Local Control Network LCN-SHS Series User manual

LCN-SHS
Installation guide Local Control Network - building controls in perfection
1
Sensor module for DIN rail mounting
The LCN-SHS is a sensor module for building installation in Bus technology. It has the
same functions as the LCN-SH, however without electronic (dimming) outputs.
Application
The 2HP sized LCN-SHS module is for installing in
dry rooms in main and normal distribution boxes.
It has 3 electronic outputs (see illustration), which
are seperately controlled. Amongst other things,
the push-button converters LCN-BT4H / LCN-
BU4L, the relay contacts LCN-R8H / LCN-R2H /
LCN-R4M2H and also the binary sensors LCN-
BT4H/LCN-BU4L (as mentioned above) can be
connected.
The operating programme from the LCN-SHS
includes further functions like 2 proportional
regulators, 5 thresholds, the LCN panel system
etc..
L
L
NNDD
push button-
connection
impulse sensor-
connection
periphery
connection
phase
N
data
sensor side
power side
LCN
Sensor-Modul
Controller
U =230V, P =0.4W
N V
LCN-SHS
status LEDs
®

LCN-SHS Installation guide
Local Control Network - building controls in perfection
2
The connection
The module has two connecting blocks: the power supply side with screwless terminals and
the sensor side with three plug connections.
The terminals are colourfully marked as follows
Description: Colour: Function:
orange data wire
blue neutral wire
L,L black phase (live)
The power connections are voltage fixed up to max. 4kV(L+N) according to VDE, additio-
nal measures against overvoltage in operational conditions are not necessary. Measures
for lightning protection in the building should be applied as usual (coarse protection).
Note:
As always with electronic, suppressor elements (e.g.VDR´s) are to be planned with coils
from 230V~ contactors and relays, that are installed in the same distribution boxes as the
LCN modules.
D,D
N,N
®

3
LCN-SHS
Installation guide Local Control Network - building controls in perfection
Sensor technology
The red sensor connecting plugs are protected only in a low extent against overvoltage. A
contact with 230V will destroy the module. The sensor terminals are on the N potential,
which means they are not decoupled from the electrical isolation. That´s why you must
make sure, that a protection against contact for the user in every operating condition is
ensured. The push-buttons from all of the approved switch panel systems ensure this
protection.
The module has three sensor connections, which can be used as additional switchings, if
necessary as actuator. The functions can be programmed with the setup programme LCN-
P or LCN-PRO:
T-connection:
Over a LCN-T8 or push-button converter (LCN-BT4H/BU4L), max. 8 conventional push-
buttons can be evaluated. Apart from that, there are a selection of sensors that can be
connected here alternatively. The module has the required analogue value processing with
up to 12bit accuracy.
I-connection:
Here the IR-receiver for the remote control can be connected, additionally the binary
sensor LCN-B3I, the motion detector LCN-BMI, the transponder reader LCN-UT and the
temperature sensor LCN-TS. These components can be operated parallel on the I-
connection by using the LCN-IV.
The I-connection can alternatively be served as a counter for pulses up to 1kHz, when no
further periphery is connected.
®

4
LCN-SHS Installation guide
Local Control Network - building controls in perfection
P-connection:
Here you can connect for example, the 4-way binary sensor (LCN-BT4H/-BU4L), the
current sensor (LCN-BS4) and the relay blocks (LCN-R8H/-R4M2H/-R2H. The LCN-
BT4H/BU4L and LCN-BS4 will be detected automatically. The LCN-R8H has to be
activated first with the LCN-P or LCN-PRO .
Notes about the sensor technology:
The module monitors overloads and short circuits (T-, I-, P-port) on its sensor technology.
Should the module be short circuited on its periphery, due to wiring errors, it will switch off
the power supply from the sensor for 4 seconds by itself. If 2 further tests show the same
error, it will switch off for 8s + 30s and a status message will be sent to the bus:
“module reports overload/short circuit periphery.”,
apart from that the red LED will flash cyclic, as long as the sensor technology is
switched off.
In this case check the connected sensor technology and the wiring.
The LCN-SHS module stays accessible and operational even after these errors!
®

5
LCN-SHS
Installation guide Local Control Network - building controls in perfection
Status display of the lamps
nr. of flashes message
normal operation
self testing-error, module is not programmed
bus error: module cannot send
(reserved)
module is in programming mode
nr. of flashes message
key was pressed, command was sent
different errors: please check with PC and the LCN-PRO
received telegram data was faulty
IR-telegram received from unauthorised sender
received illegal command (will be ignored)
error in the structure of a received command
parameter of a command exceeds permitted limit
command received cannot be carried out at the moment
periphery (T-,I-connection) was overloaded and/or
short circuited. Both LED´s left and right side of the T-connection,
show switch and dimming conditions of the outputs.
GREEN (flashes constantly):
1
2
3
4
5
RED (flashes only when occurances are entered):
1
2
3
4
5
6
7
8
cyclic (30s.)
®

6
LCN-SHS Installation guide
Local Control Network - building controls in perfection
In the menus and help texts found in the programme LCN-PRO, further informations and
properties of the module are available.
Without parameterization the module has no functions.
Because no access to the module is required when first programming, (no programming
button, all functions are controlled over the bus), the module may be installed before being
setting up. In this case the serial number of the unprogrammed module should be noted in
the building plan, for better identification.
Despite its extensive functionalities, the LCN system is simple to install and programme: It´s
all in the hands of the electrician. However a training course is necessary for every
electrician, who installs this system. The direct users support over the telephone hotline,
is only free of charge and open to installers who have taken part in a training course.
Important note:
®

7
LCN-SHS
Installation guide Local Control Network - building controls in perfection
Properties of the built-in control progamme::
Issued numbers:
group members:
command tables:
links:
scene storage:
Timers (amount):
outputs (2):
keys (4):
key blocking (1):
output blocking (2x1):
clock (1):
relay (2):
module ID: 5..254, group nr.: 5..254
segment nr.: 5..124
12 (fixed) plus 10 (dynamic)
A, B, C & D with each 2 * 8 targets
(each 3 commands) and
32 targets at 3 commands (double operation)
depending on: logic, time, sensors, output-
conditions, panel and fault report-processing
(4-way) according to DIN.
10 x 10 per light group (brightness & ramp)
10ms..40 min
each 1s .. 45 days
each 1s .. 45 days
1s .. 45 days (part & full blockage)
0,3s .. 6500 s
30ms ..4 min
®

8
LCN-SHS Installation guide
Local Control Network - building controls in perfection
Measured value processing
triggering:
pre processing:
evaluation:
counting/computing:
Remote control
keys:
amount access codes:
zentral access control:
transponder:
Properties of the built-in control progamme:
8, 10 or 12 bit
value correction, hum sound suppression, remote
query
two continuous controllers
input sizes can be calculated as difference values
5 thresholds (=10 commands) with hysteresis
0 ... 30000, can be cascaded
16 (with LCN-RT: 4 key levels)
250 + serial number evaluation (transponder)
> 16 mio codes
16 codes evaluated direct, many over LCN-GVS
®

9
LCN-SHS
Installation guide Local Control Network - building controls in perfection
Connection:
power supply:
power consumption:
terminals/wire type (load side):
connection sensor side:
Technical data:
230VAC 15%, 50/60Hz (110VAC version available)
0,4W
screwless, solid max. 2,5mm² oder fine wire with end sleeves
max. 1,5mm²
loop through current max. 16A
T-, I- und P-connection
±
®

10
LCN-SHS Installation guide
Local Control Network - building controls in perfection
Technical data:
ISSENDORFF KG, 31157 Sarstedt
LCN-SHS D012/2012
0 0
-10 C..+ 40 C
max. 80% rel., non condensing
use as stationary installation according to VDE632, VDE637
IP20
38mm (2HP) x 92mm x 66,5mm
DIN rail 35 mm (DIN50022)
Installation:
operating temperature:
air humitidy:
environmental conditions:
protection art:
dimensions (BxDxH):
installation:
Technical information and images are non binding. Changes are reserved.
Technical hotline: +49 5066 998844 or www.LCN.de
®
This manual suits for next models
5
Popular Controllers manuals by other brands

Simrad
Simrad 301 DP user guide

Zehnder Pumpen
Zehnder Pumpen ZP SPEEDCONTROL COMFORT operating manual

gefran
gefran WATTCOR W312 Installation and operation manual

Evenheat
Evenheat Set-Pro operating manual

ITT
ITT Engineered Valves Advantage 2.1 8 Series Installation and operation manual

PPM Technology
PPM Technology SPC-1 Operation manual

Profi-pumpe
Profi-pumpe PSM01134U operating instructions

AMX
AMX AXB-CAM Specifications

Porsche
Porsche Home Energy Manager installation manual

Bray
Bray Series 70 Installation, operation and maintenance manual

Meade
Meade DS-2090AT-TC instruction manual

Phoenix Mecano
Phoenix Mecano LD1000E Assembly instructions