EM-7802-G Rev.5 P. 2 / 10
COMPONENT IDENTIFICATION
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
MS X10 X1
NODE ADD. B.RATE
CNFG.
12345678
0123456789ABCDEF
10 11 12 13
2341
15 16 17 18
7896
14
5
NS
23415
(A) Status Indicator LED
(B) Node Address Setting Rotary SW
(C) Baud Rate Setting Rotary SW
(D) Operating Mode Setting DIP SW (SW1)
(E) PC Configurator Jack
(F) Discrete Output Status Indicator LED
(G) DeviceNet, Power Supply Terminals
(H) Output Terminals
(A)
(G) (H)
(B) (C) (D) (E) (F)
■STATUS INDICATOR LED
ID S TAT E TO INDICATE
MS Green Operating in a normal condition
Blinking Green Standby (needs commissioning)
Red Critical failure
Blinking Red Minor failure
OFF No power supplied
NS Green Link on-line and connections in the
established state
Blinking Green Link on-line but no connections in
the established state
Red Critical link failure
Blinking Red Minor link failure
OFF No power supplied
■DISCRETE OUTPUT STATUS INDICATOR LED
LED red indicators show the signal status.
ON : LED ON
OFF : LED OFF
■NODE ADDRESS
Node Address is selected between 1 and 63 in decimal. The
left switch determines the tenth place digit, while the right
switch does the ones place digit of the address.
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
8
7
6
Node Address Setting (x1)
Factory setting : 00
Node Address Setting (x10)
■BAUD RATE
Baud Rate is selected with the rotary switch.
5
4
3
2
1
0
9
8
7
6
Baud Rate Setting
0 : 125 kbps (factory setting)
1 : 250 kbps
2 : 500 kbps
3 thr. 9 : Auto-tracking
The R7D communicates in the baud rate setting detected at
the startup with the switch set to the positions 0 (125 kbps),
1 (250 kbps) or 2 (500 kbps).
For the settings 3 through 9, it analyzes the PLC’ s network
to determine the baud rate on the network.
■OPERATING MODE
(*) Factory setting
• Extension: SW1-1, 1-2
SW1-1 SW1-2 EXTENSION
OFF OFF No extension (*)
ON OFF Discrete input, 8 or 16 points
OFF ON Discrete output, 8 or 16 points
• Output at the Loss of Communication: SW1-4
SW1-4 OUTPUT AT THE LOSS OF COMMUNICATION
OFF Reset the output (turned off)
ON Hold the output (*)
(maintains the last data received normally)
Note: Be sure to set unused SW1-3 and 1-5 through 1-8 to
OFF.
■DeviceNet TERMINAL ASSIGNMENT
23415
NO. ID FUNCTION, NOTES
1 V+ Network power supply +
2 CAN_H Network data High
3 Drain Shield
4 CAN_L Network data Low
5 V– Network power supply –
■OUTPUT TERMINAL ASSIGNMENT
10
+24V
11
Y1
12
Y3
1
0V
2
Y0
3
Y2
13
Y5
4
Y4
14
Y7
5
Y6
15
Y9
6
Y8
16
YB
7
YA
17
YD
8
YC
9
YE
18
YF
NO.
ID FUNCTION
NO.
ID FUNCTION
1 0V 0V (common) 10 +24V 24V DC
2 Y0 Output 0 11 Y1 Output 1
3 Y2 Output 2 12 Y3 Output 3
4 Y4 Output 4 13 Y5 Output 5
5 Y6 Output 6 14 Y7 Output 7
6 Y8 Output 8 15 Y9 Output 9
7YA Output 10 16 YB Output 11
8 YC Output 12 17 YD Output 13
9 YE Output 14 18 YF Output 15
■EXTENSION MODULE
Combinations with all extension modules are selectable.