manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. M-system
  6. •
  7. I/O System
  8. •
  9. M-system R8-YS2 User manual

M-system R8-YS2 User manual

Other M-system I/O System manuals

M-system R30PA2 User manual

M-system

M-system R30PA2 User manual

M-system R3-SV4 User manual

M-system

M-system R3-SV4 User manual

M-system Devicenet R7F4DD-DA16A-H User manual

M-system

M-system Devicenet R7F4DD-DA16A-H User manual

M-system Devicenet R7F4DD-DA16B-C User manual

M-system

M-system Devicenet R7F4DD-DA16B-C User manual

M-system R7M-EA8/UL User manual

M-system

M-system R7M-EA8/UL User manual

M-system Devicenet R7F4HD-DA32B User manual

M-system

M-system Devicenet R7F4HD-DA32B User manual

M-system R7D-YS2 User manual

M-system

M-system R7D-YS2 User manual

M-system R8 Series User manual

M-system

M-system R8 Series User manual

M-system R7D-RS4 User manual

M-system

M-system R7D-RS4 User manual

M-system R7 Series User manual

M-system

M-system R7 Series User manual

M-system M5SN User manual

M-system

M-system M5SN User manual

M-system R7D-YV2 User manual

M-system

M-system R7D-YV2 User manual

M-system R7M-DAC16C-R User manual

M-system

M-system R7M-DAC16C-R User manual

M-system R7G4FML3-6-DA16 User manual

M-system

M-system R7G4FML3-6-DA16 User manual

M-system R7ML-DC16B-R User manual

M-system

M-system R7ML-DC16B-R User manual

M-system R7L-EA8 User manual

M-system

M-system R7L-EA8 User manual

M-system R80NCIT1 User manual

M-system

M-system R80NCIT1 User manual

M-system R3-SV4 User manual

M-system

M-system R3-SV4 User manual

M-system R7L-DC16B-R User manual

M-system

M-system R7L-DC16B-R User manual

M-system Mini-MW Series User manual

M-system

M-system Mini-MW Series User manual

M-system R3-BSW User manual

M-system

M-system R3-BSW User manual

M-system R30SVF4 User manual

M-system

M-system R30SVF4 User manual

M-system R7L-DC16A User manual

M-system

M-system R7L-DC16A User manual

M-system R8-FS16N User manual

M-system

M-system R8-FS16N User manual

Popular I/O System manuals by other brands

SMC Networks EX600-AXA Installation & maintenance manual

SMC Networks

SMC Networks EX600-AXA Installation & maintenance manual

Siemens SIMATIC ET 200SP HA Equipment manual

Siemens

Siemens SIMATIC ET 200SP HA Equipment manual

Advantech PCM-27J3AU Startup manual

Advantech

Advantech PCM-27J3AU Startup manual

Hitachi HX-RIO3 Series user manual

Hitachi

Hitachi HX-RIO3 Series user manual

ICP DAS USA tM-AD2 quick start

ICP DAS USA

ICP DAS USA tM-AD2 quick start

IFM AL1200 operating instructions

IFM

IFM AL1200 operating instructions

Allen-Bradley D Series installation instructions

Allen-Bradley

Allen-Bradley D Series installation instructions

Allen-Bradley 1794-OF8IH installation instructions

Allen-Bradley

Allen-Bradley 1794-OF8IH installation instructions

Allen-Bradley SLC 500 1746-FIO4I user manual

Allen-Bradley

Allen-Bradley SLC 500 1746-FIO4I user manual

WAGO I/O-SYSTEM 750 manual

WAGO

WAGO I/O-SYSTEM 750 manual

System Sensor M201E installation instructions

System Sensor

System Sensor M201E installation instructions

NTP Technology Penta 721 digital I/O installation guide

NTP Technology

NTP Technology Penta 721 digital I/O installation guide

Bosch B208 user manual

Bosch

Bosch B208 user manual

Acces I/O products MPCIE-ISODIO-16 Hardware manual

Acces I/O products

Acces I/O products MPCIE-ISODIO-16 Hardware manual

ExpertDAQ EX-9017F Operation manual

ExpertDAQ

ExpertDAQ EX-9017F Operation manual

SeaLevel SeaI/O-580E user manual

SeaLevel

SeaLevel SeaI/O-580E user manual

Technosoft iPOS360x MX Technical reference

Technosoft

Technosoft iPOS360x MX Technical reference

National Instruments 776570-00 user manual

National Instruments

National Instruments 776570-00 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

R8-YS2
P. 1 / 4EM-9745 Rev.1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: inf[email protected].jp
DC CURRENT OUTPUT MODULE
(2 points, isolated) MODEL R8-YS2
INSTRUCTION MANUAL
BEFORE USE ....
Thank you for choosing M-System. Before use, check the
contents of the package you received as below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
DC current output module.......................................... (1)
■MODEL NO.
Confirm that the model number described on the product is
exactly what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES
•Theequipmentmustbemountedinsideapanel.
•Theactualinstallationenvironmentssuchaspanelcon-
figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.
■GENERAL PRECAUTIONS
•Beforeyouremoveormounttheunit,turnoffthepower
supply and output signal for safety.
•Switches on the side of the module can be set for mainte-
nance only while the power supply is off. Do not access
them while the power is supplied.
■ ENVIRONMENT
•Indooruse
•Whenheavydustormetalparticlesarepresentintheair,
install the unit inside proper housing with sufficient ven-
tilation.
•Donotinstalltheunitwhereitissubjectedtocontinuous
vibration. Do not apply physical impact to the unit.
•Environmentaltemperaturemustbewithin-10to+55°C
(14to131°F)withrelativehumiditywithin30to90%RH
in order to ensure adequate life span and operation.
■WIRING
•Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
•Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
•Theunitisdesignedtofunctionassoonaspowerissup-
plied,however,awarmupfor10minutesisrequiredfor
satisfying complete performance described in the data
sheet.
INSTALLATION
■HOW TO MOUNT THE MODULE ON DIN RAIL
A
B
• I/O Module
Confirm that the locking clamps of the I/O module are set.
Insert the module in parallel to the next one while aligning the grooves of
both modules (A & B in the above figure).
Maintain it perpendicularly to the rail.
More I/O modules can be added in the same manner.
R8-YS2
P. 2 / 4EM-9745 Rev.1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: inf[email protected].jp
• Protective Cover
The protective cover is to be attached over the connected I/O module
at the right end.
Align the hooks on the cover with the grooves of the module and slide it
straight until the hooks are latched.
Groove
Hook
When removing the cover, pull it out while squeezing the hooks inward.
■HOW TO UNMOUNT THE MODULE ON DIN RAIL
• Removing an intermediate module
Caution !
1) Be careful not to hurt your hand by pointed edges of the internal
communication bus connector.
2) I/O modules cannot hold tightly on the DIN rail by themselves without
power/network module.
Secure them to the position if necessary by using DIN rail end plates.
Release the locking clamps and pull out straight the module.
R8-YS2
P. 3 / 4EM-9745 Rev.1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: inf[email protected].jp
COMPONENT IDENTIFICATION
• Range
Same range for all channels. Use PC Configurator to set
independent ranges per channel.
OUTPUT RANGE SW2-1
0−20mADC OFF
4−20mADC(*) ON
• Output at The Loss of Communication
Same output for all channels.
OUTPUT AT THE LOSS OF COMMUNICATION SW2-5
OutputHold(*)
(last data correctly rerceived is hold) OFF
Stop output ON
[Note]ForStopoutput,outputxedat-5%,0mAmin.when
configuration mode is DIP switch setting.
Output fixed at scaling value at the loss of communication
when configuration mode is PC.
• Terminator DIP SW
TERMINATOR SW SW2-6
Without(*) OFF
With ON
• Conguration Mode
CONFIGURATION MODE SW2-8
DIPswitchsetting(*) OFF
PC Configurator and communication ON
[Note]BesuretosetunusedSW2-2through2-4and2-7to
OFF.
■PC CONFIGURATOR
The following parameters can be set with using PC Configu-
ratorSoftware(model:R8CFG):
•Outputsettingbychannels(range,scaling,zero/gainad-
justments,scalingvalueatpoweron,slalingvalueatthe
loss of communication)
•Commonsetting(lossofinternalbuscommunicationde-
tection time)
TurnSW2-8ONtoallowprogrammingbythePCCongu-
ratorviathePower/NetworkModule.
RefertotheusersmanualfortheR8CFGfordetailedopera-
tion of the software program.
■INDICATOR LED
LED
OPERATION
FUNCTION
Status OFF Stopping
GreenON Valid host communication
GreenBlinking
Reading/writingconguration
RedON Setting error
RedBlinking Parameter error
Output
Status
OFF Output data in the range
RedBlinking Output data out of range
■OUTPUT CONNECTOR ASSIGNMENT
PIN ID FUNCTION
No.
1 + Output (+)
2 NC No connection
3 NC No connection
4 − Output (−)
1
2
3
4
■OPERATING MODE
(*)Factorysetting
• Module Address
The SW1-1, SW1-2, SW1-3, SW1-4 determines the tenth
placedigit,whiletheSW1-5,SW1-6,SW1-7,SW1-8doesthe
ones place digit of the address.
Addressisselectedbetween0to31.
(Factorysetting:0)
MODULE ADDRESS
SW1
×10 1234
×1 5 6 7 8
0 OFF OFF OFF OFF
1OFF OFF OFF ON
2 OFF OFF ON OFF
3OFF OFF ON ON
4OFF ON OFF OFF
5 OFF ON OFF ON
6 OFF ON ON OFF
7 OFF ON ON ON
8ON OFF OFF OFF
9ON OFF OFF ON
AO_I2
AO_I1
8
7
6
5
4
3
2
1
SW1 SW2
On
RUN
Status Indicator LED
Output Status Indicator LED
Internal Bus Connector
Output Connector 1
Output Connector 2
Function Setting
DIP SW
■ FRONT VIEW ■ SIDE VIEW
R8-YS2
P. 4 / 4EM-9745 Rev.1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: inf[email protected].jp
EXTERNAL DIMENSIONS unit: mm (inch)
CONNECTION DIAGRAM
115 (4.53)
DIN RAIL
(35 mm wide)
[3 (.12)] [4 (.16)]
24 (.94) 59 (2.32)
55 (2.17)
6 (.24) 7 (.28)6 (.24)7 (.28)
+
NC
NC
-
OUTPUT 1
+
NC
NC
-
OUTPUT 2
1
2
4
3
1
2
4
3
OUTPUT CONNECTOR 1
INTERNAL POWER
INTERNAL BUS
EXC. SUPPLY OUTPUT CONNECTOR 2
BUS CONNECTOR
WIRING INSTRUCTIONS
■ e-CON connector
PWBconnectorXN2D-1474-S002(Omron)
RecommendedcableconnectorXN2A-1470(Omron)*1
Applicablewiresize:0.08mm2(AWG28)-0.5mm2(AWG20)
Outersheathdiameter:max.1.5dia
*1.The cable connector is not included in the package.
  Refertothespecicationsoftheproduct.