LH-20S USER MANUAL
7
Fig. 4. Testing the moisture level between the resistance wire and the carrier pipe and
detecting the short circuit
The primary reasons for performing this measurement will be explained later in Practical
Advice. At this point, it should simply be noted that the measurement for the resistance wire is
sometimes performed instinctively after detecting moisture between the copper wire and the
carrier pipe in order to confirm the detected condition for both wires. In most cases, also after
detecting moisture, the two results are compared. Although the comparison of the results is
unlikely to produce useful conclusions, it should be performed just in case.
It happens very seldom that attempts to locate moisture in a branched pipeline system can be
made directly after detecting the moisture. Even when the secondary measurement indicates
that the insulation of the copper wire is in good condition, it is possible that there are several
leakages, and proper actions need to be undertaken in order to locate them all. First, divide
the moisturized alarm loop into separate sections by disconnecting the connections in
terminal boxes (BS-AD; PPA) and everywhere else. Then, using the above-described
secondary measurement method (fig. 4), measure the moisture level in each section. When
moisture is detected in two or more sections, form alarm loops by connecting (e.g. in a
terminal box) the end of the “moist” wire (MH≤11) from one pipe with the end of the twin
“dry” wire (MH=0; >99MΩ) from the second pipe. Only after forming such substitute alarm
loops you can attempt to locate the leakages (moisture). Note that the length of the alarm loop
formed from two resistance wires located in separate pipes is twice as large as the length
specified in the technical documentation. Furthermore, if the pipeline system is branched, the
resistance wire in one branch may be extended with the copper wire in a separate branch. For
these reasons, substitute loops should be formed with the help of the connection diagram.
Sometimes, moisture appears simultaneously in two parallel (located in separate pipes)
sections of wires which are to be connected to form a substitute loop. In such cases, use an
additional copper wire lined outside the tested sections of the heating pipelines.
3.3.
Secondary Measurements when the Przerwana pętla (Open Loop) or HI
messages are displayed or in case of Unstable Measurement Results
of the length and resistance of the alarm loop
Secondary measurements need to be performed when one of the situations mentioned in the
heading of this section occurs during primary measurements. When the Przerwana pętla
(Open Loop) message is displayed, check the detector wires of the LH-20S and all other
connections of the alarm loop (connection boxes, joints of the connectors welded to carrier
pipes). Detector wires (red and blue) are in good condition if, after shorting them together, the
second line of the detector display displays 0m and 0÷4Ω.
Presented below are some of the possible measurement results of the LH-20S detector which
signal that the alarm loop is open.
1) MH=0 >99MΩ 2) MH=10 2,2MΩ3) MH=0 >99MΩ