
6 (10)
Adjustment
As the LK Minishunt M60n is intended for con-
nection to existing heating systems, the available
drive pressure and ow on the primary side are
often unknown. Without this information the
theoretical adjustment values of the minishunt
cannot be calculated. Adjustment should then be
carried out as described below.
If the available drive pressure and ow on the
primary side are known, the theoretical adjust-
ment for the minishunt can be calculated, refer
to the Project planning and design guidance for
LK Underoor heating.
1. Carry out air bleeding of the oor heating
system and the minishunt, as shown above.
2. Start the circulation pump. Upon start up,
use the pump's automatic venting routine
to remove accumulated air in the pump.
The automatic venting routine starts after 3
seconds and proceeds for 10 min. The ven-
ting routine is indicated with a fast ashing
green diode light.
After completing the venting process, the
constant pressure curve that best matches
the requirements of the system is chosen,
see the capacity chart.
3. Set the switch 2/1 pos. 18 for single or twin
pipe radiator systems (twin pipe radiator
system is factory set at delivery). For single
pipe systems the valve is gradually ope-
ned until the correct heating capacity and
temperature is achieved to the following
radiators.
4. Set the primary temperature from the hea-
ting source to the minishunt temporarily to
approx. 55 °C.
5. Set the temperature limiter TEMP to pos. 12
in accordance with the table below. Normal
setting is about 45 ºC.
6. Set the thermostat valve pos. 4 in accord-
ance with the table below.
7. Allow the system to stabilise for about 10
min. The feed temperature should now be
35-45 ºC.
NOTE!
If the temperature is too low, see
Troubleshooting. Note that at start up a
system in an unheated concrete slab,
can take up to 24 hours before the feed
temperature has reached the correct level.
NOTE!
If the temperature is too high, adjust
the feed temperature using the temperature
limiter pos.12 in accordance with the table
below.
8. Finish by resetting the primary temperature
from the heat source to normal temperature.
Settings for the temperature limiter (TEMP)
For limiting the feed temperature for underoor
heating.
Settings for the tempera-
ture limiter (TEMP)
Max. temperature
0 22 ºC
1 25 ºC
2 35 ºC
3 40 ºC
4 45 ºC
5 55 ºC
Settings for the thermostat with a capillary
tube connected sensor
Settings for the thermo-
stat
Room temperature
1 8 ºC
2 14 ºC
3 20 ºC
4 26 ºC
5 32 ºC
Circulation pump
The circulation pump has automatic speed con-
trol, which reduces power consumption and gi-
ves a quieter operation as the pump adjusts the
ow according to the requirements of the system.
A cast arrow on the pump housing indicates the
direction of the ow.
EN.33.C.204.2022-02-10
Assembly instructions | LK Minishunt M60n