manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. M-system
  6. •
  7. I/O System
  8. •
  9. M-system R3-AS8 User manual

M-system R3-AS8 User manual

Other M-system I/O System manuals

M-system R3-SV4 User manual

M-system

M-system R3-SV4 User manual

M-system R3-US4 User manual

M-system

M-system R3-US4 User manual

M-system R7D-YS2/UL User manual

M-system

M-system R7D-YS2/UL User manual

M-system R8-PA4 User manual

M-system

M-system R8-PA4 User manual

M-system R7F4DC-DA16A-H User manual

M-system

M-system R7F4DC-DA16A-H User manual

M-system R7F4HC-DAC32D-K User manual

M-system

M-system R7F4HC-DAC32D-K User manual

M-system R3S-DA16 User manual

M-system

M-system R3S-DA16 User manual

M-system R7M-EA8/UL User manual

M-system

M-system R7M-EA8/UL User manual

M-system R7 Series User manual

M-system

M-system R7 Series User manual

M-system R7F4HC-DC32B-K User manual

M-system

M-system R7F4HC-DC32B-K User manual

M-system R7F4DC-DC16A-H User manual

M-system

M-system R7F4DC-DC16A-H User manual

M-system Devicenet R7F4DD-DC16B-H User manual

M-system

M-system Devicenet R7F4DD-DC16B-H User manual

M-system R80YVT4N User manual

M-system

M-system R80YVT4N User manual

M-system R8 Series User manual

M-system

M-system R8 Series User manual

M-system MDR-8 User manual

M-system

M-system MDR-8 User manual

M-system R80DAT16A2 User manual

M-system

M-system R80DAT16A2 User manual

M-system R3Y-SS16N User manual

M-system

M-system R3Y-SS16N User manual

M-system R7C-DA16 User manual

M-system

M-system R7C-DA16 User manual

M-system R3-BSW User manual

M-system

M-system R3-BSW User manual

M-system R3-SV8N User manual

M-system

M-system R3-SV8N User manual

M-system R3-SV4A User manual

M-system

M-system R3-SV4A User manual

M-system R3-SV4A User manual

M-system

M-system R3-SV4A User manual

M-system R7C-YV2 User manual

M-system

M-system R7C-YV2 User manual

M-system R7K4DH-1-DAC32A User manual

M-system

M-system R7K4DH-1-DAC32A User manual

Popular I/O System manuals by other brands

SMC Networks EX600-AXA Installation & maintenance manual

SMC Networks

SMC Networks EX600-AXA Installation & maintenance manual

Siemens SIMATIC ET 200SP HA Equipment manual

Siemens

Siemens SIMATIC ET 200SP HA Equipment manual

Advantech PCM-27J3AU Startup manual

Advantech

Advantech PCM-27J3AU Startup manual

Hitachi HX-RIO3 Series user manual

Hitachi

Hitachi HX-RIO3 Series user manual

ICP DAS USA tM-AD2 quick start

ICP DAS USA

ICP DAS USA tM-AD2 quick start

IFM AL1200 operating instructions

IFM

IFM AL1200 operating instructions

Allen-Bradley D Series installation instructions

Allen-Bradley

Allen-Bradley D Series installation instructions

Allen-Bradley 1794-OF8IH installation instructions

Allen-Bradley

Allen-Bradley 1794-OF8IH installation instructions

Allen-Bradley SLC 500 1746-FIO4I user manual

Allen-Bradley

Allen-Bradley SLC 500 1746-FIO4I user manual

WAGO I/O-SYSTEM 750 manual

WAGO

WAGO I/O-SYSTEM 750 manual

System Sensor M201E installation instructions

System Sensor

System Sensor M201E installation instructions

NTP Technology Penta 721 digital I/O installation guide

NTP Technology

NTP Technology Penta 721 digital I/O installation guide

Bosch B208 user manual

Bosch

Bosch B208 user manual

Acces I/O products MPCIE-ISODIO-16 Hardware manual

Acces I/O products

Acces I/O products MPCIE-ISODIO-16 Hardware manual

ExpertDAQ EX-9017F Operation manual

ExpertDAQ

ExpertDAQ EX-9017F Operation manual

SeaLevel SeaI/O-580E user manual

SeaLevel

SeaLevel SeaI/O-580E user manual

Technosoft iPOS360x MX Technical reference

Technosoft

Technosoft iPOS360x MX Technical reference

National Instruments 776570-00 user manual

National Instruments

National Instruments 776570-00 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

R3-AS8
P. 1 / 4 EM-8440 Rev.1
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
the contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
DC current input alarm module ................................ (1)
■ MODEL NO.
Check that model No. described on the specification label is
exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, including installation, connection and basic
maintenance procedures.
INSTRUCTION MANUAL
MODEL R3-AS8
DC CURRENT INPUT ALARM MODULE
(8 points, isolated)
POINTS OF CAUTION
■ CONFORMITY WITH EC DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrated in
a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.
■ HOT INSERTION/REMOVAL OF MODULES
Removing or replacing modules does not affect other modules
on the same backplane. It is possible to replace them without
removing the power supply. However, replacing multiple
modules at once may greatly change line voltage levels. We
recommend that you replace them one by one.
■ ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ventila-
tion.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH in
order to ensure adequate life span and operation.
■ WIRING
• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present. Do not install them in the same duct.
■ UNUSED INPUT CHANNELS
• Set the unused input channels to ±20mA or 0 – 20mA range.
Unused channels left open with 4 – 20mA setting are equal
to the input lower than -15%, which sets a data abnormality
at the PLC or the host device.
Open circuit with the input range set to ±20mA means 50%
of the full-scale. An alarm setpoint must be set to a value that
does not trip an unwanted alarm.
• Unused channels can be specified and set so on the PC
Configurator Software (model: R3CON) without needing the
above mentioned setting.
■ AND ....
• The unit is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data sheet.
INSTALLATION
Use the Installation Base (model: R3-BSx).
R3-AS8
P. 2 / 4 EM-8440 Rev.1
COMPONENT IDENTIFICATION
•Conversion Rate: SW3
SW CONVERSION RATE
160 ms (*)80 ms 40 ms 20 ms
SW3-1 OFF ON OFF ON
SW3-2 OFF OFF ON ON
(*) Factory setting
SW2SW1
ON
1
2
3
4
5
6
7
8
ON
ON
1
2
3
4
5
6
7
8
SW3
1
2
3
4
5
19
20
21
22
15
16
17
18
23
24
25
26
27
28
6
7
8
9
10
11
12
13
14
1
2
3
4
■FRONT VIEW
ERR LED
RUN LED
■SIDE VIEW
Range
Input 1-4 (SW1)
or
Input 5-8 (SW2)
Conv.
Rate
■ DIMENSIONS mm (inch)
TERMINAL CONNECTIONS
Connect the unit as in the diagrams below and the next page.
TERMINAL
COVER
5
19
20
21
22
15
16
17
18
23
24
25
26
27
28
6
7
8
9
10
11
12
13
14
1
2
3
4
130 (5.12)
27.5 (1.08) 109 (4.29) POSITIONING
GUIDE
28–M3
SCREW
6.2
(.24)
■SIDE DIP SW
•Input Range: SW1, SW2 (selectable per 4 channels)
INPUT 1 through INPUT 4 (SW1)
INPUT 5 through INPUT 8 (SW2) RANGE
1234
OFF OFF OFF OFF
4 – 20mA
(*)
ON OFF OFF OFF 0 – 20mA
OFF ON OFF OFF
-20 – +20mA
■STATUS INDICATOR LED
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with the input abnormality;
Green in normal operating conditions.
R3-AS8
P. 3 / 4 EM-8440 Rev.1
■ CONNECTION DIAGRAM WIRING INSTRUCTIONS
■SOLDERLESS TERMINAL mm (inch)
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable. Solderless
terminals with insulation sleeve do not fit. Applicable wire
size: 0.3 – 0.5 mm2
3.2 (.13) dia.
4 min.
(.16)
12 (.47) max.
6 max.
(.24)
3 (.12) max.
2
INTERNAL POWER
BUS A
BUS B*
*For dual redundant communication.
BUS CONNECTOR
9
3
6
8
11
16
12
19
17
20
22
25
26
23
–
INPUT 1 +
–
INPUT 2 +
–
INPUT 3 +
–
INPUT 4 +
–
INPUT 5 +
–
INPUT 6 +
–
INPUT 7 +
–
INPUT 8 +
5
R3-AS8
P. 4 / 4 EM-8440 Rev.1
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
productwasoriginallypurchasedifsuchproducthasbeenusedundernormaloperatingconditionsandproperlymaintained,M-System'ssoleliability,andpurchaser'sexclusiveremedies,
under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To
submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]
OUTPUT DATA DESCRIPTIONS
Four alarm setpoints are selectable per each input. Two (2)
word (16 bits ×2) data is transmitterd to the PLC or the host
device via the R3 network module.
ALARM SETTING
The following parameters are programmable using the PC
Configurator Software (model: R3CON).
■ALARMTRIP POINT (-15.00 to +115.00%)
Four alarm setpoints are selectable per each input.
■ALARM TYPE (High or Low)
High or Low alarm is selectable for each alarm trip point.
High alarm: An alarm is set when the input signal goes above
the setpoint.
Low alarm: An alarm is set when the input signal goes be-
low the setpoint.
■DEADBAND (HYSTERESIS)
(0.00 to 100.00%; factory set to 5.00)
Deadband (deviation between the points where the alarm is
set and reset) is selectable for each alarm trip point.
■POWER ON DELAY TIME
(0.0 to 99.0 seconds; factory set to 5.0)
The alarm output start functioning in the preset time after
the power has been turned on.
This setting is common to all four points.
■ALARM ON DELAY TIME
(0.0 to 99.0 seconds; factory set to 1.0)
The alarm output is set when the preset time elapses after
the input has entered in the alarm range.
This setting is common to all four points.
■ALARM HOLD TIME
(0.0 to 99.0 seconds; factory set to 1.0)
The alarm output is held for the preset time even if it is
reset in shorter time.
This setting is common to all four points.
0
15
Alarm 1
Alarm 2 Input 1
Alarm 3
Alarm 4
Alarm 1
Alarm 2 Input 2
Alarm 3
Alarm 4
Alarm 1
Alarm 2 Input 3
Alarm 3
Alarm 4
Alarm 1
Alarm 2 Input 4
Alarm 3
Alarm 4
0
15
Alarm 1
Alarm 2 Input 5
Alarm 3
Alarm 4
Alarm 1
Alarm 2 Input 6
Alarm 3
Alarm 4
Alarm 1
Alarm 2 Input 7
Alarm 3
Alarm 4
Alarm 1
Alarm 2 Input 8
Alarm 3
Alarm 4
0
+1