manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Liebert
  6. •
  7. Surge Protector
  8. •
  9. Liebert PowerSure PST User manual

Liebert PowerSure PST User manual

PowerSure™PST
Quick-Start Guide for 350-500VA; 120V
WHAT’SINTHE BOX
• Quick-Start guide
• PowerSure family user manual on CD (also
at www.liebert.com)
• Warranty card
• RJ-11 cord, 7 ft. (2.1 m)
• USB cable, 6 ft. (1.8m)
For more details, refer to the PowerSure user
manual on CD.
Para una información más detallada, consulte
el manual del usuario de la familia PowerSure
en el CD.
Refer to Bottom for
Cautionary Markings
Power ON/OFF/
Alarm Silence
Utility Indicator*
(Green)
Site Wiring Fault Indicator
(Red)
Fault Indicator* (Red/Green)
USB port
Circuit
protector
Output receptacles
(surge protection
only) Data Line
Protection
Connectors
TOP OF UPS LEFT SIDE OF UPS
RIGHT SIDE OF UPS
Power cord
6.5 ft. (2m)
Output receptacles
(battery backup and
surge protection)
INSTALLATION
Read all safety, installation and operating instructions in the PowerSure family user
manual on the included CD or at www.liebert.com before operating the UPS. Adhere
to all warnings on the unit and in the manual.
1. Install the UPS indoors in a controlled environment, where it cannot be accidentally
turned off. Place it in an area of unrestricted airflow around the unit, away from
water, flammable liquids, gases, corrosives and conductive contaminants. Maintain
a minimum clearance of 4 inches (100mm) on each side of the UPS. Maintain an
ambient temperature range of 32°F to 104°F (0°C to 40°C).
2. Plug the PST’s power cord into an AC outlet. Check the Site Wiring Fault Indicator
on the rear; if it is illuminated, refer to the Troubleshooting section.
3. Plug any computers and monitors into the orange receptacles for battery backup
and surge protection; other office machines that do not exceed the capacity of the
UPS may be plugged into either of the two (2) black receptacles, which provide
surge protection only.
4. Connect Phone/Fax/DSL/Internet/Modem devices to data line connectors.
5. Press and release the ON/OFF/Alarm Silence button to turn on the UPS. The UPS will beep and the Utility Indicator will illuminate (green).
6. Turn on connected equipment.
Plug this type of equipment
into black receptacles ONLY
Plug computers, monitors,
routers and cash registers into
orange receptacles
Inkjet
printers
Scanners Fax
machines
CONTROLS AND INDICATORS
This button controls output power to
the connected load and has three
functions:
•Turns the PowerSure PST ON
•Turns the PowerSure PST OFF
•Silences PowerSure PST alarms
TURN THE UPS ON: Press and release the
main ON/OFF button to start the UPS. An
audible alarm will sound briefly.
TURN THE UPS OFF: When the PST is ON,
hold the main ON/OFF button down for more
than 2 seconds to shut it down. An audible
alarm will sound briefly.
SILENCE AN ALARM: When a UPS alarm is
active, press and release the main ON/OFF
button to silence the audible alarm (Excep-
tions: low battery, overload and overtempera-
ture). DO NOT hold the button down for more
than 2 seconds or the PST will shut down.
CHECK THE PST’S CONDITION: Three sta-
tus indicators on the front of the UPS illumi-
nate to specify the status of the UPS (see
Troubleshooting section for details).
SITE WIRING FAULT INDICATOR (AMBER)
The Site
Wiring
Fault Indi-
cator on
the top of
thePST,
as shown,
illumi-
nates amber when the UPS detects a line-
neutral reversal or a poor neutral-ground.
(See Troubleshooting Chart if indicator is
illuminated.)
Site Wiring
Fault
Indicator
(Amber)
Top of UPS
SPECIFICATIONS
Model Number PA350-120U PA500-120U
Model Rating VA / W 350/225 500 / 300
DIMENSIONS: in (mm)
Unit W x D x H 6.6 x 9.8 x 3.7
(168 x 250 x 95)
6.6 x 9.8 x 3.7
(168 x 250 x 95)
Shipping W x D x H 9.4 x 13.8 x 5.6
(238 x 350 x 142)
9.4 x 13.8 x 5.6
(238 x 350 x 142)
WEIGHT: lbs (kg)
Unit 11.7 (5.3) 13.5 (6.1)
Shipping 12.1 (5.5) 13.9 (6.3)
INPUT AC PARAMETERS
Surge Protection 603J
Voltage Range Without
Battery Operation 98VAC - 140VAC ±3VAC
Frequency 57 - 63 Hz (±0.4Hz)
Input Power Cord 6.5 ft.attached, w/ NEMA 5-15 P
OUTPUT AC PARAMETERS
Output Receptacles
(3) NEMA 5-15R (orange) battery
backup+surge protection
(2) NEMA 5-15R (black) surge
protection
Voltage (Battery Mode) 120VAC ±8%
Output Current 2.9 A 4.2 A
Waveform (Battery Mode) Stepped Sinewave
Frequency (Battery Mode) 60Hz ±1Hz
Overload Warning >100%
Overload Shutdown >110%
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead
acid
Quantity x Voltage x Rating 1 x 12V x 5 Ah 1 x 12V x 7 Ah
Transfer Time 4 – 6 ms typical
Back-up Time: At 77°F (25°C), resistive loading, w/
fully charged batteries:
Full load 5 minutes 3 minutes
Half load 16 minutes 15 minutes
Recharge Time 12 hours to 90% capacity, after full
discharge into resistive load
ENVIRONMENTAL
Operating
Temperature
+32°F to + 104°F
(0°C to +40°C)
Storage
Temperature
+5°F to + 122°F (-
15°C to +50°C)
Relative
Humidity
0% to 95%, non-
condensing
Operating
Elevation
Up to 10,000 ft.
(3000 m) at 86°F
(30°C) w/o
derating
Audible Noise < 40 dBA, at 1
meter
AGENCY
Safety UL 1778, c-UL
Listed
Surge
ANSI C62.41,
Category A, Level
3, (IEEE 587,
Category A);
EN61000-4-5,
Level 3, Criteria A
ESD EN61000-4-2,
Level 3, Criteria A
Susceptibility EN61000-4-3,
Level 2, Criteria A
Electrical Fast
Transient/Burst
EN61000-4-4,
Level 3, Criteria A
Emissions
FCC Part 15,
Subpart B,
Class B
Harmonics EN61000-3-2
Conducted
Immunity EN61000-4-6
Flicker EN61000-3-3
Transportation ISTA Procedure
1A
COMMUNICATIONS
The PowerSure PST has a USB interface port for communication that will work with the built-in Microsoft
Power Manager software on the user’s PC, if the PC is so equipped. It will provide UPS status and man-
ages the automatic, orderly shutdown of the computer. The UPS (USB) communications meets HID stan-
dard, version 1.11. All USB models are compatible with Microsoft Windows 2000, Windows XP and Mac
OS 10.2 or later. All USB models ship with a 6 ft. (1.8m) USB cable.
All manuals and user guides at all-guides.com
all-guides.com
SL-23275QS (9/03) Rev.0
TROUBLESHOOTING
The information below indicates various symptoms a user may
encounter in the event the PowerSure PST experiences a problem.
Use this information to determine whether external factors caused
the problem. See Troubleshooting Chart for suggested remedy.
GUIDE TO STATUS INDICATORS
1. The Fault indicator
illuminates, indicating the
UPS detected a problem.
2. An alarm sounds, alerting that the
UPS requires attention. The alarm
can be silenced except for low
battery, overload and
overtemperature warning
conditions.
3. Utility and/or Battery indicators
may be illuminated as a diagnostic
aid to the operator, as shown
below:
Fault
(Red)
Site Wiring
Fault (Amber)
Utility/Battery
(Green) Diagnosis/
Audible Alarm
Normal Mode
——ON
UPS is
operating in
Normal Mode;
no beep.
— — Flashing
Battery Test
has been
initiated; no
beep.
— Flashing ON Site Wiring
Fault; no beep.
Flashing — ON
The unit is
overloaded;
beep every
half-second
ON — ON
The UPS has
failed;
continuous
beep
Flashing — —
Unit has shut
down due to
overload;
continuous
beep
ON — —
The UPS shut
down due to
failure;
continuous
beep
Battery Mode
— — Flashing
The UPS is
operating in
Battery mode;
beep every 5
seconds.
— — Flashing
UPS battery is
low; beep every
half-second
Flashing — Flashing
The unit is
overloaded;
beep every
half-second
ON — Flashing
The UPS has
failed;
continuous
beep
Fault
Indicator
Site Wiring
Fault Indicator
Utility/Battery
Indicator
!
+-
TROUBLESHOOTING CHART
If the UPS fails to operate properly, turn off the unit and repeat
the steps in the Installation section of this manual. If the prob-
lem persists, refer to the chart below:
Problem Cause Solution
UPS will not
start
Overload/
Short circuit
Check the circuit
protector on the side of
the UPS. If it is tripped,
reset it and restart the
UPS.
For further help, call
your local dealer,
Liebert representative
or the Liebert
Worldwide Support
Group.
UPS starts
on battery,
but will not
switch to AC
UPS not
plugged in
Plug in power cord
securely.
Circuit
protector
tripped
Reset the circuit
protector and restart the
UPS.
Power not
available at
utility
receptacle
Have the utility
receptacle checked by a
qualified electrician.
Input voltage
below
threshold
Wait until the voltage
rises to an appropriate
level or have the utility
receptacle checked by a
qualified electrician.
AC
overvoltage
Wait until voltage lowers
to an appropriate level
or have the utility
receptacle checked by a
qualified electrician.
UPS shuts
down, Fault
Indicator lit
Overload/
Short circuit
Check the circuit
protector on the rear of
the UPS. If it is tripped,
reset it and restart the
UPS.
If the problem persists,
disconnect some of the
equipment from your
UPS—the total wattage
of your equipment must
not exceed the capacity
of the UPS. For further
help, call your local
dealer, Liebert
representative or the
Liebert Worldwide
Support Group.
Internal UPS
fault
Site Wiring
Fault
Indicator
illuminated
Line-neutral
reversal/Poor
ground
connection
Have the utility checked
by a qualified
electrician.
UPS not
providing
expected
backup time
Overload Reduce load.
Battery not
charged due
to a recent
outage
Recharge battery.
MAINTENANCE
The PowerSure PST UPS requires very little maintenance. Follow these
practices to prevent problems.
CLEANING THE UPS
The following will help ensure trouble-free operation for years:
• Vacuum dust from the ventilation intake occasionally.
• Wipe the cover periodically with a dry cloth.
MAINTAINING BATTERIES
The batteries are valve-regulated, nonspillable, lead acid and must be
kept charged to retain their design life. The UPS continuously charges the
batteries when connected to the utility supply, even while the UPS is
switched off.
When storing the UPS, it is recommended to plug in the UPS for at least
24 hours every four to six months to ensure full recharge of the batteries.
WARRANTY REGISTRATION
To register for warranty protection:
• Visit the Quick Links section of our Web site at:
http://www.liebert.com
• Click on Product Warranty
Registration and fill in the form.
IF YOU HAVE ANY QUESTIONS,
PLEASE CONTACT US AT:
US: 800-222-5877
Outside the US: 614-841-6755
upstech@liebert.com
All manuals and user guides at all-guides.com

Other Liebert Surge Protector manuals

Liebert F277Y800-03 Manual

Liebert

Liebert F277Y800-03 Manual

Liebert Active Tracking User manual

Liebert

Liebert Active Tracking User manual

Liebert Little Glass House User manual

Liebert

Liebert Little Glass House User manual

Liebert Liebert Interceptor H2120Y444R-03 Manual

Liebert

Liebert Liebert Interceptor H2120Y444R-03 Manual

Liebert AccuVar User manual

Liebert

Liebert AccuVar User manual

Liebert LM250120YARCE Manual

Liebert

Liebert LM250120YARCE Manual

Liebert 100 User manual

Liebert

Liebert 100 User manual

Liebert Integrated Secured Protection User manual

Liebert

Liebert Integrated Secured Protection User manual

Liebert 100 - 2 User manual

Liebert

Liebert 100 - 2 User manual

Liebert MP-C5120 User manual

Liebert

Liebert MP-C5120 User manual

Liebert NET1080T User manual

Liebert

Liebert NET1080T User manual

Liebert LM User manual

Liebert

Liebert LM User manual

Liebert Power Strips User manual

Liebert

Liebert Power Strips User manual

Liebert Liebert LPGE Series User manual

Liebert

Liebert Liebert LPGE Series User manual

Liebert II User manual

Liebert

Liebert II User manual

Popular Surge Protector manuals by other brands

Gembird SIS-TUV user manual

Gembird

Gembird SIS-TUV user manual

LEGRAND SANUS SA-OWSP60 instruction manual

LEGRAND

LEGRAND SANUS SA-OWSP60 instruction manual

Intermatic AG3000 Installation instruction

Intermatic

Intermatic AG3000 Installation instruction

Maruson AVR Series user manual

Maruson

Maruson AVR Series user manual

Infinite Transtector ACP 100DR2 Series installation instructions

Infinite

Infinite Transtector ACP 100DR2 Series installation instructions

Chenzhu CZLB-EX Series user manual

Chenzhu

Chenzhu CZLB-EX Series user manual

Echogear EGAV-ASBC62 owner's guide

Echogear

Echogear EGAV-ASBC62 owner's guide

Chamberlain LiftMaster 990LM quick start guide

Chamberlain

Chamberlain LiftMaster 990LM quick start guide

Transtector CPX Series installation instructions

Transtector

Transtector CPX Series installation instructions

CyberPower B0520SC0-FR user manual

CyberPower

CyberPower B0520SC0-FR user manual

Leviton R Series manual

Leviton

Leviton R Series manual

Panamax MIW-XT installation instructions

Panamax

Panamax MIW-XT installation instructions

Monster MDP 650 Instructions and warranty information

Monster

Monster MDP 650 Instructions and warranty information

Philips SPP4220WA Specifications

Philips

Philips SPP4220WA Specifications

Adcom ACE-315 owner's manual

Adcom

Adcom ACE-315 owner's manual

Shopify EVP-3PH quick guide

Shopify

Shopify EVP-3PH quick guide

Eaton Crouse-hinds series instruction sheet

Eaton

Eaton Crouse-hinds series instruction sheet

ABB REU615 Applications manual

ABB

ABB REU615 Applications manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.