PFR-1750 LOAD CO NTRO L
INSTALLATIO N, SET UP AND ADJUSTMENT
Th e M o d e l P FR-1 7 5 0 m o n i t o rs t h e t ru e p o w e r g o i n g t o a m o t o r.
By se nsing po we r (vo lts x amps x po we r fac to r) rathe r than just
amps, there is much greater sensitivity. The unit has two adjust-
able trip points.
MOUNTING
Wiring is done to un-pluggable terminal strips on the rear of the unit.
Th re e wa ys to m o u n t :
•Ondoororraceway-usecutouttemplate
•PanelMount-usetemplate+optionalBezelKit(NoCharge)
•Onwall-onstandardoutdoorjunctionbox+optional
Outlet Box Adapter (No Charge)
VO LTAGE
120 volts AC is taken from two of the phases. If the motor starter
already has a 120-volt control transformer with 10VA
of free capacity, it can be used. Otherwise, install a separate
transformer. It is okay if the secondary betrig is grounded.
BE SURE TO NOTE WHICH TWO PHASES SUPPLY THE
TRAN SFO RM ER.
In 1 2 0 / 2 0 8 V t hre e -p h a se syst e m , t he 1 2 0 V M UST c o m e
fro m a tra nsfo rm e r c o nn e cte d to two o f the p ha se s. The
120V phase to ground voltage cannot be used.
CURRENT
Th e c u r re n t sig n a l is t a ke n fro m t h e REMAIN IN G p h a s e .
Th is c u r re n t s a m p le p a s se s t h ro u g h t h e Ra n ge Fin d e r To ro id .
It is VERY IMPO RTANT that the current signal comes from the phase
that IS NOT supplying the 120V control transformer. Be extra careful
when the machine has reversing starters or multi-speed windings. If a
wrong phase is used the control will either:
•Workbackwards •Havereducedsensitivity
If yo u a re u sin g a va ria ble fre que nc y d rive , u se a d iffe re nt c o ntro l.
Call LOAD CONTROLS, INC. for help.
LO A D C O N TRO LS
INC O RPO RATED
Call LOAD CONTROLS, INC for help.
PFR-1750 LOAD CONTROL
INSTALLATION, SET UP AND ADJUSTMENT
MOUNTING
VOLTAGE
CURRENT
FU LL SCALE CAPACITY AT 4 6 0 VO LTS
Th e Ra n ge Fin d e r To ro id h a s s ix m o to r siz e c h o ic e s.
Se le ct o ne tha t is e q ua l o r la rge r than yo u r m o to r. Th is
will leave some headroom.
•
For motors less than 5 HP (460 volt), take extra turns.
•Formotorsgreaterthan50HP,useRangeFinder
To r o i d + C u r r e n t Tr a n s f o r m e r .
MOTO R FULL % FULL RANGE TURNS CURRENT
SIZE SCALE LO AD FIND ER TRANS-
CAPACITY SWITCH FORMER
1/2 HP .6 HP 123 2 ON 8
11.251232ON4
1-1/2 1.65 109 2 ON 3
22.701342ON2
33.801283ON2
55.501102ON1
7-1/2 8.25 110 3 ON 1
10 11.0 110 4 ON 1
15 27.5 183 5 ON 1
20 27.5 137 5 ON 1
25 27.5 110 5 ON 1
30 55.0 183 6 ON 1
40 55.0 138 6 ON 1
50 55.0 110 6 ON 1
60 84.0 140 1 ON 1 100:5
75 84.0 112 1 ON 1 100:5
100 130 130 1 ON 1 150:5
125 130 104 1 ON 1 150:5
150 173 115 1 ON 1 200:5
200 216 108 1 ON 1 250:5
250 260 104 1 ON 1 300:5
300 346 115 1 ON 1 400:5
MULTIPLIERS
Fo r n o m in al vo lta ge s o t h e r t h a n 4 6 0 vo lt s,
multiply 460V full scale by:
208V = .45
230V = .5
380V = .83
415V = .9
575V = 1.25
For Kilowatts multiply Full Scale HP x .746
Fo r m o to r siz e s o r c ap ac itie s n o t in ta b le :
% Full Load = Full Scale Capacityx 100
Yo u r M o t o r S i z e
+ -
4-20
MA OUTPUT
REMOTE RESET
REMOTE
TRIP 1
RELAY OUTPUTS —
POWER ON, NOT TRIPPED
TRIP 2 TRIP 1
12345678 910111213141516
MOTOR
RANGE FINDER
TOROID
CURRENT FROM
REMAINING PHASE
VOLTAGE TRANSFORMER
WITH 120V SECONDARY
TRIP 2
FULL SCALE CAPACITY AT 460 VOLTS
MULTIPLIERS
FO R MO TO RS LESS TH AN 5 HP
Ta k e m o r e “ t u r n s ” o f t h e l e g t h r o u g h t h e To r o i d . Ea c h
time the wire passes through the Toroid is a “turn”.
This is o n e tu rn. This is tw o turns.
FO R M O TO RS G REATER TH AN 5 0 HP
A Curre nt Tra nsfo rm e r is use d to re duc e the p rima ry
current. The 5-amp secondary passes through the Toroid.
Pass se co n d ary o f CT t h ro u gh t o ro id .
CAUTIO N
Whe n current is flowing through the primary o f the
external current transformer, always have a wire be-
tween the two brass Terminals on the CT.
If the y are le ft o pe n, dange ro us and de struc tive vo lt-
ages can develop.
RAN GE FIN D ER TO RO ID HOOKING UP THE RESET
Control can be reset three ways:
•
Manually with the Reset button on the control.
•Remotelywitharemotelylocatedresetbutton
or relay.
•Automaticwithajumper.
Re m o te Re se t -
Momentarily connect Terminal 4 to Terminal 6 for Trip 2.
Momentarily connect Terminal 5 to Terminal 6 for Trip 1.
Auto m atic Re se t-
Ju m p e r Te rm in a l 4 o r 5 to Te rm in a l 6 .
Th e t e rm in a ls fo r Re s e t ge n e ra te a sm a ll a m o u n t o f
current (8-12 milliamps). To reset, you just need to
connect the terminal to the circuit common (Terminal 6).
Th e sw it c h e s o r re la ys t h a t yo u u se m u st b e su it a b le fo r
lo w c urre n t (G o ld fla sh e d c o nta cts, Re e d Re lays, Me rc ury
Switche s).
4-20 MILLIAMP ANALOG OUTPUT
Th e An a lo g O u t p u t is d ire c tly p ro p o r tio n a l t o Fu ll Sc a le
capacity. It is always active. 500 ohm maximum con-
nected impedance.
Te r m i n a l 2 4 -2 0 m A P o s it ive
Te r m i n a l 3 4 -2 0 m A N e g a t ive
Use twisted pair or in noisy environments, use shielded
cable. Ground shield at other end.
Use the Full Scale capacity from the chart to scale
external meter, chart recorders or computers.
THE PFR-1750 POWERS THE 4-20MA SIGNAL.
DON’TUSEAN EXTERNALDC POWER SUPPLY.
SPECIFICATIONS PFR-1750
EN C LO S U RE
Glass-filled Polycarbonate
NEMA 4, 4X - STYLE
(3 1/ 4 ” x 6 1 / 4” x 2 ”)
(83 mm x 160 mm x 54 mm)
CAPACITY
To 5 0 h o r s e p o w e r d ir e c t ly
through Toroid
To 5 0 0 h o r s e p o w e r w it h e x t e r n a l
Current Transformer & Toroid
DIGITALLOAD DISPLAY
.4” LED 3 Digit
RELAY O U TPU TS
(2) Fo rm C 3 AMP @ 300 VAC o r
1/8 HP @240 VAC
La t c h w h e n t r ip p e d
1 1/8” Hole
3 1/2”
2”
2 3/8”
ANALO G O UTPU T
4-20mA; powered by the
PFR-1750 500 O HM
maximum connected
im pe d a nc e
RESPO N SE TIME
25 Milliseconds
TEM P ER ATU RE
0ºC - 55ºC
TIM ERS
Start-up a n d Trip D e lay(s)
0-90 second
0-2 second in .1 second
incre m e nts
2-90 second in 1 second
incre m e nts
CAUTION
THE PFR-1750 POWERS THE 4-20 MA SIGNAL
DON’T USE AN EXTERNAL DC POWER SUPPLY!
SPECIFICATIONS PFR-1750
RANGE FINDER TOROID
HOOKING UP THE RESET
4-20 MILLIAMP ANALOG OUTPUT
FOR MOTORS LESS THAN 5 HP
FOR MOTORS GREATER THAN 50 HP
TO SET FULL SCALE
ï After hook-up, find your HP , KW or % fr om the chart.
ï Decide if y ou want to display HP, % or KW .
ï The c ycles through the choices sho wn below and
blinks slowly for each choice. Each pr ess of moves
you to the next choice.
FULL
SC ALE
FULL
SC ALE
FRONT P ANEL SET-UP TIPS
1) None of t he settings will be changed until you hold
down and the fast blinking stops.
2) Five seconds af ter you have pressed a button, the
Control will return to normal oper ation.
3) If you hold do wn the digits will continue to
change.
4) You only need t o do when you install the Contr ol
(or if y ou change the hook-up).
ENTER
FULL
SC ALE
DIGITS ÆDECIMAL ÆDECIMAL ÆDECIMAL ÆHP Æ%ÆKW
XXX. XX.X X.XX
to change if this is if this is if this is if this is if this is if this is
your choice, your choice, your choice, your choice, your choice, your choice,
press press press press press press
Ø Ø Ø Ø Ø Ø Ø
until fast until fast until fast until fast until fast until fast until fast
blink stops blink stops blink stops blink stops blink stops blink stops blink stops
ENTER ENTER ENTER ENTER ENTER ENTER ENTER
TO VIE W AND CHANGE TH E SET POINTS
AND DEL AY TIMES
c ycles through the choices. The LED f or each choice
will turn ON.
To change a setting, use
Press ENTER until quick blinking s tops to store your new
choice.
After 5 seconds if y ou havenít pressed any buttons,
control will return t o normal oper ation.
Start-up Timer
The Start-up Timer bypases the Control during motor
start-up to avoid false trips because of curr ent inrush. For
convenience, the TIMING BEGINS WHEN THE MO TO R
STARTS. The S tart-up LED stays lit until the start-up period
is over.
The start-up time should be:
ï Long enough so that the load has s tabilized.
To bypass Start-up Timer set time to zer o seconds.
Dela y Timers
To avoid nuisance trips fr om short overloads, Dela y
Timers bypass the Contr ol for the select ed time. The
relays wonít trip until the time is exceeded. If t he trip
condition goes away before the time is up, the timer
resets to zer o.
ï Start with minimum Dela y. If y ou are getting trips
where you donít w ant them, increase the Dela y
Time.
888-600-3247
10 PICKER ROAD 508-347-2606
STURBRIDGE, MA 01566 FAX 508-347-2064
11/2001
53 TEC HN O LO G Y PARK RO AD
STURBRIDGE, M A 01566
888-600-3247
508-347-2606
FAX 508-347-2064
None of the settings will be changed until you hold
FRONT PANEL SET-UP TIPS
Five seconds after you have pressed a button, the
Control will return to normal operation.
• After hook-up, find your HP, KW or % from the chart
• Decide if you want to display HP, % or KW
•
presspresspress
Delay Timers
To avoid nuisance trips from short overloads, Delay
Timers bypass the Control for the selected time. The
relays won’t trip until the time is exceeded. If the trip
condition goes away before the time is up, the timer
resets to zero.
• Start with minimum Delay. If you are getting
trips where you don’t want them, increase the Delay
Time.
The LED for each choice
Press ENTER until quick blinking stops to store your new
choice.
After 5 seconds if you haven’t pressed any buttons,
control will return to normal operation.
Start-up Timer
The Start-up Timer bypasses the Control during motor
start-up to avoid false trips because of current inrush. For
convenience, the Start-up LED stays lit until the start-up
period is over.
The start-up time should be:
• Long enough so that the load has stabilized
To bypass Start-up Timer set time to zero seconds
10/2015
when you install the Control
(or if you change the hook-up).
to do
TO VIEW AND CHANGE THE SET POINTS
AND DELAY TIMES
shown
cycles through the choices. The LED for each choice
will turn ON.

Popular Measuring Instrument manuals by other brands

FUTURO 112405 instructions

FUTURO

FUTURO 112405 instructions

EUTECH INSTRUMENTS CYBERSCAN PHION 510 PHION METER instruction manual

EUTECH INSTRUMENTS

EUTECH INSTRUMENTS CYBERSCAN PHION 510 PHION METER instruction manual

EUTECH INSTRUMENTS ECOSCAN DO 6 DO METER instruction manual

EUTECH INSTRUMENTS

EUTECH INSTRUMENTS ECOSCAN DO 6 DO METER instruction manual

Kilews KTM-CSH Operation manual

Kilews

Kilews KTM-CSH Operation manual

ABB AK101 user guide

ABB

ABB AK101 user guide

Twinno T6570 operating manual

Twinno

Twinno T6570 operating manual

GeoMax Zoom 25 Series quick guide

GeoMax

GeoMax Zoom 25 Series quick guide

Microlife PF200 instruction manual

Microlife

Microlife PF200 instruction manual

Ametek AMEVision 3050-OLV user manual

Ametek

Ametek AMEVision 3050-OLV user manual

Fluke 321 Instruction card

Fluke

Fluke 321 Instruction card

Agreto PFM II user manual

Agreto

Agreto PFM II user manual

SATO KEIRYOKI SK-620PH instruction manual

SATO KEIRYOKI

SATO KEIRYOKI SK-620PH instruction manual

Neptune Technology CMIU Installation and maintenance guide

Neptune Technology

Neptune Technology CMIU Installation and maintenance guide

Aeris A300 XT quick start guide

Aeris

Aeris A300 XT quick start guide

SKC 701-001NBS operating instructions

SKC

SKC 701-001NBS operating instructions

Vernier Go Direct ORP manual

Vernier

Vernier Go Direct ORP manual

Huma-i White HI-100 user manual

Huma-i

Huma-i White HI-100 user manual

PCB Piezotronics IMI SENSORS 607A11/075AC Installation and operating manual

PCB Piezotronics

PCB Piezotronics IMI SENSORS 607A11/075AC Installation and operating manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.