. The backlight is controlled in the programming.
PC SOFTWARE (SFPAX)
The SFPAX is a Windows based program that allows configuration of the
7558 meter from a PC. Using SFPAX makes it easier to program the 7558 meter
and allows saving the 7558 program in a PC file for future use. On-line help is
available within the software. A 7558 serial plug-in card is required to program
the meter using the software.
Installation
The 7558 meets NEMA 4X/IP65 requirements for indoor use when
properly installed. The unit is intended to be mounted into an enclosed panel.
Prepare the panel cutout to the dimensions shown. Remove the panel latch and
cardboard sleeve from the unit and
discard the cardboard sleeve. Slide the
panel gasket over the rear of the
unit to the back of the bezel.
The unit should be installed
fully assembled. Insert the
unit into the panel cutout.
While holding the unit in place, push the panel latch over the rear of the unit
so that the tabs of the panel latch engage in the slots on the case. The panel
latch should be engaged in the farthest forward slot possible. To achieve a
proper seal, tighten the latch screws evenly until the unit is snug in the panel
(Torque to approximately 7 in-lbs [79N-cm]). Do not over-tighten the screws.
Installation Environment
The unit should be installed in a location that does not exceed the maximum
operating temperature and provides good air circulation. Placing the unit near
devices that generate excessive heat should be avoided.
The bezel should be cleaned only with a soft cloth and neutral soap product.
Do NOT use solvents. Continuous exposure to direct sunlight may accelerate
the aging process of the bezel.
Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate
the keypad of the unit.
1.0 INSTALLING THE METER
OPTIONALPLUG-IN CARDS AND ACCESSORIES
PANEL CUT-OUT
1.0 INSTALLING THE METER
PANEL CUT-OUT
1.0 INSTALLING THE METER
PANEL CUT-OUT
1.0 INSTALLING THE METER
PANEL CUT-OUT

5
The meter has three jumpers that must be set prior to applying power. The
three jumpers are Bridge Excitation, Input Range, and User Input Logic. The
Jumper Selections Figure is an enlargement of the jumper area shown below.
To access the jumpers, remove the meter base from the meter case by firmly
squeezing and pulling back on the side rear finger tabs. This should lower the
latch below the case slot (which is located just in front of the finger tabs). It is
recommended to release the latch on one side, then start the other side latch.
Bridge Excitation
One jumper is used to select bridge excitation to allow use of the higher
sensitivity 24 mV input range. Use the 5 V excitation with high output (3
mV/V) bridges. The 5 V excitation also reduces bridge power compared to 10
V excitation.
A maximum of four 350 ohm load cells can be driven by the internal bridge
excitation voltage.
Input Range
One jumper is used to select input range. The value selected in programming
must match the jumper setting. Select a range that is high enough to
accommodate the bridge output to avoid overload.
User Input Logic Jumper
One jumper is used for the logic state of all three user inputs. If the user
inputs are not used, it is not necessary to check or move this jumper.
Main
Circuit
Board
JUMPER
LOCATION
JUMPER
LOCATION
USER INPUT
INPUT RANGE
REAR TERMINALS
FRONT DISPLAY
BRIDGE
Main
Circuit
Board
JUMPER
LOCATION
JUMPER
LOCATION
USER INPUT
INPUT RANGE
REAR TERMINALS
FRONT DISPLAY
BRIDGE
Main
Circuit
Board
JUMPER
LOCATION
JUMPER
LOCATION
USER INPUT
INPUT RANGE
REAR TERMINALS
FRONT DISPLAY
BRIDGE
Main
Circuit
Board
JUMPER
LOCATION
JUMPER
LOCATION
USER INPUT
INPUT RANGE
REAR TERMINALS
FRONT DISPLAY
BRIDGE
Main
Circuit
Board
JUMPER
LOCATION
JUMPER
LOCATION
USER INPUT
INPUT RANGE
REAR TERMINALS
FRONT DISPLAY
BRIDGE
Main
Circuit
Board
JUMPER
LOCATION
JUMPER
LOCATION
USER INPUT
INPUT RANGE
REAR TERMINALS
FRONT DISPLAY
BRIDGE
Main
Circuit
Board
JUMPER
LOCATION
JUMPER
LOCATION
USER INPUT
INPUT RANGE
REAR TERMINALS
FRONT DISPLAY
BRIDGE
Main
Circuit
Board
JUMPER
LOCATION
JUMPER
LOCATION
USER INPUT
INPUT RANGE
REAR TERMINALS
FRONT DISPLAY
BRIDGE
.
Input Range
.
Main
Circuit
Board
JUMPER
LOCATION
JUMPER
LOCATION
USER INPUT
INPUT RANGE
REAR TERMINALS
FRONT DISPLAY
BRIDGE
Circuit
WIRING OVERVIEW
Electrical connections are made via screw-clamp terminals located on the
back of the meter. All conductors should conform to the meter’s voltage and
current ratings. All cabling should conform to appropriate standards of good
installation, local codes and regulations. It is recommended that power supplied
to the meter (DC or AC) be protected by a fuse or circuit breaker.
When wiring the meter, compare the numbers embossed on the back of the
meter case against those shown in wiring drawings for proper wire position.
Strip the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed (stranded
wires should be tinned with solder). Insert the lead under the correct screw-
clamp terminal and tighten until the wire is secure. (Pull wire to verify
tightness.) Each terminal can accept up to one #14 AWG (2.55 mm) wire, two
#18 AWG (1.02 mm), or four #20 AWG (0.61 mm).
EMC INSTALLATION GUIDELINES
Although this meter is designed with a high degree of immunity to Electro-
Magnetic Interference (EMI), proper installation and wiring methods must be
followed to ensure compatibility in each application. The type of the electrical
noise, source or coupling method into the unit may be different for various
installations. The unit becomes more immune to EMI with fewer I/O
connections. Cable length, routing and shield termination are very important
and can mean the difference between a successful or a troublesome installation.
Listed below are some EMC guidelines for successful installation in an
industrial environment.
1. The meter should be mounted in a metal enclosure, which is properly
connected to protective earth.
2. Use shielded (screened) cables for all Signal and Control inputs. The shield
(screen) pigtail connection should be made as short as possible. The
connection point for the shield depends somewhat upon the application.
Listed below are the recommended methods of connecting the shield, in order
of their effectiveness.
a. Connect the shield only at the panel where the unit is mounted to earth
ground (protective earth).
b. Connect the shield to earth ground at both ends of the cable, usually when
the noise source frequency is above 1 MHz.
c. Connect the shield to common of the unit and leave the other end of the
shield unconnected and insulated from earth ground.
3. Never run Signal or Control cables in the same conduit or raceway with AC
power lines, conductors feeding motors, solenoids, SCR controls, and
heaters, etc. The cables should be run in metal conduit that is properly
grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.
4. Signal or Control cables within an enclosure should be routed as far away as
possible from contactors, control relays, transformers, and other noisy
components.
5. In extremely high EMI environments, the use of external EMI suppression
devices, such as ferrite suppression cores, is effective. Install them on Signal
and Control cables as close to the unit as possible. Loop the cable through the
core several times or use multiple cores on each cable for additional
protection. Install line filters on the power input cable to the unit to suppress
power line interference. Install them near the power entry point of the
enclosure. The following EMI suppression devices (or equivalent) are
recommended:
Ferrite Suppression Cores for signal and control cables:
Fair-Rite # 0443167251 (RLC #FCOR0000)
TDK # ZCAT3035-1330A
Steward #28B2029-0A0
Line Filters for input power cables:
Schaffner # FN610-1/07 (RLC #LFIL0000)
Schaffner # FN670-1.8/07
Corcom #1VR3
Note: Reference manufacturer’s instructions when installing a line filter.
6. Long cable runs are more susceptible to EMI pickup than short cable runs.
Therefore, keep cable runs as short as possible.
7. Switching of inductive loads produces high EMI. Use of snubbers across
inductive loads suppresses EMI.
Snubber: RLC#SNUB0000.
3.0 W IRING THE METER
2.0 SETTING THE JUMPERS
’
.
.
.
3.0 W IRING THE METER
2.0 SETTING THE JUMPERS
’
.
.
.
3.0 W IRING THE METER
2.0 SETTING THE JUMPERS
’
.
.
.
3.0 W IRING THE METER
2.0 SETTING THE JUMPERS
JUMPER SELECTIONS
The indicates factory setting.

6
3.1 POWER WIRING
3.4 SETPOINT (ALARMS) WIRING
3.5 SERIAL COMMUNICATION WIRING
3.6 ANALOG OUTPUT WIRING
3.2 INPUT SIGNAL WIRING
Before connecting signal wires, the Input Range Jumper should be verified for proper position.
3.3 USER INPUT WIRING
Before connecting the wires, the User Input Logic Jumper should be verified for proper position. If User Inputs are
not used, then skip this section. Only the appropriate User Input terminal has to be wired.
DEADLOAD COMPENSATION
In some cases, the combined deadload and liveload output may exceed the
range of the 24 mV input. To use this range, the output of the bridge can be
offset a small amount by applying a fixed resistor across one arm of the bridge.
This shifts the electrical output of the bridge downward to within the operating
range of the meter. A 100 K ohm fixed resistor shifts the bridge output
approximately -10 mV (350 ohm bridge, 10 V excitation).
Connect the resistor between +SIG and -SIG. Use a metal film resistor with
a low temperature coefficient of resistance.
BRIDGE COMPLETION RESISTORS
For single strain gage applications, bridge completion resistors must be
employed externally to the meter. Only use metal film resistors with a low
temperature coefficient of resistance.
Load cells and pressure transducers are normally implemented as full
resistance bridges and do not require bridge completion resistors.
AC Power
Terminal 1: VAC
Terminal 2: VAC
}See appropriate plug-in card bulletin for details.
Sinking Logic
Terminals 8-10
Terminal 7
In this logic, the user inputs of the
meter are internally pulled up to +5 V
with 22 K resistance. The input is
active when it is pulled low (<0 .7 V).
Connect external switching device between
appropriate User Input terminal and User Comm.
}
4-Wire Bridge Input
2-Wire Single Ended Input 6-Wire Bridge Input
Sourcing Logic
Terminals 8-10:
+ VDC through external switching device
Terminal 7:
-VDC through external switching device
In this logic, the user inputs of the meter are
internally pulled down with 22 K resistance.
The input is active when a voltage greater
than 2.5 VDC is applied.
Sourcing Logic
Terminals 8-10:
+ VDC through external switching device
Terminal 7:
-VDC through external switching device
In this logic, the user inputs of the meter are
internally pulled down with 22 K resistance.
The input is active when a voltage greater
than 2.5 VDC is applied.
Sourcing Logic
Terminals 8-10:
+ VDC through external switching device
Terminal 7:
-VDC through external switching device
In this logic, the user inputs of the meter are
internally pulled down with 22 K resistance.
The input is active when a voltage greater
than 2.5 VDC is applied.
Sourcing Logic
Terminals 8-10:
+ VDC through external switching device
Terminal 7:
-VDC through external switching device
In this logic, the user inputs of the meter are
internally pulled down with 22 K resistance.
The input is active when a voltage greater
than 2.5 VDC is applied.

7
4.0 REVIEWING THE FRONT BUTTONS AND DISPLAY
5.0 PROGRAMMING THE METER
4.0 REVIEWING THE FRONT BUTTONS AND DISPLAY
5.0 PROGRAMMING THE METER
4.0 REVIEWING THE FRONT BUTTONS AND DISPLAY
5.0 PROGRAMMING THE METER
4.0 REVIEWING THE FRONT BUTTONS AND DISPLAY
5.0 PROGRAMMING THE METER
PROGRAMMING MODE ENTRY (PAR KEY)
The Display Mode is the normal operating mode of the meter. The
Programming Mode is entered by pressing the PAR key. If it is not accessible,
then it is locked by either a security code or hardware lock.
PARAMETER MODULE ENTRY (ARROW & PAR KEYS)
The Programming Menu is organized into modules. These modules group
together parameters which are related in function. The display alternates
between Pro and the current parameter module. The arrow keys (F1 and F2) are
used to select the desired parameter module. The displayed module is entered
by pressing the PAR key.
PARAMETER MENU MOVEMENT (PAR KEY)
Each parameter module has a separate module menu (which is shown at the
start of each parameter module discussion). The PAR key is pressed to advance
to a particular parameter without changing the programming of preceding
parameters. After completing a module, the display will return to Pro NO.
Programming may continue by accessing additional parameter modules.
SELECTION/VALUE ENTRY (ARROW & PAR KEYS)
In the parameter module, the display will alternate between the current
parameter and the selections/values for that parameter. The arrow keys (F1 and
F2) are used to move through the selections/values for that parameter. By
pressing the PAR key, the displayed selection is stored and activated. This will
also advance the meter to the next parameter.
PROGRAMMING MODE EXIT (DSP KEYor at Pro NO PAR KEY)
The Programming Mode is exited by pressing the DSP key (from anywhere
in the Programming Mode) or the PAR key (with Pro NO displayed). This will
commit any stored parameter changes to memory and return the meter to the
Display Mode. If a parameter was just changed, the PAR key should be pressed
to store the change before pressing the DSP key.
PROGRAMMING TIPS
It is recommended to start with Parameter Module 1. If lost or confused while
programming, press the DSP key and start over. When programming is
complete, it is recommended to record the parameter programming on the
Parameter User Chart and lock-out parameter programming with a user input or
lock-out code.
FACTORY SETTINGS
Factory Settings may be completely restored in Parameter Module 9. This is
a good starting point when experiencing programming problems. Some
parameters can be left at their Factory Settings without affecting basic start-up.
These parameters are identified throughout the Module explanations. Try the
Factory Settings for these parameters unless a specific selection or value is
known.
ALTERNATING SELECTION DISPLAY
In the explanation of the parameter modules, the following dual display with
arrows will appear. It is to illustrate the display alternating between the
parameter on top, and the parameter’s factory setting on the bottom. In most
cases, selections and values for the parameter will be listed on the right.
Indicates Program
Mode Alternating
Display
OVERVIEW
PROGRAMMING MENU
FRONT PANEL
Function key 1; hold for 3 seconds for Second Function 1**
Hold with F1, F2to scroll value by x1000
* Display Readout Legends may be locked out in Factory Settings.
** Factory setting for the F1, F2, and RST keys is NO mode.
Reset (function key)**RST
Decrement selected parameter valueFunction key 2; hold for 3 seconds for Second Function 2**F2
Increment selected parameter valueF1
Store selected parameter and index to next parameterAccess parameter listPAR
Quit programming and return to display modeIndex display through max/min/total/input readoutsDSP
PROGRAMMING MODE OPERATIONDISPLAY MODE OPERATIONKEY
.
R
.
.
.
AL
s
FRONT PANEL
.
.
.
.
FRONT PANEL
.
.
.
.
Ä
Å
0.02u
rANGE
FRONT PANEL
* Only accessible with appropriate Plug-in card.

8
Ä
Ä
Å
KEY
StYLE
Ä
Å
0.000
0.000 0.00000.000.00
INPUT RANGE
DISPLAY DECIMAL POINT
DISPLAY ROUNDING*
mV
mV
SELECTION
Select the input range that corresponds to the external signal. This selection
should be high enough to avoid input signal overload but low enough for the
desired input resolution. This selection and the position of the Input Range
Jumper must match.
SCALING POINTS*
Linear - Scaling Points (2)
For linear processes, only 2 scaling points are necessary. It is recommended
that the 2 scaling points be at opposite ends of the input signal being applied.
The points do not have to be the signal limits. Display scaling will be linear
between, and continue past, the entered points up to the limits of the Input
Signal Jumper position. Each scaling point has a coordinate-pair of Input Value
( ) and an associated desired Display Value ( ).
Nonlinear - Scaling Points (Greater than 2)
For non-linear processes, up to 16 scaling point may be used to provide a
piece-wise linear approximation. (The greater the number of scaling points
used, the greater the conformity accuracy.) The Input Display will be linear
between scaling points that are sequential in program order. Each scaling point
has a coordinate-pair of Input Value (INP) and an associated desired Display
Value (dSP). Data from tables or equations, or empirical data could be used to
derive the required number of segments and data values for the coordinate pairs.
In the SFPAX software, several linearization equations are available.
Select the decimal point location for the Input, MAX and MIN displays. (The
TOT display decimal point is a separate parameter.) This selection also affects
and x parameters and setpoint values.
502010
521
Rounding selections other than one cause the Input Display to ‘round’ to the
nearest rounding increment selected (ie. rounding of ‘5’ causes 122 to round to
120 and 123 to round to 125). Rounding starts at the least significant digit of
the Input Display. Remaining parameter entries (scaling point values, setpoint
values, etc.) are not automatically adjusted to this display rounding selection.
SCALING STYLE
If Input Values and corresponding Display Values are known, the Key-in
() scaling style can be used. This allows scaling without the presence of a
live input signal. If Input Values have to be derived from the actual input signal
source or simulator, the Apply ( ) scaling style must be used.
INPUT VALUE FOR SCALING POINT 1
For Key-in (Key), enter the known first Input Value by using the arrow keys.
(The Input Range selection sets up the decimal location for the Input Value).
For Apply (APLY), apply the input signal to the meter, adjust the signal source
externally until the desired Input Value appears. In either method, press the
PAR key to enter the value being displayed. The DSP key can be pressed
without changing the previously stored INP1 value in the APLY style.
FILTER SETTING*
The input filter setting is a time constant expressed in tenths of a second. The
filter settles to 99% of the final display value within approximately 3 time
constants. This is an Adaptive Digital Filter which is designed to steady the
Input Display reading. A value of ‘0’ disables filtering.
FILTER BAND*
The digital filter adapts to variations in the input signal. When the variation
exceeds the input filter band value, the digital filter disengages. When the
variation becomes less than the band value, the filter engages again. This allows
for a stable readout, but permits the display to settle rapidly after a large process
change. The value of the band is in display units, independent of the Display
Decimal Point position. A band setting of ‘0’ keeps the digital filter
permanently engaged.
to seconds
to display units
-19999 to 19999
Å
20.000
INP 2
INPUT VALUE FOR SCALING POINT 2
-19999 to 19999
Å
0.00
dSP 1
DISPLAY VALUE FOR SCALING POINT 1
-19999 to 19999
to
apply signal
APLY
key-in data
KEY
INP 1
INPUT RANGE
DISPLAY DECIMAL POINT
mV
mV
SELECTION
Select the input range that corresponds to the external signal. This selection
should be high enough to avoid input signal overload but low enough for the
desired input resolution. This selection and the position of the Input Range
Jumper must match.
and
100
Rounding selections other than one cause the Input Display to ‘round’ to the
nearest rounding increment selected (ie. rounding of ‘5’ causes 122 to round to
120 and 123 to round to 125). Rounding starts at the least significant digit of
the Input Display. Remaining parameter entries (scaling point values, setpoint
values, etc.) are not automatically adjusted to this display rounding selection.
to seconds
to
Ä
apply signal
INPUT RANGE
DISPLAY DECIMAL POINT
mV
mV
SELECTION
Select the input range that corresponds to the external signal. This selection
should be high enough to avoid input signal overload but low enough for the
desired input resolution. This selection and the position of the Input Range
Jumper must match.
and
Rounding selections other than one cause the Input Display to ‘round’ to the
nearest rounding increment selected (ie. rounding of ‘5’ causes 122 to round to
120 and 123 to round to 125). Rounding starts at the least significant digit of
the Input Display. Remaining parameter entries (scaling point values, setpoint
values, etc.) are not automatically adjusted to this display rounding selection.
to
Ä
Å
0.02u
rANGE
Ä
Å
2
Pt5
INPUT RANGE
DISPLAY DECIMAL POINT
±240 mV
0.2u
±24 mV
SELECTION
0.02u
Select the input range that corresponds to the external signal. This selection
should be high enough to avoid input signal overload but low enough for the
desired input resolution. This selection and the position of the Input Range
Jumper must match.
1NP dSP
round and dSP
Rounding selections other than one cause the Input Display to ‘round’ to the
nearest rounding increment selected (ie. rounding of ‘5’ causes 122 to round to
120 and 123 to round to 125). Rounding starts at the least significant digit of
the Input Display. Remaining parameter entries (scaling point values, setpoint
values, etc.) are not automatically adjusted to this display rounding selection. KEY
APLY
Ä
Å
1.0
FILtr
Ä
Å
0.10
bANd
0.0 25.0
0to 250
2 16
PARAMETER MENU
RANGE
RESOLUTION
*Factory Setting can be used without affecting basic start-up.
Enter the first coordinating Display Value by using the arrow keys. This is
the same for KEY and APLY scaling styles. The decimal point follows the dECPt
selection.
For Key-in (KEY), enter the known second Input Value by using the arrow
keys. For Apply (APLY), adjust the signal source externally until the next
desired Input Value appears. (Follow the same procedure if using more than 2
scaling points.)
RANGE
RESOLUTION
RANGE
RESOLUTION
RANGE
RESOLUTION
Ä
Å
0.01
round
Ä
Å
0.00
dECPt
5.1 MODULE 1 - Signal InputParameters( )
l-lNP

9
Ä
Å
100.00
dSP 2
DISPLAY VALUE FOR SCALING POINT 2
-19999 to 19999
General Notes on Scaling
1. Input Values for scaling points should be confined to the limits of the Input
Range Jumper position.
2. The same Input Value should not correspond to more than one Display Value.
(Example: 20 mA can not equal a display of 0 and 10.)
This is referred to as readout jumps (vertical scaled segments).
3. The same Display Value can correspond to more than one Input Value.
(Example: 0 mA and 20 mA can equal a display of 10.)
This is referred to as readout dead zones (horizontal scaled segments).
4. For input levels beyond the first programmed Input Value, the meter extends
the Display Value by calculating the slope from the first two coordinate pairs
(INP1 /dSP1 &INP2 /DSP2). If INP1 – 4 mA and DSP1 – 0, then 0 mA
would be some negative Display Value. This could be prevented by making
INP1 – 0 mA / dSP1 – 0, INP2 – 4 mA / dSP2 – 0, with INP3 – 20 mA /
dSP3 – the desired high Display Value. The calculations stop at the limits of
the Input Range Jumper position.
5. For input levels beyond the last programmed Input Value, the meter extends
the Display Value by calculating the slope from the last two sequential
coordinate pairs. If three coordinate pair scaling points were entered, then the
Display Value calculation would be between INP2 /dSP2 &INP3 /DSP3.
The calculations stop at the limits of the Input Range Jumper position.
(
/ .
(
/ .
(
/ .
5.2 MODULE 2 - User Input andFront Panel Function Key
Parameters ( )
PARAMETER MENU
Ä
Å
NO
USr-1
Ä
Å
NO
NO FUNCTION
No function is performed if activated. This is the factory setting for all user
inputs and function keys.
Ä
Å
PROGRAMMING MODE LOCK-OUT
Programming Mode is locked-out, as long as activated
(maintained action). A security code can be configured to
allow programming access during lock-out.
ZERO (TARE) DISPLAY
Ä
Å
rEL
USr-1
Ä
Å
rEL
F1
The three user inputs are individually programmable to perform specific
meter control functions. While in the Display Mode or Program Mode, the
function is executed the instant the user input transitions to the active state.
The front panel function keys are also individually programmable to perform
specific meter control functions. While in the Display Mode, the primary
function is executed the instant the key is pressed. Holding the function key for
three seconds executes a secondary function. It is possible to program a
secondary function without a primary function.
In most cases, if more than one user input and/or function key is programmed
for the same function, the maintained (level trigger) actions will be performed
while at least one of those user inputs or function keys are activated. The
momentary (edge trigger) actions will be performed every time any of those
user inputs or function keys transition to the active state.
Enter the second coordinating Display Value by using the arrow keys. This
is the same for KEY and APLY scaling styles. (Follow the same procedure if
using more than 2 scaling points.)
Ä
Å
d-rEL
USr-1
Ä
Å
d-rEL
F1
RELATIVE/ABSOLUTE DISPLAY
This function switches the Input Display between Relative and Absolute.
The Relative is a net value that includes the Display Offset Value. The Input
Display will normally show the Relative unless switched by this function.
Regardless of the display selected, all meter functions continue to operate based
on relative values. The Absolute is a gross value (based on Module 1 DSP and
INP entries) without the Display Offset Value. The Absolute display is selected
as long as the user input is activated (maintained action) or at the transition of
the function key (momentary action). When the user input is released, or the
function key is pressed again, the input display switches back to Relative
display. AbS (absolute) or rEL (relative) is momentarily displayed at transition
to indicate which display is active.
Note:In the following explanations, not all selections are available for both
user inputs and front panel function keys. Alternating displays are shown
with each selection. Those selections showing both displays are available for
both. If a display is not shown, it is not available for that selection. USr-1
represents all three user inputs. F1 represents all five function keys including
the secondary function.
The Zero Display provides a way to zero the Input Display value at various
input levels, causing future Display readings to be offset. When activated
(momentary action), rESEt flashes and the Display is set to zero. At the same
time, the Display value (that was on the display before the Zero Display) is
subtracted from the Display Offset Value and is automatically stored as the new
Display Offset Value (oFFSt). If another Zero (tare) Display is performed, the
display will again change to zero and the Display reading will shift accordingly.
Ä
Å
d-HLd
USr-1
HOLD DISPLAY
The display is held but all other meter functions
continue as long as activated (maintained action).
5.2 MODULE 2 - User Input andFront Panel Function Key
Parameters ( )
PARAMETER MENU
F1
PLOC
USr-1
.
.
5.2 MODULE 2 - User Input andFront Panel Function Key
Parameters ( )
PARAMETER MENU
.
.
5.2 MODULE 2 - User Input andFront Panel Function Key
Parameters (2FNC )
PARAMETER MENU
.
.

10
Ä
Å
A-HLd
USr-1
HOLD ALL FUNCTIONS
Ä
Å
SYNC
USr-1
SYNCHRONIZE METER READING
Ä
Å
bAt
USr-1
Ä
Å
bAT
F1
STORE BATCH READING IN TOTALIZER
Ä
Å
d-tot
USr-1
SELECT TOTALIZER DISPLAY
Ä
Å
rtot1
USr-1
Ä
Å
r-tot
F1
RESET TOTALIZER
Ä
Å
rtot2
USr-1
RESET AND ENABLE TOTALIZER
Ä
Å
E-tot
USr-1
ENABLE TOTALIZER
Äf-H1
USr-1
Ä
Å
d-Lo
USr-1
SELECT MAXIMUM DISPLAY
SELECT MINIMUM DISPLAY
Ä
Å
F1
RESET MAXIMUM
RESET MINIMUM
Ä
Å
r-HI
USr-1
Ä
Å
r-Lo
F1
RESET, SELECT, ENABLE MAXIMUM DISPLAY
The meter disables processing the input, holds the
display, and locks the state of all outputs as long as
activated (maintained action). The serial port continues data
transfer.
The meter suspends all functions as long as activated
(maintained action). When the user input is released, the
meter synchronizes the restart of the A/D with other
processes or timing events.
The Input Display value is one time added (batched) to the Totalizer at
transition to activate (momentary action). The Totalizer retains a running sum
of each batch operation until the Totalizer is reset. When this function is
selected, the normal operation of the Totalizer is overridden.
The Totalizer display is selected as long as activated
(maintained action). When the user input is released, the
Input Display is returned. The DSP key overrides the active
user input. The Totalizer continues to function including
associated outputs independent of being displayed.
When activated (momentary action), rESEt flashes and the Totalizer resets
to zero. The Totalizer then continues to operate as it is configured. This
selection functions independent of the selected display. Ä
Å
r-HL
USr-1
Ä
Å
r-HL
F1
RESET MAXIMUM AND MINIMUM
SETPOINT SELECTIONS
Ä
Å
Print
USr-1
Ä
Å
Print
F1
PRINT REQUEST
When activated (momentary action), rESEt flashes and the Maximum and
Minimum readings are set to the present Input Display value. The Maximum
and Minimum function then continues from that value. This selection functions
independent of the selected display.
LISt - Select main or alternate setpoints
r-1 - Reset Setpoint 1 (Alarm 1)
r-2 - Reset Setpoint 2 (Alarm 2)
r-3 - Reset Setpoint 3 (Alarm 3)
r-4 - Reset Setpoint 4 (Alarm 4)
r-34 - Reset Setpoint 3 & 4 (Alarm 3 & 4)
r-234 - Reset Setpoint 2, 3 & 4
(Alarm 2, 3 & 4)
r-ALL - Reset Setpoint All (Alarm All)
When activated (momentary action), rESEt flashes and
the Totalizer resets to zero. The Totalizer continues to
operate while active (maintained action). When the user
input is released, the Totalizer stops and holds its value.
This selection functions independent of the selected
display.
The Totalizer continues to operate as long as activated
(maintained action). When the user input is released, the
Totalizer stops and holds its value. This selection functions
independent of the selected display.
The Maximum display is selected as long as activated
(maintained action). When the user input is released, the
Input Display returns. The DSP key overrrides the active
user input. The Maximum continues to function
independent of being displayed.
The Minimum display is selected as long as activated
(maintained action). When the user input is released, the
Input Display returns. The DSP key overrides the active
user input. The Minimum continues to function
independent of being displayed.
When activated (momentary action), rESEt flashes
and the Minimum reading is set to the present Input
Display value. The Minimum function then continues
from that valve. This selection functions independent of
the selected display.
When activated (momentary action), rESEt flashes
and the Maximum reading is set to the present Input
Display value. The Maximum function then continues
from that value. This selection functions independent of
the selected display.
When activated (momentary action), the Maximum
value is set to the present Input Display value. Maximum
continues from that value while active (maintained action).
When the user input is released, Maximum detection stops
and holds its value. This selection functions independent
of the selected display. The DSP key overrides display
activated by the user input but not the Maximum function.
The meter issues a block print through the serial port when activated. The
data transmitted during a print request is programmed in Module 7. If the user
input is still active after the transmission is complete (about 100 msec), an
additional transmission occurs. As long as the user input is held active,
continuous transmissions occur.
Ä
Å
r-Lo
USr-1
RESET, SELECT, ENABLE MINIMUM DISPLAY
When activated (momentary action), the Minimum
value is set to the present Input Display value. Minimum
continues from that value while active (maintained action).
When the user input is released, Minimum detection stops
and holds its value. This selection functions independent
of the selected display. The DSP key overrides display
activated by the user input display but not the Minimum
function.
The following selections are accessible only with the Setpoint plug-in card
installed. Refer to the Setpoint Card Bulletin shipped with the Setpoint plug-in
card for an explanation of their operation.
Setpoint
Card
Only
r-HI
.
.
.
.
.
.
..
.
.
.
.
.
.
..
Å
.
.
.
.
.
.
..
{

11
Ä
Å
0
CodE
PROGRAM MODE SECURITY CODE*
By entering any non-zero value, the prompt CodE 0 appears when trying to
access the Program Mode. Access is only allowed after entering a matching
security code or universal code of 222. With this lock-out, a user input would
not have to be configured for Program Lock-out. However, this lock-out is
overridden by an inactive user input configured for Program Lock-out.
Ä
Å
LOC
SP-1
Ä
Å
LOC
SP-2
Ä
Å
LOC
SP-3
Ä
Å
LOC
SP-4
SP-1 SP-2 SP-3 SP-4 SETPOINT ACCESS*
The setpoint displays can be programmed for LOC, or Ent (See
following table). Accessible only with the Setpoint plug-in card installed.
Ä
Å
0.0
HI-t MAX CAPTURE DELAY TIME*
When the Input Display is above the present MAX value for this delay time,
the meter captures that Display Value as the new MAX reading. A delay time
helps to avoid false captures of sudden short spikes.
Ä
Å
0.0
LO-t MIN CAPTURE DELAY TIME*
When the Input Display is below the present MIN value for this delay time,
the meter captures that Display Value as the new MIN reading. A delay time
helps to avoid false captures of sudden short spikes. Ä
Å
OFF
b-LIt UNITS LABEL BACKLIGHT*
The Units Label Kit Accessory contains a sheet of custom unit overlays
which can be installed in to the meter’s bezel display assembly. The backlight
for these custom units is activated by this parameter.
Ä
Å
0.00
OFFSt DISPLAY OFFSET VALUE*
The Display Offset Value is the difference from the Absolute (gross)
Display value to the Relative (net) Display value for the same input level. The
meter will automatically update this Display Offset Value after each Zero
Display. The Display Offset Value can be directly keyed-in to intentionally
add or remove display offset. See Relative / Absolute Display and Zero
Display explanations in Module 2.
Ä
Å
2
dSP-t DISPLAY UPDATE RATE*
This parameter determines the rate of display update. A value of 20 updates
per second disables the internal correction and allows for the fastest possible
output response.
Ä
Å
rEd
HI
Ä
Å
rEd
Lo
!
Å
rEd
tOt
MAXIMUM DISPLAY LOCK-OUT*
MINIMUM DISPLAY LOCK-OUT*
TOTALIZER DISPLAY LOCK-OUT*
These displays can be programmed for LOC or rEd. When programmed for
LOC, the display will not be shown when selected by the DSP key. It is
suggested to lock-out the display if it is not needed. The associated function will
continue to operate even if its display is locked-out.
rEd
.
!
.
!
.
Ä
5.3 MODULE 3 - Display and Program Lock-out
Parameters ( )
PARAMETER MENU
5.3 MODULE 3 - Display and Program Lock-out
Parameters ( )
PARAMETER MENU
5.3 MODULE 3 - Display and Program Lock-out
Parameters ( )
PARAMETER MENU
5.3 MODULE 3 - Display and Program Lock-out
Parameters (3-LOC)
PARAMETER MENU
5.4 MODULE 4 - Secondary Function Parameters ( )
PARAMETER MENU
*Factory Setting can be used without affecting basic start-up.
*Factory Setting can be used without affecting basic start-up.
0to 250
0.0 to 3275.0 sec.
0.0 to 3275.0 sec.
-19999 to 19999
1 2 5 10
OFFON
SELECTION DESCRIPTION
LOC Not selectable in Display Mode.
rEd Selectable, but not changeable in Display Mode
during Program Lock-out.
Ent Selectable and changeable in Display Mode during
Program Lock-out.
20 updates/sec.
Ä
Å
0
At-t
Auto-Zero Tracking
0to 250 sec. Ä
Å
0.02
At-b
Auto-Zero Band
1to 4095
The meter can be programmed to automatically compensate for zero drift.
Drift may be caused by changes in the transducers or electronics, or
accumulation of material on weight systems.
Auto-zero tracking operates when the readout remains within the tracking
band for a period of time equal to the tracking delay time. When these
conditions are met, the meter re-zeroes the readout. After the re-zero operation,
the meter resets and continues to auto-zero track.
The auto-zero tracking band should be set large enough to track normal zero
drift, but small enough to not interfere with small process inputs.
For filling operations, the fill rate must exceed the auto-zero tracking rate.
This avoids false tracking at the start of the filling operation.
Fill Rate ≥ tracking band
tracking time
Auto-zero tracking is disabled by setting the tracking band parameter – 0.
5.4 MODULE 4 - Secondary Function Parameters ( )
PARAMETER MENU
5.4 MODULE 4 - Secondary Function Parameters ( )
PARAMETER MENU
5.4 MODULE 4 - Secondary Function Parameters ( )
PARAMETER MENU
4-SEC

12
*Factory Setting can be used without affecting basic start-up.
5.5 MODULE 5 - Totalizer (Integrator) Parameters ( )
PARAMETER MENU
Ä
Å
0.00
dECPt
TOTALIZER DECIMAL POINT*
For most applications, this matches the Input Display Decimal Point
(dECPt). If a different location is desired, refer to Totalizer Scale Factor.
0.000 0.00000.000.00
Ä
Å
_IN
tbASE
TOTALIZER TIME BASE
For most applications, this matches the process rate the Input Display value
represents. If the Totalizer is being accumulated through a user input
programmed for Batch, then this parameter does not apply.
Ä
Å
1.000
SCFAC
TOTALIZER SCALE FACTOR*
For most applications, the Totalizer reflects the same decimal point location
and engineering units as the Input Display. In these cases, the Totalizer Scale
Factor is 1.000. The Totalizer Scale Factor can be used to scale the Totalizer to
a different value than the Input Display. Common possibilities are:
1. Changing decimal point location (example tenths to whole)
2. Changing engineering units (example inches to meters)
3. Changing both decimal point location and engineering units.
4. Average over a controlled time frame.
Details on calculating the scale factor are shown later.
If the Totalizer is being accumulated through a user input programmed for
Batch, then this parameter does not apply.
Å
Locut
TOTALIZER LOW CUT VALUE*
-19999 to 19999
0.000 to 65.000
A low cut value disables Totalizer when the Input Display value falls below
the value programmed.
Ä
Å
NO
TOTALIZER POWER UP RESET*
Reset buffer
Do not reset buffer
rSt
NO
The Totalizer can be reset to zero on each meter power-up by setting this
parameter to reset.
SEC -seconds (÷ 1)
dRY -days (÷ 86400)
TOTALIZER HIGH ORDER DISPLAY
When the total exceeds 5 digits, the front panel annunciator TOT flashes. In
this case, the meter continues to totalize up to a 9-digit value. The high order 4
digits and the low order 5 digits of the total are displayed alternately. The letter
“h” denotes the high order display.
TOTALIZER BATCHING
The Totalizer Time Base and scale factor are overridden when a user input or
function key is programmed for store batch (bAt). In this mode, when the user
input or function key is activated, the Input Display reading is one time added
to the Totalizer (batch). The Totalizer retains a running sum of each batch
operation until the Totalizer is reset. This is useful in weighting operations,
when the value to be added is not based on time but after a filling event.
TOTALIZER USING TIME BASE
Totalizer accumulates as defined by:
Input Display x Totalizer Scale Factor
Totalizer Time Base
Where:
Input Display - the present input reading
Totalizer Scale Factor - 0.001 to 65.000
Totalizer Time Base - (the division factor of tbASE)
Example: The input reading is at a constant rate of 10.0 gallons per minute. The
Totalizer is used to determine how many gallons in tenths has flowed.
Because the Input Display and Totalizer are both in tenths of gallons, the
Totalizer Scale Factor is 1. With gallons per minute, the Totalizer Time Base
is minutes (60). By placing these values in the equation, the Totalizer will
accumulate every second as follows:
10.0 x 1.000 –.1667 gallon accumulates each second
60
This results in:
10.0 gallons accumulates each minute
600.0 gallons accumulates each hour
TOTALIZER SCALE FACTOR CALCULATION EXAMPLES
1. When changing the Totalizer Decimal Point (dECPt) location from the
Input Display Decimal Point (dECPt), the required Totalizer Scale Factor
is multiplied by a power of ten.
Example: Input (dECPt)–0.0 Input (dECPt)– 0.00
(x = Totalizer display is round by tens or hundreds)
2. When changing the Totalizer engineering units, the Totalizer Scale Factor
is the known conversion multiplier from Input Display units to Totalizer
units. Example: If Input Display is feet and the Totalizer needs to be in
yards, the conversion multiplier from feet to yards is 0.333. Enter 0.333 as
the Totalizer scale factor.
3. When changing both the Totalizer engineering units and Totalizer Decimal
Point, the two calculations are multiplied together. Example: Input
Display – feet in tenths (0.0) with Totalizer – whole yards (0), the scale
factor would be 0.033.
4. To obtain an average reading within a controlled time frame, the selected
Totalizer Time Base is divided by the given time period expressed in the
same timing units. Example: Average temperature per hour in 4 hour
period, the scale factor would be 0.250. To achieve a controlled time
frame, connect an external timer to a user input programmed for rtot2.
The timer will control the start (reset) and the stopping (hold) of the
Totalizer.
_IN - minutes (÷ 60)
hour -hours (÷ 3600)
The Totalizer accumulates (integrates) the Input Display value using one of
two modes. The first is using a time base. This can be used to provide an
indication of total flow, usage or consumption over time. The second is through
a user input or function key programmed for Batch (one time add on demand);
where accumulation is based on a completed event. If the Totalizer is not
needed, its display can be locked-out and this module can be skipped during
programming.
Scale
Factor
0.00 10
0.0 1
0 .1
x10 .01
x100 .001
Totalizer
dECPt
.001x10
.010
.1
0.0
1
0.00
10
0.000
Scale
Factor
Totalizer
dECPt
5.5 MODULE 5 - Totalizer (Integrator) Parameters ( )
PARAMETER MENU
.
.
.
.
-
-
-
.
.
o
.
.
-
5.5 MODULE 5 - Totalizer (Integrator) Parameters ( )
PARAMETER MENU
.
.
.
.
-
-
.
.
.
.
-
5.5 MODULE 5 - Totalizer (Integrator) Parameters (S-tot)
PARAMETER MENU
.
.
.
.
Ä199.99
P-uP
-
-
.
.
.
-

13
5.6 MODULE 6 - Setpoint (Alarm) Parameters ( )
PARAMETER MENU
CONFIGURE
- SELECT SETPOINT TO
- SETPOINT HYSTERESIS
- SETPOINT VALUE
- SETPOINT ACTION
to
to FLASH
rEu
YES
LAtC2
rEu
0.0 to 3.275.0 sec
0.0 to 3.275.0 sec
nor
OFF
LIt-n - SETPOINT ANNUNCIATORS
NO
Stb-n - STANDBY OPERATION
LAtC1
AUto
rST-n - RESET ACTION
nor
out-n - OUTPUT LOGIC
tOF-n - OFF TIME DELAY
tON-n - ON TIME DELAY
5.6 MODULE 6 - Setpoint (Alarm) Parameters ( )5.6 MODULE 6 - Setpoint (Alarm) Parameters ( )5.6 MODULE 6 - Setpoint (Alarm) Parameters (6-Spt)
SPSEL
SP-4SP-2
SP-3NO SP-1
HYS-n
SP-n
Rct-n
1 65000
-19999 99999
bANdAb-LO
TotHIAU-LO
dE-LOAb-HI
totLoAU-HI
dE-HIOFF
5.7 MODULE 7 - Serial Communications Parameters ( )
PARAMETER MENU
19200
9600
8
4800
2400
1200
600
7
dAtA - DATA BITS
300
bAUd - BAUD RATE
YES
0to 99
NO
NO
Abru - ABBREVIATED PRINTING
Addr - METER ADDRESS
Odd
EVEN
PAr - PARITY BIT
SPNttot
HILOINP
OPt - PRINT OPTIONS
5.7 MODULE 7 - Serial Communications Parameters ( )5.7 MODULE 7 - Serial Communications Parameters ( )5.7 MODULE 7 - Serial Communications Parameters (7-SrL)
5.8 MODULE 8 - Analog Output Parameters ( )
PARAMETER MENU
0-10
4-20
totHI
LOINP
0-20
tYPE - ANALOG TYPE
ASIN - ANALOG ASSIGNMENT 0.0 to 10.0 sec.
udt - ANALOG UPDATE TIME
AN-LO - ANALOG LOW SCALE VALUE -19999 to 99999
-19999 to 99999
Modules 6, 7, and 8 are accessible only with the appropriate plug-in cards installed. A quick overview of each Module is
listed below. Refer to the corresponding plug-in card bulletin for a more detailed explanation of each parameter selection.
This module is for RS232 and RS485.
AN-HI - ANALOG HIGH SCALE VALUE
5.8 MODULE 8 - Analog Output Parameters ( )5.8 MODULE 8 - Analog Output Parameters ( )5.8 MODULE 8 - Analog Output Parameters (8-Out)

14
5.9 MODULE 9 - Factory Service Operations ( )
PARAMETER MENU
Ä
Å
CodE
RESTORE FACTORY DEFAULTS
Use the arrow keys to display CodE 66 and press
PAR. The meter will display rESEt and then return to
CodE 50. Press DSP key to return to Display Mode. This
will overwrite all user settings with the factory settings.
The meter has been fully calibrated at the factory. Scaling
to convert the input signal to a desired display value is
performed in Module 1. If the meter appears to be indicating
incorrectly or inaccurately, refer to Troubleshooting before
attempting to calibrate the meter.
When recalibration is required (generally every 2 years), it should only be
performed by qualified technicians using appropriate equipment. Calibration
does not change any user programmed parameters. However, it may affect the
accuracy of the input signal values previously stored using the Apply (APLY)
Scaling Style.
Calibration may be aborted by disconnecting power to the meter before
exiting Module 9. In this case, the existing calibration settings remain in effect.
CALIBRATION Analog Output Option Card Calibration
Before starting, verify that the precision voltmeter (voltage output) or current
meter (current output) is connected and ready. Allow a 30 minute warm up
period. Then perform the following procedure:
1. Use the arrow keys to display Code 48 and press PAR.
2. Use the arrow keys to choose OUt and press PAR.
3. Using the chart below, step through the five selections to be calibrated. At
each prompt, use the 7558 arrow keys to adjust the external meter display
to match the selection being calibrated. When the external reading matches,
or if this range is not being calibrated, press PAR.
4. When NO appears remove the external meters and press PAR twice.
Note: Allow a 30 minute warm up period.
Warning: Calibration of this meter requires a signal source with an accuracy of
0.01% or better and an external meter with an accuracy of 0.005% or better.
Input Calibration
Before starting, connect -SIG (rear terminal 4) to COMM (rear Terminal 5).
This allows a single ended signal to be used for calibration. Connect the
calibration signal to +SIG (rear terminal 3) and -SIG (rear terminal 4). Verify
the Input Range jumper is in the desired position. (Refer to product literature
for jumper positions.) Perform the following procedure:
1. Press the arrow keys to display Code 48 and press PAR.
2. Choose the range to be calibrated by using the arrow keys and press PAR.
3. When the zero range limit appears on the display, apply 0 mV between +SIG
and -SIG.
4. Press PAR and ---- will appear, wait for next prompt.
5. When the top range limit appears on the display, apply the corresponding
+SIG and -SIG voltage (20 mV or 200 mV).
6. Press PAR and ---- will appear, on the display for about 10 seconds.
7. When NO appears, press PAR twice to exit programming.
8. Repeat the above procedure for each range to be calibrated or to recalibrate
the same range. It is only necessary to calibrate the input ranges being used.
9. When all desired calibrations are completed, remove -SIG to COMM
connection and external signal source.
10. Restore original configuration and jumper settings.
Ä
Å
48
CodE
PROBLEM REMEDIES
NO DISPLAY CHECK: Power level, power connections
PROGRAM LOCKED-OUT
MAX, MIN, TOT LOCKED-OUT CHECK: Module 3 programming
INCORRECT INPUT DISPLAY VALUE
CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level,
Module 4 Display Offset is zero, DSP is on Input Display
PERFORM: Calibration (If the above does not correct the problem.)
“OLOL” in DISPLAY (SIGNAL LOW) CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level
“ULUL” in DISPLAY (SIGNAL HIGH) CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level
JITTERY DISPLAY INCREASE: Module 1 filtering, rounding, input range
CHECK: Wiring is per EMC installation guidelines
MODULES or PARAMETERS NOT ACCESSIBLE CHECK: Corresponding plug-in card installation
ERROR CODE (Err 1-4) PRESS: RST Key (If unable to clear, contact the factory.)
TROUBLESHOOTING
For further assistance, contact technical support.
CHECK: Active (lock-out) user input
ENTER: Security code requested
SELECTION EXTERNAL METER ACTION
0.0A 0.00
4.0A 4.00 Adjust if necessary, press PAR
20.0A 20.00 Adjust if necessary, press PAR
0.0u 0.00 Adjust if necessary, press PAR
10.0u 10.00 Adjust if necessary, press PAR
Adjust if necessary, press PAR
5.9 MODULE 9 - Factory Service Operations ( )
.
.
.
.
.
PROBLEM REMEDIES
NO DISPLAY CHECK: Power level, power connections
PROGRAM LOCKED-OUT
MAX, MIN, TOT LOCKED-OUT CHECK: Module 3 programming
INCORRECT INPUT DISPLAY VALUE
CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level,
Module 4 Display Offset is zero, DSP is on Input Display
PERFORM: Calibration (If the above does not correct the problem.)
“OLOL” in DISPLAY (SIGNAL LOW) CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level
“ULUL” in DISPLAY (SIGNAL HIGH) CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level
JITTERY DISPLAY INCREASE: Module 1 filtering, rounding, input range
CHECK: Wiring is per EMC installation guidelines
MODULES or PARAMETERS NOT ACCESSIBLE CHECK: Corresponding plug-in card installation
ERROR CODE (Err 1-4) PRESS: RST Key (If unable to clear, contact the factory.)
For further assistance, contact technical support.
CHECK: Active (lock-out) user input
ENTER: Security code requested
5.9 MODULE 9 - Factory Service Operations ( )
.
.
.
PROBLEM REMEDIES
NO DISPLAY CHECK: Power level, power connections
PROGRAM LOCKED-OUT
MAX, MIN, TOT LOCKED-OUT CHECK: Module 3 programming
INCORRECT INPUT DISPLAY VALUE
CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level,
Module 4 Display Offset is zero, DSP is on Input Display
PERFORM: Calibration (If the above does not correct the problem.)
“OLOL” in DISPLAY (SIGNAL LOW) CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level
“ULUL” in DISPLAY (SIGNAL HIGH) CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level
JITTERY DISPLAY INCREASE: Module 1 filtering, rounding, input range
CHECK: Wiring is per EMC installation guidelines
MODULES or PARAMETERS NOT ACCESSIBLE CHECK: Corresponding plug-in card installation
ERROR CODE (Err 1-4) PRESS: RST Key (If unable to clear, contact the factory.)
For further assistance, contact technical support.
CHECK: Active (lock-out) user input
ENTER: Security code requested
5.9 MODULE 9 - Factory Service Operations (9-FCS)
66
.
.
.
PROBLEM REMEDIES
NO DISPLAY CHECK: Power level, power connections
PROGRAM LOCKED-OUT
MAX, MIN, TOT LOCKED-OUT CHECK: Module 3 programming
INCORRECT INPUT DISPLAY VALUE
CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level,
Module 4 Display Offset is zero, DSP is on Input Display
PERFORM: Calibration (If the above does not correct the problem.)
“OLOL” in DISPLAY (SIGNAL LOW) CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level
“ULUL” in DISPLAY (SIGNAL HIGH) CHECK: Module 1 programming, Input Range Jumper position, input connections, input signal level
JITTERY DISPLAY INCREASE: Module 1 filtering, rounding, input range
CHECK: Wiring is per EMC installation guidelines
MODULES or PARAMETERS NOT ACCESSIBLE CHECK: Corresponding plug-in card installation
ERROR CODE (Err 1-4) PRESS: RST Key (If unable to clear, contact the factory.)
For further assistance, contact technical support.
CHECK: Active (lock-out) user input
ENTER: Security code requested

15
DISPLAY PARAMETER FACTORY
SETTING USER SETTING
rANGE INPUT RANGE 0.02u
dECPt DISPLAY DECIMAL POINT 0.00
round DISPLAY ROUNDING 0.01
FILtr FILTER SETTING 1.0
bANd FILTER BAND 0.10
StYLE
PtS
SCALING STYLE
SCALING POINTS
KEY
2
INP 1 INPUT VALUE 1 0.000
dSP 1 DISPLAY VALUE 1 0.00
INP 2 INPUT VALUE 2 20.000
dSP 2 DISPLAY VALUE 2 100.00
INP 16
dSP 10
INP 12
dSP 6
INP 14
dSP 8
dSP 4
INP 15
dSP 16
dSP 9
INP 11
dSP 5
13
dSP 7
dSP 3
dSP 15
INP 10
dSP 11
INP 6
dSP 13
INP 8
INP 4
dSP 14
INP 9
INP 5
dSP 12
INP 7
INP
INPUT VALUE 16
DISPLAY VALUE 10
INPUT VALUE 12
DISPLAY VALUE 6
INPUT VALUE 14
DISPLAY VALUE 8
DISPLAY VALUE 4
INPUT VALUE 15
DISPLAY VALUE 16
DISPLAY VALUE 9
INPUT VALUE 11
DISPLAY VALUE 5
INPUT VALUE 13
DISPLAY VALUE 7
DISPLAY VALUE 3
DISPLAY VALUE 15
INPUT VALUE 10
DISPLAY VALUE 11
INPUT VALUE 6
DISPLAY VALUE 13
INPUT VALUE 8
INPUT VALUE 4
DISPLAY VALUE 14
INPUT VALUE 9
INPUT VALUE 5
DISPLAY VALUE 12
INPUT VALUE 7
INPUT VALUE 3
0.000
0.00
0.000
0.00
0.000
0.00
0.00
0.000
0.00
0.00
0.000
0.00
0.000
0.00
0.00
0.00
0.000
0.00
0.000
0.00
0.000
0.000
0.00
0.000
0.000
0.00
0.000
0.000
DISPLAY PARAMETER USER SETTING
FACTORY
SETTING
USr-1 USER INPUT 1 NO
USr-2 USER INPUT 2 NO
USr-3 USER INPUT 3 NO
F1 FUNCTION KEY 1 NO
F2 FUNCTION KEY 2 NO
rSt RESET KEY NO
Sc-F1 2nd FUNCTION KEY 1 NO
Sc-F2 2nd FUNCTION KEY 2 NO
I-INP Signal Input Parameters
2-FNC User Input and Function Key Parameters
3-LOC Display and Program Lockout Parameters
4-SEC Secondary Function Parameters
5-tOt Totalizer (Integrator) Parameters
8-Out Analog Output Parameters
7-Srl Serial Communication Parameters
DISPLAY PARAMETER USER SETTING
FACTORY
SETTING
HI
LO
MAX DISPLAY LOCK-OUT rEd
rEd
tOt rEd
SP-3
SP-1
SETPOINT 3 ACCESS
SETPOINT 1 ACCESS
LOC
LOC
SP-4
SP-2
SETPOINT 4 ACCESS
SETPOINT 2 ACCESS
LOC
LOC
CodE SECURITY CODE 0
HI-t MAX CAPTURE DELAY TIME 0.0
LO-t MIN CAPTURE DELAY TIME 0.0
At-b
At-t
dSP-t
AUTO-ZERO TRACK BAND
AUTO-ZERO TRACK DELAY
DISPLAY UPDATE TIME
0.02
0
2
OFFSt
b-LIt
DISPLAY OFFSET VALUE
UNITS LABEL BACKLIGHT
0.00
OFF
DISPLAY PARAMETER USER SETTING
FACTORY
SETTING
DISPLAY PARAMETER FACTORY
SETTING USER SETTING
dECPt TOTALIZER DECIMAL POINT 0.00
tbASE TOTALIZER TIME BASE _IN
SCFAC TOTALIZER SCALE FACTOR 1.000
Locut TOTALIZER LOW CUT VALUE -199.99
P-UP TOTALIZER POWER UP RESET NO
DISPLAY PARAMETER FACTORY
SETTING USER SETTING
bAUd BAUD RATE 9600
dAtA DATA BIT 7
PAr PARITY BIT Odd
Addr METER ADDRESS 0
Abru ABBREVIATED PRINTING YES
INP PRINT INPUT VALUE YES
tot PRINT TOTAL VALUE YES
HILO PRINT MAX & MIN VALUES YES
SPNt NO
PRINT SETPOINT VALUES
PARAMETER FACTORY
SETTING USER SETTING
tYPE 4-20
ASIN ANALOG ASSIGNMENT INP
AN-LO ANALOG LOW SCALE VALUE 0.00
AN-HI ANALOG HIGH SCALE VALUE 100.00
udt ANALOG UPDATE TIME 0.0
ANALOG TYPE
DISPLAY
PARAMETER VALUE CHART Programmer Date
7558 Strain Gage meter Meter# Security Code
MIN DISPLAY LOCK-OUT
TOTAL DISPLAY LOCK-OUT
40.00
nor
NO
AUto
nor
0.0
0.0
0.02
40.00
30.00
OFF
SP-4
USER SETTING
nor
NO
AUto
nor
0.0
0.0
0.02
30.00
OFF
SP-3
FACTORY
SETTING
USER SETTING
FACTORY
SETTING
20.00
nor
NO
AUto
nor
0.0
0.0
0.02
20.00
10.00
SETPOINT VALUE (alternate)*
OFF
SP-2
USER SETTING
nor
SETPOINT ANNUNCIATORS
LIt-n
NO
STANDBY OPERATION
Stb-n
AUto
RESET ACTION
rST-n
nor
OUTPUT LOGIC
out-n
0.0
OFF TIME DELAY
tOF-n
0.0
ON TIME DELAY
tON-n
0.02
SETPOINT HYSTERESIS
HYS-n
10.00
SETPOINT VALUE (main)
SP-n
OFF
SETPOINT ACTION
ACt-n
SP-1
FACTORY
SETTING
USER SETTING
FACTORY
SETTING
PARAMETERDISPLAY
6-SPt Setpoint (Alarm) Parameters
* Select alternate list to program these values.
3
PRINT T
T
FACT
TT
INP

16
7558 PROGRAMMING QUICK OVERVIEW
Table of contents
Popular Measuring Instrument manuals by other brands

Starr Instruments
Starr Instruments GMX-01 user manual

ETI
ETI ENA3D TECHNICAL MANUAL OF INSTALLATION

SZBJ
SZBJ BM5263 Operator's manual

Dwyer Instruments
Dwyer Instruments 477AV-000 Specifications-installation and operating instructions

Bosch
Bosch Professional GIC 4-23 C Original instructions

Rohde & Schwarz
Rohde & Schwarz NRT 1080.9506.02/.62 operating manual